
AIR BOOSTER 
Model: AB-2 
The Air Booster is designed to increase the flow of heated air or cooled air in 
branch ducts of a heating and central air conditioning system. The Air Booster, can 
also be used to improve the air flow of a gravity warm air furnace. 
The Air Booster should be installed in branch ducts serving individual rooms, where 
proper air flows can not be achieved. 
Note: Installer must supply junction box. 

INSTALLATION 
The Air Booster is not designed for installation in 
the main air supply ducts. Locating the Air 
Booster near the outlet end of a problem branch 
duct will provide the best performance. 
The Air Booster is designed to operate in round 
ducts 6-inches in diameter or larger and 
rectangular ducts 6-inches wide by 6-inches 
deep or larger. 
CAUTION: Do not install the Air  
Booster where the air temperature 
within the duct exceed 180oF. The 
Air Booster should not be installed 
into vertical duct pipes. 
1. Locate the Air Booster in the 
duct pipe near the problem 
area. Allow adequate space for 
the removal of the unit for 
servicing or annual inspection. 
2. Attach  the  self-adhesive 
template provided to the duct 
surface. Make sure the arrows 
on the template point in the 
direction of the desired air flow. 
After the template has been 
secured to the duct pipe, cut a 
slot in the pipe along the 
indicated lines on the template. 
Then remove the remainder of 
the template from the pipe. 
(See Figure 1A or 1B) 
Figure 2B
3. Insert the Air Booster into the 
slot, making sure the fan blade 
points in the direction of the air 
Figure 3B
flow. Position the Air Booster so 
the fan blade does not rub 
against the inside surface of the duct. Mark on the duct the location of the 6-hole positions in the base plate. Remove 
the Air Booster and drill 1/8-inch diameter holes through the duct pipe where indicated. 
4. Remove center knockout from the installer supplied outlet box bottom. (See Figure 2A) Before installing Air Booster 
into the duct pipe, fasten the outlet box onto the base plate with the #10-32 UNF screws and nuts provided. (See  
Figure 2B) 
5. Insert the Air Booster into the cut slot of the duct pipe. Make sure the fan blade is pointed toward the outlet of the 
duct. Secure the Air Booster onto the duct with the sheet metal screws provided. (See Figure 3A or 3B) 
Page 2

UNIT WIRING INSTRUCTIONS 
ELECTRICAL DATA 
VOLTS  AMPS  HZ  WATTS  RPM  THERMAL OR IMPEDANCE PROTECTION 
120 VAC  .60  60  35  3000  YES 
A permanent wiring method must be used for power connection. It is recommended that a minimum size of 14 AWG wire 
for electrical supply connections and wiring should be suitable for 90oC (194oF) temperature. The Air Booster should be 
wired with an overcurrent protection device (fuse or circuit breaker) rated 15 amperes or less. Wiring method should be in 
accordance with the National Electrical Code and any local code requirements. 
CAUTION: Disconnect electrical power before wiring. Do not route electrical wiring along heated duct pipes. 
WIRING METHOD NO. 1 
Controlling the Air Booster through a standard on/off wall switch. (See Figure 
4 for wiring diagram) This method allows for manual control of the Air Booster 
unit in the area desired. 
 WIRING METHOD NO. 2 
Controlling the Air Booster through a central heating/air conditioning forced air 
system. (See Figure 5 for wiring diagram) This method allows for automatic 
operation of the Air Booster unit. The Air Booster is wired in parallel with the 
appliance blower motor. This operates the Air Booster whenever the 
appliance blower operates. 
Figure 4
CAUTION: Do not wire the Air Booster to an appliance blower 
motor if: 
The appliance motor is not rated for 120 volts AC single phase 
and operating at 60 cycles. 
The blower motor control is a variable speed tap type, solid 
state speed control or any of the type of controls not designed 
for dual motor control. 
Consult appliance manual for this information. 
NOTE: All wire splice connections should be made within an  
electrical junction box. 
MAINTENANCE
CAUTION: Disconnect electrical power supply before performing maintenance. 
Periodic removal and cleaning of the Air Booster unit is recommended for forced central heating/air conditioning systems. 
Annual removal and cleaning of the Air Booster unit is recommended for gravity warm air heating systems not equipped 
with a return air filter. 
Page 3