Festo VZWF-...-M22C series Operating Instructions Manual

Solenoid valve VZWF-...-M22C
Festo AG & Co. KG
Postfach 73726 Esslingen Deutschland +49 711 347-0 www.festo.com
Operating instructions 8065862
1611b [8065864]
Original: de
Solenoid valve VZWF-...-M22C English...................................
1 Design
3
8
7
6
2
5
4
1
9
aJ
aA
1 Port 1: Input 2 Valve body 3 Electrical plug with seal and
mounting screw
4 Solenoid coil mounting with
shaped rubber part, washer and hex nut
1)
5 Solenoid coil mounting with
O-ring, aluminium shaped part, toothed disc and socket head screw
1)
6 Solenoid coil 7 O-ring 8 Armature guiding tube 9 Port 2: Output aJ Arrow for flow direction aA Thread for mounting bracket
1) Mounting variant dependent on the size
Fig. 1
2 Function
The solenoid valve VZWF–...–M22C is a forced 2/2-way valve with solenoid coil. The membrane of the valve is coupled with the magnetic core of the coil. This allows the forced solenoid valve to switch between input and output without pressure difference. The solenoid valve VZWF–...–M22C is closed in the de-ener gised state (Normally Closed - NC).
Fig. 2
When current flows, the armature opens the pilot control hole in the valve seat seal and lifts the membrane from the valve seal either directly or supported by differential pressure of the medium pressure. If the power supply is cut off, the pilot control hole is closed by spring force. The supply pressure affects the mem brane and supports the sealing of the membrane on the valve seat.
3 Application
Solenoid valves of the VZWF–...–M22C series are intended to be used for con trolling the flow of gaseous and liquid media in rigid piping systems. The valve is suitable for vacuum operation with p
abs
> 100 mbar.
 The product may only be used in its original state without unauthorized modific
ations. Opening the valve body or dismantling the armature guiding tube is not permitted.
 Take into consideration the operating conditions at the location of use. Provide
sufficient thermal circulation.  Use the product only in perfect technical condition.  Only use media in accordance with specification. Before using other media,
please contact our customer support.  Operation with chemically unstable gases, abrasive media and hard materials is
not permitted.  Use the solenoid valves only in the flow direction indicated.  Wear suitable personal protective clothing, e.g. safety shoes and safety gloves.  Comply with all applicable national and international regulations.  Dispose of the product in an environmentally friendly manner. When doing this,
also take residual media into account (potential recycling of hazardous waste).
Return to Festo
Hazardous substances can endanger the health and safety of personnel and cause damage to the environment. To prevent hazards, the product should only be re turned upon explicit request by Festo. – Consult your regional Festo contact. – Complete the declaration of contamination and attach it to the outside of the
packaging. – Comply with all of the legal requirements for the handling of hazardous sub
stances and the transport of dangerous goods.
4 Product variants
Characteristic Value Description
Type VZWF Solenoid valve, forced
Version –, B Standard, Function-optimised
Valve type L In-line valve
Valve function M22C 2/2-way valve, normally closed (NC)
Connection to valves and fittings
G14 bis G2 Pipe thread in accordance with DIN ISO 228
N14 bis N2 NPT standard pipe thread in accordance with
ANSI B 1.20.1 Nominal diameter 135, 275, 400, 500 13,5 mm, 27,5 mm, 40 mm, 50 mm
Sealing materials –, E, V Standard (NBR), EPDM, FPM
Nominal operating voltage
1, 2A, 3A 24 V DC, 110 V AC (50-60 Hz), 230 V AC (50-60 Hz)
Electrical connection P4 Plug socket, 3-pin
Medium pressure 6, 10 max. 6 bar, max. 10 bar
Corrosion protection –, R1 Standard (brass), Stainless steel
Fig. 3
5 Transport and storage
 When shipping used products: Comply with all legal requirements for handling
hazardous substances and transporting dangerous goods. For return to Festo è Kapitel 3.
 Store the product in a cool, dry, UV- and corrosion-protected environment.
6 Installation
Note
Installation should only be conducted by qualified specialized personnel. Avoid mechanical stresses, particularly on the solenoid coil and the armature guiding tube.
Requirements
– The piping system is unpressurized, and no medium flows in it. – The lines are clean. – The lines ends are mounted. – The power supply is switched off.
Note
For fault-free operation, the effective line cross section at the input end should be at least as large as it is at the output end. Take proper account of the pipeline cross sections, line lengths and elements that may reduce the flow rate (angle sections etc.).
Clean valve
Residues of grease may be evident on the product due to the production process used.  Clean valve immediately before installation.
Connect lines
1. Bring the solenoid valve into its installation position. Please note the direction of flow. The permissible flow direction is marked by an arrow on the valve body. In vacuum mode, connect up vacuum at output end.
2. Screw the valve plugs into the pipeline ends. Comply with the permissible tight ening torques (è Fig. 6).
3. Establish the electrical connection. For this purpose use only the associated socket type (è Fig. 7). – Connect electrical cables to the socket. – Attach seal to the electrical contacts. – Put on plug and lock with fastening screw (tightening torque 0.3…0.5 Nm).
4. Connect the power supply.
7 Commissioning
Note
Commissioning only by qualified specialist personnel. When incompressible media are used (e.g. neutral water) pressure surges arise in the piping system because of the switching of the valve. Before commission ing, check the compatibility of the devices in the system in order to avoid dam age to them. If necessary adjust your application parameters.
 Note the information on the rating plate.  Operate the solenoid coils only with upstream fuses.  Only start up the solenoid valve when it is fully installed and fitted.  Check the connection points for tightness  Before commissioning, check that the operating conditions and permissible limit
values have been observed (è Technical Data).
8 Operation
Warning
Risk of injury due to hot surface! The valve can become hot while in operation.  Do not touch the valve during operation or immediately afterward.
 Comply with the operating conditions.  Always observe the permissible limit values.
9 Maintenance and care
 Every 6 months, check product from the outside for leakage and function.  Clean product regularly. The permissible cleaning agent is soap suds.
10 Disassembly
Warning
Risk of injury from combustion and chemical burns. The media in the piping system and the valve can be hot and under pressure. Medium residues can be in the product and escape when open or dismantled.  Allow the valve and piping to cool and depressurize them.  Wear specified protective equipment.
Note
Disassembly of the valve only by qualified specialized personnel.
1. De-pressurize the pipeline.
2. Switch off the power supply.
3. Empty the pipeline and valve completely. – Ensure that no one is in front of the outlet opening. – Catch discharging media in a suitable container.
4. Remove the solenoid valve from the pipeline (electrical socket connection, mounting bracket and screws).
Replacement of the solenoid coil
In the case of repair, the solenoid coil can be replaced.
Dismantling:
1. Switch off the power supply.
2. Disconnect the electrical socket connection.
3. Leave the solenoid valve and solenoid coil to cool.
4. Loosen the retaining nut and take the magnetic coil and the O-ring from the armature guiding tube.
Mounting:
1. Push the O-ring, the solenoid coil and the elements of the particular mounting kit above the armature guiding tube.
2. Tighten the retaining nut (tightening torque è Technical Data).
11 Troubleshooting
Malfunction Possible cause Remedy
Solenoid valve does not close
Solenoid valve faulty.  Replace solenoid valve.
Wrong mounting position or flow direction.  Correct mounting position.
Nominal voltage still applied.  Check electrical connection.
Solenoid valve does not open
Solenoid coil or solenoid valve faulty.  Replace solenoid coil.
 Replace solenoid valve.
Nominal voltage is interrupted or insufficient.
 Check voltage.
Fig. 4
12 Technical data
General VZWF
Valve function 2/2-way valve, single solenoid, closed
Design Diaphragm valve, forced
Actuation type Electrical
Sealing principle Soft
Assembly position Magnet standing
Medium Compressed air in accordance with ISO 8573-1:2010 [7:-:-],
Inert gases, Water, Neutral liquids
1)
Direction of flow Non-reversible
Max. viscosity [mm2/s] 22
Grade of filtration [μm] 50
Temperature of medium [°C] –10...+80
Ambient temperature [°C] –10...+35
Protection class IP65
Note on material for housing Brass casting (standard), Stainless steel casting
Note on material for seals NBR, EPDM, FPM
Note on materials for screws High-alloy stainless steel
1) Other media on request
Fig. 5
Connecting thread G¼N¼GyNyG½N½G¾N¾G1N1G1¼
N1¼
G1½ N1½G2N2
Nominal diameter [mm] 13.5 27.5 40 50
Flow factor K
v
[m3/ h] 1.8 2.2 2.5 7.5 11.0 20.0 22.5 28.0
Standard nominal flow rate
[l/min] 1920 2350 2660 8020 11750 21370 23500 29900
Medium pressure
1)
[bar] 0…10 0…6 0…10 0…6
Switching times air on2)[ms] 130 275 620 1220
Switching times air off2)[ms] 180 290 1140 2140
Max. tightening torque pipe connection
[Nm] 35 60 105 200 350 450 540 620
Max. tightening torque coil fastening
[Nm] 2.0 4.0
Weight [kg] 1.0 1.5 4.5 6.5
1) Vacuum operation with p
abs
> 100 mbar possible
2) Longer switching times with liquid media dependent on the viscosity
Fig. 6
Electrical data VZWF-...1 VZWF-...2A VZWF-...3A
Nominal voltage – Direct current – Alternating current (50/60 Hz)
[V DC] [V AC]
24 (_10%)––
110 (_10%)–230 (_10%)
Rated output for solenoid coil VACS-H1P [W]
[VA]11–
– 19 / 16
1)
– 18 / 15
1)
Rated output for solenoid coil VACS-G2P [W] 30 30
2)
Surge voltage capacity [kV] 2.5 4.0
Duty cycle [%] 100
Electrical connection Device plug as per EN 175301-803, Form A
Connecting cable cross section [mm2]0.75…1.5
Connection cable diameter [mm] 5…9
1) Switching power / holding capacity
2) Operation with rectifier plug
Fig. 7