Festo MPA-L Series, MPA-L-MPM-VI, MPA-L-FB-VI Description

MPA−L valve terminal
Description Pneumatic MPA−L
Valve terminal
Type: MPA−L−MPM−VI MPA−L−FB−VI
Description
556 354 en 1008NH [722 279]
Contents and general safety instructions
Original de. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Edition en 1008NH. . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
Designation P.BE−MPAL−EN. . . . . . . . . . . . . . . . . . . . . . . . . .
OrderNo. 556
354. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E (Festo AG&Co. KG, D73726 Esslingen, Federal Republic of Germany, 2010) Internet:http://www.festo.com E−Mail: service_international@festo.com
The copying, distribution and utilization of
this document as well as the communication of its contents to others without express authorization is prohibited. Offenders will be held liable for the payment of damages. All rights are reserved, in particular the right to carry out patent, registered design or ornamental design registration.
Festo P.BE−MPAL−EN en 1008NH
I
Contents and general safety instructions
®
TÜV
is a registered trade mark of the respective trademark owner. . . . . . . . . . . . . . . . .
in certain countries.
VDE
®
is a registered trade mark of the respective trademark owner. . . . . . . . . . . . . . . . .
in certain countries.
Torx
®
is a registered trade mark of the respective manufacturer in. . . . . . . . . . . . . . . . .
certain countries.
II
Festo P.BE−MPAL−EN en 1008NH
Contents and general safety instructions

Contents

Intended use VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Areas of application and approval by authorities VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Target group VIII . . .
Service VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Structure of this manual VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Important user instructions IX . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terms and abbreviations XI . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
1. Overview of components 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 The valve terminal MPA−L 1−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Valve terminal design 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Electrical multi−pin connection 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.1 Versions of the connector 1−6 . . . .
1.3.2 Versions of the IP protection class 1−7 . . . . . . . . . . . . . . . .
1.4 Electrical connection via CPX terminal 1−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5 Description of components 1−9 . .
1.5.1 Valves 1−9 . . . . . . . . . . . . .
1.5.2 Main and additional power supply 1−10 . . . . . . . . .
1.5.3 Pilot air supply 1−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5.4 Exhaust air 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5.5 Sub−bases and pressure zone separation 1−13 . . . . . . . . . . . . . . . . . . . .
1.5.6 Vertical stacking 1−15 . . . . . . . . . . . . . . . .
1.5.7 Pressure regulating plates 1−16 . . . . . . . . . . . . . . . . . . . . . . .
1.6 Connecting elements 1−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7 Display and control elements 1−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7.1 Identification system" (as per catalogue) 1−23
1.7.2 Manual override (MO) 1−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7.3 Pressure regulator 1−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7.4 Switching status
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
displays for valves 1−25 . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . .
. . .
. . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . .
. . . . . . . . .
. . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . .
2. Mounting 2−1 . . . . . . . . . . . . . . . . . . . . . .
2.1 General instructions on mounting/dismantling 2−3 . . . . . . . . . . . . . . .
Festo P.BE−MPAL−EN en 1008NH
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . .
III
Contents and general safety instructions
2.2 Installation/removal on an H−rails 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Wall installation/removal 2−9 . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1 Standard mounting points of the valve terminal 2−9 . . . . . . . . . . . . .
2.3.2 Additional mountings of the valve terminal 2−11 . . . . . . . . . . . . . . . . . . .
2.4 Fitting/removing optional inscription label holders 2−13 . . . . . . . . . . . . . . . . . . .
. .
.
3. Installation 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .
3.1 Compressed air preparation 3−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1 Operation with unlubricated compressed air 3−3 . .
. . . . . . . . . . . . . . .
3.1.2 Operation with lubricated compressed air 3−3 . . . . . . . . . . . . . . . . . . . .
3.2 General instructions on installation 3−6 . . . . . .
3.3 Connecting the valve terminal MPA−L 3−7 . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
3.3.1 Pilot control of the solenoid coils (pilot air supply) 3−7 . . . . . . . . . . . . .
3.3.2 Valve terminal MPA−L with pressure zone separation 3−8 . . . . . . . . . .
3.3.3 Setting the pressure regulating valve 3−10 . . . . . . . . . . . . . . . . . . . . . . .
3.3.4 Vacuum/low pressure operation 3−11 . . . . . . . . . . . . . . . . . . .
. . . . . . . .
3.4 Connecting the pneumatic lines 3−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.1 Installation/replacement of the
3.4.2 Laying the tubing 3−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
threadless car tridges 3−15 . . . . . . . . . .
. . . .
3.4.3 Common pneumatic lines 3−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Connecting the electric cables 3−21 . . . . . .
3.6 Address assignment of the valves 3−24 . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
3.6.1 Valve terminal MPA−L with multi−pin plug connection 3−28 . . . . . . . . . . .
3.6.2 Valve terminal MPA−L with CPX terminal 3−28 . . . . . . .
4. Commissioning 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 General Information 4−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . .
4.1.1 Prior to commissioning 4−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2 Pressure build−up in the
overall supply 4−3 . . . . . . . . . . . . . . . . . . . . . .
4.2 Checking the valves and the valve/actuator combination 4−6 . . . . . . . . . . . . . . .
4.3 Mounting/removing the optional manual
override cover cap 4−11 . . . . . . . . . . . .
.
IV
Festo P.BE−MPAL−EN en 1008NH
Contents and general safety instructions
4.4 Troubleshooting 4−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4.1 Switching status
4.4.2 Impairment of functions 4−13 . . . . . . . . . . . . . . . . . . . . . . . . . . .
indicator of the solenoid coils 4−13 . . . . . . . . . . . . . . .
. . . . . . .
4.4.3 Operating states of the pneumatic system 4−15 . . . . . . . . . . . . . . . . . . .
5. Conversion and maintenance 5−1 . . . . . . . . . . . . . . . .
5.1 General preventive action 5−3 . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
5.2 Maintaining the valve terminal MPA−L 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.1 Clean
5.2.2 Replacing valves or cover plates 5−5 . . . . . . . . . . . . . .
or replace flat plate silencer 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
5.3 Conversion of the MPA−L valve terminal 5−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.1 Tie rod system 5−7
5.3.2 Exchange sub−base, supply plate or extend or exchange
right−hand end plate 5−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.3 Replace the electronic module 5−14 . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
5.3.4 Conversion between ducted and unducted exhaust air 5−15 . . . . . . . . .
5.3.5 Conversion between internal and external pilot air supply 5−16 . . . .
. . .
5.3.6 Converting the valve terminal MPA−L to different pressure zones 5−18 .
5.3.7 Conversion of the left−hand end plate of IP40 on IP65 cover 5−19 . . . . .
5.3.8 Conversion of the outlet direction of the multi−pin cable 5−19 . . . . . . . .
5.3.9 Conversion of the end plate
between multi−pin and
CPX connection 5−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Replace the pneumatic interface 5−24
A. Technical appendix A−1 . . . . . . . . . . . . . .
A.1 Technical data A−3 . . . . . . . . . . . . . . . . .
A.2 Festo accessories A−12 . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. Supplementary overview of components B−1 . . . . . . . . . . . . . . .
. . . . . . . . . . . .
B.1 Overview of valve position components B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Index C−1 . . . .
Festo P.BE−MPAL−EN en 1008NH
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V
Contents and general safety instructions
VI
Festo P.BE−MPAL−EN en 1008NH
Contents and general safety instructions

Intended use

The MPA valve terminals are intended for fitting into a machine or automated system and must be used exclusively as follows:
In industrial applications
In original status without unauthorised modifications.
Only the conversions or modifications described in the documentation supplied with the product are permitted.
In perfect technical condition
If used together with additional ponents, such as actuators, the specified limits for pressures, temperatures, electrical data, torques etc. must be observed.
In addition to the safety instructions in this manual always observe the regulations of the trade associations and the German Technical Control Board (TÜV) and the VDE condi tions or corresponding national conditions on−site.

Areas of application and approval by authorities

The product fulfils the requirements of the EU directives and is marked with the CE marking symbol.
Standards and test values, which the product must comply with and fulfil, can be found in the section A.1 Technical data". The product−relevant EC directive can be found in the declaration of conformity.
commercially available com
Festo P.BE−MPAL−EN en 1008NH
VII
Contents and general safety instructions

Target group

This manual is intended exclusively for technicians trained in control and automation technology.

Service

Please consult your local Festo repair service if you have any technical problems.

Structure of this manual

This manual contains general basic information on fitting, installing and commissioning the valve terminal MPA−L, as well as on its mode of operation.
VIII
Festo P.BE−MPAL−EN en 1008NH
Contents and general safety instructions

Important user instructions

Danger categories
This description contains instructions on the possible dangers which can arise if the product is not used correctly. These instructions are marked (Warning, Caution, etc.), printed on a shaded background and marked additionally with a picto gram. A distinction is made between the following danger warnings:
Warning
... means that failure to observe this instruction may result in serious personal injury or material damage.
Caution
... means that failure to observe this instruction may result in personal injury or material damage.
Festo P.BE−MPAL−EN en 1008NH
Note
... means that failure to observe this instruction may result in material damage.
Additio na l ly, the following pictogram designates text passages, which describe activities with electrostatically sensitive devices:
Electrostatically sensitive devices: inappropriat e handling can result in damage to components.
IX
Contents and general safety instructions
Identification of special information
The following pictograms designate text passages that contain special information.
Pictograms
Information: Recommendations, tips and references to other sources of information.
Accessories: Information on necessary or useful accessories for the Festo product.
Environment: Information on environmentally friendly use of Festo products.
Text designations
· Bullet points indicate activities that may be carried out
in any sequence.
1. Numerals indicate activities that must be carried out in the sequence specified.
Arrowheads indicate general listings.
X
Festo P.BE−MPAL−EN en 1008N H
Contents and general safety instructions

Terms and abbreviations

The following product−specific terms and abbreviations are used in this manual:
Term/abbreviation
Blanking plate Plate without valve function for sealing vacant valve positions on
Cartridge fitting Plug connector for connection of the power supply cables to the valve
Components Common term for pneumatic interface, multipin sub−base, exhaust
Electronics module Module in the sub−base with an LED and solenoid coil management
End plate Extreme right−hand plate with/without connections for power and
Exhaust plate Plate for ducted exhaust with connection 3/5
MO Manual override
MPA1 Sizes of the solenoid valves: MPA1 = 10 mm wide
Multi−pin plug connection Electrical connection for controlling the valve terminal MPA−L
Pneumatic interface The pneumatic interface is the interface between the modular
Pneumatic module Module consisting of pneumatic Sub−base, electronics module,
Meaning
sub−bases (vacant position).
terminal
plate, silencer, pneumatic sub−base or pneumatic supply plate, end plate, pressure regulator plate, solenoid valve and cover plate
pilot pressure and exhaust air, and extreme left−hand plate with multi− pin plug connection and CPX terminal as well as holes for H−rail and wall mountings.
electrical peripherals of the CPX terminal and the MPA−L pneumatics
solenoid valves or cover plates
Solenoid valves Monostable solenoid valve with a solenoid coil, double−solenoid or
mid−position valves with two solenoid coils and additional variants
Sub−base Plate with working lines 2 and 4 for the mounting of valves and verti
cal stackings
Supply plate Plate for (additional) supply of compressed air to the solenoid valves,
e.g. with several pressure zones.
Festo P.BE−MPAL−EN en 1008NH
XI
Contents and general safety instructions
Term/abbreviation Meaning
Valve terminal MPA−L Modular performance valve manifolds light valve terminal (Type 34)
Vertical stacking Pneumatic components that are installed between the sub−base and
multi−pin plug connection or for CPX−Terminal
the solenoid valve
Tab.0/1: Product−specific terms and abbreviations
XII
Festo P.BE−MPAL−EN en 1008NH

Overview of components

Chapter 1
1−1Festo P.BE−MPAL−EN en 1008NH
1. Overview of components

Contents

1. Overview of components 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 The valve terminal MPA−L 1−3 . . . .
1.2 Valve terminal design 1−4 . . . . . . . . . .
1.3 Electrical multi−pin connection 1−5 . . . . . . . . . . . . . .
1.3.1 Versions of the connector 1−6 . . . . . . . . . . . . . . . . . . . . . . . .
1.3.2 Versions of the IP protection class 1−7 . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 Electrical connection via CPX terminal 1−8 . . . . .
1.5 Description of components 1−9 . . . . . . . . . . . . . . . . . . . . . .
1.5.1 Valves 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5.2 Main and additional power supply 1−10 . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5.3 Pilot air supply 1−11
1.5.4 Exhaust air 1−13 . . . . . . .
1.5.5 Sub−bases and pressure zone separation 1−13 . . . . . . .
1.5.6 Vertical stacking 1−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5.7 Pressure regulating plates 1−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6 Connecting elements 1−20 . . . . . . . . .
1.7 Display and control elements 1−22 . . . . . . . . . . . .
1.7.1 Identification system" (as per catalogue) 1−23 . . . . . . . . . . . . . . . . . . .
1.7.2 Manual
1.7.3 Pressure regulator 1−24 . . . . . . . . . . .
1.7.4 Switching status displays for valves 1−25 . . . . . . . . . . . . . . . . .
override (MO) 1−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . .
. . . . . . . .
1−2
Festo P.BE−MPAL−EN en 1008N H
1. Overview of components
1.1 The valve terminal MPA−L
Festo supports your automation tasks at machine level with the valve terminal MPA−L. The modular structure of the valve terminal MPA−L enables you to match this valve terminal opti mally to your machine or system.
The valve terminal MPA−L provides the following connections:
Common ducts for supply and exhaust air
Electric signals from all
solenoid coils
Working lines (2) and (4) are provided for each valve position on the individual pneumatic sub−bases. The valves are sup plied with compressed air (operating pressure and pilot pres sure) via the common channels and connections in the basic components. The exhaust air (from the valves and the pilot exhaust air)
is also exhausted via these common channels. Further components for compressed air supply are also avail able, e.g. in order to supply pressure zones.
The valve terminal MPA−L is equipped with current reduction. The nominal current of the solenoid coils is then reduced after the high−current phase (switching procedure). The cur rent reduction offers
the following advantages:
The valve terminal MPA−L has a lower power consumption
The power unit for the voltage supply to the valve ter
minal MPA−L can be designed more economically depend ing on the individual case
The solenoid coils have less leakage power and produce
less waste heat
Festo P.BE−MPAL−EN en 1008NH
1−3
1. Overview of components

1.2 Valve terminal design

The valve terminal MPA−L consists of the following pneumatic and electric components: The most important components are shown in Fig.1/1.
1
2
3
1 Multipin sub−base with cover (here:
IP40 cover)
2 Pneumatic supply plate with exhaust
plate for ducted exhaust air (3/5)
3 Sub−base with electronic module and
valve or blanking plate
5
4
4 Sub−bases, 4 off set, with common
electronic module and valves or blanking plates
5 Vertical stacking (here: Pressure
regulator plate with installed valve and optional pressure gauge)
6 Right−hand end plate
6
Fig.1/1: Main components of the valve terminal MPA−L
1−4
Festo P.BE−MPAL−EN en 1008N H
1. Overview of components
The following operating modes can be used  independently of valve type:
Standard operation with one or more pressure zones
Reversible operation with compressed air supply via
connections (3), (5) and exhaust via port (1)
Low−pressure operation at 0 ... 3 bar
Vacuum operation at −0.9 ... 0 bar
1.3 Electrical multi−pin connection
The electrical connection of the solenoid coils is made cen trally via a multi−pin plug in the left−hand end plate, which is available in various variants for the he valve terminal MPA−L (see Tab.1/1). One or two solenoid coils per v alve position can be controlled. Each solenoid coil occupies one pin of multi−pin plug.
the
Festo P.BE−MPAL−EN en 1008NH
1−5
1. Overview of components

1.3.1 Versions of the connector

Multi−pin connection, Type of left−hand end plate
Plug type Number of controllable
solenoid coils
Sub−D with 9pins 1, 2, 3, ... 8
Sub−D with 25pins 1, 2, 3, ... 24
Sub−D with 44pins 1, 2, 3, ... 32
Terminal strip
1)
1, 2, 3, ... 32
Ribbon cable
1) Note that all cables to a cable harness must be grouped to ensure EMC conformity.
2) Note that all 0 V−/24V supply cables must be used and grouped to a cable harness.
2)
1, 2, 3, ... 32
Tab.1/1: Multi−pin plug types of the left−hand end plates
1−6
Festo P.BE−MPAL−EN en 1008N H
1. Overview of components

1.3.2 Versions of the IP protection class

For variants with sub−D plugs the multipin connection can be implemented with various cover types (see Tab.1/2).
Multipin sub−base
Cover types for sub−D plug
IP65 cover: closed cover, Protection class IP65, with pre−prepared cable Exclusively for the sub−D plug with 25−/44 pins.
IP40 cover: open cover, protection class IP40 (In this case: Sub−D with 25 pins
Tab.1/2: Multipin sub−base and cover types
.
Festo P.BE−MPAL−EN en 1008NH
1−7
1. Overview of components

1.4 Electrical connection via CPX terminal

The electrical interface of the solenoid coils on the CPX ter minal is made centrally via the pneumatic interface (see Fig.1/2). Per valve position one or two solenoid coils and within the valve terminal MPA−L maximum 32solenoid coils can be controlled via the CPX terminal.
1 CPX bus node
2 Pneumatic inter
face
1
3 Optional: addi
tional CPX module
4
4 Multipin sub−
base of the CPX terminal
2
3
Fig.1/2: Electric components of the valve terminal MPA−L with CPX terminal
1−8
Festo P.BE−MPAL−EN en 1008N H
1. Overview of components

1.5 Description of components

1.5.1 Valves

The valve terminal MPA−L can be fitted with 2x2/2−, 2x3/2−way valves, 5/2−way valves and 5/3−way valves and further valve types (see Tab.  1 /3 ).
Valve labelling The valves on the MPA−S valve terminal are marked by
identification codes (see Tab.1/3). By means of this identifi  cation on the top of the valve, you can ascertain the ment fitted on your valve terminal MPA−L.
equip
ID code
B 5/3−way valve, mid−position open
D Two monostable 2/2−way valves, normally closed, pneumatic spring return
DS Two monostable 2/2−way valves, normally closed, pneumatic spring return
I 5/3−way valve, mid−position exhausted
R 5/3−way valve, mid−position closed
H Two monostable 3/2−way valves, control side 12 normally open, control side 14
HS Two monostable 3/2−way valves, control side 12 normally open, control side 14
I Tw o 2/2−way valves, normally closed, pneumatic spring return
J 5/2−way double pilot valve
K Two monostable 3/2−way valves, normally closed, pneumatic spring return
KS Tw o monostable 3/2−way valves, normally closed, pneumatic spring return
Valve
normally closed, pneumatic spring return
normally closed, pneumatic spring return
With dual−pressure operation: Operating pressure via connection (1) or connection (5) With vacuum operation: Operating pressure at connection (1), Vacuum at connection (5) (e.g. for vacuum switching with ejector pulse)
Festo P.BE−MPAL−EN en 1008NH
1−9
1. Overview of components
ID code Valve
M Monostable 5/2−way valve
N Two monostable 3/2−way valves, normally closed, pneumatic spring return
NS Two monostable 3/2−way valves, normally open, pneumatic spring return
W Monostable 3/2−way valve, open in basic position, external compressed air
X Monostable 3/2−way valve, closed in basic position, external compressed air
L Blanking plate for sealing an vacant valve position
supply via connection 2
supply via connection (4)
Tab.1/3: Identification codes of the valves
Further information on the valves can be found in AppendixB.

1.5.2 Main and additional power supply

The main supply of the valve terminal with operating pressure can be made via a pneumatic supply plate (see Fig.1/3) or via the right−hand end plate with lateral ports (Tab.1/4 below).
1−10
Festo P.BE−MPAL−EN en 1008N H
1. Overview of components
1 Supply plate
2 Exhaust plate for
ducted exhaust air

1.5.3 Pilot air supply

2
1
Fig.1/3: Pneumatic supply plate
The pneumatic supply plate can also be used for additional power supplies. These are, forexample, necessary in the case of valve terminals operated with several pressure zones or when a large number of valves on the valve terminal are switched simultaneously to flow.
Festo P.BE−MPAL−EN en 1008NH
The pilot control of the solenoid coils is supplied with internal or external pilot air. This pilot air is made available for the complete valve terminal (also via the pressure zones) via the right−hand end plate (see Tab.1/4).
A selector plate on the right−hand end plate makes it possible to branch the pilot take it from the separate supply via the port (12/14).
Note
Internal pilot air supply is only permitted if the operating pressure of the last pressure zone (at the right−hand end plate) is between 3 and 8 bar .
air internally from the supply port (1) or to
1−11
1. Overview of components
End plate type Properties
End plate without connections at side
space−saving, low end plate with front, round selector
plate
separate pneumatic supply plate required for the valve
terminal
End plate with exhaust ports at side
high end plate with upper, square selector platesupply connections (1), (3) and (5) are integrated at the
side
Tab.1/4: Right−hand end plate versions
The way in which the pilot control of your valve terminal is set can be determined from Tab.1/5. The conversion between the internal and external pilot air supply is described in Chapter 5.3.5.
1−12
Festo P.BE−MPAL−EN en 1008N H
1. Overview of components
Pilot control variant
Properties Internal pilot air supply External pilot air supply
Identification on the end plate/ Setting of the selector plate
Type of pilot air supply Internally from the supply
Requirement The operating pressure must be
Int" Ext"
port(1) distributed operating pressure
in the range 3...8bar and be free of pressure fluctuations.
Tab.1/5: Features of the pilot control variants

1.5.4 Exhaust air

The exhaust (3) and (5) of the air is exhausted together via the flat plate silencer and the exhaust plate or separately via the right−hand end plate with ports at the side.
The pilot exhaust air (82/84) is led to a connection on the right−hand end plate and can either be ducted there hausted via a silencer.
1.5.5 Sub−bases and pressure zone separation
Externally via the pilot connection (12/14) supplied, separately controllable pressure (3...8 bar )
The operating pressure can be below 3bar and above 8bar , so long as separately controlled pilot pressure (3...8bar) is availabl e.
or ex
Festo P.BE−MPAL−EN en 1008NH
The valves of valve terminal MPA−L are supplied pneumati cally via the sub−bases and via the electronic module that is installed in the sub−base (see Fig.1/4).
In addition to the individual sub−bases there are also the 4 off sub−bases with common 4 off electronic module.
1−13
1. Overview of components
1 Sub−base
2 Electronics
module
2
1
Fig.1/4: Sub−base with electronic module
In addition valves within a valve terminal MPA−L can be sup plied with different pressures by creating different pressure zones. The separation of the pressure zones is achieved by special sub−bases. In each case the valve mounted to the right of the special sub−base belongs to the next (following to the right) pressure zone, which is the valve mounted on the special sub−base in the current pressure zone.
The sub−bases with integrated pressure zone separation are in various versions with corresponding identification (see Tab.1/6):
on
1−14
Festo P.BE−MPAL−EN en 1008N H
1. Overview of components
Sub−base design MPA1
Supply duct (1) separated
Exhaust ducts (3) and (5) separated
Supply channel (1) and exhaust ducts (3) and (5) separate
Type: VMPAL−AP−...−T1
Type: VMPAL−AP−...−T135
Type: VMPAL−AP−...−T135
Tab.1/6: Variants of the sub−bases with integrated pressure zone separation
Pressure zone separation of the pilot channels (12) and (14) is not provided, as on the valve terminal MPA−L the air supply for the pilot control of the valves is supplied centrally via the right−hand end plate.

1.5.6 Vertical stacking

Festo P.BE−MPAL−EN en 1008NH
You can fit further pneumatic components to each valve position between the sub−base and the valve. These vertical stackings enable you to implement certain additional func tions as desired.
1−15
1. Overview of components
Components
Tab.1/7 shows the main structure and possible components of the vertical stacking.
Directional control valves
Vertical stacking, optional
Sub−base Type VMPAL−AP−... with electronics module
See chapter  1.5.1.
 Pressure regulator plate
Type VMPA...B8−R... C2−C−... (Pressure gauge optional), see Chapter 1.5.7
 Pressure shut−off plate, Type VMPA1−HS
Tab.1/7: Components of the vertical stacking

1.5.7 Pressure regulating plates

Mode of operation A pressure regulator plate with adjustable pressure regulator
can be installed between the sub−base and the valve in order to control the force of the connected actuators. This pressure regulator maintains an essentially constant output pressure (secondary side) independent of supply pressure (primary side) and air consumption.
Identification The pressure regulator plates of
marked on the valve terminal MPA−L with the Ident. code. This is marked on the side of the pressure regulator plate. Using Tab.1/8 you can identify the pressure regulator plates.
1−16
the vertical stacking are
Festo P.BE−MPAL−EN en 1008N H
1. Overview of components
ID
Vertical stacking component
code
PF Pressure regulator plate for connection (1), supply pressure 6 bar
PH Operating pressure regulator plate for connection (2), supply pressure 6 bar
PG Work pressure regulator plate for connection (4), supply pressure 6 bar
PA Pressure regulator plate for connection (1), supply pressure 10 bar
PC Operating pressure regulator plate for connection (2), supply pressure 10 bar
PB Work pressure regulator plate for connection (4), supply pressure 10 bar
T Pressure gauge for pressure regulator plate
Tab.1/8: Identification of the regulator plates in the type code
The circuit symbol of the pressure regulating valve is provided in appendix B, Tab.B/5.
P pressure regulating valve(identification PF, PA)
Supply process The P pressure regulating valve regulates the pressure in
front of the valve in duct (1)/(P). This provides the same regulated air pressure in channels (2) and (4).
Exhaust procedure The exhaust flow is from channel (2) to channel (3) and from
channel (4) to channel (5) through the pressure regulator
the valve terminal.
plate to
The advantages of this pressure regulating valve are:
The pressure regulating valve is not affected by exhausting,
since the pressure is regulated upstream of the valve.
The pressure regulating valve can always be adjusted
because the pressure from the valve terminal is always present.
Festo P.BE−MPAL−EN en 1008NH
1−17
1. Overview of components
Application examples:
An equal air pressure is required at working lines (2)
and (4).
A lower air pressure (e.g.3bar) than the operating pres 
sure present on the valve terminal (e.g.8bar) is required.
A or B pressure regulator (identifier PH, PG, PC, PB)
Supply process The work or operating pressure regulator regulates the
relevant pressure of the air (see 1 in Tab.1/9) when the pressure medium has flowed through the valve. The exhaust air is passed through the pressure regulator plate and is switched to the relevant exhaust duct in the valve (see 2 in Tab.1/9).
Exhaust
procedure During exhausting the air is passed unregulated through the
valve and the pressure regulator plate to the valve terminal (see 3 in Tab.1/9).
Pressure regulator
Pressurizing Exhaust process:
regulated pressure of the work
exhaust vented via the pressure regulator plate 2
air 1
A pressure regulating valve
B pressure regulating valve
in channel (4) from channel (2) to channel (3) from channel (4) to channel (5)
in channel (2) from channel (4) to channel (5) from channel (2) to channel (3)
Tab.1/9: Mode of operation of the A and B pressure regulator
Restrictions:
The exhaust flow in the regulating direction is limited by
the pressure regulating valve.
1−18
unregulated exhaust vented via the regulator 3
Festo P.BE−MPAL−EN en 1008N H
1. Overview of components
The pressure of the air in channel (2) can only be set and
read on the pressure gauge when the valve is in the switch position: Flow from (1) to (2).
Application examples:
If different air pressures are required at ports (2) and (4)
instead of the operating pressure of the valve terminal.
Fig.1/5
shows the following switching position of the operat  ing pressure regulator: The air is passed from channel (1) through the pressure regu lator plate and the valve to the operating pressure regulator, where it is regulated and then passed to connection (2) of the sub−base. The unregulated exhaust air is then fed channel (4) through the pressure regulator plate and then to channel (5) and vented.
via
2
1
4
1 Control regulator within the pressure
regulator plate
2 Valve
Fig.1/5: B pressure regulating valve
Festo P.BE−MPAL−EN en 1008NH
3
3 Pressure regulator plate
4 Sub−base
1−19
1. Overview of components

1.6 Connecting elements

Pneumatic elements The following pneumatic connecting elements can be found
on the valve terminal MPA−L:
1
2
1 Common exhaust port (3/5) Valve"
2 Pilot air connections (12/14) and
(82/84) dependent on the design of the right−hand end plate (see Chapter1.5.3)
Fig.1/6: Pneumatic connecting elements
1−20
3
4
3
3 Supply connections Operating
pressure" (1)
4 Working lines (2) and (4), per valve
Festo P.BE−MPAL−EN en 1008N H
1. Overview of components
Electrical elements The following electrical connecting elements can be found
on the pneumatic components of the valve terminal MPA−L:
1 Sub−D multipin
plug with cable
2 Connection for
functional earth
3
3 Sub−D connection
(here: 25−Pin versions)
2
Fig.1/7: Electric connecting elements of valve terminal MPA−L with multipin connection
1
Festo P.BE−MPAL−EN en 1008NH
1−21
1. Overview of components

1.7 Display and control elements

The following connecting and control elements can be found on the valve terminal MPA−L:
1
5
1
switching status indicator (yellow LEDs) of the valves
3 Inscription panel
4 Slot for inscription label holder
2 Manual override (per pilot solenoid
coil, non−detenting or detenting)
(see Chapter 2.4)
5 Pneumatic interface fault LED
(see Chapter 3.6.2)
Fig.1/8: Display and control elements on the example of the valve terminal with CPX
terminal
2
3
4
1−22
Information on the electrical connection and display compo nents of the CPX bus node is provided in the corresponding Electronics description" (see the system description for your CPX terminal, table Descriptions of the CPX
terminal").
Festo P.BE−MPAL−EN en 1008N H
1. Overview of components
1.7.1 Identification system" (as per catalogue)
Alternatively or supplementary to the inscription labels attached to sub−bases, inscription labels with large surface areas can be attached to the pneumatic interface.
Information about corresponding accessories can be found in the Festo Catalogue (see www.festo.com\catalogue).

1.7.2 Manual override (MO)

The manual override (MO) enables the valve to be actuated when not electrically activated or energised. You only need to switch on the compressed air supply. You should use the manual override especially when commissioning the pneu matic system, in order to check the function and operation of the valve or the
Non−detenting actuation The valve is activated by pushing the manual override.
On release of the manual override the spring−loaded valve switches automatically from the switch position to the normally open position.
valve−actuator combination.
Detenting actuation By turning the manual override clockwise the switch position
by hand.
1−23
Festo P.BE−MPAL−EN en 1008NH
can be detented. It remains actuated until it is reset
These basic functions of the manual override can be changed by installing a corresponding manual override cover cap: With a cover for manual override, code: N, locking is pre vented. The manual override can then only be operated by non−detenting. With a cover for manual override, code: V, the manual over ride
can be safeguarded against undesired operation
The operation of the manual override is described in Chapter4.2.
1. Overview of components

1.7.3 Pressure regulator

On the pressure regulator plate you will find the following display and control elements:
Note
A manually actuated valve (by manual override) cannot be actuated electrically. Conversely, an electrically actuated valve cannot be activated using the mechanical manual override. The valve only returns to the rest position when both actuations are reset.
1 Adjusting screw
for pressure regulator plate MPA1
1
2
2 Pressure gauge
(optional)
3 Connection for
pressure gauge (can be tilted 90)
3
Fig.1/9: Display and control element of the pressure regulator plates
1−24
Festo P.BE−MPAL−EN en 1008N H
1. Overview of components

1.7.4 Switching status displays for valves

There is an LED and a manual override for each solenoid coil. The position of the LED and MO for the relevant solenoid coil is as follows:
2
1
2
1
1 LED and manual override for valve
solenoid coil 14
Fig.1/10: The assignment of LEDs and manual overrides to the solenoid coils
12 12 12 12
14 14 14 14 14 14 14 14
2 LED and manual override for valve
solenoid coil 12
The switching states of the solenoid coils and their signifi cance can be found in Chapter 4.4.1.
Festo P.BE−MPAL−EN en 1008NH
1−25
1. Overview of components
1−26
Festo P.BE−MPAL−EN en 1008N H

Mounting

Chapter 2
2−1Festo P.BE−MPAL−EN en 1008NH
2. Mounting

Contents

2. Mounting 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 General instructions on mounting/dismantling 2−3 . . . . . . . . . . . . . . . . . . . . . . .
2.2 Installation/removal on an H−rails 2−4 . . . . . . . . . . . . . . . .
2.3 Wall installation/removal 2−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1 Standard mounting points of the valve terminal 2−9 . . . . . . . . . . . . . . .
2.3.2 Additional mountings of the valve terminal 2−11 . . . . . . . . . . . .
2.4 Fitting/removing optional inscription label holders 2−13 . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . .
. . . . . . .
2−2
Festo P.BE−MPAL−EN en 1008N H
2. Mounting

2.1 General instructions on mounting/dismantling

Warning
Uncontrolled movements of the connected actuators and loose tubing can cause injury to persons and/or damage to property .
Before carrying out mounting, installation and maintenance work, switch off the following:
 Compressed air supply The operating and load voltage supplies.
Note
Handle all modules and components of the valve terminal MPA−L with great care. Note especially the following:
 The specified torques must be complied with.  Electrostatically sensitive devices.
Therefore, do not touch any contact surfaces.
Festo P.BE−MPAL−EN en 1008NH
Note
Mount the valve terminal MPA−L so that there is sufficient space for heat dissipation and ensure that the maximum limits for temperatures are observed (see Technical specifications").
2−3
2. Mounting
2.2 Installation/removal on an H−rails
The valve terminal MPA−L is suitable for fitting onto an H−rail (support rail as per EN 60715). There is a guide groove on the back for hanging the valve terminal onto the H−rail.
Caution
H−rails with mounted valve terminals can break if they are subjected to vibration exceeding severity level 1:
 0.15 mm Amplitude at 15 ... 58 Hz 2g acceleration at 58 ... 150 Hz This can damage the valve terminal, your machine or your
system.
· In this case use wall mounting.
· Note the permitted values for vibration and shock
(see Tab.A/2 in Appendix A).
2−4
Caution
H−rail mounting without an H−rail clamping unit is not per mitted.
· Secure the valve terminal MPA−L using the H−rail clamping:
against sliding down with the retaining screw intended for this purpose (see Tab.2/1 and Fig.2/1)  against unintentional loosening/opening.
In order to mount the valve terminal onto an H−rail you will require the following mounting kits:
for valve terminal MPA−Ls with multi−pin plug connection:
Mounting,
type CPA−BG−NRH. This kit contains 2 M4x10
screws and 2 clamping elements.
for valve terminal MPA−Ls with CPX terminal: Mounting,
type VMPAF−FB−BG−NRH. This set consists of 3 clamping components, two M4x12 screws and one M4x10 screw.
Festo P.BE−MPAL−EN en 1008N H
2. Mounting
Valve terminal variant Mounting points
MPA−L with multi−pin plug connection
1
MPA−L with CPX terminal
1
2
Tab.2/1: Mounting points for H−rail mounting
Mounting Proceed as follows:
1. Make sure that the mounting surface can support
the weight of the valve terminal MPA−L (weights see appendix A, Tab.A/1).
Required mounting of the H−rail clamping units: In the right−hand end plate
and the multipin sub−base: each with one M4 screw 1 and each with a clamping
1
component
Required mounting of the H−rail clamping units: In the end plates:
each with one M4 screw 1 and each with a clamping component
1
In the pneumatic interface:
one M6 screw 2 and a clamping component
Festo P.BE−MPAL−EN en 1008NH
2. Mount the H−rail (DIN mounting rail EN60715 − 35x7.5;
width 35mm, height 7.5mm). Make sure there is suffi  cient space for connecting the power supply
cables and tubing. Fasten the H−rail(see Fig.2/1) to the mounting surface approximately every 100 mm.
3. Mount the H−rail clamping units at all required mounting points (see Tab.2/1). Make sure that the clamping ele  ment (see Fig.2/1, 3) lies horizontally to the H−rail.
2−5
2. Mounting
1 H−rail
2 Retaining screw
of the H−rail clamping unit
3 Clamping
component of the H−rail clamping unit
4 Mounting surface
4. Hang the valve terminal MPA−L onto the H−rail (see Fig.2/1, arrow A).
5. Swing the valve terminal MPA−L onto the H−rail (see Fig.2/1, arrow B).
(A)
1
2
3
Fig.2/1: Fitting the valve terminal MPA−L onto a H−rail
6. Turn the clamping components to the mechanical lock vertically behind the H−rail (see Fig.2/2, Arrow A) and tighten the locking screws of the H−rail clamping compo nent with1.3Nm ±10%, to protect the v alve terminal MPA−L against slipping or sliding down.
2−6
4
(B)
Festo P.BE−MPAL−EN en 1008N H
2. Mounting
1 H−rail
2
2 MPA−LConnection
blocks
3 Vertically rotated
clamping compo− nent of the H−rails clamping units
1
(A)
3
Fig.2/2: Rear view: Fitting the valve terminal M PA−L onto a H−rail
Additional information on H−rail mounting of the valve terminal MPA−L with CPX terminal can be found in the CPX system description.
Dismantling Proceed as follows:
Festo P.BE−MPAL−EN en 1008NH
1. Loosen the retaining screw of the H−rail clamping unit  (for position of the screws, see Tab.2/1). Make sure that the clamping components
2. Swing the valve terminal MPA−L forwards from the H−rail (see Fig.2/3, arrow A).
3. Lift the valve terminal MPA−L off the H−rail (see Fig.2/3, arrow B).
are horizontal to the H−rail.
2−7
2. Mounting
1 H−rail
2 Retaining screw
of the H−rail clamping unit
3 Clamping
component of the H−rail clamping unit
4 Mounting surface
(A)
1
2
3
4
(B)
Fig.2/3: Dismantling the valve terminal MPA−L
2−8
Festo P.BE−MPAL−EN en 1008N H
2. Mounting

2.3 Wall installation/removal

Note
Installation on uneven, flexible surfaces can damage the valve terminal MPA−L.
· Mount the valve terminal MPA−L only on flat, torsionally
rigid surfaces.
Note
The overloading of mounting holes or natural resonance when vibrating can cause damage.
· In addition to the information about standard mounting
points in Chapter 2.3.1 also observe the information about additional mounting points in Chapter 2.3.2.

2.3.1 Standard mounting points of the valve terminal

The end plates, the multipin sub−base and pneumatic interface contain holes for fitting the terminal onto a wall (see Tab.2/2).
Festo P.BE−MPAL−EN en 1008NH
2−9
2. Mounting
Variant Mounting points
Valve terminal MPA−L with multi−pin plug connection
2
1 2
1
Valve terminal MPA−L with CPX terminal
2
1
2
1
3
Tab.2/2: Standard mounting points for wall mounting
Mounting Proceed as follows:
1. Make sure that the mounting surface is flat and that it can support the valve terminal MPA−L (weights see appendix A, Tab.A/1).
 Multipin sub−base:
two M4 1 or M6 screws 2
2
each
 Right end plate:
two M4 1 or M6 screws 2
1
each
2
1
 End plates:
two M4 1 or M6 screws 2
2
each
 Pneumatic interface:
two M6 screws 3
1
2
1
2−10
2. Make sure there is sufficient space for connecting the power supply cables and tubing.
3. Drill mounting holes in the mounting surface.
4. Fasten the sufficient length to the mounting surface (see Tab.2/2).
valve terminal MPA−L with M4 or M6 screws of
Festo P.BE−MPAL−EN en 1008N H
2. Mounting
Dismantling Proceed as follows:
1. Prevent a hanging−mounted valve terminal MPA−L from falling down before you loosen it from the mounting surface.
2. Loosen the mounting screws (see Tab.2/2).
3. Remove the valve terminal MPA−L from the mounting surface.

2.3.2 Additional mountings of the valve terminal

Valve terminal MPA−L The valve terminal MPA−L has standard mounting points for
wall mounting.
The use of addit i o n a l mountings, type VMPAL−BD, is necessary under the following conditions (Tab.2/3):
For increased vibration/shock loads (limits for vibrations
and shock see Appendix A, Tab. A/2 and:
CPX terminal A
Festo P.BE−MPAL−EN en 1008NH
For valve terminal MPA−Ls that are longer than 200 mm,
additional mountings must be used every 130 mm.
CPX terminal on the valve terminal MPA−L with four or more interlinking blocks must be fitted with additional mounting clips, type CPXBG−RW−..., (see CPX system description).
2−11
2. Mounting
Variant Mounting points
Valve terminal MPA−L with multi−pin plug connection
1
Valve terminal MPA−L with CPX terminal
1
Tab.2/3: Additional mounting for wall mounting
Mounting Proceed as follows:
 For each mounting,
type VMPAL−BD, half of which is clipped into two neighbour ing sub−bases (see also
Information in Appendix A,
Tab.A/2): one M6 screw 1
2−12
1. Attach the mounting to the rear lower surface in such a way that each half of it lies on two adjacent connection/ supply plates.
2. Rotate (1.) the mounting in the direction of the slots of the connection/supply plates (see Fig.2/4).
3. Press up (2.) the mounting on
the connection/supply
plates until the hooks snap into the slots.
Festo P.BE−MPAL−EN en 1008N H
2. Mounting
1 Mounting,
Type VMPAL−BD
2 Slots in
connection and supply plates
1
2
Fig.2/4: Assembly of an additional mounting
1.
2.

2.4 Fitting/removing optional inscription label holders

For identification of the valves or the working ports labels can be attached to the sub−bases, if corresponding Inscrip tion label holders type VMPAL−ST−AP−10, are fitted.
Information about accessories can be found in the Festo Catalogue (see www.festo.com\catalogue).
Mounting Proceed as follows:
Festo P.BE−MPAL−EN en 1008NH
2−13
2. Mounting
1
1. Press the label holder in the recess of the sub−base (see Fig.2/5), until it engages.
2. Press the label from above into the label holder.
1 Support for label
holder on the sub−base
2 Label holder, type
VMPAL−ST−AP−10
3 Label,
Type IBS 6x10
Fig.2/5: Fitting the identification plate
Dismantling Proceed as follows:
· Remove the label holder from the sub−base, using a cross
slot screwdriver if necessary, (see Fig.2/6) by suppor ting on the valve located above.
1 Label holder with
label
3
1
2
Fig.2/6: Dismantling the label holder
2−14
Festo P.BE−MPAL−EN en 1008N H

Installation

Chapter 3
3−1Festo P.BE−MPAL−EN en 1008NH
3. Installation

Contents

3. Installation 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Compressed air preparation 3−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1 Operation with unlubricated compressed air 3−3 . . .
3.1.2 Operation with lubricated compressed air 3−3 . . . . . . . . . . . . . . . . . . . .
3.2 General instructions on installation 3−6 . . . . . . . .
3.3 Connecting the valve terminal MPA−L 3−7 . . . . . . . . . . . . . . . . . . . . .
3.3.1 Pilot control of the solenoid coils (pilot air supply) 3−7 . . . . . . . . . . . . .
3.3.2 Valve terminal MPA−L with pressure zone separation 3−8 . . . . . . . . . . .
3.3.3 Setting
3.3.4 Vacuum/low pressure operation 3−11 . . . . . . . . . . . . . . . . . . . .
3.4 Connecting the pneumatic lines 3−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.1 Installation/replacement of the threadless cartridges 3−15
3.4.2 Laying the tubing 3−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.3 Common pneumatic lines 3−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Connecting the electric cables 3−21 . . . . . . . .
3.6 Address assignment of the valves 3−24 . . . . . . . . . . . . . . . .
3.6.1 Valve terminal MPA−L with multi−pin plug connection 3−28 . . . . . . . . . . .
3.6.2 Valve terminal MPA−L with CPX terminal 3−28 . . . . . . . . .
the pressure regulating valve 3−10 . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . .
. . . . . . .
. . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . .
3−2
Festo P.BE−MPAL−EN en 1008N H
3. Installation

3.1 Compressed air preparation

Caution
Unfiltered or incorrectly lubricated compressed air will reduce the service life of the valve terminal.

3.1.1 Operation with unlubricated compressed air

Caution
Too much residual oil content in the compressed air will reduce the service life of the valve terminal.
If bio−oils are used (oils with synthetic ester or true ester
basis, e.g. rape or methylester), the residual oil content must not exceed 0.1mg/m
When using mineral oils (e.g. HLP oils to DIN 5 1524,
parts1 to 3) or similar oils based on poly−alpha− olefins (PAO), the maximum residual oil content of
3
5mg/m
This avoids operative malfunction of the valves.
must not be exceeded (see ISO8573−1 Class4).
3
(see ISO8573−1 class2).
Excessive residual oil is not permissible irrespective of the compressor oil, as otherwise the basic lubrication will be washed out with time.

3.1.2 Operation with lubricated compressed air

Operate system equipment with unlubricated compressed air, if possible. This is better for the environment. Festo pneu matic valves and actuators have been designed so that, if used as intended, they will not require additional lubrication and will still achieve a long service life.
Festo P.BE−MPAL−EN en 1008NH
3−3
3. Installation
Caution
Operation with lubricated compressed air will cause the life−time lubrication, which is necessary for unlubricated operation, to be washed out".
Note the following instructions if lubricated compressed air must be used: The compressed air prepared with the compressor must correspond in quality to unlubricated compressed air. If possible, do not operate all of
your equipment with lubricated compressed air. If possible, always install the lubricators directly upstream of the consuming actuators.
Caution
Unsuitable additional oil and an excessive oil content in the compressed air reduce the service life of the valve ter minal.
 Use Festo special oil OFSW−32 or the alternatives listed
in the Festo catalogue (as specified in DIN51524−HLP32; basic oil viscosity 32CST at40 °C).
 The additional lubrication must not exceed 25 mg/m
3
(ISO8573−1 class 5).
 Make sure that the lubricator setting is correct
(see following section)
This avoids operative malfunction of the valves.
Setting the lubricator: With the machine running (typical operating status) 0.2 to
max. 1 drops/min. or 0.5 to 5 drops/1000l of air .
Checking the setting: The procedure described below can be used for checking
setting of the lubricator.
Proceed as follows, in order to check the service units with respect to condensate and lubricator settings two times per week.
3−4
Festo P.BE−MPAL−EN en 1008N H
the
3. Installation
1. Ascertain the actuator which is furthest from the lubricato r.
2. Ascertain the valve terminal which controls this cylinder.
3. Remove the silencer, if fitted, from port (3/5).
4. Hold a piece of white cardboard 10cm in front of the exhaust port.
5. Let the system run for a short period. There must be only a slight yellow
colouring on the card
board.
If oil droplets appear, this is an indication that too much oil has been used. Another indicator is the coloration or the condition of the exhaust air silencer. Distinctly yellow colour ing of the filter element or drops of oil on the silencer indicate that the lubricator setting is
too high.
Festo P.BE−MPAL−EN en 1008NH
3−5
3. Installation

3.2 General instructions on installation

Warning
Uncontrolled movements of the connected actuators and loose tubing can cause injury to persons and/or damage to property.
Before carrying out mounting, installation and mainten ance work, switch off the following:
 Compressed air supply  The operating and load voltage supplies.
Pay attention to the following: The components of the valve terminal contain electrostatically sensitive components. if you touch the contact surfaces of the plug connectors or if you do not observe the handling specifications for electro− statically sensitive devices.
The components will be damaged
Note
Handle all modules and components of the valve terminal MPA−L with great care.
Note especially the following:  Screws must be fitted accurately (in particular to avoid
damage to threads on plastic housing parts) and
screwed in by hand  The specified torques must be observed  Clean connecting services (avoidance of leaking and
contact faults) and intact seals and sealing surfaces  Close unused connections with blanking plugs to avoid
contamination and maintain reliability.
back pressure When exhausting large volume actuators or if the exhaust
performance is too small, back pressures can build up in the valve terminal exhaust ducts. The back pressures can lead to pneumatic actuation of other valves, especially
with un
switched 3/2−way valves that are normally closed.
3−6
Festo P.BE−MPAL−EN en 1008N H
3. Installation
To avoid back pressures:
· Optimise the ventilation and exhaust performance of
the valve terminal e.g. by using lar ger pipe diameters or additional compressed air supply via pneumatic supply plates with exhaust via silencers and exhaust plate.
· Separate exhaust ducts by using pressure zones if
necessary (see Chapter 1.5.3).
3.3 Connecting the valve terminal MPA−L
Connections on the following components are available for supplying the valve terminal:
To the pneumatic supply plate, type VMPAL−SP
To the right−hand end plate, type VMPAL−EPR−SP

3.3.1 Pilot control of the solenoid coils (pilot air supply)

Internal pilot air supply If the operating pressure lies between 3 ... 8 bar , you can
operate the pilot control of the solenoid coils with an inter nally branched pilot air supply.
Note
· Internal pilot air supply is branched centrally from sup
ply connection(1) for all solenoid coils. When operating the valve terminal with several pressure zones the inter nal pilot air supply is taken from the pressure zone, which is directly adjacent to the right−hand end plate (see Fig.3/1 and Fig.3/2).
Festo P.BE−MPAL−EN en 1008NH
3−7
3. Installation
External pilot air supply If the operating pressure lies below 3bar or abo ve 8 bar,
pilot control of the solenoid coils must be operated with an external pilot air supply.
Note
· Use preferably closed−loop regulated external pilot air.
Reliable faultless operation of the valve terminal is then
possible, e.g. even with fluctuating operating pressure.
· The external pilot air supply is supplied centrally for all
solenoid coils via pilot connections(12/14) on the right−
hand end plate. This also applies when the valve ter
minal is operated with two pressure zones.
· For external pilot air supply the pilot air pressure must
be adapted to the operating pressure, but only within
the values of 3 ... 8bar.
The conversion between the internal and external pilot air supply is described in Chapter 5.3.6.
3.3.2 Valve terminal M PA−L with pressure zone separation
The pressure zones are separated from each other by special sub−bases (see Chapter 1.5.5). Each pressure zone must be supplied by pneumatic supply plate and via a right−hand end plate with side connections with compressed air. The position of the supply plate within the pressure zone (left, centre or right) is arbitrary.
By fitting a second can provide additional supply air and exhaust air to optimise the ventilation and exhaust performance of the valve ter minal. For each additional pressure zone a special sub−base is re quired for separation and a special pneumatic supply plate is required for supply (see Fig.3/1 and
3−8
supply plate within a pressure zone you
Fig.3/2).
Festo P.BE−MPAL−EN en 1008N H
3. Installation
The following diagrams show as an example the assignment of the supply and exhaust ports to the valves on a valve ter minal with three and four pressure zones and blocked chan nels (1), (3) and (5) and with blocked channel (1).
1
Zone 1
6
5
1 Pressure zone1
2 Pressure zone2
3 Pressure zone3
4 Right−hand end plate (here: Version
without side connections)
23
Zone 2
Zone 3
5 Supply plate (here: for pressure
zone1)
6 Identification of the special sub−base
with integrated pressure zone separation (here: for the separation of channels (1) and (3/5) between pressure zone 1 and pressure zone 2)
4
Fig.3/1: Example: Valve terminal MPA−L with three pressure zones
Festo P.BE−MPAL−EN en 1008NH
3−9
3. Installation
5
1
Zone 1
7
6
1 Pressure zone1
2 Pressure zone2
3 Pressure zone3
4 Pressure zone4
5 Right−hand end plate with supply
connection (1) and exhaust ports (3) and (5) for pressure zone 4
2
Zone 2
34
Zone 3
Zone 4
6 Supply plate (here: for pressure
zone1)
7 Identification of the special sub−base
with integrated pressure zone separation (here: for the separation of channel (1) between pressure zone 1 and pressure zone 2)
Fig.3/2: Example: Valve terminal MPA−L with four possible pressure zones

3.3.3 Setting the pressure regulating valve

Using the adjusting screw on the pressure regulator plate (see Fig.3/3) you can change the flow (see also Flow diagrams of the pressure regulator valve plates" in Appendix A).
3−10
Festo P.BE−MPAL−EN en 1008N H
3. Installation
Proceed as follows:
· Turn the adjusting screw clockwise to increase the flow.
· Turn the adjusting screw anti−clockwise to decrease the
flow.
1 Adjusting screw
2 Pressure gauge
connection
Fig.3/3: Setting the pressure regulator plate

3.3.4 Vacuum/low pressure operation

Note
The 2x2/2−way valves with Ident. code D, I and the 2x3/2−way valves with Ident. code N, K, H are not suitable for vacuum or low pressure operation.
· For the abovementioned valves use a separate pressure
zone for mixed operation with other valves in vacuum oper ation on the same valve terminal.
· The operating pressure for this pressure zone must be
set in accordance with the diagram in Fig.A/1.
If valves are used for switching a vacuum, then filters must be used in the suction line to avoid operative malfunctions caused by foreign matter sucked into the line.
1
2
Festo P.BE−MPAL−EN en 1008NH
3−11
3. Installation
Valve sub−bases
The following conditions must be fulfilled in order that you can operate the valve terminal at supply connection (1) with vacuum or low pressure between −0.9 ... 3 bar:
The pilot control of the solenoid coils is operated with a
regulated external pilot air supply.
The valve terminal is fitted with the following valve sub−
(see Tab.3/1) and sometimes has additional pres 
bases sure zones.
Pressure zone with vacuum or low pressure supply via supply connection (1)
Pressure zone with excess pressure supply port (1)
1) The valve plates with Ident. code D, H, K, N and I are not vacuum or low−pressure operation!
2) In accordance with diagrams in Appendix A, Fig.A/3
3) In accordance with diagrams in Appendix A, Fig.A/1
1)
3)
via supply
The pressure zone must be fitted only with the following valve sub−bases:  5/2−way valve, monostable (Ident. code M)  5/2−way double pilot valve (Ident. code J)  5/3−way valves (Ident. codes B, E and G)  3/2−way valve (Ident. code W and X) see
note. 2 x 3/2−way valves (Ident. code HS, KS and NS) 2x 2/2−way valve (Ident. code DS)
The pressure zone can be fitted additionally with the following valve sub−bases:  2x3/2−way valves (ident. code H, K and N) 2 x 2/2−way valves (Ident. code D, I), see also following instruc
tions
2)
and the following
Tab.3/1: Valve sub−bases, suitable for vacuum and low pressure
The pressure ranges of individual valve types can be found Tab.A/4 in the T echnical Specification..
3−12
Festo P.BE−MPAL−EN en 1008N H
3. Installation
Note
Valves with Ident. code I, 2 x 2/2−way valves: With these valves, vacuum is supplied at connection (5).
Solenoid coil 14 switches the vacuum to connection (4)
The operating pressure at supply connection (1) can be
used as an ejector pulse at connection(2). The operating pressure is switched to connection2 with solenoid coil If the valve terminal is also equipped with other valves, then operate these vacuum and low pressure valves in a separate pressure zone with a separate exhaust duct (5).
Valves with Ident. codes W and X, 3/2−way valves: These valves can be supplied individual l y and therefore
operated in the pressure range of
−0.9 ... 10bar . They are independent of supply connection (1) of the valve terminal. The connections via which these valves are supplied with compressed air or vacuum and via which exhaust air is removed are shown in Tab. 3/ 2 .
The pilot air is supplied via the valve terminal.
12.
3/2−way valve
Ident. code X (4) (3)
Ident. code W (2) (5)
Tab.3/2: Connections to the valves with Ident. code X and W

3.4 Connecting the pneumatic lines

As pneumatic connection elements, terminal screws and threadless cartridges with safety slot and and clamp strap are used in the MPA−L valve (seeFig.3/4 and Tab.3/3).
Festo P.BE−MPAL−EN en 1008NH
Compressed air or vacuum via connection
Exhaust via port
3−13
3. Installation
(3/5)
Clamps straps are used for the positive−locking connection of cartridges and can be mounted both form above and from below on sub−bases (seeFig.3/5). For pneumatic supply plates a clamp strap is fitted from above and for the exhaust plate from below.
If elbow connectors or multiple distributors are used, the air flow will be
reduced slightly.
(1)
(2) (4)
(12/14) (82/84)
(3)
(1)
(5)
Fig.3/4: Pneumatic connections of the valve terminal MPA−L (here: End plate for fitting
in exhaust ports)
3−14
Festo P.BE−MPAL−EN en 1008N H
3. Installation
Line Connection code
(ISO 5599)
Compressed air or vacuum, Exhaust air (3), (5)
External pilot air supply ducted pilot exhaust air
Air or vacuum (2) or (4) QSPKG10 Cartridge in the sub−base
1) Depending on what you have ordered, the valve terminal may already be fitted with cartridges/ screw connectors.
(1)
(12/14)
(82/84)
Port size (ISO 228)
QSPKG20 Cartridge in the pneumatic supply
G¼" Fitting in the right−hand end plate
M7 Fitting in the right−hand end plate
1)
Port
plate and in the exhaust plate
Tab.3/3: Assignment of the connections

3.4.1 Installation/replacement of the threadless cartridges

Installation Proceed as follows:
1. For selecting the correct cartridge use: Tab.3/3
2. Press in and turn the cartridge to the stop in the port.
Festo P.BE−MPAL−EN en 1008NH
3. Keep the cartridges in the pressed in state and inser t a suitable clamp strap in the slot (see Fig.3/5). Obser ve the guide steps on both sides. The clamp strap must slot into
the end position.
3−15
3. Installation
Caution
Danger of injury by automatic loosening of parts under pressure.
On pneumatic actuation cartridges can loosen and be ejected at high speed, if the clamp strap is not inserted securely in the safety slot.
After installation check each cartridge for secure seating.
3−16
Festo P.BE−MPAL−EN en 1008N H
3. Installation
Fig.3/5: Assembly of clamp straps for positive locking of the cartridges
Festo P.BE−MPAL−EN en 1008NH
3−17
3. Installation
Replacement Proceed as follows:
1. Check that the installed clamp straps can be seen from the underside of the valve terminal. If not: First loosen the screws of the valve that is mounted over the sub−base concerned and remove the valve so that the clamp strap can be removed from above.
2. For pneumatic supply plates:
the screws on the upper part (exhaust plate and
Loosen cover plate of the silencer) and remove it.
3. Using a narrow slotted screwdriver lever the clamp strap over the lugs and remove it.
4. Pull the cartridge out and replace it with a suitable type (see Tab.3/3).

3.4.2 Laying the tubing

Note
· Seal unused connections with a blanking plugs to
ensure the reliability of the valve terminal.
Mounting Proceed as follows:
1. Press the hose into the hose connector as far as the stop (see Fig.3/6).
2. Check the secure attachment of the hose to the cartridge.
3. For reasons of clarity, bundle the tubing together with:  Tube straps or  Multiple tubing holders
1 Cartridge fitting
1
2 Locking ring
Fig.3/6: Fitting the tubing
3−18
2
Festo P.BE−MPAL−EN en 1008N H
3. Installation
Dismantling Proceed as follows:
Warning
If the pneumatic tubing is under pressure when dismantled, it may move suddenly and unexpectedly, causing injury to persons. Carry out the following steps before disconnecting the pneumatic tubing on the valve terminal MPA−L:
· Switch off the compressed air supply.
· Make sure that all pneumatic tubing is unpressurized.
· Exhaust all actuators controlled by valves which are
closed in normal or mid−positions.
Note
To disconnect the hoses from the cartridges, use releasing tool type QSO from Festo, or a screwdriver. When using a screwdriver:
· Press down the locking ring only with the broad side of
the blade.
1. Identify all pneumatic hoses to avoid confusion when reconnecting.
2. Press down the locking ring of the cartridge e.g. with a screwdriver or Festo QSO releasing tool (see Fig.3/7).
3. Remove the tubing from the cartridge.
1 Cartridge fitting
1
2 Locking ring
Fig.3/7: Disconnecting the tubing
Festo P.BE−MPAL−EN en 1008NH
2
3−19
3. Installation

3.4.3 Common pneumatic lines

Note
In the case of several systems with centrally ducted ex haust:
· Use non−return valves in the common exhaust lines (3/5)
or (82/84) in order to prevent functional impairment due to back pressures.
1 First valve
terminal MPA−L
1
2 Common exhaust
lines (3/5)
3 Central pilot air
exhaust tubing(82/84)
4 Central exhaust
line (3/5)
5 Second valve
terminal MPA−L
6 Common exhaust
lines (82/84)
Fig.3/8: Common lines with non−return valves
34 5
2
6
2
6
2
3−20
Festo P.BE−MPAL−EN en 1008N H
3. Installation

3.5 Connecting the electric cables

Warning
· Use only PELV circuits as per IEC/EN 60204−1 for the
electric power supply (protective extra−low voltage, PELV). Also observe the general requirements for PELV circuits in accordance with IEC/EN 60204−1.
· Use only power sources that guarantee reliable
electrical isolation of the operating voltage as per IEC/EN 60204−1.
Protection against electric shock (protection against direct and indirect contact) is guaranteed in accordance with IEC/EN 60204−1 by using PELV circuits (electrical equipment of machines, general requirements).
Festo P.BE−MPAL−EN en 1008NH
Note
Ascertain which measures, in line with your EMERGENCY STOP procedures, are necessary for putting your machine/ system into a safe state in the event of an EMERGENCY STOP(e.g. switching off the operating voltage for the valves and output modules, switching off the compressed air).
Valve terminal MPA−L with multi−pin plug connection: Information on the
electrical connection of the valve terminal with one of the multi−pin plug connections can be found in the in User’s manual, enclosed with the product.
Valve terminal MPA−L with CPX terminal: Instructions on connecting the operating voltage can be found in the CPX system manual.
Detailed instructions on connecting the CPX modules (bus node,
I/O modules etc.) can be found in the relevant descrip tions for the CPX module (see CPX system description, table Descriptions of the CPX terminal").
3−21
3. Installation
Load voltage supply The load voltage supply of the valves for the valve terminal
MPA−L is exclusively via the multi−pin plug connection and via the CPX terminal.
Earthing the valve terminal MPA−L
Note
Earth your valve terminal MPA−L!
· For multi−pin plug connection:
Connect one of the earth connections (see Tab.2/1) with low impedance to the earth potential, by choosing the shortest possible line with the largest cross section.
· For CPX terminal:
Connect both earth connections (see Tab.2/1) with low impedance to the earth potential, by choosing the shortest possible line with the largest cross section. Observe in addition the supplementary information in the CPX system description.
This serves to avoid interference due to electromagnetic influences and and ensures electromagnetic compatibility in accordance with
EMC directives.
3−22
Festo P.BE−MPAL−EN en 1008N H
3. Installation
Valve terminal variant Earth terminals
MPA−L with multi−pin plug connection
1
MPA−L with CPX terminal
1
Tab.3/4: Earth connections of the valve terminal MPA−L
to the left−hand end plate 1
or
2
to the right−hand end plate 2
to the left−hand end plate 1
2
and
to the right−hand end plate 2
Festo P.BE−MPAL−EN en 1008NH
3−23
3. Installation

3.6 Address assignment of the valves

Addresses are allocated in ascending order without gaps, from left to right (see the following example). A valve position consisting of a sub−base with electronics module, occupies according to the integrated electronic module the following number of addresses (see Tab.3/5):
Electronics module Number of
Type Housing colour
Individual electronic module
VMPA1−EVAP−10−1 grey one address
VMPA1−EVAP−10−2 black two addresses
4 off electronic module
VMPA1−EVAP−10−1−4 grey one address (4x)
addresses per valve position:
3−24
VMPA1−EVAP−10−2−4 black two addresses (4x)
Electronic module of the pneumatic supply plate
VMPA1−EVAP−20−SP black none, looped
through
Tab.3/5: Available electronic module address assignment
Note
Address assignment does not depend on whether blanking plates or valve plates are fitted.
If a valve position occupies 2 addresses, the following applies:
Pilot solenoid 14 occupies the less significant ad
dress.
Pilot solenoid coil 12 occupies the more significant
address
Festo P.BE−MPAL−EN en 1008N H
3. Installation
For controlling the valves, each solenoid coil is assigned to a certain pin of the multi−pin plug socket (see Tab.3/6).
Note
Use a uniform method of control within a multi−pin plug: Preferably, all control signals should be positive switching (0 −> 1/off −> on), otherwise all control signals negative− switching (1 −> 0/on −> off).
Mixed mode control is not permitted!
Pin Address Val ve
position
Solenoid coil
Electronics module
number
1
0
2
1
3
2
4
3
5
4
6
5
7
6
8
7
9
8 9
10 11
12 13
14 15
1)
10
11 12
13 14
15 16
17 16 8 14 VMPA1−EVAP−10−1
0 14
1 14
2 14
3 14
4 14 VMPA1−EVAP−10−2−4
5 14
6 14
1)
7
1)
12
12
12
12
12
12
VMPA1−EVAP−10−2−4 (black, for 4 MPA1 valves each with two solenoid coils)
(black, for 4 MPA1 valves each with two solenoid coils)
(grey, for an MPA1 valve with a solenoid coil)
Festo P.BE−MPAL−EN en 1008NH
3−25
3. Installation
Pin Electronics moduleSolenoid
Address
Val ve position
coil
number
181917
18
... ... ... ... ...
25 0V/24V
1) Address is for a solenoid coil reserved by the electronic module, not used in the current example.
2) Mixed operation is not permitted.
9 14
2)
12
VMPA1−EVAP−10−2 (black, for an MPA1 valve with two solenoid coils)
Tab.3/6: Example: Address assignment of an valve terminal
MPA−L with 25 pin multi−pin plug connection and 10valve positions
Note
Addresses may be shifted if the valve terminal is extended.
3−26
Festo P.BE−MPAL−EN en 1008N H
3. Installation
1
234
8
1 Addresses of the solenoid coils 14
(manual override 14)
2 Addresses of the solenoid coils 12
(manual override 12)
3 LED for solenoid coil 12
5
8
6
79
6 Sub−base with VMPA1−EVAP−10−2
electronic module assigned two addresses per valve position
7 Sub−base with VMPA1−EVAP−10−1
electronic module assigned one address per valve position
4 LED for solenoid coil 14
5 Unused/reserved valve position
8 Four sub−bases with four
VMPA1−EVAP−10−2−4 electronic modules assigned two addresses per valve position
9 Supply plate with MPA1−EVAP−20−SP
electronic module (no address assigned)
Fig.3/9: Example: Address assignment for valve terminal MPA−L with multi−pin plug
connection (view)
Festo P.BE−MPAL−EN en 1008NH
3−27
3. Installation
1
3.6.1 Valve terminal M PA−L with multi−pin plug connection
For an valve terminal MPA−L with a multi−pin plug connection the maximum number of controllable solenoid coils is related to the plug type used (see Chapter.1.3).
3.6.2 Valve terminal M PA−L with CPX terminal
Pneumatic interface The pneumatic interface of the valve terminal MPA−L creates
the mechanical and electrical connection between the CPX terminal and MPA pneumatic modules.
Display and connecting elements
The pneumatic interface has the following display and con necting elements (Fig.3/10):
1 Connecting plug
to the MPA pneumatic modules
5
4
2 Rotary switch
under a cover cap (torque: 0.5Nm ±10%)
3 Inscription field
4 Fault LED (red)
5 Connecting plug
to the CPX interlinking blocks
Fig.3/10: Display and connecting elements on the pneumatic interface
3−28
Festo P.BE−MPAL−EN en 1008N H
2
3
3. Installation
Error LED Error messages are displayed on the one hand via the red LED
on the pneumatic interface and on the other hand transferred from the pneumatic interface to the CPX bus nodes. These error messages to and from the pneumatic interface can be inclusively suppressed by parameterisation on the CPX ter minal (module
code: 70d).
Fault LED
Procedure Status Error
(red)
ON
OFF
off
ON
OFF
LED lights up
Faultless operation. None
Fault in load voltage for valves
Load voltage for the valves (V missing or too low.
VAL
)
Tab.3/7: Statuses of the error LED of the pneumatic interfaces
Configuration of the address space
From the point of view of the CPX terminal the pneumatic interface is seen as an electrical module with a variable (configurable via the rotary switch) number of digital outputs for the control of the attached valves
For a valve terminal MPA−L with CPX terminal a maximum of 32solenoid coils are controllable, independently tion of the rotary switch (see Tab.3/8).
Note
On conversion or expansion of the valve terminal MPA−L the number of output addresses assigned by the pneu matic system via the rotary switch on the pneumatic inter face must be checked and adapted if necessary. This is not necessary if previously a sufficiently large ad dress space for the expansion has been
Error handling
number
5 Apply and
increase voltage
of the posi 
reserved.
Festo P.BE−MPAL−EN en 1008NH
3−29
3. Installation
Rotary switch Switch position Maximum
number of controllable Solenoid coils
0 4
1 8
2; 3 16
4; 5; 6; 7 24
8 (condition upon de livery)
9 32
32
Tab.3/8: Configuration of address space size
Adjustment rules for the size of the address space
If the number of solenoid coils fitted is less than the
number of output addresses set with the rotary switch, the superfluous addresses will be reserved for later ex tensions (if the maximum number of valves is fitted, out put addresses will then remain unused).
Modifications to the configuration will not become effec
tive
until the operating voltage is switched on again.
Further instructions on addressing the pneumatic modules of the valve terminal MPA−L with CPX terminal can be found in the electronics manual for the module (see CPX system de scription, table Manuals on the CPX terminal").
3−30
Festo P.BE−MPAL−EN en 1008N H

Commissioning

Chapter 4
4−1Festo P.BE−MPAL−EN en 1008NH
4. Commissioning

Contents

4. Commissioning 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 General Information 4−3
4.1.1 Prior to commissioning 4−3 . .
4.1.2 Pressure build−up in the overall supply 4−3 . . . . . . . . . . . .
4.2 Checking the valves and the valve/actuator combination 4−6 . . . . . . . . . . . . . . .
4.3 Mounting/removing the optional manual override cover cap 4−11 . . . . . . . . . . .
4.4 Troubleshooting 4−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4.1 Switching
4.4.2 Impairment of functions 4−13 . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4.3 Operating states of the pneumatic system 4−15 . . . . . . . . . . . . . . . . . . .
status indicator of the solenoid coils 4−13 . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .
.
. . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4−2
Festo P.BE−MPAL−EN en 1008N H
4. Commissioning

4.1 General Information

4.1.1 Prior to commissioning

· Switch off the power supply before connecting or discon
necting plug connectors (otherwise functional damage).
· Only commission a valve terminal that has been mounted
and wired completely.
· Make sure that there is a sufficient supply of fresh air
(cooling) for the following operating conditions:  When the maximum number of valves are fitted  When the maximum operating voltage is applied  When the solenoid coils are constantly under stress
· Note the specifications concerning the medium.
4.1.2 Pressure build−up in the overall supply
Warning
If the pressure build−up of the pilot air supply is too slow or delayed, this may cause the actuators to perform sudden unexpected movements under the following condi tions:
 When the compressed air is connected via a soft−start
valve (gradual pressure build−up) and If there are electric signals (e.g. after EMERGENCY STOP) This can
injury to persons.
· Operate the valve terminal with an external pilot air
Festo P.BE−MPAL−EN en 1008NH
cause damage to the machine or system and even
supply (3 ... 8 bar). Branch the pilot air supply before
the soft−start valve (see Fig.4/1).
4−3
4. Commissioning
The pilot air supply must reach a pressure of 3 ... 8 bar. Otherwise it is not ensured that the valve will switch directly (see Fig.4/1).
If the pressure is less than 3 bar, there may be a delay before the valve is switched, in spite of an electric signal being pres
The gradual pressure build−up of the overall supply does
ent. not affect the actuator in that case. The actuator would react suddenly (e.g. a cylinder would extend or retract suddenly , depending on the valve function).
82/84
42
14 12
12/14
1
53
2
4−4
3
1
12/14
1
1 Externally supplied pilot air supply (3 to 8 bar),
branched before the soft−start valve
2 Soft−start valve (slow build up in pressure of complete
supply)
Fig.4/1: Example of valve−cylinder combination with slow
pressure build−up of the complete system
Festo P.BE−MPAL−EN en 1008N H
2
4. Commissioning
The table below shows the effects of gradual start−up pressurisation when there are electric signals present:
External pilot air supply
Branched down stream of the soft− start valve
Branched up stream of the soft− start valve
Pressure rise in overall supply
slowly slowly after pressure
slowly fast before pressure
Pressure rise in the pilot air supply (12/14)
Tab.4/1: Effects of slow start−up pressurisation
Time when a valve reverses
rise at (1)
rise at (1)
Movement of the actuator
fast
slowly
Festo P.BE−MPAL−EN en 1008NH
4−5
4. Commissioning

4.2 Checking the valves and the valve/actuator combination

The valve terminal MPA−L should be commissioned as follows:
Commissioning variants
Preliminary test of the pneuma tic tubing connection
Complete commissioning of the overall system
Activity
Test the valve−actuator combina tion by means of the manual override
Installing and connecting the overall system. Program control via PLC/indu strial PC.
Tab.4/2: Commissioning variants
Commissioning the pneumatic components by means of the manual override is described below.
Commissioning of the CPX terminal is described in the appropriate description for the CPX bus node (see CPX system description, table Descriptions of the CPX terminal").
4−6
Festo P.BE−MPAL−EN en 1008N H
4. Commissioning
Warning
Before actuating the manual overrides: Uncontrolled actuation of solenoid coils can cause the
actuators to perform sudden unexpected movements which may cause personal injury and material damage.
· Disconnect the power supply for the solenoid coils at
the relevant connections on the valve terminal MPA−L. This prevents accidental actuation of the solenoid coils. Before switching on the power supply: During commissioning, manual overrides that are in the
switched state can cause actuators to perform sudden unexpected movements. These movements can cause injury to persons and damage to property.
· Make sure that all manual overrides are reset to their
initial position. You will thereby avoid undefined switching states of the
valves.
Festo P.BE−MPAL−EN en 1008NH
Warning
Before testing the valve/actuator combination:  Make sure that nobody is in the danger zone.
Note
A valve that has been switched by an electric signal cannot be reset by the manual override. The electric signal is dominant in this case.
· Reset the electric signal before actuating the manual
override.
Proceed as follows:
1. Switch on the compressed air supply.
4−7
4. Commissioning
2. Check the functioning and operation of each individual valve/actuator combination by actuating the manual over ride as shown in the following diagrams.
Note
Incorrect actuation of the non−detenting manual override can lead to malfunctioning or damage to the manual over ride.
· Use a screwdriver (blade width max.3mm) to actuate
the manual override.
· Operate the manual override to max. 25 N.
3. With a detenting manual override: After testing the valves, make sure that all manual overrides are in their initial positions again.
Caution
Valves with manual overrides in switch position can move actuators unintentionally during commissioning. This can cause injury to people and damage to property.
· Prior to commissioning, reset all manual overrides to
their initial positions again.
If the manual override is in the actuated state, it is not possible to reset the valve to its neutral position with an electric signal. The manual override is dominant in this case.
4−8
4. Switch off the compressed air supply after testing the valves.
Festo P.BE−MPAL−EN en 1008N H
4. Commissioning
Non−detenting operation of manual override (return: automatic)
Operation Valve response
· Use a screwdriver (max. blade
width 3 mm) to press down the plunger of the manual override until the valve switches.
Note:
In the case of manual overrides without a cover cap, do not turn the pressed−down plunger as otherwise the manual override will lock.
· Press and hold in the stem of
the manual override.
· Put down the screwdriver. The spring force presses the stem
The pilot valve switches and sets the power valve to the switch posi tion.
The valve remains switched.
of the manual override back to the neutral position. Pilot valve returns to the neutral posi tion and so too does the monostable power valve (not for bistable valves, codeJ).
Tab.4/3: Non−locking operation of the manual override
Festo P.BE−MPAL−EN en 1008NH
4−9
4. Commissioning
Note
The detenting operation of the manual override is only possible if a manual override cover cap is not fitted.
Detenting operation of the manual override (return: manual)
Operation Valve response
· Use a screwdriver (max. blade
width 3mm) to press down the plunger of the manual override until the valve switches.
· Then turn the plunger a quarter
turn in a clockwise direction.
· Put down the screwdriver. The valve maintains its switching
· Using the screwdriver rotate
the stem anti−clockwise a quarter turn backwards.
· Put down the screwdriver.
The pilot valve switches and sets the power valve to the switch posi tion.
position.
The spring force presses the stem of the manual override back to the neu tral position. Pilot valve returns to the neutral posi tion and so too does the monostable power valve (not for bistable valves codeJ).
Tab.4/4: Detenting operation of the manual override
4−10
Festo P.BE−MPAL−EN en 1008N H
4. Commissioning

4.3 Mounting/removing the optional manual override cover cap

Mounting Proceed as follows:
1. Make sure that the relevant manual overrides are in a non−actuated state. If necessary set a detenting manual override back to the initial position (see Tab.4/4).
2. Place the cover cap on the manual override so that the snap hooks of the cover can grip into the recess on the manual override.
3. Clip the manual override cover caps into the recesses in the manual overrides (see Fig.4/2).
1 Manual override
cover caps
1
2 Manual override
(MO)
Fig.4/2: Mounting the MO cover caps
Festo P.BE−MPAL−EN en 1008NH
2
4−11
4. Commissioning
Note
The manual override cover caps serve for limiting the function of the manual override and are constructed so that they can only be removed with a great deal of strength. During dismantling the snap hooks of the manual override cover cap will be damaged.
Dismantling Proceed as follows:
· Use a suitable screwdriver to lift the manual override
cover caps out of the manual overrides (see Fig.4/3).
4−12
Fig.4/3: Dismounting the manual override cover caps
Further information can be found in the assembly instructions enclosed with the cover caps.
Festo P.BE−MPAL−EN en 1008N H
4. Commissioning

4.4 Troubleshooting

4.4.1 Switching status indicator of the solenoid coils

The LEDs on the valves show the switching statuses of the solenoid coils.
LED (yellow)
Switching position of the valve
Neutral position Logical 0 (signal not applied)
off
Switching position (normal case)
LED lights up
Neutral position (error) logical 1 (signal is present, valve has not
Tab.4/5: Meaning of the LED display

4.4.2 Impairment of functions

After switching on the compressed air supply or when subse quently testing the individual valves, you can learn the following about the operating status of the pneumatic system:
Meaning
Logical 1 (signal is present, valve has switched)
switched):  Load voltage of the valves lies below the
permitted tolerance range
 Compressed air supply not OK
or
 Pilot exhaust air blocked
or
 Servicing required
Festo P.BE−MPAL−EN en 1008NH
4−13
4. Commissioning
Operating status of the pneumatic system
Error handling when the compressed air supply has been switched off
Air escapes from ...  Common line or working
· Check assembly of the tubing
line connections
Valve or pneumatic system...  Does not react as expected
 Not
· Check the installation of the tubing lines
· Check the electric cables
· Bring the detenting manual override into the basic position
· After switching on again check the operating pressure (if necessary
for each pressure zone). Set operating pressure in accorda n ce with instructions in chapter 3.
· Servicing required
For valve terminals which must be operated with closed−loop regulated external pilot air:
· After switching on again, check the pilot pressure (if necessary ,
set as a factor of the operating pressure, see chapter 3)
Tab.4/6: Function impairment of the pneumatic system
4−14
Festo P.BE−MPAL−EN en 1008N H
4. Commissioning

4.4.3 Operating states of the pneumatic system

The following conditions should be fulfilled, in order that the desired pneumatic operating states listed below can be achieved:
Desired pneumatic
Requirement Description
operating status
Zero leakage  Tubing connected with care
Fast reaction Sufficient pressure supply by means
Trouble−free Non−return valves in common ex
Two or more pressure zones
Vacuum or low−pres sure operation
EMERGENCY STOP of pressure zones
Slow start−up after EMERGENCY STOP
 Regulated pilot air supply
of pressure supply modules
haust line
 Limiting the pressure zones by
means of separating seals with blocked channels
 Appropriate number of pneu
matic air supply plates for supplying the different pressure zones.
Externally supplied regulated pilot air supply (3 ... 8 bar)
Guaranteeing the controller function for the pilot air supply despite the overall supply being switched off
If control signals are present, the pi lot air supply must have a pressure of 3 ... 8 bar immediately after being switched on
Exhaust the valve terminal MPA−L via all the exhaust plates or via the flat plate silencer
This applies when several systems with centrally ducted exhaust air are used
Subsequent conversion possible (see Chapter 5)
Vacuum/low−pressure operation not with 3/2−way valves
The controller regulates the pilot air supply to all the valve plates on a valve terminal MPA−L
Tab.4/7: Pneumatic operating states
Festo P.BE−MPAL−EN en 1008NH
4−15
4. Commissioning
4−16
Festo P.BE−MPAL−EN en 1008N H
Loading...