Festo VPPE-3-1-1/8-x-E1 Series Operating Instructions Manual

War ni ng..................................................
For electrical isolation of operating voltage:
• Use only power units whic h guarante e reliable electrical isolation of the operating voltage as per IEC/DIN EN 60204-1. Observe also the general requirementsfor PELV power circuits as per IEC/DIN EN 60204-1.
1 Supply port (1) 2 Electrical connection 3 Status LED (green) 4 Earth terminal, external (front and back side) 5 Operating key upwards (UP) 6 LED disp lay 7 Operating key do wnwards (DOWN) 8 Edit key 9 Pressure output (2)
aJ Vent ing ( 3) aA Front fastening hole aB Side fastening hole
1
2
3
5
6
4
7
8
9
aJ
aA
aB
1
aB
2
6
65
7
9
aJ
aA
4
4
Type:...E1T
Type:...E1
8
3
Fig. 1
Proportional press ure regulating valve en
..................
Note.......................................................
• Installa tion a nd com missioning may only be performed in accordance with the operating instructions and by qualified personnel.
1 Application and function
The VPPE-... is designed to control pressure proportion­ately to a specified setpoint value. Replacement of manually adjustable pressure regulators by remote ly,e lectrically adjustable regulators, to have different machine parameters available quickly and auto­matically, for example.
Supply port
Setpoint value
Setpoint value
Pressure output
Vent ing
Pin 5
2 Variants of the VPPE-...
Type code of the VPPE-...
VPPE-3- 1-1/8-6-010-E1T
12
3
Item Featur es Meaning
1
Pressure regulation range: 2 6 10
0.02 … 2.0 bar
0.06 … 6.0 bar
0.1 … 10.0 bar
2
Setpoint specification: 010 420
0 … 10 V (voltage) 4 … 20 mA ( current)
3
Control unit: E1 Typ e of mo u nti ng : T
7-segment LED display Supply manifold mounting
3 Con ditions of use
General conditions for the correct and safe use of the product, which must be observed at a ll times:
• Observe the spe cified limit s (e.g. for pressures, temperatures and electric voltage).
• Makesurethereisasupplyofcorrectlyprepared compressedair in accordance with the specifications on the me dium Technical s pecifications.
• Please o bserve the pre vailing ambient conditions.
• Please c omply with national and loc al safe ty laws and regulations.
• Remove all transport packing, such as protective wax, foils, c aps, ca rdboard bo xes (wit h exce ption of the covers in the p neumatic c onnections). The individual materials can be st ored in containers for recycling purposes.
• Slowly pres surize the complet e system. This will prevent uncontrolled movements from occurring.
• Note the warnings and instructions –ontheproduct – in these operating instructions.
• Use the product in its original state without undertaking any modific ations.
4 Fitting
4.1 Mechanical
• Handle the VPPE-... with care so that the electrical connect ion is not damaged . Such d amage reduc es the operat ional reliability.
• Make sure there is sufficient space for the cable connection and tube couplings. This avoids breakage of the c onnecting ca ble.
• Put the VPPE-... as close as possible to the consuming device. This leads to improvedcontrol precision annd shorter response times.
• Push two screws (M4) into t he side mounting holes aB or the front mounting holes aA (see Fig. 1), max. t orque: 2 Nm.
• Fasten the VPPE-... in the intended location.
4.2 Pneumatic
• Remove the covers on the compressed air connections.
• Attach the pneumatic tubing to the following connec­tions (see Fig. 1): – S upply port (1) 1 – Pressure output (2) 9
• Install a silencer at venting (3) (item aJ )orremovethe exhaust with ducted tubing.
Note.......................................................
The posit ion of the pneumatic connections depends on the variant orde red.
4.3 Electrical
Note.......................................................
Make sure that the cable is laid as follows: – not squashed –notbent –notstretched.
• U se accessories from Fest o (see “Accessories”): – p lug socket with cable
or – socket cable, ready-to-use. This ensure s that the specified protec tion class IP65 and EMC are achieved.
Note......................................................
Toensure E MC safety,the device must be earthed as follows:
• Use the earth terminal (see Fig. 1).
• U se the following earthing accessories (included in delivery): – Self-cutting screw – Flat plug –Contact disc
• Connect the circuitry of the VPPE-... as show in the circuit diagram. Preferably use cable from Fest o.
1
2
3
5
4
PIN no. Colour1)VPPE
1 brown +24 VDC
2 white Analogue input – setpoint value / – w
3 blue GND
4 black Analogue input + setpointvalue / + w
(0 … 10 V or 4 … 20 mA)
5 grey Switch output (24 V) o r
analogue output (0 … 10 V or 4 … 20 mA) + actual value / X
OUT
1)
Colour is only valid for accessory cable from Festo
5 Commissioning
Note......................................................
• The VPPE-... interprets setpoint signals less than
0.1 V as 0 V and setpoint signals less than 4.16 m A as 4 mA. In this case, the output pressure is set to 0 ba r through activation of the vent ilation valve. Asaresult,aclearvalveconditionisassuredat w=0.
• Safety position: In case of setpoint cable break of the voltage variant, the output pressure is set to 0 bar. In case of setpoint cable break of the current variant, or in case of loss of power supply, the output pressure re mains uncon­trolled. Leakage produc es a change in pressure in th e long term.
• Connect t he VPPE-. .. with a se tpoint signal. The VPPE has a so-called “differential input”. The setpoint signal is applied t o the contact Pin 2 and Pin 4, whereby the lower potential must be connected to contact Pin 2 and the higher potential to contact Pin 4. Contact Pin 2 (– setpoint)can be connected to contact Pin 3 ( G ND).
• A pply current t o the VPPE-... with direct current (Supply voltage U
V
=24VDC±10%).
• P re ssurise the VPPE-... with a supply pressure (p1 ) at least 1 bar higher than the maximum desired output pressure. A proportional output pressure ( p2) is set automatically.
The following out put pressure range is then assigned t o the set point signal range 0 … 1 0 V or 4 … 20 mA:
Setpoint
Output pressure range of the variant
psig
nal range
2bar 6bar 10 ba r
0…10Vor 4…20mA
0.02 … 2 bar 0.06… 6 bar 0.1… 10 bar
5.1 Recommended par ameter sets
The valves in all pressure variants are set at the factory with Preset 2.
Preset
Preset
recommendation
1 2 3
Consumingdevice volumes <0.5l ~0.5l >0.5l
5.2 VPPE display and meaning
Notes on the following table: Preset, control behaviour: Youc an select the desired factory parameter set in the menu on the VPPE (Pr1, Pr2, Pr3).
Dis­play
Meaning Description
[An] Analogu e Output: Analogue
[bAr] bar Pressure unit
[Eco] ECO mode Display sw itch-off (adjustabl e)
[Frc] Force Manual se tpoint i nput
[HY] Hysteresis Spread, switch difference
[in] Setpoint value Whenkey is pressed (1 sec.), [in]
appears. When the key is released, the setpoint value is displayed.
[Loc] Lock Input blocked with Pin code
[n.Hi] Switch normally
closed
Contact (normally closed)
[n.Lo] Switchnormally
open
Contact (normally open)
[OFS] Offset Zeropointlift(outputpressure
withoutsetpointvalue)
[out] Actual value When key is pre ssed (1 sec .), [out]
appears. When the key is released, the actual value is displayed.
[PA] Kilo pascal Pressure unit ( in KPa !)
[Pin] Pin code Enter val ue for locking (1 … 999)
[Pr1] Preset 1 (see section 5.1)
[Pr2] Preset 2 (see section 5.1)
[Pr3] Preset 3 (see section 5.1)
[PSi] psi Pressure uni t
[rES] Reset
(factory setting)
Switch on device with pressed + + Edit keys. Obse rve th e instructionin chapter 10.
[rnG] Range Pressure range adj ustment
[Snr] Display series
number
Switch on device with pressed + Edit keys: Series number is displayed to 6 places, first [xxx.] than [xxx],alternating approx. 2 sec.
[SOF] Display software
version
Switch on device with pressed + Edit keys: Software v ersion appears
[SP] Switching point (see section 5.3)
[SP.H] Switching point high Top switching point (see section 5.3)
[SP.L] Switchingpoint low Bottom switching point
(see section 5.3)
[SP.O.] Set point ok Setpointvalue reached
(see section 5.3)
[unL] Unlock Lock rem ove d
Threshold value comparator
(see section 5.3)
Window comparator (see section 5.3)
[._..] ECOmode activated After x seconds (adjustable), a line
moves thr ough the display [._..]
VPPE-3-1-1/8-...-E1 (LED-Display)
Operating instructions
Original: de
Festo AG & Co. KG Postfach D-73726 Esslingen Phone: +49/711/347-0 www.festo.de
0909a 749 698
5.3 Configuringthe output
Dependingon the variant ordered, the actual vale is displayed at the analogue output [An] 0 … 10V or 4…20mA. If a switch output is chosen, the following modes can be selected: Threshold value, windo w compar ator, or SP.O.. Switching points (SP...)and hysteresis (HY) The swit ching point is o nly active when a switch ing point or window comparator is active. The value of the hysteresis specifies the tolerance in which t he cont rol deviatio n can move without causing a singal change at the output (Pin 5). Setting SP.O. The SP.O.signal means that the setpoint value has been reached in the range (+/-) of the set hysteresis.
With threshold value comparator setting
P
1
0
Hy
OUT
SP
OUTOUT
Switching character istic (nor mally open)
P
1
0
SP
Hy
OUT
Switching character istic NC (normally closed)
With window comparator setting
Hy Hy
P
1
0
OUT
SP.L
SP.H
Switching character istic (nor mally open)
P
1
0
OUT
SP.L SP.H
Hy
Hy
Switching character istic NC (normally closed)
With setting SP.O.
Hysteresis
Setpoint value
Actual value
SP.O. signal
U[V]
p[bar]
t
t
5.4 Display symbols menu
Notes on the following table: [x.xx] = pres sure display (actua l value o r setpoint value) [ ... ] =Ent er value (with f lashing display)
– The main menu se lc t ion can be made in only one
direction with th e Selec tion key
.
– Wit hin a menu opt ion, the selectio n can usually be
made with the
or key.
– I f no selection is made within 10 s ec. in the main
menu or 80 sec. wit hin a menu opt ion, the display automatica lly jumps back to the basic position, exception[Frc].
Menu = main menu selection [x.xx] = value input (setpoint value/actual value) Further in the menu = press Edit key With flas hing display (grey bac kground) = selection option with keys

Change value [ ... ] = with keys Selection/sa ve value = press Edit ke y
No.
Menu Selection possibility 
1
[x.xx]
(1 sec.) = [in] (1 sec.) = [out]
2 [Pr...]
[Pr...] Pr1 Pr2 Pr3
3 [bAr]
[bAr] bAr PA PSI
4 [OFS]
[ ... ]
5 [rnG]
[ ... ]
6 [Frc] 0.00… 10.0 V (volta ge varia nt)
4.00 … 20. 0 mA (curr ent varia nt)
[ ... ]
7 [An]
[An] SP.O.
SP SP.L HY
[ ... ] [ ... ] [ ... ]
[ ... ] [ ... ] [ ... ]
HY SP.H [n.Lo/ n.Hi]
[ ... ] [ ... ] [n.Lo/ n.Hi]
[ ... ] [ ... ]
[n.Lo/ n.Hi] HY
[n.Lo/ n.Hi] [ ... ]
[ ... ]
n.Lo/ n.Hi
n.Lo/ n.Hi
8 [Eco]
[OFF]
[OFF] [1 … 999] sec.
9 [Pin]
[OFF]
[OFF] [1 … 999]
Back to no. 1
6Operation
Note......................................................
• Make sure, when switching off the VPPE-. . . , that first the set value voltage, then the supply voltage and finally the supply pressure a re switched off.
The green status LED lights up when the actual value is equal to or in a range of ±1 % (FS) of the setpoint value.
Lock [Loc] – unlock [unL] If a Pin code was entered with [ Pin], [Loc] is shown in the displayandtheeditmodeislockedviathePincode. If a flashing [0] appears, enter the correc t Pin. After the correct Pin is entered, [unL] is displayed. If the e ntry is incorrect, the VPPE jum ps to the basic po sition.
7 Care and maintenance
• Clean the housing of the VPPE-... with a soft cloth only. The perm itted cle aning agent is a mild s oap- water solution, max. 50 °C.
8 Accessories
Note......................................................
You can find product acc essories under:
http://www.festo.com/catalog
9 Eliminating faults
Faul t
Possible caus e Re medy
VPPE-... does not
No powe r, LED does not light
Check co nnection o f the 24 VDC power supply
react
No set value voltage Check control unit;
check connection
VPPE-...defective Sendthedevicetothe
Festo repair service
Flow vol ume too low
Connectio n are narrowing the flo w diameter (swivel fittings)
Use an alternat ive connection
Pressure increase to o slow
Large cylinder volumes andlongtubinglength
– Cho ose different
parameter set
Pressure constant despite changed setpoint input
– Break of the supply
cable(thelastoutput pressure se t remains intact uncontrolled). Slow pressuredrop due to leakage
– Too little supply
pressure p1
– Replace supply cable
– Increase supply
pressure
10 Reset to factory setting
Note......................................................
By resetting to factory setting, the current settings are lost.
– If needed, note down these settings before
resetting.
Reset [rES] returns settings to factory setting. To do this, press a nd hold the following keys “ +  +Edit”andthen switch on the device. Then the following parameters are set:
Para­meters
Setting / value
x.xx Permanent display (actual value/setpoint value)
Pr2 (universal control behaviour)
bar bar
OFS 000
rnG for 10 bar ty pe: 10.0
for6bartype: 6.00 for2bartype: 2.00
Frc Disp lay show s current p ressure at pressure output (p2)
An Output: Analogue
Eco OFF
PIN OFF
11 Technicalspecifications
Type
VPPE-3-1-1/8-...-E1
Design Proportional pressureregulating valve
Mounting position Asdesired, preferably vertical
(electronics upward)
Medium Filtered, non-lubricated compressed air
(filter fineness min. 40 μm), no condensationallowed
Pressure ranges
2bartype 6bartype 10 bar type
– Permitted supply
pressure
3…4bar 6…8bar 6…11bar
– Control range 0.02 … 2 bar 0.06… 6 bar 0.1 … 10 b ar
Supply pressure p1 at least 1 bar above output pressure p2
Standard rated flow see Fig. 2
Totalleakage in new condition
<5l/h
Connectio ns G1/8
Rated width – Pr essurisation –Venting
5mm
2.5 mm
Protection class IP65 in combination with connector socket
according to accessories.
Perm. temp. range – Surroundi ngs –Storage –Medium
0…+60°C –10… +60°C +10… +50 °C
Electrical connection Plug contact M12x1, 5-p in
Permitted supply voltage
24 VDC ±10 %
Setpoint value size Input resistor
0…+10V/4…20mA 10 k(voltage)/ 250 (cu rrent)
Load actual value output
min. 2 k(voltage) max. 500 (current)
Linearity fault max. ±1 % FS (full scale) at 24 VDC and
25 °C
Residual ripple 10 %
Vibration and sho ck –Vibration
–Shock
Tested as per DI N/IEC 68 / EN 60068 Part 2-6, Severity class 2 Tested as per DI N/IEC 68 / EN 60068 Part 2-27, Severity class 2
Power consumption max. 4.2 W
Electromagnetic compatibility – EMC interference
emissionand resistance
See conformity declaration www.festo.co m CE conformity for industrial installations fulfilled
Materials –housing –cover – seals –lubrication
Al PA NBR silicon-free
Weig ht approx.390 g
VPPE-3-1-1/8-6-...
VPPE-3-1-1/8-2-...
VPPE-3-1-1/8-10-...
Fig. 2