Festo IFB11-03 Electronic Manual

Valve terminal type 03/04−B
Electronics manual
Valve terminal with Fieldbus connection
Type IFB11−03
Fieldbus protocol:
− DeviceNet
− Philips DIOS
Manual
163 956 en 0503g
Contents and general instructions
Authors S. Breuer, H. Hohner, E. Klotz. . . . . . . . . . . . . . . . .
Editors H.J. Drung, M.Holder. . . . . . . . . . . . . . . . . . . . . . . .
Original de.
Translation transline Deutschland GmbH. . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . .
Layout Festo AG & Co., Dept. KG−GD. . . . . . . . . . . . . . . . . . .
Typesetting DUCOM. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
Edition en 0503g. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Title MANUAL−EN. . .
Designation P.BE−VIFB11−03−EN. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .
Orderno. 163 956. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E (Festo AG&Co., D73726 Esslingen, Federal Republic of Germany, 2000) Internet:http://www.festo.com E−Mail: service_international@festo.com
The copying, distribution well as the communication of its contents to others without expressed authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved, in particular the right to carry out patent, utility model or orna mental design registrations.
Festo P.BE−VIFB11−03−EN en 0503g
and utilization of this document as
I
Contents and general instructions
II
Festo P.BE−VIFB11−03−EN en 0503g
Contents and general instructions
Contents
Designated use VII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Target group VIII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service VIII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Important user instructions IX. . . . . . . . . . . . . . . . . . .
Abbreviations XI. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manuals for this valve terminal XIII. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Additional modules for this valve terminal XIV. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
1. Summary of components 1−1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
1.1 Summary of multifunctional Festo valve terminals 1−3. . . . . . . . . . . . . . . . . . . .
1.2 Description of components 1−4. . . . . . . . . .
1.2.1 Types 03/04−B: Electric modules 1−4. . . . . . . . . . . . . . . . . .
1.2.2 Type 03: MIDI pneumatic modules 1−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . .
1.2.3 Type 03: MAXI pneumatic modules 1−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.4 Type 04−B: ISO pneumatic modules 1−7. . . . . .
1.3 Method of operation 1−8. . . . . . . . . . . . . . . . . . . . . .
2. Fitting 2−1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Fitting the modules and components 2−3. . . . . . . . . . . . . . . . . .
2.1.1 Earthing the end plates 2−4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . .
2.2 Fitting onto a hat rail (type 03) 2−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Fitting the valve terminal onto a wall 2−9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. Installation 3−1. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 General connection methods 3−3. . . . . . . . .
3.1.1 Cable selection fieldbus cables 3−4. . . . . . . . . . . . . . . . . .
3.1.2 Cable selection operating voltages 3−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Fieldbus nodes 3−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.1 Opening and closing the nodes 3−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.2 Configuring the valve terminal 3−8. . .
3.2.3 Setting the station number 3−9. . . . . . . . . . . . .
3.2.4 Possible station numbers 3−10. . . . . . . . . . . . . . . . . . . . . .
Festo P.BE−VIFB11−03−EN en 0503g
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . .
. . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
III
Contents and general instructions
3.2.5 Setting the fieldbus baud rate 3−12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.6 Setting the fieldbus protocol 3−13. . . . . .
3.2.7 Setting the compatibility (DeviceNet configuration) 3−14. . . . . . . . . . . . . .
3.2.8 Analog I/O modules 3−15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . .
. .
3.3 Switching on the power supply 3−16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.1 Calculating the current consumption 3−17. . . .
3.3.2 Connecting the power supply 3−19. . . . . . . . . . . . . . . . . . . .
3.4 Connecting the fieldbus interface 3−24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . .
3.4.1 Philips DIOS connection instructions 3−28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.2 Connection instructions Selectron SELECAN 3−29. . . . . . . . .
. . . . . . . . . . . . . . . .
3.4.3 Connection instructions Allen−Bradley DeviceNet 3−30. . . . . . . . . . . . . . . . . . . . .
3.4.4 Connection instructions for Festo DeviceNet (SF 60) 3−30. . .
3.4.5 Terminating resistor 3−31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4. Commissioning 4−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . .
4.1 Addressing and configuring the valve terminal 4−3. . . . . . . . . . . . . . . . . . . . . . .
4.1.1 Ascertaining the configuration data 4−3. . . . . . . . .
4.1.2 Address assignment of the valve terminal 4−6. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . .
4.1.3 Address assignment after extension/conversion 4−11. . . . . . . . . . . . . . . . . . . . . .
4.2 General instructions on commissioning 4−13. . . . . . . . . . . . . . . .
4.2.1 Switching on the power supply 4−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . .
4.3 Philips Dios  Principles of commissioning and diagnosis 4−15. . . . . . . . . . . . . . .
4.3.1 General information 4−15. . . . . . . . . . . . . . . . . . . . . . . .
4.3.2 Configuration with Philips Dios 4−17. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .
4.3.3 Addressing the inputs/outputs with Philips DIOS 4−20. . . . . . . . . . . . . . . . . . . . .
4.3.4 Diagnosis with Philips Dios 4−24. . . . . . . . . .
4.3.5 Status bits with Philips Dios 4−26. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
4.4 Selectron SELECAN  Principles of commissioning and diagnosis 4−29. . . . . . . .
4.4.1 General information 4−29. . . . . . . . . . . . .
4.4.2 Configuration with Selectron SELECAN 4−31. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
4.4.3 Addressing the inputs/outputs with Selectron SELECAN 4−32. . . . . . . . . . . . . . .
4.4.4 Diagnosis with Selectron SELECAN 4−35. . . . . . . . . . .
4.4.5 Status bits with Selectron SELECAN 4−36. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . .
4.5 Allen−Bradley DeviceNet  Principles of commissioning and diagnosis 4−39. . . .
IV
Festo P.BE−VIFB11−03−EN en 0503g
Contents and general instructions
4.5.1 General information 4−39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.2 Configuring DeviceNet slave features
(EDS) 4−40. . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.3 General notes on parameterizing with the DeviceNet 4−42. . . . . . . . . . . . . . . . . .
4.5.4 Notes on parametrization with RSNetWorx for DeviceNet 4−43. . . . . . . . . . . . . . .
4.5.5 Diagnosis with the DeviceNet 4−50. . . . . . . . . . . . . . . . . . . . . . . . .
4.5.6 Status bits on the DeviceNet 4−51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . .
5. Diagnosis and error treatment 5−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 Overview of diagnosis options 5−3. . . .
5.2 On−site diagnosis 5−4. . . . . . . . . . . . . . . . .
5.2.1 LEDs on the bus node 5−4. . . . . . . . . . . . . . . .
5.2.2 LEDs of the valves 5−7. . . . . . . . . . . . . . . . . . . .
5.2.3 LEDs of the input/output modules 5−9. . . . . . . . . . . . . . . . . . .
5.2.4 Testing the valves 5−11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Status bits 5−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.1 Short circuit/overload 5−17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Error treatment 5−18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . .
5.4.1 Reaction to errors in the control system 5−18. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.2 Position of the status
5.4.3 Short circuit/overload at an output stage 5−19. . . .
5.5 Type 04−B: fuses for the pilot solenoids 5−20. . . . . . . . . . . . . . . . . . . . .
A. Technical appendix A−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
bits 5−19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . .
. . . .
A.1 Technical specifications A−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.2 Cable length and
A.3 Examples of circuitry A−12. . . . . . . . . . . . . . . . .
A.3.1 Power supply type 03  internal layout A−13. . . . . . . . . . . . . . . . .
cross−sectional area A−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
A.3.2 Power supply type 04−B  internal layout A−14. . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. Accessories B−1. .
B.1 DeviceNet compatibility
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
configuration of SW−Version V1.3/1.4 B−3. . . . . . . . . .
B.2 Controlling analog I/O modules with DeviceNet B−9. . . . . . . . . . . . . . . . . . . . . .
B.2.1 Controlling the analog IOs with the bus B−15. . .
B.2.2 Structure of the analog word B−16. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
Festo P.BE−VIFB11−03−EN en 0503g
V
Contents and general instructions
B.2.3 Status bits with analog modules B−24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.3 Connecting the cable to the plug/sockets B−25. . . . . .
B.4 Accessories B−28. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.5 Overview DeviceNet−Specifications B−32. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . .
B.6 Details on DeviceNet Objects B−35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.6.1 Identity Object: Class
B.6.2 Router Object: Class Code 02 (0x02) B−38. . . . . . . . . . .
B.6.3 DeviceNet Object: Class Code 03 (0x03) B−39. . . . . . . . . . . . . . . . . . . . . . . . .
Code 01 (0x01) B−35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . .
B.6.4 Assembly Object: Class Code 04 (0x04) B−41. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.6.5 Connection Object: Class Code 05 (0x05) B−43. . . . . . .
C. Index C−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
VI
Festo P.BE−VIFB11−03−EN en 0503g
Contents and general instructions
Designated use
The valve terminal described in this manual is intended ex clusively for use as follows:
for controlling pneumatic and electric actuators (valves
and output modules)
for interrogating electric sensor signals by means of the
input modules.
Use the valve terminal only as follows:
in accordance with designated use
in faultless technical condition.
without any modifications
by the user
If additional commercial components such as sensors and actuators are connected, the specified limits for pressures, temperatures, electrical data, torques, etc. must not be ex ceeded.
Please observe the standards specified in the relevant chapters and comply with technical regulations, as well as with national and local regulations.
Festo P.BE−VIFB11−03−EN en 0503g
VII
Contents and general instructions
Target group
This manual is intended exclusively for technicians trained in control and automation technology with experience in instal ling, commissioning, programming and diagnosing program mable logic controllers and fieldbus systems.
Service
Please consult your local Festo repair service if you have any technical problems.
VIII
Festo P.BE−VIFB11−03−EN en 0503g
Contents and general instructions
Important user instructions
Danger categories
This manual contains instructions on the dangers which may occur if the product is not used correctly. These instructions are marked with a heading (Warning, Caution, etc.), printed on a shaded background and accompanied by a pictogram. A distinction is made between the following danger cat egories:
Warning
This means that there is a danger of serious human injury and damage to property if these instructions are not ob served.
Caution
This means that there is a danger of human injury and damage to property if these instructions are not observed.
Please note
This means that there is a danger of damage to property if these instructions are not observed.
In addition, the following pictogram marks passages in the text which describe activities involving electrostatically sensi tive components:
Festo P.BE−VIFB11−03−EN en 0503g
Electrostatically sensitive components: Incorrect handling may result in damage to the components.
IX
Contents and general instructions
Marking special information
The following pictograms mark passages in the text contain ing special information.
Pictograms
Information: recommendations, tips and references to other sources of information.
Accessories: information on necessary or useful accessories for the Festo product.
Environment: information on the environmentally−friendly use of Festo products.
Text markings
S The bullet denotes activities which can be carried out in
any sequence.
1. Figures
denote activities which must be carried out in the
order specified.
Hyphens denote general activities.
X
Festo P.BE−VIFB11−03−EN en 0503g
Contents and general instructions
Abbreviations
The following product−specific abbreviations are used in this manual:
Abbreviation
Terminal or valve terminal Valve terminal type 03 or type 04−B with or without electric I/Os
Node Field bus node/control unit
Sub−base
Single solenoid sub−base
Double solenoid sub−base
I O I/O
P−module General pneumatic module
I/O module
Meaning
Type 03: Pneumatic sub−base for two valves Type 04−B Manifold sub−base with Intermediate solenoid plate MUH and pneuma tic valve with hole pattern as per ISO 5599/2 size 1, 2 or 3 incl.
Sub−base for single−solenoid valves
Sub−base for double−solenoid valves or mid−position valves
Input Output Input and/or output
Module with digital inputs or outputs in general
PLC Programmable logic controller; in brief: controller
FO Fibre−optical waveguide
Fig.0/1: Index of abbreviations
Festo P.BE−VIFB11−03−EN en 0503g
XI
Contents and general instructions
Please note
For most of the drawings in this manual, we have used a simplified representation of a type 03 valve terminal with four pneumatic sub−bases and four input/output modules (standard fitting).
1 Input/output
modules
123
2 Field bus node
3 Valves
Fig.0/2: Standard fitting for the drawings
XII
Festo P.BE−VIFB11−03−EN en 0503g
Contents and general instructions
Manuals for this valve terminal
Depending on what you have ordered and on the further ex tension of your complete system, the following Festo manuals are necessary for the complete documentation of the modular valve terminal:
Festo designation
P.BE−MIDI/MAXI−03−... Pneumatics manual
P.BE−VIISO−04−B−... Pneumatics manual
P.BE−VIEA−03/04B−.. Supplementary description for
P.BE−VIAX−03... Analog I/O manual
P.BE−VIFB11−03/04B−... Electronics manual
Title/product
 Valve terminal type 03, MIDI/MAXI
 Valve terminal type 04−B, ISO 5599−2
I/Omodules (digital I/O modules 4I, 8O, 4O, high−current output modules, multiI/O modules)
 Fieldbus connection FB11 (this man
ual)
Fig.0/3: Manuals for this valve terminal
Festo P.BE−VIFB11−03−EN en 0503g
XIII
Contents and general instructions
Additional modules for this valve terminal
The multifunctional valve terminal can be extended with the following modules:
I/O modules
Type designation Title
VIGE−03−FB−... Input module with 4, 8 or 16 inputs, PNP or NPN, 4−pin or 5−pin,
with/without electronic fuse,
VIGA−03−FB−... Output module with 4 outputs, PNP or NPN, 4−pin or 5−pin
VIGV−03−FB−... Additional supply module 24 V/25 A for high−current outputs
VIEA−03−FB−... Multi I/O module with 12 inputs and 8 outputs, PNP
VIAP−03−FB Analog I/O module with 1 input and 1 output
VIAU−03−FB−... Analog I/O module with 3 inputs and 1 output
Type voltage (−U) or current (−I)
Fig.0/4: Additional modules
XIV
Festo P.BE−VIFB11−03−EN en 0503g
Contents and general instructions
The valve terminals can be connected to the controllers of various manufacturers. The current manual contains the con figuration of the PLC and terminal addressing for the following control systems:
Controller
Controller (PLC) Fieldbus module Fieldbus/protocol
manufacturer
Allen−Bradley PLC 5/xx
SLC 500 PC/IPC
Festo SF 60 1747−SDN
Phillips P8 Compact line DLC 100/200 DIOS
Selectron PMC 40
MAS PC/IPC
1771−SDN 1747−SDN 1170−KFD
CPU 42 CPU 751/752 PCI 701
DeviceNet
RCD SELECAN SELECAN
Fig.0/5: Overview of possible controllers/fieldbus protocols (extract)
Notes regarding the DeviceNet fieldbus protocol
Please note
This manual refers to valve terminals with fieldbus connec tion FB11 from software version date 26.02.99 (see type plate) or software version 2.0 (see sticker on the operating system EPROM) or higher.
Festo P.BE−VIFB11−03−EN en 0503g
From this software status, the configuration of the valve terminal is supported by two EDS files. The current manual describes
commissioning with the DeviceNet Manager
V3.005.
Service
Please consult your local Festo repair service if you have any technical problems.
XV
Contents and general instructions
XVI
Festo P.BE−VIFB11−03−EN en 0503g
Summary of components
Chapter 1
1−1Festo P.BE−VIFB11−03−EN en 0503g
1. Summary of components
Contents
1. Summary of components 1−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Summary of multifunctional Festo valve terminals 1−3. . .
1.2 Description of components 1−4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . .
1.2.1 Types 03/04−B: Electric modules 1−4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2 Type 03: MIDI pneumatic modules 1−5
1.2.3 Type 03: MAXI pneumatic modules 1−6. . . . . . . . . . . . .
1.2.4 Type 04−B: ISO pneumatic modules 1−7. . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Method of operation 1−8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . .
. .
1−2
Festo P.BE−VIFB11−03−EN en 0503g
1. Summary of components
1.1 Summary of multifunctional Festo valve terminals
The multifunctional valve terminal is composed of individual modules and components.
Valve terminal
Type 03 Electric modules
Type 03: Pneumatic modules
Type 04−B ISO pneumatic modules
Description of the modules
Electric modules suited to types 03/04B (PNP or NPN), fitted with:  Digital inputs (modules with 4, 8 or 16 inputs)  Digital outputs (modules with 4 outputs) 0.5 A  High−current outputs 2 A  Multi−I/Os (module with 12 inputs/8 outputs) 0.5 A
 Analogue I/Os, AS−i master (not possible with all nodes)
Pneumatic modules type 03, fitted with:  Sub−bases (MIDI and MAXI) fitted with 5/2−way single−solenoid
valves, 5/2−way double−solenoid valves, 5/3−way mid−position valves (with auxiliary pilot air) or cover plates
 Special modules for pressure supply, for forming pressure
zones
Pneumatic modules type 04−B, fitted with:  Adapter plate for manifold sub−bases as per ISO 5599−2 in
sizes1, 2 and 3
 Manifold sub−bases for intermediate solenoid plates with hole
pattern as per ISO 5588−2, fitted with pneumatic valves (single− solenoid, double−solenoid, mid−position) or cover plates
 Components for high−level sub−bases (pressure regulator inter
mediate plates, restrictor plates etc.)
Fig.1/1: Summary of modules for the multifunctional Festo valve terminals
Festo P.BE−VIFB11−03−EN en 0503g
1−3
1. Summary of components
1.2 Description of components
1.2.1 Types 03/04−B: Electric modules
The following connecting and display elements can be found on the electric modules:
2 3 456 7
1
9
1 Input socket for two electric inputs
(PNP or NPN)
2 Red LED (error display per input
module with electronic fuse)
3 Two green LEDs (one LED per input)
4 Input socket for one electric input
(PNP or NPN)
8
6 Output socket for electric output (PNP)
7 Yellow LED (status display per output)
8 Red LED (error display per output)
9 Further modules (e.g. additional power
supply, high−current outputs PNP/NPN)
5 Green LED (per input)
Fig.1/2: Connecting and display elements on the electric modules
1−4
Festo P.BE−VIFB11−03−EN en 0503g
1. Summary of components
1.2.2 Type 03: MIDI pneumatic modules
The following display and operating elements can be found on the pneumatic MIDI modules type03:
1 23
1 Yellow LEDs (per valve solenoid coil)
3 Valve location inscription field (desig
nation signs)
2 Manual override (per valve solenoid
coil), either locking or non−locking
Fig.1/3: Display and operating elements on the MIDI modules type 03
4 Unused valve location with cover plate
4
Festo P.BE−VIFB11−03−EN en 0503g
1−5
1. Summary of components
1.2.3 Type 03: MA XI pneumatic modules
The following display and operating elements can be found on the pneumatic MAXI modules type 03:
1 2
3
1 Yellow LED (per valve solenoid coil)
2 Manual override (pervalve solenoid
coil), either locking or non−locking
3 Unused valve location with cover plate
Fig.1/4: Display and operating elements on the MAXI modules type 03
1−6
45
4 Valve location inscription field (desig
nation signs)
5 Regulator for limiting the pressure of
the auxiliary pilot air
Festo P.BE−VIFB11−03−EN en 0503g
1. Summary of components
1.2.4 Type 04−B: ISO pneumatic modules
The following connecting, display and operating elements can be found on the pneumatic ISO modules type04−B:
12345 6 7
1
1
8
2
2
45
1 Adapter plate type 04−B
2 Fuses for the valves
5
1
Manual override (per pilot solenoid 14, non−locking)
2
Manual override (per pilot solenoid 12, non−locking)
3 Power supply connection
1
4
Fig.1/5: Operating, display and connecting elements on the ISO modules type 04−B
Yellow LEDs (per pilot solenoid 14)
2
Yellow LEDs (per pilot solenoid 12)
6 Valve location inscription field
7 0.135A fuse (perpilot solenoid)
8 Adapter cable for power supply to the
node and the I/O modules
Festo P.BE−VIFB11−03−EN en 0503g
1−7
1. Summary of components
1.3 Method of operation
The node controls the following functions:
it connects the valve terminal to the appropriate field bus
it performs the system settings of the valve terminal. An
it controls data transfer to/from the field bus module of
and to the power supply.
automatic valve test and further node−dependent func tions can be set.
your control
system
1 Incoming field
bus
2 Continuing field
bus
3 Node
4 Compressed air
5 Work air (2, 4)
Internal control of the valve terminal
12
4
3
5
Fig.1/6: Summary of the functions of a valve terminal
1−8
Festo P.BE−VIFB11−03−EN en 0503g
1. Summary of components
The input modules process input signals (e.g. from sensors) and transmit these signals via the field bus to the controller.
The output modules are universal electric outputs and control low−current consuming devices with positive logic, e.g. further valves, bulbs, etc.
Additional I/O modules for special applications are also avail able.
Further information on the
use of all I/O modules can be found in the Supplementary description of the I/O modules" for your valve terminal.
The pneumatic modules perform the following functions:
they form the common channels for supply and exhaust
air
they supply electric signals from all the valve solenoid
coils
Work connections 2 and 4 are provided
for each valve loca
tion on the individual pneumatic modules.
The valves are supplied with compressed air via the common channels on the pneumatic end plate or via special supply modules. The exhaust air and pilot exhaust are also vented via these channels/modules. Further modules for pressure supply are also available, e.g. for working
with different pres sures or for fitting either MIDI/MAXI valves or ISO valves on a node.
Festo P.BE−VIFB11−03−EN en 0503g
Further information on their use can be found in the Pneu matics manual" for your valve terminal.
1−9
1. Summary of components
1−10
Festo P.BE−VIFB11−03−EN en 0503g
Fitting
Chapter 2
2−1Festo P.BE−VIFB11−03−EN en 0503g
2. Fitting
Contents
2. Fitting 2−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Fitting the modules and components 2−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.1 Earthing the end plates 2−4. . . . . .
2.2 Fitting onto a hat rail (type 03) 2−6. . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Fitting the valve terminal onto a wall 2−9. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
2−2
Festo P.BE−VIFB11−03−EN en 0503g
2. Fitting
2.1 Fitting the modules and components
The valve terminal is supplied from the factory ready fitted. If you wish to supplement or replace individual modules or components, please follow the instructions in the following manuals:
Supplementary description of the I/O modules" for fit
ting the electric I/O modules
Pneumatics manual" for fitting the pneumatic modules
Fitting instructions supplied with the
product in the case
of modules and components ordered at a later date.
Please note
Handle all modules and components of the valve terminal with the utmost care. Pay particular attention to the follow ing:
 Make sure that screws are not distorted and not sub
jected to mechanical stress. Make sure that screws are correctly aligned (otherwise their threads may be dam aged).
 Make sure that the specified
torques are not exceeded.  Avoid misalignment between the modules (IP 65).  Make sure that connecting surfaces are clean (avoid
leakage and contact faults).
 The contacts of type 03 valve solenoid coils must not be
bent (they are not resistant to bending, i.e. they will break off if bent backwards).
Festo P.BE−VIFB11−03−EN en 0503g
 Electrostatically sensitive components
Do not
touch the contact surfaces of the plug connectors
on the sides of the modules and components.
2−3
2. Fitting
2.1.1 Earthing the end plates
The valve terminal possesses both a left−hand and a right− hand end plate as a mechanical termination of the valve ter minal. These end plates fulfil the following requirements:
they comply with protection class IP 65.
they contain connections/contacts for earthing.
they contain holes for fitting the valve terminal onto a wall
and, in unit.
the case of type03, also for the hat−rail clamping
Please note
When supplied from the factory, the end plates of the valve terminal are earthed internally. If you wish to extend/con vert the type 03 valve terminal, earth the end plates of the valve terminal as described below.
You thereby avoid faults caused by electromagnetic in fluences.
Earth the end plates after extension/conversion
as follows:
1. Right−hand end plate (type 03): In order to earth the right−hand end plate, connect the ready−fitted cable on the inside to the appropriate con tacts on the pneumatic modules or on the node (see diagram below).
2. Left−hand end plate: The left−hand end plate is connected conductively to the other components by means of
the ready−fitted spring
contacts.
Remark: Instructions on earthing the complete valve terminal can be found in the chapter Installation". The diagram below shows how the end plates are fitted using as an example a type 03 valve terminal.
2−4
Festo P.BE−VIFB11−03−EN en 0503g
2. Fitting
1 23
1
1 Seals
2 Contact for the earth cable
Fig.2/1: Fitting the end plates (example of type 03 valve terminal)
3 Ready−fitted earth cable
4 Fastening screws max.1Nm
4
Festo P.BE−VIFB11−03−EN en 0503g
2−5
2. Fitting
2.2 Fitting onto a hat rail (type 03)
The valve terminal is suitable for fitting onto a hat rail (sup port rail as per EN 50022). For this purpose there is a guide groove on the rear of all modules in order that they can be hung on a hat rail (see Fig. 2/3).
Caution
 Fitting the valve terminal onto a hat rail without a hat−rail
clamping unit is not permitted.
If the valve terminal is fitted in a sloping position or if it
is subject to vibration, secure the hat−rail clamping unit additionally:
− against sliding down and use the locking screws (item3) to protect it against unintentional opening.
loosening/
Please note
If the valve terminal is fitted in a horizontal position and
if the load is at rest, the hat−rail clamping unit can be used without locking screws (item 3).
If you do not have a hat−rail clamping unit for your valve
terminal, you can order this and fit it at a
later stage.
 The use of MIDI or MAXI clamping units depends on the
end plates available (MIDI/MAXI).
Hat−rail clamping unit (type 03)
In order to fit the valve terminal onto a hat rail, you will re quire a hat−rail clamping unit. This must be fitted on the rear of the end plates as shown in the diagram below. Pay particu lar attention to the following:
2−6
Festo P.BE−VIFB11−03−EN en 0503g
2. Fitting
Before fitting:
S Make sure that the surfaces for glueing on the rubber feet
are clean (cleaned with spirit).
S Make sure that the flat−head screws (item 3) are tight
ened.
After fitting:
S Fasten the lever with a locking screw (item 7).
3
2
1
Lever
1
2 O−ring
1
4
5
6
*)
4 Self−adhesive rubber foot
5 Clamping elements
3 Flat−head screw
*) Different lever lengths with MIDI and MAXI
Fig.2/2: Fitting the hat−rail clamping unit
Festo P.BE−VIFB11−03−EN en 0503g
6 Locking screw
2−7
2. Fitting
Proceed as follows:
1. Ascertain the weight of your valve terminal as described in chapter 2.3
2. Make sure that the mounting surface can support this weight.
3. Fit a hat rail (support rail as per EN 50022 − 35x15; width35 mm, height 15 mm).
4. Fasten the hat rail to the fastening surface at least every 100mm.
1 Hat−rail clamping
unit unlocked
2 Hat−rail clamping
unit locked
3 Locking screw
5. Hang
6. If the hat−rail clamping unit is subject to vibration or if it is
the valve terminal onto the hat rail. Fasten the valve terminal on both sides with the hat−rail clamping unit to prevent it from tilting or sliding (see Fig.2/3).
fitted in a sloping position, fasten it with two locking screws (item
3) against unintentional loosening/opening.
Fig.2/3: Fitting the type 03 valve terminal to a hat rail
2−8
1 332
Festo P.BE−VIFB11−03−EN en 0503g
2. Fitting
2.3 Fitting the valve terminal onto a wall
Caution
In the case of long valve terminals with several I/O mod ules, use additional support brackets for the modules (ap proximately every 200 mm). You can thereby avoid:
 overloading the fastening eyes on the left−hand end
plate  the terminal sagging (I/O side)  natural resonance
Proceed as follows:
1. Ascertain the weight of your valve terminal
(weigh or
calculate). Reference values:
Valve terminal module
Type 03
per pneumatic module (incl. valves)
Type 04−B manifold sub−bases  Adapter plate and right−hand end
 per pneumatic module (incl. manifold
Node 1 kg 1 kg 1 kg
I/O module 0.4 kg 0.4 kg 0.4 kg
*) Components for high−level linking: Weight see Pneumatics manual
*)
*)
plate
sub−base, intermediate solenoid plate and valve)
MIDI
0.8 kg
ISO size 1
3.0 kg
1.2 kg
MAXI
1.2 kg
ISO size 2
3.2 kg
1.6 kg
ISO size 3
4.1 kg
2.4 kg
Festo P.BE−VIFB11−03−EN en 0503g
2. Make sure that the mounting surface can support this weight. Check to see if you require support brackets for the I/O modules.
3. If necessary, use spacers.
2−9
2. Fitting
4. Fasten the valve terminal, depending on the type, as shown in the following table. The valve terminal can be fitted in any desired position.
Type of valve terminal
Type 03  with four M6 screws on the left−hand and
Type 04−B  with two M6 screws on the left−hand end plate
Fastening methods
right−hand end plate. In the case of valve terminals with several I/O modules, use additional support brackets for the modules (approximately every 200 mm).
 with three M6 screws (ISO sizes 1 and 2) or
M8 (ISO size 3) on the adapter plate and on
the right−hand end plate.
If required, use the following additional methods of fastening: a fastening screw per manifold sub−base  the hole on the bottom of the manifold sub−
base (blind hole", see Pneumatics manual) In the case of valve terminals with several I/O
modules, use additional support brackets for
the modules (approximately every 200 mm).
Fig.2/4: Possibilities for fitting onto a wall
2−10
Festo P.BE−VIFB11−03−EN en 0503g
Installation
Chapter 3
3−1Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
Contents
3. Installation 3−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 General connection methods 3−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1 Cable selection fieldbus cables 3−4. . . . . .
3.1.2 Cable selection operating voltages 3−5. . . . . . . . . . . . . . . . .
3.2 Fieldbus nodes 3−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.1 Opening and closing the nodes 3−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . .
3.2.2 Configuring the valve terminal 3−8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.3 Setting the station number 3−9
3.2.4 Possible station numbers 3−10. . . . . . . . .
3.2.5 Setting the fieldbus baud rate 3−12. . . . . . . . . . . . . . .
3.2.6 Setting the fieldbus protocol 3−13. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
3.2.7 Setting the compatibility (DeviceNet configuration) 3−14. . . . . . . . . . . . . . . . . . .
3.2.8 Analog I/O modules 3−15. . . . . . . . . . . .
3.3 Switching on the power supply 3−16. . . . . . . . . . . . .
3.3.1 Calculating the current consumption 3−17. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . .
3.3.2 Connecting the power supply 3−19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Connecting the fieldbus
3.4.1 Philips DIOS connection instructions 3−28. . . . . . . . . . . .
interface 3−24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
3.4.2 Connection instructions Selectron SELECAN 3−29. . . . . . . . . . . . . . . . . . . . . . . . .
3.4.3 Connection instructions Allen−Bradley
3.4.4 Connection instructions for Festo DeviceNet (SF 60) 3−30. . . . . . . . . . . . . . . . . . .
3.4.5 Terminating resistor 3−31. .
3−2
DeviceNet 3−30. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
3.1 General connection methods
Warning
Before carrying out installation and maintenance work, switch off the following:
 the compressed air supply  the operating voltage supply for the electronics (pin 1) the operating voltage supply for the outputs/valves (pin2).
You can thereby avoid:
uncontrolled movements of loose tubing.
unexpected movements of the connected actuators
non−defined switching states of the electronic compo
nents.
Festo P.BE−VIFB11−03−EN en 0503g
3−3
3. Installation
3.1.1 Cable selection fieldbus cables
The fieldbus cable should be a twisted, screened 4−wire cable.
Please note
Use the cable type specified in the PLC manual for your controller. Take into account the distance and the selected fieldbus baud rate.
The following table provides standard values for the maxi mum distance dependent on the selected baud rate for the DeviceNet protocol. Precise details can be found in the man ual for your control system.
Baud rate
Max. length of the main cable
125 kBaud 500 m 6 m 156m
250 kBaud 250 m 78m
500 kBaud 100 m 39m
Branch line length
Maximum per device
Sum of all branch lines
Not all the specified baud rates are supported by all PLCs, controllers or PC/I PC. For other protocols, please see data in the manual of the relevant controller. You must also comply with any other restrictions regarding the maximum branch line lengths.
3−4
Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
3.1.2 Cable selection operating voltages
Several parameters must be observed when connecting the operating voltages. Further information can be found in the following chapters:
Chapter 3: Installation
Section: Connecting the operating voltages"
− Calculating the current consumption
− Power unit layout
− Cable lengths and cross−sections
Chapter 3: Installation
Section: Connecting the fieldbus"
− Calculating the current consumption
− Cable lengths and cross−sections
Bus interfaces
Appendix A: Cable lengths
− Determining the length and cross−section using tables
− Calculating using equations
and cross−sections
Festo P.BE−VIFB11−03−EN en 0503g
3−5
3. Installation
3.2 Fieldbus nodes
3.2.1 Opening and closing the nodes
Warning
Before carrying out installation and maintenance work, switch off the following:
 the compressed air supply  the operating voltage supply for the electronics (pin 1) the operating voltage supply for the outputs/valves (pin2).
You can thereby avoid:
uncontrolled movements of loose tubing.
unexpected movements of the connected actuators
non−defined switching states of the electronic compo
nents.
Caution
The nodes of the valve terminal contain electrostatically sensitive components.
S Do not therefore touch any contacts. S Observe the regulations for handling electrostatically
sensitive components.
You will then prevent the electronics in the node from being damaged.
3−6
Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
You will find the following connecting and display elements on the cover of the node:
1 Green LED
2 Red LED
3 Plug for fieldbus
cable
4 Fuse for the oper
ating voltage of the inputs
5 Operating voltage
connection
1
1
2
3
45
Fig.3/1: Cover of the nodes
Opening Unscrew and remove the 6 Phillips screws in the cover. Care
Closing Replace
Festo P.BE−VIFB11−03−EN en 0503g
Please note
The cover is linked to the internal printed circuit boards by means of the cable for the operating supply connection and cannot, therefore, be removed completely.
fully lift up the cover. Do not damage the cable through mech anical stress.
the cover. Place the cables for the operating voltage into the housing so that they are not squashed. Tighten the Phillips screws in the cover in diagonally opposite sequence.
3−7
3. Installation
Ô
Ô
Ô
3.2.2 Configuring the valve terminal
There are four circuit boards in the node. There is an LED and two plugs for the fieldbus cables on board 2; on board 3 there is an LED and a switch for setting the configuration
1 Green LED
2 Red LED
3 Address selector
switch (Station no.)
4 Baud rate
5 Protocol
6 Compatibility
DNconfiguration
7 Board 4
8 Board 3
9 Flat plug for
operating voltage connection
1
aC
aB
aA
aJ
1
2 3
4
5 6
7 8
aJ Board 2
aA Screening cover
aB Board 1
aC Plug for fieldbus
cable
Fig.3/2: Connections, display and operating elements on the node
3−8
9
Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
3.2.3 Setting the station number
Use the two address selector switches on board 3 to set the station number of the valve terminal. The switches are num bered from 0... 9. The arrow on the address selector switches indicate the units or tens figure of the station number set.
1 Address selector
switches UNITS figures
2 Address selector
switches TENS figures
1
Fig.3/3: Address selector switch
Please note
Station numbers can only be assigned once per connection.
Recommendation: Assign the station numbers in ascending order. If necessary, assign the station numbers to suit the machine structure of your system.
2
Festo P.BE−VIFB11−03−EN en 0503g
3−9
3. Installation
3.2.4 Possible station numbers
SPS/PLC Address designa
Station numbers
tion
Allen−Bradley and Festo DeviceNet
Philips DIOS Nodes−No./Network
Selectron SELECAN Nodes module 1; ...; 29
Nodes 0; ...; 63
1; ...; 29
module
Fig.3/4: Station numbers
Proceed as follows:
1. Switch off the operating voltage.
2. Assign an unused station number to the valve terminal.
3. Use a screwdriver to set the arrow of the relevant address selector switch to the units or tens figure of the desired station number.
Example:
1 Setting with field
bus address: 05
2 Setting with field
bus address: 38
Fig.3/5: Function of the address selector switch
3−10
12
UNITS
TENS
Festo P.BE−VIFB11−03−EN en 0503g
UNITS
TENS
3. Installation
1 Fieldbus
baudrate
In addition to the address selector switch, the node also con tains a DIL switch which can be used to set the following func tions:
Fieldbus baud rate
Fieldbus protocol
Compatibility DN configuration
The DIL switch is composed of four switch elements. These are numbered from 1 to 4. The ON position is marked.
2 Fieldbus protocol
and compatibility of the DeviceNet configuration
Fig.3/6: Position of DIL switch
1
2
Festo P.BE−VIFB11−03−EN en 0503g
3−11
3. Installation
3.2.5 Setting the fieldbus baud rate
Please note
Set the fieldbus baud rate on the valve terminal so that it corresponds to the setting of the fieldbus module/inter face of the master.
Note that with identical DIL switch settings (1,2), there can be different baud rates produced with the various proto cols.
Warning
With the Selecan protocol: if you use the PMC 40 as the master, set a baud rate higher than 20 kBaud.
This prevents uncontrolled switching on/off of the valves.
Manu
Protocol Fieldbus baud rate [kBaud]
facturer
Allen− Bradley and Festo
Philips DIOS 20 kBaud 100 kBaud 500 kBaud 1000 kBaud
Selectron Selecan 20 kBaud not
Setting the DIL switch
DeviceNet 125 kBaud 250 kBaud 500 kBaud
100 kBaud 500 kBaud 1000 kBaud
with PMC 40
Fig.3/7: Setting the fieldbus baud rate
3−12
Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
3.2.6 Setting the fieldbus protocol
Settings are dependent on the control system used.
Manufacturer
Allen−Bradley, Omron and others Philips/
Selectron
Protocol DeviceNet DIOS/Selecan
Setting the DILswitch
1)
Further information regarding software versions with reference to the DeviceNet protocol can be found on the next two pages.
Compatible with Version V1.3/1.4
1)
Current Version
1)
V2.0
(delivery status)
Current Version
1)
V2.0 with support of analog I/O modules
Fig.3/8: Setting the fieldbus protocol
Festo P.BE−VIFB11−03−EN en 0503g
3−13
3. Installation
3.2.7 Setting the compatibility (DeviceNet configuration)
From February 1999, the fieldbus node FB11 will be available in an updated and improved software version for the DeviceNet. This new software version offers various simpler methods for the configuration and commissioning of a valve terminal with DeviceNet.
The new software version is no longer compatible with field bus nodes with earlier software
22.07.96 or earlier). However, you can switch current fieldbus
nodes to the older software version and therefore create com patibility with an older DeviceNet configuration.
versions (V1.3/1.4 of
Please note
If you replace a valve terminal with an earlier software ver sion of the fieldbus node with a valve terminal using cur rent software version V2.0 (26.02.99) and want to retain your current DeviceNet configuration:
S Set the DIL switches 3 and 4 to ON. This permits the
fieldbus nodes to support
software version V1.3/1.4 and
avoids configuration errors in the existing DeviceNet.
If you wish to install the valve terminal with the latest soft ware version (delivery status):
Configure the new valve terminal in your DeviceNet as shown in Chapter 4.2.3.
3−14
Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
DeviceNet configuration
Compatibility with earlier versions V1.3/1.4
Current software version V2.0
(from 26.02.99)
(up to 22.07.96)
Settings of the DIL switch
Delivery status
Fig.3/9: Setting the compatibility (DeviceNet configuration)
3.2.8 Analog I/O modules
Current software version V2.0
with support of analog I/O modules (from x.04.2000)
For applications with analog I/Os on the DeviceNet, a maxi mum of 8 analog inputs and 8 analog outputs can also be used in one valve terminal. An overview of additional mod ules for the valve terminal can be found in Fig.0/4.
Further information on analog I/O modules and their oper ation with
DeviceNet can be found in Chapter 4.xx and in the
manual Analog input/output modules" P.BE−VIA X−03/04B−...
Festo P.BE−VIFB11−03−EN en 0503g
3−15
3. Installation
3.3 Switching on the power supply
Warning
S Use only PELV circuits as per IEC/DIN EN 60204−1 (Pro
tective Extra−Low Voltage, PELV) for the electrical supply. Consider also the general requirements for PELV circuits in accordance with IEC/DIN EN 60204−1.
S Use power supplies which guarantee reliable electrical
isolation of the operating voltage as per IEC/DIN EN 60204−1.
By the use of
PELV circuits, protection against electric shock (protection against direct and indirect contact) is guaranteed in accordance with IEC/EN 60204−1 (Electrical equipment for machines, General requirements).
Caution
The load voltage supply for the outputs/valves must be fused externally with maximum 10 A (slow blowing). With the external fuse you can avoid functional damage to the valve terminal in the event of a short circuit.
3−16
Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
Before connecting the power supply, please note the follow ing:
S Avoid long distances between the power unit and the
valve terminal. If necessary, calculate the maximum per mitted distance as described in Appendix A.
S The following apply as orientation values for your valve
terminal.
Cross−sectional area of cable
1.5 mm
2.5 mm
Current consumption (at VB = 24 V): Operating voltage (pin 1) = 2.2 A Operating voltage (pin 2) = 10 A
2 2
S If necessary, calculate the complete current consumption
as shown in the table below and then select a suitable power unit and suitable cable cross−sectional area.
3.3.1 Calculating the current consumption
The table below shows you how to calculate the complete current consumption for the valve terminal. The values speci fied have been rounded up. If you wish to use other valves or modules, please refer to the relevant technical specifications for their current consumption.
Distance
8 m 14 m
Festo P.BE−VIFB11−03−EN en 0503g
3−17
3. Installation
Current consumption for electronics and inputs (Pin 1 on the node, 24 V ± 25 %)
Node
Number of simultaneously assigned sensor inputs ____ x 0.010 A
Power supply for sensors (see manufacturer specifications) ____ x _____ A
Current consumption for electronics and inputs (pin 1 on the node) max.2.2 A
Current consumption of valves and outputs (pin2 on the node, 24 V ± 10 %)
Number of valve coils (simultaneously actuated): Type 03: MIDI: ____ x 0.055 A
MAXI: ____ x 0.100 A
Type 04: MIDI: ____ x 0.140 A Number of simultaneously actuated electric outputs: ____ x 0.010 A Load current of simultaneously actuated electric outputs ____ x _____ A
0,200A
+
Σ A
+
Σ A
=
Σ A A
Σ A
+
Σ A
+ Σ A
Current consumption of outputs (Pin 2 on the node) max. 10 A
Current consumption on the node
Current consumption of high−current outputs*) (Pin 1 of additional supply
Number of high−current output modules fitted
Load current of simultaneously actuated high−current output modules ____ x _____ A
Current consumption of high−current outputs *) per additional supply module max. 25 A
*)
Fig.3/10: Calculating the complete current consumption
3−18
24 V/25 A)
____ x 0.100 A
*)
=
Σ A A
Σ A
+
Σ A
=
Σ A Σ A
Festo P.BE−VIFB11−03−EN en 0503g
+
=
Σ A
3. Installation
3.3.2 Connecting the power supply
The following separate supplies of +24V DC are provided via the power supply connection:
the operating voltage for the internal electronics and the
inputs of the input modules (pin 1: +24 V DC, tolerance ±25%, external fuse M3.15A recommended).
the load voltage for valve outputs and outputs of the out
put modules (pin 2: fuse max. 10 A (slow blowing) required).
+24 V DC, tolerance ±10%, external
1 Power supply for
type 03
2 Power supply for
type 04B
1
2
Fig.3/11: Type−specific power supply connection
Please note
Check within the framework of your EMERGENCY STOP circuit, to ascertain which measures are required for put ting your machine/system in a safe state in the event of an EMERGENCY STOP (e.g. switching off the load voltage for the valves and output modules, switching off the pres sure).
Festo P.BE−VIFB11−03−EN en 0503g
3−19
3. Installation
1 24V supply for
electronics and inputs
2 24V load voltage
supply for valves and outputs
3 0V
The pin assignments of the power supply connection on the node (type 03) and on the adapter block (type 04−B) are identical.
1
4
2
3
4 Earth
connection
Fig.3/12: Pin assignment of the power supply connection for types 03/04−B
Please note
Common operating and load voltage supplies for pin 1 (electronics and inputs) and pin 2 (outputs/valves):
S In this case, note that the lower tolerance of ±10% for
both current circuits must be observed.
Check the 24V load voltage of the outputs while your system is operating. Make sure that the load lies within the permitted tolerance even during operation at full load.
Recommendation: Use a closed−loop power unit.
voltage of the outputs
3−20
Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
Potential equalization
The valve terminal has two earth connections for potential equalization.
on the load voltage connection (pin 4 incoming socket).
on the left−hand end plate (M4 thread).
Please note
S Always connect the earth potential to pin 4 of the volt
age connection.
S Connect the earth connection of the left−hand end plate
to the earth potential with low impedance (short cable with large cross−sectional area).
S By means of low−impedance connections, you can be
sure that the housing of the valve terminal
and the ear th connection at pin 4 have the same potential and that there are no equalizingcurrents.
You can thereby avoid interference due to electromagnetic influences and you can ensure electromagnetic compatibil ity in accordance with the EMC guidelines.
Festo P.BE−VIFB11−03−EN en 0503g
3−21
3. Installation
Example of connection
The diagram below shows as an example the connection of a common 24V power supply for pin 1 and pin 2. Please note here that:
the load voltage supply for the outputs/valves must be
protected with an external fuse of maximum 10A (slow blowing) against short circuit/overload.
the power supply for
the electronics and the inputs should be protected with an external fuse of 3.15 A against short circuit/overload (recommendation).
the power supply for the sensors is also protected with
the fuse fitted (2 A).
the common tolerance of 24 V DC
10 % must be ob
served.
both connections are connected for potential equalization
and that equalizing currents are avoided.
the load voltage at pin 2 (valves/electric outputs) can be
switched off separately.
3−22
Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
3
5
0V
24 V
1
3.15A
230V
24V
10%
10A
2
3
5
1 Fuse for sensor inputs (2A)
34
4 Load voltage can be switched off separ
ately .
2 Earth connection pin 4 designed for
12A
5 External fuses
3 Potential equalization
Fig.3/13: Example  connection of a common 24V power supply and the potential equal
ization(example for type 03)
Festo P.BE−VIFB11−03−EN en 0503g
3−23
3. Installation
3.4 Connecting the fieldbus interface
A fieldbus plug is provided on the node for connecting the valve terminal to the fieldbus.
This plug is used to connect the two bus cables, the voltage supply (+24 V and 0 V) for the bus interface and the cable screen. The hardware basis of the bus interface is formed by
CAN bus. It is typical with this bus that the bus interface
the is supplied with voltage via the fieldbus plug.
Bus connection is made using a branch line with a 5−pin M12 socket with PG 9 screw connector. This can be ordered from FESTO (Type: FBSD−GD−9−5POL, Part No. 18324). Alterna tively, you can manufacturers (see Appendix A, Accessories).
obtain ready−to−use bus cables from other
Please note
Check in the manual of your PLC which T−adapter and the maximum branch line length is permitted for your con troller!
Appendix A provides an overview of suitable installation accessories.
The following overview shows the main bus connections.
3−24
Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
1
2
3
4
1 Power supply bus interface
2 Fieldbus
3 Screening/shield
Fig.3/14: Bus interface structure
5
4 Branch line
5 T−adapter
Festo P.BE−VIFB11−03−EN en 0503g
3−25
3. Installation
Current consumption of all bus interfaces
Number of connected Festo valve terminals_______ 50 mA
Current consumption of remaining fieldbus interfaces
Current consumption of sensor inputs/sensor supplies supplied via the bus
Total current consumption of all bus interfaces
+
+
=
Σ  A
Σ  A
Σ  A
Σ A
Avoid long distances between the bus power supply and the bus slaves!
Calculate the permissible distance if required (see Appen dixA also).
Please note
Bus slaves from different manufacturers have different tolerances regarding interface supply. Take this into account when determining the bus lengths.
3−26
For Festo valve terminals: U
= 25 V
max
U
= 11.5 V
min
Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
g
Caution
S Make sure of the correct polarity when you connect the
fieldbus interface.
S Connect the screening/shield.
The following diagram shows the pin allocation of the fieldbus interface. Connect the fieldbus cables to the appropriate pins of the bus cable socket. Note also the connecting instructions in further diagrams, as well the instructions in
the PLC manual
for your controller.
1 Internal
RCnetwork
2 Node housing
GND Bus + 24VBus
Data −
Data +
Screenin
1
1M 220nF
2
Fig.3/15: Pin assignment of fieldbus interface
Festo P.BE−VIFB11−03−EN en 0503g
3−27
3. Installation
3.4.1 Philips DIOS connection instructions
Please note
Check the connection assignments of the module in the PLC manual for your controller.
Connect the fieldbus cables of your control system as follows to the fieldbus interface of the valve terminal:
PLC plug/pin assignment
View
nc = not connected
PIN Signal designation
BUS − GND
BUS +
+ 24V
0V
Valve terminal pin assignment of fieldbus interface
Data − Pin 5
nc
Data + Pin 4
+24V Bus Pin 2
GND Bus Pin 3
Screen Pin 1
Fig.3/16: Philips DIOS connection assignment
3−28
Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
3.4.2 Connection instructions Selectron SELECAN
Please note
Check the connection assignments of the module in the PLC manual for your controller.
Connect the fieldbus cables of your control system as follows to the fieldbus interface of the valve terminal:
PLC plug/pin assignment
Valve terminal pin assignment of fieldbus interface
View
PIN Signal designation
CAN −
GND
CAN +
+ 24V
0V
Data − Pin 5
nc
Data + Pin 4
+24V Bus Pin 2
GND Bus Pin 3
Screen Pin 1
Fig.3/17: Connection assignment Selectron SELECAN
Festo P.BE−VIFB11−03−EN en 0503g
3−29
3. Installation
3.4.3 Connection instructions Allen−Bradley DeviceNet
Please note
Check the connection assignments of the module in the PLC manual for your controller.
Connect the fieldbus cables of your control system as follows to the fieldbus interface of the valve terminal:
PLC plug/pin assignment
Valve terminal pin assignment of fieldbus interface
View
Signal designation
RED
WHITE
BARE
BLUE
BLACK
24V Bus Pin 2
Data + Pin 4
Screen Pin 1
Data − Pin 5
GND Bus Pin 3
Fig.3/18: Connection assignment for Allen−Bradley DeviceNet
3.4.4 Connection instructions for Festo DeviceNet (SF 60)
The pin assignments on the Festo DeviceNet Master SF 60 and on the valve terminal with FB 11 are identical (see Figure3/19).
3−30
Festo P.BE−VIFB11−03−EN en 0503g
3. Installation
3.4.5 Terminating resistor
If the valve terminal to be connected is located on the end of the fieldbus, a terminating resistor must be installed (matched).
Recommendation: Install the required terminating resistor in compliance with the recommendations of ODVA (Open DeviceNet Vendor Association) or Allen-Bradley (see the manual for your controller). The following diagram shows an example:
1
1 Terminating resistor
2 Power unit for 24 V supply
3 Powertapfor24Vsupply
4 Device Box Tap
5 T-Port Tap
23 4 51
6789
6 PC with DN interface converter and
DN Manager Software
7 1770-KFD or 1784-PCD
8 Series 9000 Photoelectronic sensor
9 Festo SF 60 DeviceNet-Scanner
Fig. 3/19: Example – Terminating resistor connected to T-distributor (T-Port Tap)
Festo P.BE-VIFB11-03-EN en 0503g
3-31
3. Installation
The required terminating resistance (120 Ohm, 0.25 Watt) can also be cheaply installed in the socket of the fieldbus cable. Proceed as follows:
1. Clamp the wires of the resistor together with those of the fieldbus cable between the wires Data + (PIN 4) and Data− (PIN 5) of the bus cable socket.
Please note
In order to ensure proper connection, we recommend that you clamp the wires of the resistor and those of the field bus cable in a common cable end sleeve.
2. Mount the bus cable socket on the fieldbus plug.
3−32
Festo P.BE−VIFB11−03−EN en 0503g
Commissioning
Chapter 4
4−1Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
Contents
4. Commissioning 4−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Addressing and
4.1.1 Ascertaining the configuration data 4−3. . . . . . . . . . . . . . . . . . . . .
configuring the valve terminal 4−3. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
4.1.2 Address assignment of the valve terminal 4−6. . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.3 Address assignment after extension/conversion 4−11. . .
. . . . . . . . . . . . . . . . . . .
4.2 General instructions on commissioning 4−13. . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.1 Switching on the power supply 4−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Philips Dios  Principles of commissioning and diagnosis 4−15. .
4.3.1 General information 4−15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . .
4.3.2 Configuration with Philips Dios 4−17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.3 Addressing the
4.3.4 Diagnosis with Philips Dios 4−24. . . . . . . . . . . . . . . . . . . . . .
4.3.5 Status bits with Philips Dios 4−26. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
inputs/outputs with Philips DIOS 4−20. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . .
4.4 Selectron SELECAN  Principles of commissioning and diagnosis 4−29. . . . . . . .
4.4.1 General information 4−29. . . . . . . . . . . . . . . . . . . . . . . . .
4.4.2 Configuration with Selectron SELECAN 4−31. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . .
4.4.3 Addressing the inputs/outputs with Selectron SELECAN 4−32. . . . . . . . . . . . . . .
4.4.4 Diagnosis with Selectron SELECAN 4−35. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .
.
4.4.5 Status bits with Selectron SELECAN 4−36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5 Allen−Bradley DeviceNet  Principles
4.5.1 General information 4−39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.2 Configuring DeviceNet slave features (EDS) 4−40. . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.3 General notes on parameterizing with the DeviceNet 4−42. . . . . . . . . .
4.5.4 Notes on parametrization with RSNetWorx for DeviceNet 4−43. . . . . . . . . . . . . . .
4.5.5 Diagnosis with the DeviceNet 4−50. . . . . . . . . . . . . . . . . .
4.5.6 Status bits on the DeviceNet 4−51. . . . . . . . . . . . . . . . . . . . . . . . . . .
4−2
of commissioning and diagnosis 4−39. . . .
. . .
. . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
4.1 Addressing and configuring the valve terminal
4.1.1 Ascertaining the configuration data
Before configuring, ascertain the exact number of available inputs/outputs. A multifunctional valve terminal consists of a varying number of I/Os, depending on what you have ordered.
Please note
S The status bits must be treated like inputs and occupy
four additional input addresses.
S The maximum possible extension of the valve terminal is
limited by the addressing limits of the relevant field bus protocol and the mechanical limits of the valve terminal.
S Type 04−B
With this valve terminal, the assignment of
the valve addresses can be set fixed by means of a DIL switch in the adapter block. This manual valve terminal configur ation (Address reser ving") is described in the Appendix of the Pneumatics manual for type 04−B.
Festo P.BE−VIFB11−03−EN en 0503g
4−3
4. Commissioning
The table below shows the number of I/Os required per mod ule for configuration.
Type of module
MIDI/MA XI manifold (type 03)  Single solenoid sub−base  Double solenoid sub−base
ISO manifold (type 04−B)  Single solenoid sub−base  Double solenoid sub−base
4−output module (4 digital outputs)
4−input module (4 digital inputs)
8−input module (8 digital inputs)
16−input module (16 digital inputs) Multi I/O module
Status bits
**)
Number of I/Os assigned
2O 4O
1O 2O
4O
4I
8I
16I
12I + 8O
4I
*)
Fig.4/1: Number of assigned I/Os per module
Copy the following table for further calculations.
4−4
*) The I/Os are assigned automatically within the valve terminal,
irrespective of whether an input/output is actually used.
**) The status bits are assigned automatically within the terminal,
as soon as there are input modules.
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
Inputs
Calculating the number of inputs/outputs
1. Number of 4−input modules ________ x 4
2. Number of 8−input modules ________ x 8
3. Number of 16−input modules ________ x 16
4. Number of other inputs, e.g. multi I/O module
5. The 4 status bits are assigned internally automatically by the valve terminal.
Total number of inputs to be configured
Outputs
6. Number of single−solenoid sub−bases M IDI/MAXI ________ x 2
7. Number of double−solenoid sub−bases MIDI/MAXI ________ x 4
8. Number of type 04−B single−solenoid sub−bases
9. Number of type 04−B double−solenoid sub−bases
*)
*)
________ x 1
________ x 2
+
+
+
+
=
+
+
+
Σ Ι
Σ Ι
Σ Ι
Σ I
4 I
Σ I
Σ Ο
Σ Ο
Σ Ο
Σ Ο
*)
Note the possible address reservations with type 04−B
10.Check to see if the sum of 6.  9. is divisible by four without remainder. This check is necessary because of the 4−bit−orientated internal addressing of the terminal. The following distinction is made: a) if divisible by four without remainder: continue with point 11. b) If not: round up to the next half byte (+1...3).
11.Number of 4−output electric modules ________ x 4
12.Number of other outputs, e.g. multi I/O module
Total number of outputs to be configured
Festo P.BE−VIFB11−03−EN en 0503g
Intermediate sum 6.9.
= Σ Ο
+  2 O
+
Σ Ο
+
Σ O
=
Σ Ο
4−5
4. Commissioning
4.1.2 Address assignment of the valve terminal
The address assignment of the outputs of a multifunctional valve terminal depends on the equipment fitted on the valve terminal. A distinction is made between the following equip ment fitted:
valves and digital I/O modules.
only valves.
only digital I/O modules.
The basic rules described below apply to the address assign ment of these fitting after each of these basic rules.
variants. A detailed example is given
Please note
If two addresses are assigned for one valve location, the following assignment applies:
 lower−value address: pilot solenoid 14  higher−value address: pilot solenoid 12
Information on reserving addresses of the valves on the type 04−B valve terminal can be found in the Pneumatics manual for type 04−B.
4−6
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
Basic rules of addressing
With mixed fitting, the address assignment of the valves, digi tal I/O modules and status bits is taken into account.
Outputs
1. The address assignment of the outputs does not depend on the inputs.
2. Address assignment of the valves:  Assign the addresses in ascending order without gaps.  Counting begins on the node from left to Maximum 26 valve solenoid coils can be addressed.
right.
Type 03:  Single−solenoid sub−bases always occupy 2 addresses  Double−solenoid sub−bases always occupy
4addresses
Type 04−B  Single−solenoid sub−bases always occupy 1 address  Double−solenoid sub−bases always occupy
2addresses
3. Round up to 4 bits: The following distinction is made: a) If the number of valve addresses can be
divided by 4
without remainder, continue with point 4.
b) If the number of valve addresses cannot be divided by 4
without remainder , you must round up to 4 bits because of the 4−bit orientated addressing. The bits thus rounded up in the address range cannot be used.
Festo P.BE−VIFB11−03−EN en 0503g
4−7
4. Commissioning
4. Address assignment of the output modules: After the (4−bit rounded) addresses of the valves the digital outputs must be addressed.  Assign the addresses in ascending order without gaps. Counting begins on the node from right to left.  Counting on the individual modules is made from the
top to the bottom.
Digital output modules
occupy 4 or 8 addresses.
Inputs
1. The address assignment of the inputs does not depend on the outputs.
2. Address assignment of the input modules:  Assign the addresses in ascending order without gaps.  Counting begins on the node from right to left. On the individual modules from the top to the bottom.  Input modules
occupy 4, 8, 12 or 16 addresses.
3. Status bits: The address assignment of the status bits depends on the fitting variants of the inputs and the configuration.
The following always applies: The status bits are only available if input modules
are connected to the valve terminal and are configured
 Addressing
The status bits
are transmitted to the four highest−
value positions of the configured address range.
4−8
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
1 2 3456
When the power supply is switched on, the valve terminal automatically recognizes all available pneumatic modules and digital input/output modules and assigns the appropri ate addresses. If a valve location is not used (cover plate) or if an input/output is not connected, the relevant address will still be assigned. The diagram below shows signment as an example.
the address as
1 4−input module
2 8−input module
3 4−output module
Fig.4/2: Address assignment of a valve terminal with digital I/Os (example type 03)
Remarks on the diagram
If single−solenoid valves are fitted onto double−solenoid
sub−bases of valve terminal type 03 (MIDI/MAXI), four addresses will be reserved for valve solenoid coils; the higher address in each case will then remain unused (see address 3
if unused valve locations are fitted with cover plates, the
addresses will still be assigned (see addresses 12, 13).
4 Single sub−base
5 Double sub−base
6 Round up
or Fig.4/1).
Festo P.BE−VIFB11−03−EN en 0503g
4−9
4. Commissioning
Due to the 4−bit orientated addressing of the modular
valve terminal, rounding up to the full four bits is always made on the last valve location (if the fitting does not al ready use the full four bits). This means that two ad dresses cannot perhaps be used (see addresses 14, 15).
Additional
notes on valve terminals without I/O modules
If only valves are used, the address assignment will always be as described in the section Basic rules for addressing".
Please note
 Maximum 26 valve solenoid coils can be addressed.  The last two locations on the valve side are not rounded
up.
 Valve terminals without input modules do not require a
configuration for the inputs. The status bits are not therefore available.
Additional instructions for valve terminals without valves
If only electric I/Os are used,
the address assignment will always be as described in the section Basic rules for addres sing".
4−10
Please note
 Counting begins immediately to the left of the node.  The last two locations on the valve side are not rounded
up.
 The maximum possible amount of equipment which can
be fitted on the valve terminal is limited by the addres sing limits of the relevant field bus protocol and the mechanical limits
of the valve terminal (max. 96 inputs
or 48 outputs).
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
4.1.3 Address assignment after extension/conversion
A special feature of the multifunctional valve terminal is its flexibility. If the demands made to the machine change, the equipment fitted on the valve terminal can also be changed.
Caution
If the valve terminal is extended or converted at a later stage, the input/output addresses may be shifted. This applies in the following cases:
 when one or several pneumatic sub−bases are added or
removed at a later stage (types 03/04−B).
 Type 03: when a pneumatic sub−base for two single−
solenoid valves is replaced
by a sub−base for two
double−solenoid valves or vice versa.
 Type 04−B when a pneumatic sub−base for one single−
solenoid valve is replaced by a sub−base for a double− solenoid valve or vice versa.
 when additional input/output modules are added be
tween the node and the existing input/output modules.
 when existing input/output modules are
removed or replaced by input/output modules which occupy fewer or more input/output addresses.
If the configuration of the inputs is modified, the addresses of the status bits may be shifted.
Festo P.BE−VIFB11−03−EN en 0503g
4−11
4. Commissioning
12 3 4 5436
The diagram below shows, as an example, the modifications which occur to the address assignment when more equip ment is added to the standard fitting of the previous diagram. 2 double−solenoid and 2 single−solenoid sub−bases have been added to the valve side. An 8−input module and a 4−output module have been removed from
the electric I/Os.
1
4−input module
2 4−output module
3 Single sub−base
Fig.4/3: Address assignment of a valve terminal with digital I/Os after extension
(example type 03)
Remarks on the diagram Pressure supply modules and intermediate pressure supply modules do not occupy any addresses.
4 Double sub−base
5 Power supply
6 No rounding
4−12
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
4.2 General instructions on commissioning
Before commissioning or programming, compile a configur ation list of all connected field bus slaves. On the basis of this list, you can:
carry out a comparison between the NOMINAL and the
ACTUAL configurations , in order to ascertain if there are any connection faults
access these specifications during the syntax check of a
program, in order to avoid addressing errors.
Configuration of the CP system requires a very accurate pro cedure, as different configuration specifications are required for each system, due, amongst other things, to the modular structure of each system. Please comply with the instructions in the following sections.
The accompanying CD−ROM includes product−specific icons
some DeviceNet EDS files for the Festo valve terminals.
and
S To see a quick preview about the CD−ROM contents, read
the file Readme.txt" on the CD−ROM.
Festo P.BE−VIFB11−03−EN en 0503g
4−13
4. Commissioning
4.2.1 Switching on the power supply
Please note
Please observe also the instructions in the manual for your controller.
This controller automatically carries out a comparison be tween the NOMINAL and the ACTUAL configurations when switched on. For this configuration run it is important that:
the configuration specifications are complete and correct.
the power supply for the programmable logic controller
that for the fieldbus slaves is switched on either sim
and ultaneously or in the sequence indicated below.
Please observe the following points when switching on the power supply:
Common power supply: Feed in the common power sup
ply for the control system and all fieldbus slaves via a central power unit or a
central switch.
Separate power supply: If the control system and fieldbus
slaves have separate power supplies, the following se quence must be complied with when switching on:
1. Switch on the operating voltage supply for all fieldbus slaves.
2. Switch on the operating voltage supply for the controller.
4−14
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
4.3 Philips Dios  Principles of commissioning and diagnosis
4.3.1 General information
When using the modular valve terminal with Philips DIOS, the following features must be noted:
The addresses of all network modules detected, i.e. in
cluding the valve terminals are assigned in sequence without gaps.
The input and output addresses are assigned indepen
dently of each other.
Please note
The sum of output and input bytes per valve terminal must not exceed 8 bytes!
Use a DLC interface with a software status above versionV1.1.
Festo P.BE−VIFB11−03−EN en 0503g
4−15
4. Commissioning
e
s
t
t
e
s
i
Possible input bytes
0 0 0 0 0 0 0 0 0
1 1 1 1 1 1 1 1
2 2 2 2 2 2 2 7 7
8
es
3 3 3 3 3 3 6 6 6
tbyt
4 4 4 4 4 5 5 5 5
inpu
5 5 5 5 4 4 4 4 4
ssibl
6 6 6 3 3 3 3 3 3
x.po Ma
7 7 2 2 2 2 2 2 2
8 1 1 1 1 1 1 1 1
0 0 0 0 0 0 0 0 0
Possible output bytes
Please refer to the manual for your controller for the method of ascertaining the total time required for transmission. The internal processing time of the Festo valve terminal is: < 1 ms.
s
tbyte
utpu
ibleo
.poss
Max.
4−16
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
4.3.2 Configuration with Philips Dios
First determine the number of input and output bytes.
Please note
Note that the number of inputs per valve terminal is in creased by 4 status bits if input stages are mounted. The 4inputs provide status information with which internal coded error messages are transferred to the DLC 100/200.
It is possible to compare the calculated number of bus slaves and the calculated number determined by the DLC 100/200.
number of input and output bytes with the
After pressing the button CONF", the seven−segment display shows the following:
number of recognised network modules (e.g. valve ter
minals)
number of input bytes
number of output bytes
Enter the calculated number of input and output bytes (+any reserves for expansion)
in the Resource Hardware  Input/
Output Modules" mask.
Festo P.BE−VIFB11−03−EN en 0503g
4−17
4. Commissioning
Example:
Valve terminal #3: 4 I−Bytes, 4 O−Bytes Valve terminal #4: 3 I−Bytes, 2 O−Bytes Valve terminal #5: 2 I−Bytes, 2 O−Bytes Valve terminal #6: 3 I−Bytes, 2 O−Bytes
After pressing the button CONF", the seven−segment display of the DLC 100/200 shows the following sequential figures:
4 (= number of recognised network modules)
12 (= number of input bytes)
10 (= number of output bytes)
If the displayed values agree with the calculated values, they can be accepted into the project. In the following example, the number of I/O bytes are rounded up so that there is no address displacement with future expansions.
4−18
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
Fig.4/4: I/O configuration DLC 100
Festo P.BE−VIFB11−03−EN en 0503g
4−19
4. Commissioning
4.3.3 Addressing the inputs/outputs with Philips DIOS
In the above example, the I/O addresses of the valve terminal start with the input/output address 4. The I/O bytes are as signed without gaps in sequence to the valve terminals with inputs and outputs separated.
The following diagram shows the assignment of the valve terminal I/Os on the I/O address range of the valve terminal configuration shown in Figure 4/8.
I/O address range Philips P8
the Philips P8 for
Configured I/O address range DLC 100/200
Address range valve terminals
Inputs
Valve terminal #3 4 Bytes
Valve terminal #4 3 Bytes
Valve terminal #5 2 Bytes
Valve terminal #6 3 Bytes
Outputs
Valve terminal #3 4 Bytes
Valve terminal #4 2 Bytes
Valve terminal #5 2 Bytes
Valve terminal #6 2 Bytes
Fig.4/5: I/O configuration DLC 100
4−20
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
The following diagrams show an example of the assignment of inputs/outputs on the valve terminals #4 and #5 for the above example:
Valve terminal #4: Input byte 6.0, 6.1, 7.0 Output byte 6.0, 6.1 Valve terminal #5: Input byte 7.1, 8.0 Output byte 7.0, 7.1
I7.0I7.1I7.2I7.3
I6.9
I6.8
I6.10I6.12
I6.11
I6.1
I6.0
I6.3
I6.2I6.4
Q6.12Q6.13Q6.14Q6.15
Q6.0
Q6.1
Q6.2
Q6.3
Q6.4
Q6.5
Q6.6
Q6.7
Q6.8Q6.9
Q6.10Q6.11
I6.13
I6.5
I6.14
I6.15
I6.6
I6.7
Fig.4/6: Example  Addressing (Valve terminal #4)
Festo P.BE−VIFB11−03−EN en 0503g
4−21
4. Commissioning
I8.0I8.1I8.2I8.3
I7.8
I7.9
I7.10
I7.11
I7.12
I7.13
I7.14
I7.15
Q7.15 Q7.14 Q7.12Q7.13
Q7.11 Q7.10 Q7.8Q7.9
Q7.0
Q7.1
Q7.2
Q7.3
Q7.4
Q7.5
Q7.6
Q7.7
Fig.4/7: Example  Addressing (Valve terminal #5)
4−22
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
Program example (Philips Dios)
Addressing a valve terminal with 20 inputs (+4 status bits) and 16 outputs (12 valve coils, 4 electric outputs).
Network module number: 4
1. Input address: 6.0
1. Output address: 6.0
Festo P.BE−VIFB11−03−EN en 0503g
Fig.4/8: Example  Program extract
4−23
4. Commissioning
4.3.4 Diagnosis with Philips Dios
The following bus diagnoses are available within the DIOS system:
Diagnosis via DLC 100/200
Diagnosis via user program
Diagnosis via DLC 100/200
Bus errors are displayed by the two seven−segment displays on the DLC 100/200.
Fig.4/9: DLC 100 seven−segment displays
The valve terminal behaves in the DIOS like equivalent Philips DIOS modules with regards to diagnosis. During a short−cir cuit on the output stages, the LED LOAD" lights up. Special error messages are not output. Errors L1−L4 and E1−E6 are also generated by the valve terminals in cases of
4−24
error.
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
Diagnosis with Philips DIOS using the user program
There are two options available when diagnosing with the user program:
Diagnosis object of system
Status bits of valve terminals
Diagnosis object of system
The following diagram shows the diagnosis object of the sys tem. The diagnosis object _CONF" is set to logic 1 if the bus configuration is faulty.
Fig.4/10: Overview of diagnosis objects
Festo P.BE−VIFB11−03−EN en 0503g
4−25
4. Commissioning
4.3.5 Status bits with Philips Dios
The status bits signal internal errors in the valve terminal. The following errors are recognised:
Under−voltage valves/outputs < 21.6 V
Under−voltage valves/outputs < 10 V
Short−circuit/overload of min. one electric output
Under−voltage sensor supply < 10 V
Further details can be found in Chapter 5 Diagnosis and error treatment" (Chapter 5.3 Status bits).
The status
bits are handled and transmitted like inputs. They always occupy the 4 highest value addresses in the available address space. If the inputs of the input−addresses there under are not used, the valve terminal will set them to logic zero".
4−26
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
The addresses of the status bits in the address space of a valve terminal  dependent on the structure of the valve ter minal  are shown in the following table:
Number of input bytes
None No address space for
1 input byte 0 ... 7 4, 5, 6, 7
2 input byte 0 ... 15 12 ... 15
3 input byte 0 ... 23 20 ... 23
4 input byte 0 ... 31 28 ... 31
5 input byte 0 ... 39 36 ... 39
6 input byte 0 ... 47 44 ... 47
7 input byte 0 ... 55 52 ... 55
8 input byte 0 ... 63 60 ... 63
Available address space
inputs
Addresses of the status bits
No status bits available
Festo P.BE−VIFB11−03−EN en 0503g
4−27
4. Commissioning
s
The following example will clarify the allocation of the inputs/ outputs and status bits:
I7.8
I8.4I8.5I8.6I8.7
I8.0I8.1I8.2I8.3
I7.9
I7.10
I7.11
I7.12
I7.13
Q7.0
Q7.1
Q7.2
Q7.3
Q7.4
Q7.5
Q7.6
Q7.7
Addressesofthestatusbit
I7.14
I7.15
Q7.15 Q7.14 Q7.12Q7.13
Q7.11 Q7.10 Q7.8Q7.9
Fig.4/11: Example  Status bit addressing
4−28
Festo P.BE−VIFB11−03−EN en 0503g
4. Commissioning
4.4 Selectron SELECAN  Principles of commissioning and diagnosis
4.4.1 General information
When using the modular valve terminal with Selectron SELECAN, the following features must be noted:
The I/O addresses of all recognised node modules, in
cluding the valve terminals, are assigned according to the node number set (station number).
The input and output addresses are assigned indepen
dently of each other.
The node numbers can
be assigned as required in
range1−29.
Only assign each node number once.
Please note
The sum of output and input bytes per valve terminal must not exceed 8 bytes!
Festo P.BE−VIFB11−03−EN en 0503g
4−29
4. Commissioning
t
y
p
l
e
o
s
a
Possible input bytes
0 0 0 0 0 0 0 0 0
1 1 1 1 1 1 1 1
2 2 2 2 2 2 2 7 7
8
tes
3 3 3 3 3 3 6 6 6
utby
4 4 4 4 4 5 5 5 5
leinp
5 5 5 5 4 4 4 4 4
ossib
6 6 6 3 3 3 3 3 3
ax.p M
7 7 2 2 2 2 2 2 2
8 1 1 1 1 1 1 1 1
0 0 0 0 0 0 0 0 0
Possible output bytes
Please refer to the manual for your controller for the method of ascertaining the total time required for transmission. The internal processing time of the valve terminal is: < 1 ms.
tes
putb
eout
ssibl
ax.po M
4−30
Festo P.BE−VIFB11−03−EN en 0503g
Loading...