Field Controls 20+UL User Manual

CONDENSATE PUMP
mallyProtected,
Model: 20+
The Field Controls Condensate Pumps are designed to automatically remove the liquid from an air conditioner evaporative coil and/or a gas condensing warm air furnace. This pump is made from a tough ABS plastic so it will resist corrosion and impacts.
ITEMS INCLUDED
1) UL & cUL Listed Condensate Pump with 6' power cord 1) Check Valve to prevent backflow of liquid into the unit
1) Instruction Sheet ULST only)
MODELS AVAILABLE
MODEL VOLTAGE CURRENT
20+UL 115VAC/60Hz 1.45 Amps 46296901 Base Model 20+ULS 115VAC/60Hz 1.45 Amps 46296902 Base Model with Overflow Safety Switch 20+ULT 115VAC/60Hz 1.45 Amps 46296903 Base Model with 20’ Flexible Tubing
20+ULST 115VAC/60Hz 1.45 Amps 46296904
20+ULS 220/60 115VAC/60Hz 1.45 Amps 46296906 Base Model with Overflow Safety Switch
SPECIFICATIONS
PART
NUMBER
DESCRIPTION
Base Model with Overflow Safety Switch and 20’ Flexible Tubing
WARNING: For indoor use only. This pump is not submersible.
FLOW HEAD (ft)
5 1 85 5 70 10 45 15
0 20
Certification: UL & cUL Listed Weight: 3.25 lbs Dimensions: 11" X 5" X 4-3/4" Tank Capacity: 2 qts. Total Motor Ratings: Ther
Double Insulated Enclosure
DO NOT DESTROY
THESE INSTRUCTIONS MUST REMAIN WITH EQUIPMENT
English ...... Page 1
Français..... Page 5
Espanõl ..... Page 8
INSTALLATION
1. Carefully unpack the unit. Check for damage and make sure all of the required parts are included. The units are thoroughly tested before packing to insure safe delivery and operation. If there is any sign of damage due to shipment return it to the place of purchase for repair or replacement.
2. Choose a mounting location near the air conditioner or furnace. The pump must be mounted level and the inlet must be below the lowest drain. The unit has two brackets built into the deck that can be used to attach the unit to a wall or to the side of the appliance with installer supplied fasteners.
3. The pump should be mounted so the deck is at least 6 1/2" above the floor. (See Figure 1) This will allow clearance for the tank to be removed later for cleaning.
CONNECTING THE PIPING
1. Run flexible tubing or pipe from the condensate drain on the evaporator pan and/or drain from furnace to one of the inlet holes on the pump. This drain line should have a continuous downward slope to allow gravity flow. Cut the end of the line at an angle so the end does not close off on the bottom of the pump's tank. (See Figure 2) NOTE: If there is an overflow
drain from the evaporator pan or from the furnace, it may be necessary to tee the overflow and the main drain together before they enter the pump. (See Figure 1)
Figure 1
2. Connect a discharge line to the barbed check valve on top of the pump. This line may be flexible tubing or rigid pipe, but must be no larger than 3/8" I.D. Extend the discharge line straight up from the pump to the highest point possible without exceeding the head/GPH capacity of the pump before directing the line to the drain. From this high point, run the discharge line to a drain with a downward slope. For best results, the drain should be below or approximately level with the bottom of the pump tank. If it is not possible to slope the line downward, make an inverted "U" trap at the high point of the discharge line above the pump. (See Figure 2)
NOTE: Although not needed for this pump, local codes may require the use of a condensate neutralizer when using this pump with a condensing gas furnace. Consult local codes for guidelines.
WIRING
Shut off electrical power at the fuse box before making any wiring connections. All wiring must be done according to local and/or applicable national codes.
1. Main Power: Unit is provided with a 6 foot long power cord. Connect this cord to a constant line voltage source, not a fan or other device that may run intermittently.
2. Safety Switch: If using the model 20+ULS or 20+ULST, the overflow safety switch may be wired in series with the appliance's thermostat to shut off the unit in the event that the pump fails. In the case where heating or cooling requirements are a necessity, the overflow safety switch may be wired into an alarm circuit. Refer to Figure 3 for wiring. Note: In most cases, use the normally closed (NC) contacts when used with a furnace or air conditioner and use the normally open (NO) contacts when used to trigger an alarm.
Figure 2
Figure 3
Page 2
TESTING
1. With the unit plugged in and the discharge line in place, pour water into the pump reservoir until the unit activates to verify the unit works.
2. To test the overflow safety circuit (Models 20+ULS and 20+ULST only): a. Energize the appliance so it runs. b. Kink the tube coming from the pump discharge, or unplug the power cord, so it cannot pump out. c. Pour water into the pump reservoir, filling it completely. d. As the water level nears the top of the unit the overflow safety switch should activate, breaking the thermostat
circuit to the appliance (or triggering an alarm circuit, if used.)
e. Un-kink the tube, or plug the cord back in, and allow the pump to empty the tank. As the water level goes down
the overflow safety switch will deactivate and the appliance will energize again (or the alarm will reset.)
MAINTENANCE
WARNING: Before attempting any maintenance on the unit, disconnect the power cord from the power supply to
reduce the risk of electric shock. Also, take whatever precautions are necessary if the safety overflow switch is wired to a thermostat or alarm circuit.
SERVICING OF A DOUBLE-INSULATED APPLIANCE
In a double-insulated product, two systems of insulation are provided instead of grounding. No grounding means is provided on a double-insulated product, nor should a means for grounding be added to the product. Servicing a double­insulated product requires extreme care and knowledge of the system, and should be done only by qualified service personnel. Replacement parts for a double-insulated product must be identical to the parts they replace. A double­insulated product is marked with the words “DOUBLE INSULATION” OR “DOUBLE INSULATED”
If the unit does not perform as stated in the above tests, remove the two screws holding the cover from the deck, and remove the cover. Verify that the float mechanism moves up and down freely. If the float binds, it may be dirty or damaged. Since the motor is totally enclosed, no maintenance is required on the motor. However, the tank and float may need to be cleaned periodically. Simply remove the four screws at the corners of the pump deck and lower the tank. The tank can now be cleaned with a mild detergent. Use a damp cloth to wipe off the float if necessary. The impeller may need to be cleaned as well.
REFER TO THE FOLLOWING IN ORDER TO CLEAN THE IMPELLER
1. Remove the entire pump from the mounting wall.
2. Disassemble the tank from the deck by removing the four screws in the corners of the deck.
3. Turn the unit upside down and remove the impeller cover by loosening the five screws on the underside of the motor.
4. The impeller and shaft assembly may then be removed and cleaned. The impeller chamber should be cleaned at this time as well.
5. Wipe off the gasket between the impeller cover and the motor housing with a damp cloth before reassembling the impeller to the motor.
6. Reassemble the tank to the deck and reinstall the pump.
REFER TO THE FOLLOWING TO CLEAN THE CHECK VALVE AND VERIFY ITS OPERATION
1. Remove the discharge line from the check valve.
2. Use a 9/16" wrench to remove the check valve from the deck of the pump.
3. Visually check the valve for obstructions. If damaged, replace.
4. To re-install the check valve, hand tighten it into the deck. Then, tighten 1/2 turn further with a wrench. Be careful not to over-tighten as this may distort the O-ring seal under the check valve.
Page 3
REPLACEMENT ITEMS
The following items are available for replacement. Refer to Figure 4 for guidance in locating and assembling replacement parts.
PART NUMBER DESCRIPTION
46297800 Main Float and Switch Assembly 46297900 Overflow Float and Switch Assembly 46298000 Check Valve* 46298100 Impeller Assembly
*NOTE: The Check Valve includes an O-ring. TROUBLESHOOTING IF THE UNIT DOES NOT FUNCTION PROPERLY, REFER TO THE
FOLLOWING
1. Unit does not run: a. Check the power supply. b. Check the appliance to see if condensation is actually
being generated.
c. Check to make sure the pump float mechanism moves
freely and clicks the activation switch when moved up and down.
d. The motor is protected by a thermal overload device,
which may have tripped. This may be verified by measuring the resistance through the motor coil. An open circuit reading indicates that the motor has overloaded, and the unit must be replaced.
e. Check the drain line(s) into the pump for obstructions.
Note: If these lines are clogged and remain clogged, the appliance may eventually be damaged.
Figure 4
2. Pump makes loud noises when running: a. Check the tank for debris and clean if necessary. The impeller may also be cleaned, if needed. Refer to the
maintenance section above for cleaning instructions.
3. Unit runs but does not pump liquid out: a. Check the activation float to be sure it is not stuck in the up position. b. Check the height of the discharge tubing to be sure it does not exceed 20 vertical feet. c. Check the discharge tube for obstructions and clear if needed. d. Check the check valve for obstructions. Refer to the maintenance section above for cleaning instructions.
4. Liquid drains back into pump from discharge line: a. Check valve may have debris in it. Refer to the maintenance section above for cleaning instructions. b. If the discharge line is plumbed so the highest point is less than 5 feet above the pump, the check valve may
allow liquid to drain out of the line. This is normal and will not damage the pump.
5. Liquid leaks from around the check valve: a. If the check valve is too tight or too loose it may leak around the O-ring. Check that the valve is hand tight, then
tighten an additional 1/2 turn with a 9/16" wrench.
b. If the O-ring under the check valve is damaged, replace with a 1/2" ID X 11/16" OD X 3/32" width O-ring, or
purchase a replacement check valve, which includes an O-ring.
Page 4
Loading...
+ 8 hidden pages