Fiamm FLX Installation & Operating Instructions Manual

FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual
This document and any confidential information it contains shall be distributed, routed or made available solely with written permission of FIAMM. FIAMM reserves the right to change or revise without notice any information or detail given in this manual Page
1
TABLE OF CONTENTS PAGE
1 OPERATING CHARACTERISTICS 2
2 INSTALLATION 4
3 CHARGING 6
4 STORAGE AND REFRESH CHARGING 8
5 MAINTENANCE AND TESTING 9
6 SAFETY 10
7 APPLICABLE STANDARDS 10
8 RECORDS DATA 10
FIAMM Industrial Batteries
FIAMM AGM Valve Regulated Recom
This document and any confidential
informa
FIAMM. FIAMM reserves the right to change
1 OPERATING
C
Capacity
and final discharge vo
Battery
capacity is rated in Ampe
discharging rate of 20 h
ours to 1.
FIAMM FLX Series batteries
can
vice versa.
Internal resistance and short ci
The internal resistance and sho
plate thickness, number of plates
charge and other variables.
Product ratings
are determined
described in IEC or BS standards
Voltage
The voltage of lead acid cells is
electrode materials (PbO2
and Pb
on the electrolyte concentration in
Power
Design life
- Engineering Manual
for different applications.
a lower voltage using hi
ghe
electrolyte specific gravity,
through performance test
ing done in accor
related to the electrochemical potential differenc
trodes and the state
of c
FIG.1 – POWER
December 2012
Page
2
with methods
is dependent
of the battery.
FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual
This document and any confidential information it contains shall be distributed, routed or made available solely with written permission of FIAMM. FIAMM reserves the right to change or revise without notice any information or detail given in this manual Page
3
According to international standards a battery is considered at the end of its service life when the battery delivers less than 80% of its rated capacity. FIAMM FLX batteries have a design life of up to 10 years. Confirmation of service life comes not only from consistent feed-back from field applications, but also from extensive accelerated thermal testing.
Operation at temperatures higher than 77° F reduces the performance life expectancy of a battery. Service life of the battery is also affected by the float voltage chosen for battery charging, as showed in figure 2.
FIG.2 – EXPECTED SERVICE LIFE VS FLOAT VOLTAGE RANGE
Capacity in relation to the temperature
The capacity available from a battery, at any particular discharge rate, changes according to the working temperature.
Capacity in relation to the discharge rate
The capacity available from a battery depends also on the rate of discharge. For FIAMM FLX batteries at 77° F please refer to table 1.
Table 1 – AVERAGE CAPACITY VS DISCHARGING RATIO
DISCHARGE RATE
(hours)
END
VOLTAGE
CAPACITY
(% of C20 Ah)
FLX
20 1.75 100 10 1.80 90
5 1.80 85 3 1.80 77 1 1.75 63
FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual
This document and any confidential information it contains shall be distributed, routed or made available solely with written permission of FIAMM. FIAMM reserves the right to change or revise without notice any information or detail given in this manual Page
4
Self discharge
The state of charge of lead acid batteries slowly decreases while on open circuit due to self discharge. In FIAMM FLX batteries, the rate of self discharge is approximately 2% per month at 77° F (+/- 5° F). In case of extended storage it is necessary to refresh the batteries every 6 months to avoid a permanent loss of capacity.
Cycling
FIAMM FLX batteries have been tested successfully according to the latest cycle life test procedure standards specified for VRLA batteries (IEC and BS).
Gassing
Having a very high recombination efficiency (>99%), for batteries operated at 77° F and under normal operating conditions, gas release is negligible. Laboratory test measurements show the following gassing rates under normal operating conditions (2.27 Vpc, 77° F):
1
st
week of service 80cc/Ah/day
2
nd
week of service 10cc/Ah/day
After stabilization (2 months) 2cc/Ah/day
Battery rooms or cabinets should have natural ventilation and should not be fully sealed.
Operation of batteries in parallel
When the required capacity exceeds the capacity of a single string of batteries, it is common practice to connect strings in parallel. It is important to pay attention to the following guidelines:
In each string only batteries of the same type, model, age and quantity should be used;
A symmetrical layout of the batteries should be designed (i.e. length and type of connector)
to minimize possible resistance variations;
Number of strings in parallel should be reasonable in terms of layout and application. If strings are properly cabled, with equal voltage losses for each string, multiple strings can be connected in parallel, safely to reach required total capacity.
2 INSTALLATION
Unpacking and inspection
Upon receiving a shipment of batteries it is important to check it carefully against related packing list. Even though each consignment is certified and inspected by FIAMM before shipping, missing parts or damages could be caused by mishandling during transportation. Any damage or any specific problem found must be reported immediately by the consignee to the carrier and to the manufacturer for further insurance or legal actions.
FIAMM FLX batteries are shipped fully charged with terminal posts insulated to avoid any possible short circuit.
Batteries delivered in cabinets
For safety reasons, it is not advisable to pre-assemble batteries strings into cabinets before shipping equipment to the site. However, if this is necessary, it is strongly recommended to protect the battery system from mechanical stress and vibrations occurring during transportation. Batteries should be properly fastened to the relevant cabinet shelves by means of plastic band and/or other adequate methods. Furthermore the cabinets should be protected using shock-absorbing packaging material. Special precautions must be taken to avoid accidental short circuits.
Handling requirements
Batteries are heavy so they require proper care in handling. Always lift each cell/block from underneath or by the lifting handles. Never apply force to, or drop anything on, the terminal posts.
Room requirements
Batteries should be installed in a clean, cool, dry room on insulated racks or in a cabinet. Care must be taken in providing adequate floor loading capability and sufficient aisle space for servicing. Good lighting is also important to carry out visual inspections. Access to the battery room must be restricted to qualified personnel only.
FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual
This document and any confidential information it contains shall be distributed, routed or made available solely with written permission of FIAMM. FIAMM reserves the right to change or revise without notice any information or detail given in this manual Page
5
Ventilation in battery room
Under normal operating conditions, the gassing rate of FIAMM FLX Series batteries is extremely low. However, the battery room should have sufficient ventilation to avoid temperature rise in the event of unexpected circumstances such as overcharge due to a charger malfunction. As accelerated recombination reaction generates heat, it is important that there allowances in ventilation to dissipated excess heat through ventilation or air conditioning.
Temperature control in battery room
Battery life and performance are optimal at a temperature of 77° F. Operation at lower temperature will reduce available capacity (for the period of time that the battery remains at low temperature). Higher operating temperatures affect battery performances and will shorten the battery service life. Air circulation within the battery room must be sufficient to avoid hot or cold spots. The total temperature spread between the hottest and the coldest cell of the same string should be maintained inside a window of +/- 5° F.
Racks
Battery racks should be grounded and made of acid resistant and insulated material. For safety reasons they should be installed as level as possible. The depth and the height of the racks, along with servicing headroom, should allow both adequate ventilation and a satisfactory servicing.
Cabinets
Good ventilation is extremely important for battery cabinets. Ventilation openings should be both at the bottom of the cabinet, and as close as possible to the top, to prevent any hydrogen accumulation in an abusive situation. Cabinets should be placed/fastened steadily to the floor.
Installation procedure
For a proper installation clean the blocks with a soft dry antistatic cloth or soft water-moistened cloth. Place each cell/block at their correct position according to the electrical layout. Start with the lowest shelf to ensure stability. Inter-tier and inter-row connections should be applied only once all blocks have been connected properly. For proper ventilation and airflow maintain a distance of .25” or greater between all battery blocks.
Interblock connecting procedure
It is extremely important to ensure proper surface contact between battery terminal posts and cables (recommended) or solid connectors used to complete each string. Each connecting surface must be clean and without oxidation. If required use very fine grit abrasive paper to remove any dirt on each surface. Do not use wire brushes or similar tools that may damage the plating film around terminals’ and connectors’ copper. Then apply a light coating of No-Ox grease to the terminals and connectors prior to installation of the connection hardware.
Terminal torque settings
To ensure a proper electrical connection between the flat surface of each terminal and the connector a calibrated torque wrench must be used. Torque the electrical connections to the settings in Table 2.
Table 2 – TORQUE SETTING VALUES
Battery Terminal Type
Torque (in-lbs)
  
  
  
Final checking of connections
To perform a final check of the connections it is advisable to measure the overall battery voltage and make sure that this value is equal to the open circuit voltage of an individual block multiplied by the number of blocks.
Paste a sticker with a progressive number to each block, making sure that the surfaces are dry and clean. It is a good practice to number the blocks beginning with #1 at the positive end of each string.
FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual
This document and any confidential information it contains shall be distributed, routed or made available solely with written permission of FIAMM. FIAMM reserves the right to change or revise without notice any information or detail given in this manual Page
6
Connection of the battery to the rectifier/load
The end positive terminal of each string of batteries should be connected to the positive terminal of the charger, and the battery negative to the charger negative. Same procedure needs to be used for load connections. A proper selection in cables and connectors should be used to avoid excessive voltage drop, as well as overheating in case of high rate discharge. If a large section of cables are used their weight should not stress cell/block terminals. A good method to use is to affix cables on the rack or the nearby wall.
3 CHARGING
Introduction
After installation, in order to ensure the best protection against power failures, it is necessary that batteries are kept in the following conditions:
float charged throughout their standby period;
fully recharged soon after a discharge.
Recharging process can be performed in several ways, depending on the site and equipment conditions, but there are two main methods:
float voltage recharge
boost charge
The IU recharge method, also known as the modified constant voltage recharge, has been used for many years and in a variety of applications. This method combines the need to have the battery quickly recharged while ensuring maximum battery life. With this method, recharge starts at a constant current rate. The voltage increases up to a pre-set value. The pre-set voltage is maintained and the current then decreases to a minimum defined value. Finally, the recharge is completed at a final constant voltage value equal to or less than that defined for float charge with the current decreasing to the value used in float.
For UPS systems that do not utilize a constant float voltage charging profile or use an Advanced Battery Management charging profile please set the charging parameters per table 3.
Table 3 – ALTERNATE CHARGING PROFILE SETTINGS
FLX MODEL CURRENT LIMIT
VOLTAGE
 

 

Recommended procedure for initial charging
For a safe installation of FIAMM FLX batteries only constant voltage chargers should be used.
The best charging method operates with a preset constant voltage value supplying an automatically limited charging current. It is called constant voltage charging with current limit and automatic crossover.
An initial charge of 2.35 to 2.40 volts per cell for at least 24 hours (at 77° F) is suggested during commissioning or before a capacity test in order to be sure that the battery is in fully charged condition.
FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual
This document and any confidential information it contains shall be distributed, routed or made available solely with written permission of FIAMM. FIAMM reserves the right to change or revise without notice any information or detail given in this manual Page
7
Float operation for standby use
For standby applications the recommended float voltage window is between 2.25 to 2.30 volts per cell depending on the model and on site temperature, as showed in table 4 (charger’s float voltage tolerance is within ± 0.005 volt per cell).
Table 4 – FLOAT VOLTAGE VS SITE TEMPERATURE
Site Temperature
(°°°°F)
Float voltage per cell
FLX
60 2.29 64 2.285 68 2.28 72 2.275 75 2.27 77 2.27 79 2.265 82 2.26 86 2.255 90 2.25 93 2.245
97 2.24 100 2.235 104 2.23
Residual current
Whenever battery chargers are working properly (and in accordance with manufacturer instructions) it is normal to have a residual float current in fully charged batteries. Residual float currents will slowly increase during a batteries life and according to cycle frequency. Although the charger is set on a fixed average voltage, it is normal to record a spread in voltage between each block inside a string. Voltage variation within ± 250mV/battery is considered as a normal value particularly in the first 12 months from initial installation.
Recharge following discharge for standby use and boost charge
At the first installation, or soon after a discharge, the recommended recharge method is to use a constant voltage equal to the float charge voltage with a maximum charge current of 25% of nominal capacity.
To reduce the recharge time, the IU recharge method can be used with a higher voltage of 2.35-2.40 V/cell at 77° F for 24 hours and a current limit of 0.25 C
10
. This process, also called boost charging, should be applied only when batteries are not in a fully charged condition and need to be recovered in a short period of time.
The battery should be placed back on float as soon as possible, ideally as soon as the charge current has dropped below 20 mA/Ah (or lower if the application has frequent power failures).
Boost charge should be used only when necessary. Frequent equalize charging can result in more water consumption, which will lead to reduced capacity and shortened battery life.
Float voltage and recharge procedures for frequent discharge applications
Whenever FIAMM FLX batteries are used in applications with frequent power failures (such as several discharges a month) float voltage should be set at a higher range compared with a standby applications range (i.e. from 2.27 to 2.30 volt per cell at 68-77° F). The recommended float voltage values necessary to maximize the battery life at different temperatures are shown in table 4. The most important target in this type of environment is to have the batteries recovering promptly after a discharge
FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual
This document and any confidential information it contains shall be distributed, routed or made available solely with written permission of FIAMM. FIAMM reserves the right to change or revise without notice any information or detail given in this manual Page
8
To reduce the recharge time, the IU recharge method can be used with a maximum voltage of 2.30 V/cell at 68-77° F for 24 hours. Current should not be over 25% of nominal capacity, especially in sites where temperature may exceeds 86° F to avoid thermal runaway, overheating or overcharging of the batteries.
For very deep cyclic applications recharge voltage should not be higher than 2.30 V/cell for 16 to 24 hrs after every discharge.
Temperature compensation of the float voltage . To optimize FIAMM FLX battery life and performance over the normal operating temperature range, the float voltage should be adjusted in accordance with table 4.
In environments where temperature fluctuations are very limited, float voltage can be adjusted manually as needed. For most sites without a climate control systems it is advisable to have batteries connected to a charger with a built-in temperature compensation circuit.
Temperature sensor needs to be positioned on or over the batteries and not in the charger.
Ripple
Excessive ripple currents can cause battery overheating, which will lead to shorter life expectancy and reduced product performance. It is recommended that voltage regulation across the system (including the load, but with battery disconnected), under steady state conditions, should be better than ± 1% through 5% to 100% load. Transient and other ripple type excursions can be accommodated provided that, with the battery disconnected but the load connected, the system peak to peak voltage, including the regulation limits, falls within ± 2.5% of the recommended float voltage of the battery. Under no circumstances should the current flowing through the battery, when it is operating under float conditions, reverse into the discharge mode.
4 STORAGE AND REFRESH CHARGING
Storage
Batteries are delivered filled and charged ready for installation. If they cannot be installed immediately, batteries need to be kept in fresh, clean dry rooms.
Refreshing charge procedure
During storage batteries will lose part of their capacity due to self-discharge (2% per month at 77° F). A freshening charge is recommended at least every 6 months (at 77° F storage temperature).
Batteries should be refreshed, even if kept in storage at 77° F, when the cell voltage drops below the values listed in table 5. A freshening charge could be carried out by charging at 2.4 V/cell for about 24 hours at 77° F (boost). If the charging system can not meet the above requirement (lower than 2.4 Vpc, it is necessary to extend the charging time 24 hrs for every 0.03V/cell lower than 2.30V/cell, for example, 120 hours at 2.28 V/cell).
Table 5 – OPEN CIRCUIT VOLTAGE VALUES REQUIRING A RECHARGE (WHEN STORAGE AT 77° F)
RANGE
OPEN CIRCUIT VOLTAGE (PER CELL)
FLX
2 months 2.120 4 months 2.105 6 months 2.095
FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual
This document and any confidential information it contains shall be distributed, routed or made available solely with written permission of FIAMM. FIAMM reserves the right to change or revise without notice any information or detail given in this manual Page
9
5 MAINTENANCE AND TESTING
FIAMM FLX Series batteries are maintenance-free with respect to the water additions, but it is important to carry out few standard maintenance procedures to ensure the longevity and the reliability of the battery.
Visual inspection
FLX Series batteries should undergo a thorough visual inspection on a periodic basis to verify the following parameters:
-Cleanliness of the battery and surrounding area;
-Signs of corrosion at the terminals, connections, or support structure (rack or cabinet);
-Block integrity (cracks, or excessive jar/cover distortion, or signs of electrolyte leaks or seepage);
-Tightness of the terminal and intercell connections.
If any block shows physical damage it is recommended to immediately check the block float voltage and/or temperature.
Cleaning
When necessary, batteries could be cleaned using a soft dry cloth or water-moistened soft cloth paying attention not to cause any ground faults.
No detergent or solvent-based cleaning agents or abrasive cleaners should be used as they may cause permanent damage to the battery plastic container and lid.
Voltage checks
All voltage measurements should be made when the entire battery has stabilized on float, at least 7 days after battery installation or after a discharge cycle.
Measure and record individual block voltages on float once a year. It is normal to have a spread of block voltages up to ± 250 mV/battery, particularly in the first year of operation. No corrective action is required in this case.
Maintaining a correct battery charging voltage is extremely important for the reliability and life of the battery. It is advisable to carry out periodic checks of the overall float voltage to verify any possible defect of the charger or connections.
Capacity/Power Test
It is very important to verify connections and potential voltage drops as high power discharge can be dangerous if connections are improper or not in good condition.
Before any discharge testing, batteries should be properly prepared with a boost charge to ensure they are in a fully charged condition. In order to take temperature readings of a battery, one pilot cell or block should be chosen. The surface temperature of the container wall center of each pilot block should be measured immediately prior to the discharge test. The individual readings should be between 59° F and 86° F. The temperature of the selected block should be considered as representative of the average temperature of the battery. It is desirable that the average basal surface temperature and the ambient temperature fall as near to the reference temperature of 77° F as possible.
In case of batteries having a capacity lower than 80% of the nominal rating it is advisable to replace them within 12 months.
FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual
This document and any confidential information it contains shall be distributed, routed or made available solely with written permission of FIAMM. FIAMM reserves the right to change or revise without notice any information or detail given in this manual Page
10
6 SAFETY
Under normal operating conditions FLX Series batteries are considered 'office compatible'. However, under abusive conditions, such as charger malfunction or physical damage, there is potential danger of corrosion or fire. Therefore it is strongly recommended to carefully read the instructions contained in this manual to avoid any critical situation. In any case local safety regulations for electrical equipment sites must be regarded as a basic requirement.
Protective material list
Make sure that the following equipment is available to personnel working with batteries:
-Engineering/installation manual;
-Insulated spanners and tools;
-Fire extinguishers;
-Proper protective clothing.
Safety Precautions
Batteries are no more dangerous than any other electrical equipment when handled properly. So for safety reasons it is necessary to follow few important precautions below reported:
-Do not allow metal objects to rest on the battery or fall across the terminal posts;
-Never wear rings or metal wristbands when working on batteries;
-Do not try to remove the battery cap to add water or acid into the cell(s);
-Do not touch non-insulated terminals or connectors as there is a risk of electric shock;
-Do not allow naked flames, hot objects or sparks near the battery;
-Do not smoke near the battery or in the battery room.
The electrolyte (diluted sulphuric acid) is extremely corrosive. Any contact with eyes can cause severe and permanent damage. Contact with skin could result in severe burns. In case of severe physical contact with electrolyte wash the affected area with running water immediately and go to the closest hospital to seek medical attention.
Decommissioning of the batteries
Most components of a lead acid battery are recyclable. Lead acid batteries must be disposed according to local regulations. It is strongly recommended that, at the end of their service life, batteries are delivered to a certified lead smelter for proper recycling.
7 APPLICABLE STANDARDS
FIAMM FLX batteries comply with International Standards. Furthermore, FIAMM valve regulated recombinant batteries are approved by most major Telecom Operators, UPS and Power Equipment manufacturers.
8 RECORDS DATA
Complete written records of the installation, maintenance and testing of the product is important to ensure a proper understanding of the operational history of the batteries.
Records are necessary for the manufacturer/user to understand when corrective actions should be taken. Data required for a proper engineering review are
Production date of batteries,
Installation date,
Historical average temperature of the site,
Float voltage,
Discharge frequency,
Load applied during each discharge.
BATTERY MAINTENANCE REPORT
Installation Date:……………………………… Battery Location:………………………………………………
Battery/Cell Type:.…………………………….. Pilot Block No.:………………………………………………..
Other::………………………………………………………………………………….……………………………………..
MONTHLY READINGS
INDIVIDUAL CELL/BLOCK READINGS
Date
String
voltage (V)
Pilot cell/block Date:
Volts Temperature (F)
Time: String voltage (V): Charge current (A): Block No. Volt
Block No. Volt 1 31 2 32
String Discharged:
Date : …………… Duration :………..
Date : …………… Duration :………..
String Equalized:
Date : …………… Duration :………..
Date : …………… Duration :………..
Remarks:
3 33 4 34 5 35 6 36 7 37 8 38
9 39 10 40 11 41 12 42 13 43 14 44 15 45 16 46 17 47 18 48 19 49 20 50 21 51 22 52 23 53 24 54 25 55 26 56 27 57 28 58 29 59 30 60
Blocks temperature: #01………., #12…………,#24…………
Blocks temperature: #36………., #48…………,#60…………
Readings taken by:
Loading...