Ferroli HSW Installation And Operation Manual

Page 1
HSW
WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION
INSTALLATION AND OPERATION MANUAL
i migliori gradi centigradi
R
F
R
I
G
E
R
A
N
T
G
A
S
E
C
O
-
F
R
I
E
N
D
L
Y
Page 2
2
The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual, if due to printing or typing mi-
stakes. The manufacturer reserves the right to apply changes and improvements to the products at any time without notice.
Dear Customer, Thank you for having purchased a FERROLI product. It is the result of many years of experiences and of particular research studies and has been made with top quality materials and advanced technologies. The CE mark guarantees that the products satisfy all the applicable European Directives. The qualitative level is kept under constant control and FERROLI products therefore offer SAFETY, QUALITY and RELIABILITY. Due to the continuous improvements in technologies and materials, the product specication as well as performances are subject to variations without prior notice.
Thank you once again for your preference FERROLI S.p.A
Page 3
3
TABLE OF CONTENTS
GENERAL FEATURES                                                                               4
General instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit dataplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unit description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit identification code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Description of components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
TECHNICAL DATA AND PERFORMANCES                                                              11
Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
NOMINAL performances - Base setting up (AB) - Radiant plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
NOMINAL performances - Base setting up (AB) - Standard plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
HEATING performances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
COOLING performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Plant side hydraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Source side hydraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Domestic hot water side hydraulic performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Operating limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Noise levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Overall dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Minimum operating area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
CONNECTIONS                                                                                    23
Hydraulic connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
RECEIVING AND POSITIONING                                                                       25
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
START UP                                                                                         26
Start up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
CONTROL SYSTEM                                                                                 27
Control system configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Heating and cooling circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Control system devices installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Wireless devices connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Control system use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Control system programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Remote thermostat programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Remote control (wired o wireless) programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Functions available for the user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Alarms table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Controller technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Sensors features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
MAINTENANCE                                                                                    43
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
SAFETY AND POLLUTION                                                                           44
General considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Refrigerant safety card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Page 4
4
GENERAL FEATURES
General instructions
Declaration of conformity
Unit dataplate
The figure shows the fields reported on the unit dataplate :
This manual and the wiring diagram supplied with the unit must be kept in a dry place for possible future consultation. The manual provides information on installation and correct use and maintenance of the unit. Before carrying out installation,
please carefully read all the information contained in this manual, which describes the procedures necessary for correct installation and use of the unit
Follow carefully the instructions contained in this manual and respect the safety regulations in force. The unit must be installed in conformity with the laws in force in the country of use. Unauthorized tampering with the electrical and mechanical equipment INVALIDATES THE WARRANTY. Check the electrical specifications given on the dataplate before making the electrical connections. Read the instructions given in the specific section on electrical connections. Deactivate the equipment in case of fault or poor operation. If the unit requires fixing, contact only specialized service centers recognized by the manufacturer and use original spare parts. The unit must be installed indoor and connected to a hydronic cooling and/or heating system. Any use different from that permitted or outside the operating limits indicated in this manual is prohibited (unless previously agreed with the firm).
The manufacturer declines any responsability for damage or injury due to non-compliance with the information given in this manual.
The firm declares that the present unit complies with the requirements of the following directives :
• Machinery directive (MD) 2006/42/EC
• Pressure equipment directive (PED) 97/23/EC
• Electromagnetic compatibility directive (EMC) 2004/108/EC
• Low voltage directive (LVD) 2006/95/EC
Codice Code
B1
Rev
Ferroli Spa Via Ritonda 78/A
(VR) Italy
A - Trademark B - Model B1 - Code C - Serial number D - Capacity in cooling at the condition W30W18 E - Capacity in heating (heat pump) at the condition W10W35 F - Power input in cooling at the condition W30W18 G - Power input in heating (heat pump) at the condition W10W35 H - Reference standard I - Power supply L - Maximum absorbed current M - Refrigerant type and charge weight N - Unit weight O - Sound pressure level at 1 metre P - IP protection level Q - Maximum pressure - high pressure side R - Maximum pressure - low pressure side S - PED certification body
Page 5
5
IH 71 VB AB 0 M 1
GENERAL FEATURES
Unit description
This series of water-water heat pumps satises the heating, cooling and domestic hot water production requirements of resi­dential plants of small and medium size.
All the units are suitable for indoor installation and can be ap­plied to fan coil plants, radiant oor plants and high efciency radiators plants.
As source both water (from well, river, lake…) or brine solutions (from geothermic probes) can be used.
The control system allows to manage not only the refrigerant circuit but the whole plant with the possibility to choose different solutions both for the heating and cooling plant and for the do­mestic hot water management. The possibility of solar panels or other heating sources integration is also available.
The heating function optimizes the ow water temperature ac­cording both to the ambient temperature and to the outdoor tem­perature through climatic curves adaptable to the building featu­res. It’s possible to manage a storage tank and two independent circuits (a direct one and a mixed one).
The domestic hot water management allows to control the th­ree way valve, the storage tank and the anti-legionella cycles (if necessary).
The cooling function can be realized through “passive cooling” (free cooling), through “active cooling” (refrigerant circuit inver-
sion) or through both systems actuated in sequence. When the unit is used in radiant oor plants, to avoid condensate genera­tion, a room humidity sensor can be installed.
The internal programmer clock allows to dene different daily switching programs for heating, cooling and domestic hot water production.
The refrigerant circuit, contained in an extractable box to sim­plify the maintenance operations, is equipped with rotary com­pressor mounted on damper supports, brazed plate heat ex­changers, thermostatic expansion valve and reverse cycle valve (for reversible units). The circuit is protected by high and low pressure switches and ow switches on both the exchangers.
The outdoor structure and the refrigerant circuit box are both thermally and acoustically insulated in order to create a dou­ble wall against sound propagation and to allow the installation in domestic places.
To avoid vibration propagation towards the hydraulic circuit the refrigerant circuit box is placed on damper supports and the con­nection pipes are exible. Moreover all the hydraulic pipes are thermally insulated to avoid condensate generation.
All the units are accurately built and individually tested in the factory. Only electric and hydraulic connections are required for installation.
Unit identification code
The codes that identify the units and the meaning of the letters used are described below.
Unit type
IH - Units suitable for hydronic plant in­stallation operating as heat pumps IP - Units suitable for hydronic plant installation operating as reversible heat pumps
Power supply
1 - 230V - 1 - 50 Hz 5 - 400V - 3N - 50 Hz
Operating range
M - Medium temperature. The unit is suitable to produce water at medium temperature
Refrigerant type
0 - R410A
Acoustic setting up
AB - Base setting up
Unit version
VB - Base version
N° compressors
Unit model
HSW
Page 6
6
GENERAL FEATURES
Description of components
External structure Basement, lateral panels and frontal panel,
are completely thermally and acoustically insulated in order to minimize thermal losses and noise emissions in the surroundings. Accessibility to internal parts is possible removing the frontal panel and the upper panel. For extraordinary manteinances also the rear panel can be removed.
Refrigerant circuit It is contained inside an extractable box to simplify the maintenance operations. The box is placed on rubber vibration dampers and is connected to the hydraulic circuit through flexible pipes in order to avoid the propagation of the vibrations generated by the compressor outside the unit. The hermetic rotary compressor (1) is mounted on damper supports and is protected against overtemperatures and overcurrents. The heat exchangers on the plant side (2) and on the source side (3) are realized with brazed stainless steel plates, properly insulated to avoid condensate generation and to minimize thermal losses, and protected by a flow switch that detects whatever water flow lack. The expansion device (4), a thermostatic expansion valve with external equalizer, allows the unit to adjust itself to the different operating conditions keeping steady the set superheating. The refrigerant circuit of each unit contains moreover solid core hermetic filter dryer (5) to restrain impurity and moisture residuals that could be present in the circuit, high and low pressure switches in order to assure the compressor to operate inside the permitted limits, 4 way reverse cycle valve (6) to allow operating mode change
reversing the refrigerant flow (only for reversible heat pumps), pressure connections SAE 5/16” - UNF 1/2” - 20 equipped with pin, gasket and blind nut, as required for the use of R410A refrigerant (they allow the complete check of the refrigerant circuit : compressor inlet pressure, compressor outlet pressure, thermostatic expansion valve upstream pressure and pressure drops accross the filter). All the pipes of the refrigerant circuit are properly insulated to avoid condensate generation and to minimize thermal losses.
Hydraulic circuit Both the hydraulic circuit on the plant side and on the source side are equipped with expansion vessel, air vents and drain valves. All the pipes are thermally insulated to avoid condensate generation and minimize thermal losses. The circuit on the plant side is moreover equipped with pressure safety valve, pressure gauge and three speed glandless pump while the water flow rate on the source side can be adjusted by means of a three speed glandless pump or by means of a two way valve.
Electrical panel. It contains all the power, control and security components necessary to guarantee the unit to work properly. The unit is managed by a microprocessor controller to which all the electrical loads and the control devices are connected. The user interface, placed on the frontal panel of the unit, allows to view and to modify, if necessary, all the parameters of the unit.
All the units are supplied with an outdoor temperature sensor, to be installed outside, in order to realize the climatic control.
Page 7
7
GENERAL FEATURES
Control system
The microprocessor controller is able to manage not only the unit itself but also all that components of the plant which allow to realize a complete system.
The main functions of the control system are :
- room temperature control according to the outdoor temperature (climatic control)
- domestic hot water production (management of 3 way valve, storage tank, anti legionella cycles…)
- management of a heating and/or cooling mixed circuit (pump and 3 way mixing valve)
- management of a heating direct circuit (only pump)
- management of a storage tank for heating and/or cooling
- management of electrical heaters for heating and domestic hot water (3 steps logic)
- solar panels integration
- passive cooling
- room humidity control for cooling with radiant systems
- internal programmer clock (for heating, cooling and domestic hot water)
- digital input for electrical energy low tariff
- alarm memory management and diagnostic
- compressor and pump operating hour counter
- possibility to manage more units in cascade (maximum 16)
Besides the standard user interface present on all the units, wired or wireless remote thermostats are available which allow to control all the operating parameters of the unit and to acquire the temperature in the different zones in order to realize a more precise and comfortable control.
The unit controller is able to manage a lot of different plant solutions enabling automatically the necessary control algorythms according to the components which have been connected.
The management of such components is possible through ad­ditional expansion modules which communicate with the unit by means of an internal bus and provide all the inputs and outputs required to full a complete system.
The controller is able to manage up to two zones in heating (one by means of a mixed circuit and the other by means of a direct circuit) and one zone in cooling (by means of a mixed circuit).
It’s possible to realize more complex plants connecting to the heat pump controller further expansion modules in order to extend without limits the number of zones to be managed.
For each zone the following parameters can be set :
- set point
- daily or weekly operating time table
- climatic control curve
- room control sensor : it can be in common with the other zones or independent (in that case it’s necessary to install an additional room thermostat)
Room temperature
20.5 C
18:28
Page 8
8
GENERAL FEATURES
Options
The controller flexibility and the big number of options available allow to get, for each model, a lot of different configurations that integrate inside the heat pump many components of the plant and allow to realize compact and tested installations.
In order to select the right configuration it is necessary to define the type of plant to which the heat pump will be connected, both for what concerning the heating and cooling circuits, and for what concerning the domestic hot water management.
Option “Source side flow rate management”
Not reversible heat pump (IH) without options
Pump
Reversible heat pump (IP) without options
2 way valve
Source side ow rate management
Pump Allows the circulation of the water on the source side.
2 way valve
Modulates the water ow rate on the source side when the water circulation is assured by an external pump.
Domestic hot water production
3 way valve
Allow to divert the hot water produced by the heat pump from the heating circuit to the domestic hot water circuit.
3 way valve with primary heat exchanger
The hot water is diverted by the three way valve on an internal heat exchanger. An internal pump assures a correct domestic hot water ow through the other side of the heat exchanger.
3 way valve with secondary heat exchanger (for integrated tank)
The hot water is diverted by the three way valve in a tank integrated in the unit (accessory). The domestic hot water is generated istantaneously by means of an internal heat exchanger and a modulating pump.
Plant buffer tank connections
The hot or cold water produced by the heat pump is used to heat or cool a buffer tank integrated in the unit (accessory) assuring a higher thermal inertia for the plant.
Passive cooling
Allows to use the source to cool down the plant water without activating the compressor.
Integrative electrical heaters
Integrate or replace the heating power supplied by the heat pump and are managed by the unit controller with a 3 step logic.
Soft starter Reduces the compressor start current.
Page 9
9
GENERAL FEATURES
In this configuration the heat pump can be coupled to a domestic hot water tank equipped with a coil designed for a maximum water temperature between 55°C and 60°C.
The anti legionella cycles have to be performed by means of electrical heaters placed on the heat pump outlet (see option “Integrative electrical heaters”) or directly inside the tank.
In this configuration the heat pump can be coupled to a domestic hot water tank without coil.
The anti legionella cycles have to be performed by means of electrical heaters placed on the heat pump outlet (see option “Integrative electrical heaters”) or directly inside the tank.
In this configuration the heat pump can produce instantaneously the domestic hot water using the hot water stored in the tank integrated in the unit (see accessory “Integrated tank”).
The temperature of the domestic hot water at the unit outlet is adjusted modulating the speed of the pump on the primary side.
The anti legionella cycles are not necessary.
Option “Domestic hot water production”
3 way valve
3 way valve with primary heat exchanger
3 way valve with secondary heat exchanger
Option “Plant buffer tank connections"
In this configuration the heat pump can heat or cool a buffer tank that increases the thermal inertia of the plant and operates as hydraulic separator.
NB If the integrated tank is used as buffer tank for the plant, it can not be used as tank for the domestic hot water production (see option "3 way valve and secondary heat exchanger").
Page 10
10
GENERAL FEATURES
Accessories
Remote thermostat
Allows operating mode selection and set point adjustment. The on board temperature sensor can be used in order to realize a climatic control.
Remote control (wired or wireless)
Replicates all the control and visualization functionalities of the controller installed on the unit. The on board temperature sensor can be used in order to realize a climatic control.
Wireless transmitter
Connected to the unit controller, allows to communicate with wireless remote control and wireless outdoor temperature sensor.
Wireless repeater Extends wireless operating range.
Wireless adaptor for outdoor temperature sensor
Allows to transform the wired outdoor temperature sensor, standard for all the units, in a wireless sensor.
Condensate sensor In cooling mode it allows the minimum ow temperature control when condensate generation occurs.
Room hygrostat In cooling mode it allows the minimum ow temperature control according to the room humidity.
Room humidity sensor (with or without display)
In cooling mode it allows the minimum ow temperature control according to the room dew point, calculated from the measured room humidity.
Rubber vibration dampers
Allow to reduce the transmission to the unit support plane of the mechanical vibrations generated by the compressor and by the pumps in their normal operating mode.
Transformer 230V / 24V - 3VA
It assures the correct power supply for the condensate sensor and for the room humidity sensor.
Integrated tank
Integrated tank, to be installed under the unit. It can be used as storage tank for domestic hot water production (coupled with units with option "Domestic hot water production" : "3 way valve and secondary heat exchanger") or as buffer tank for the plant (coupled with units with option "Plant buffer tank connections". Inside the tank a coil for solar panels integration is contained.
Pipes for solar panels connection
Allow to move the connections of the solar integration coil, available on the tank (accessory), directly on the upper side of the unit.
Refrigerant circuit box If a failure occurs inside the refrigerant circuit, it permits to restart the heat pump very quickly.
Option “Passive cooling” Option “Integrative electrical heaters”
Page 11
11
TECHNICAL DATA AND PERFORMANCES
Frame
1
Model
31 51 71 91 111
U.M.
Power supply
230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 V-ph-Hz
Technical data
Refrigerant
Type
R410A R410A R410A R410A R410A -
Compressor
Type
rotary rotary rotary rotary rotary -
Quantity
1 1 1 1 1
Power steps
0 - 100 0 - 100 0 - 100 0 - 100 0 - 100 %
Oil charge
0,35 0,43 0,67 1,13 1,13 kg
Plant side heat exchanger
Type
stainless steel
brazed plates
stainless steel
brazed plates
stainless steel
brazed plates
stainless steel
brazed plates
stainless steel
brazed plates
-
Quantity
1 1 1 1 1
Water volume
0,53 0,53 0,53 0,67 0,84 l
Source side heat exchanger
Type
stainless steel
brazed plates
stainless steel
brazed plates
stainless steel
brazed plates
stainless steel
brazed plates
stainless steel
brazed plates
-
Quantity
1 1 1 1 1
Water volume
0,67 0,67 0,67 0,84 1,04 l
Plant side hydraulic circuit
Safety valve set point
3 3 3 3 3 bar
Expansion vessel volume
10 10 10 10 10 l
Source side hydraulic circuit
Expansion vessel volume
10 10 10 10 10 l
Plant side pump
Type
3 speed
glandless pump
3 speed
glandless pump
3 speed
glandless pump
3 speed
glandless pump
3 speed
glandless pump
-
Quantity
1 1 1 1 1
Installed power
0,14 0,14 0,14 0,14 0,14 kW
Source side pump (option)
Type
3 speed
glandless pump
3 speed
glandless pump
3 speed
glandless pump
3 speed
glandless pump
3 speed
glandless pump
-
Quantity
1 1 1 1 1
Installed power
0,15 0,15 0,15 0,15 0,15 kW
Integrated tank (accessory)
Volume
120 120 120 120 120 -
Solar coil surface
1,1 1,1 1,1 1,1 1,1 m
2
Integrative electrical heaters (option)
Total installed power
9,0 9,0 9,0 9,0 9,0 kW
Power steps
0 - 33 - 66 - 100 0 - 33 - 66 - 100 0 - 33 - 66 - 100 0 - 33 - 66 - 100 0 - 33 - 66 - 100
%
Page 12
12
TECHNICAL DATA AND PERFORMANCES
NOMINAL performances - Base setting up (AB) - Radiant plants
Frame
1
Model
31 51 71 91 111
U.M.
Power supply
230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 V-ph-Hz
IH
Heating W10W35 ( source : water in 10°C out 7°C / plant : water in 30°C out 35°C )
Heating capacity 3,37 5,11 6,85 9,31 11,8
kW
Power input 0,59 0,89 1,24 1,69 2,18
kW
COP 5,71 5,74 5,52 5,51 5,41
-
Water flow rate plant side 584 883 1183 1607 2043
l/h
Available static head plant side 59 50 40 32 25
kPa
Water flow rate source side 798 1209 1612 2193 2782
l/h
Pressure drops source side 7 14 22 25 26
kPa
Heating B0W35 ( source : brine in 0°C out -3°C / plant : water in 30°C out 35°C )
Heating capacity 2,49 3,78 5,07 6,88 8,72
kW
Power input 0,58 0,89 1,23 1,66 2,14
kW
COP 4,29 4,25 4,12 4,14 4,07
-
Water flow rate plant side 431 655 876 1190 1507
l/h
Available static head plant side 63 57 50 46 41
kPa
Water flow rate source side 608 923 1228 1670 2103
l/h
Pressure drops source side 4 9 15 17 17
kPa
Data declared according to EN 14511. The values are referred to units without options or accessories. Brine = water with 30% ethylene glycol.
IP
Heating W10W35 ( source : water in 10°C out 7°C / plant : water in 30°C out 35°C )
Heating capacity 3,30 5,01 6,72 9,13 11,6
kW
Power input 0,58 0,89 1,23 1,67 2,15
kW
COP 5,69 5,63 5,46 5,47 5,40
-
Water flow rate plant side 571 866 1160 1576 2009
l/h
Available static head plant side 59 51 41 33 26
kPa
Water flow rate source side 780 1181 1578 2147 2730
l/h
Pressure drops source side 6 13 21 24 25
kPa
Heating B0W35 ( source : brine in 0°C out -3°C / plant : water in 30°C out 35°C )
Heating capacity 3,30 5,01 6,72 9,13 11,6
kW
Power input 0,58 0,89 1,23 1,67 2,15
kW
COP 5,69 5,63 5,46 5,47 5,40
-
Water flow rate plant side 571 866 1160 1576 2009
l/h
Available static head plant side 59 51 41 33 26
kPa
Water flow rate source side 780 1181 1578 2147 2730
l/h
Pressure drops source side 6 13 21 24 25
kPa
Cooling W30W18 ( source : water in 30°C out 35°C / plant : water in 23°C out 18°C )
Cooling capacity 3,59 5,43 7,27 9,87 12,6
kW
Power input 0,59 0,90 1,25 1,69 2,17
kW
EER 6,08 6,03 5,82 5,84 5,81
-
Water flow rate plant side 619 938 1257 1709 2173
l/h
Available static head plant side 58 49 37 28 21
kPa
Water flow rate source side 722 1094 1470 1995 2541
l/h
Pressure drops source side 6 12 19 21 22
kPa
Cooling B30W18 ( source : brine in 30°C out 35°C / plant : water in 23°C out 18°C )
Cooling capacity 3,51 5,30 7,11 9,63 12,3
kW
Power input 0,60 0,92 1,28 1,72 2,22
kW
EER 5,85 5,76 5,55 5,60 5,54
-
Water flow rate plant side 605 916 1229 1667 2121
l/h
Available static head plant side 59 49 38 30 23
kPa
Water flow rate source side 771 1166 1570 2127 2710
l/h
Pressure drops source side 7 13 22 25 26
kPa
Page 13
13
NOMINAL performances - Base setting up (AB) - Standard plants
TECHNICAL DATA AND PERFORMANCES
Frame
1
Model
31 51 71 91 111
U.M.
Power supply
230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 V-ph-Hz
IH
Heating W10W45 ( source : water in 10°C out 7°C / plant : water in 40°C out 45°C )
Heating capacity 3,10 4,70 6,31 8,58 10,8
kW
Power input 0,72 1,10 1,51 2,04 2,62
kW
COP 4,31 4,27 4,18 4,21 4,12
-
Water flow rate plant side 539 815 1093 1486 1877
l/h
Available static head plant side 60 52 43 36 30
kPa
Water flow rate source side 683 1032 1378 1878 2361
l/h
Pressure drops source side 5 10 17 19 20
kPa
Heating B0W45 ( source : brine in 0°C out -3°C / plant : water in 40°C out 45°C )
Heating capacity 2,32 3,51 4,72 6,40 8,11
kW
Power input 0,70 1,07 1,47 1,99 2,55
kW
COP 3,31 3,28 3,21 3,22 3,18
-
Water flow rate plant side 403 610 819 1111 1406
l/h
Available static head plant side 63 58 52 48 44
kPa
Water flow rate source side 515 779 1037 1409 1775
l/h
Pressure drops source side 3 7 11 13 13
kPa
Data declared according to EN 14511. The values are referred to units without options or accessories. Brine = water with 30% ethylene glycol.
IP
Heating W10W45 ( source : water in 10°C out 7°C / plant : water in 40°C out 45°C )
Heating capacity 3,03 4,61 6,19 8,40 10,6
kW
Power input 0,71 1,09 1,50 2,02 2,59
kW
COP 4,27 4,23 4,13 4,16 4,09
-
Water flow rate plant side 527 799 1072 1456 1842
l/h
Available static head plant side 60 53 44 37 31
kPa
Water flow rate source side 666 1009 1347 1835 2310
l/h
Pressure drops source side 5 10 16 19 19
kPa
Heating B0W45 ( source : brine in 0°C out -3°C / plant : water in 40°C out 45°C )
Heating capacity 2,27 3,44 4,62 6,27 7,96
kW
Power input 0,69 1,06 1,46 1,96 2,53
kW
COP 3,29 3,25 3,16 3,20 3,15
-
Water flow rate plant side 395 598 801 1088 1382
l/h
Available static head plant side 63 58 53 48 45
kPa
Water flow rate source side 503 760 1009 1378 1737
l/h
Pressure drops source side 3 6 11 12 13
kPa
Cooling W30W7 ( source : water in 30°C out 35°C / plant : water in 12°C out 7°C )
Cooling capacity 2,73 4,13 5,54 7,52 9,54
kW
Power input 0,59 0,91 1,26 1,69 2,16
kW
EER 4,63 4,54 4,40 4,45 4,42
-
Water flow rate plant side 469 710 952 1294 1641
l/h
Available static head plant side 62 56 48 43 38
kPa
Water flow rate source side 575 873 1174 1592 2021
l/h
Pressure drops source side 4 8 13 15 15
kPa
Cooling B30W7 ( source : brine in 30°C out 35°C / plant : water in 12°C out 7°C )
Cooling capacity 2,67 4,05 5,42 7,35 9,33
kW
Power input 0,60 0,92 1,28 1,72 2,21
kW
EER 4,45 4,40 4,23 4,27 4,22
-
Water flow rate plant side 458 695 932 1265 1605
l/h
Available static head plant side 62 56 49 44 39
kPa
Water flow rate source side 615 933 1256 1702 2162
l/h
Pressure drops source side 4 9 15 17 18
kPa
Page 14
14
TECHNICAL DATA AND PERFORMANCES
HEATING performances
Inlet temperature - source side [°C] Inlet temperature - source side [°C]
COP ( brine )
Inlet temperature - source side [°C] Inlet temperature - source side [°C]
COP ( water )
Power input ( brine and water )
Temperatura ingresso - lato sorgente [°C]
Heating capacity ( brine ) Heating capacity (water )
A
A
A
A
A
B
B
B
B
B
C
C
C
C
C
D
D
D
D
The graphs allow to get the corrective factors to be applied to the nominal performances in order to obtain the real performances in the selected operating conditions.
The reference nominal conditions are :
WATER-WATER units : W10W35
source : water in 10°C out 7°C
plant : water in 30°C out 35°C
BRINE-WATER units : B0W35
source : brine in 0°C out -3°C
plant : water in 30°C out 35°C
Outlet temperature
plant side :
A = 55°C
B = 45°C
C = 35°C
D = 25°C
Page 15
15
COOLING performances
TECHNICAL DATA AND PERFORMANCES
The performances of the units, when used as brine - water, are referred to applications in which the source side uid is a solution of water and 30% ethylene glycol by volume. Such a concentration guarantees a freezing temperature of about -15°C and allows the unit to work inside the declared operating limits.
Cooling capacity ( brine and water )
Inlet temperature - source side [°C]
Inlet temperature - source side [°C] Inlet temperature - source side [°C]
Power input ( brine and water ) EER ( brine and water )
A
A
A
B
B
B
C
C
C
D
D
D
The graphs allow to get the corrective factors to be applied to the nominal performances in order to obtain the real performances in the selected operating conditions.
The reference nominal conditions are :
WATER-WATER units : W30W7
source : water in 30°C out 35°C
plant : water in 12°C out 7°C
BRINE-WATER units : B30W7
source : brine in 30°C out 35°C
plant : water in 12°C out 7°C
Outlet temperature
plant side :
A = 24°C
B = 18°C
C = 12°C
D = 7°C
Page 16
16
TECHNICAL DATA AND PERFORMANCES
Plant side hydraulic performances
0
5
10
15
20
25
30
35
40
0 500 1000 1500 2000 2500 3000 3500
0
10
20
30
40
50
60
70
80
0 500 1000 1500 2000 2500 3000 3500
A = unit with option “Domestic hot water production” : “3 way valve”
B = unit with option “Integrative electrical heaters”
C = unit with option “Passive cooling”
B
C
A
Available static head - unit without options
9.1
3.1
5.1
7.1
11.1
The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).
Flow rate [ l/h ]
Flow rate [ l/h ]
Pressure drops to be added
Available static head [ kPa ]Pressure drops [ kPa ]
Page 17
17
TECHNICAL DATA AND PERFORMANCES
Source side hydraulic performances
0
10
20
30
40
50
60
70
80
0 500 1000 1500 2000 2500 3000 3500
0
5
10
15
20
25
30
35
40
0 500 1000 1500 2000 2500 3000 3500
3.1
5.1
7.1
9.1
11.1
3.1
5.1
7.1
9.1
11.1
Pressure drops - unit without options
The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).
Flow rate [ l/h ]
Flow rate [ l/h ]
Available static head - unit with option “Source side flow rate management” : “Pump”
Pressure drops [ kPa ]Available static head [ kPa ]
Page 18
18
Domestic hot water side hydraulic performances
TECHNICAL DATA AND PERFORMANCES
0
10
20
30
40
50
60
70
80
0 500 1000 1500 2000 2500 3000 3500
A
9.1
11.1
5.1
3.1
7.1
B
0
5
10
15
20
25
30
35
40
0 500 1000 1500 2000 2500 3000 3500
A = unit with option “Domestic hot water production” : “3 way valve”
B = unit with option “Domestic hot water production” : “3 way valve with primary heat exchanger”
Pressure drops - unit with option “Passive cooling”
The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).
Flow rate [ l/h ]
Flow rate [ l/h ]
Available static head
Pressure drops [ kPa ]Available static head [ kPa ]
Page 19
19
TECHNICAL DATA AND PERFORMANCES
Operating limits
Temperature difference between unit inlet and outlet Plant side Source side
DT max Maximum value 11 5
°C
DT min Minimum value 3 1
°C
Passive
cooling
HEATING
Inlet temperature - source side [°C]
The graphs reported below show the operating area inside which the correct working of the unit is guaranteed. The dotted lines show the operating area when brine solutions in the source side hydraulic circuit are used.
COOLING
Inlet temperature - source side [°C]
Outlet temperature - plant side [°C]Outlet temperature - plant side [°C]
Page 20
20
TECHNICAL DATA AND PERFORMANCES
Electrical data
Power supply 230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 230 - 1 - 50
V-ph-Hz
F.L.A. Maximum total current input 5,9 7,7 10,1 13,3 17,0
A
F.L.I. Maximum total power input 1,3 1,7 2,2 2,9 3,7
kW
M.I.C.
Maximum total start current 36 45 52 82 112
A
Maximum total start current with soft starter (option)
32 35 38 41 43
A
Unit
Power supply 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
V-ph-Hz
F.L.A. Maximum total current input 0,8 0,8 0,8 0,8 0,8
A
F.L.I. Maximum total power input 0,15 0,15 0,15 0,15 0,15
kW
Source side pump (option)
Power supply 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
V-ph-Hz
F.L.A. Maximum total current input 0,4 0,4 0,4 0,4 0,4
A
F.L.I. Maximum total power input 0,08 0,08 0,08 0,08 0,08
kW
Domestic hot water production pump (with option “3 way valve with primary heat exchanger”)
Power supply 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
V-ph-Hz
F.L.A. Maximum total current input 0,7 0,7 0,7 0,7 0,7
A
F.L.I. Maximum total power input 0,14 0,14 0,14 0,14 0,14
kW
Domestic hot water production pump (with option “3 way valve with secondary heat exchanger”)
Power supply
230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 230 - 1 - 50 230 - 1 - 50
V-ph-Hz
400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50
F.L.A.
Maximum total current input ( 230V - 1 - 50Hz )
39,1 39,1 39,1 39,1 39,1
A
Maximum total current input ( 400V - 3N - 50Hz )
13,0 13,0 13,0 13,0 13,0
A
F.L.I. Maximum total power input 9,0 9,0 9,0 9,0 9,0
kW
Integrative electrical heaters
Noise levels
Reference conditions
Performances referred to units operating in heating mode at nominal conditions W10W35. Unit placed in free field on reflecting surface (directional factor equal to 2). The sound power level is measured according to ISO 3744 standard. The sound pressure level is calculated according to ISO 3744 and is referred to a distance of 1 meter from the external surface of the unit.
Frame
1
Model
31 51 71 91 111
U.M.
Model
Sound power levels [dB]
by octave bands [Hz]
Sound power
level
Sound pressure
at 1 meter at 5 meters at 10 meters
63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)] [dB(A)] [dB(A)] [dB(A)]
31
73,2 63,3 48,3 31,7 31,0 22,6 20,9 21,9 74 51 36 25 19
51
74,2 64,3 49,3 32,7 32,0 23,6 21,9 22,9 75 52 37 26 20
71
74,2 64,3 49,3 32,7 32,0 23,6 21,9 22,9 75 52 37 26 20
91
75,2 65,3 50,3 33,7 33,0 24,6 22,9 23,9 76 53 38 27 21
111
75,2 65,3 50,3 33,7 33,0 24,6 22,9 23,9 76 53 38 27 21
Page 21
21
TECHNICAL DATA AND PERFORMANCES
Weights
Frame
1
Model
31 51 71 91 111
U.M.
Unit without options 130 134 136 145 148
kg
Options
Source side flow rate management
Pump 3 3 3 3 3
kg
2 way valve 2 2 2 2 2
kg
Domestic hot water production
3 way valve 3 3 3 3 3
kg
3 way valve with primary heat exchanger
9 9 9 9 9
kg
3 way valve with secondary heat exchanger
10 10 10 10 10
kg
Passive cooling 5 5 5 5 5
kg
Integrative electrical heaters 5 5 5 5 5
kg
Accessories
Integrated tank 77 77 77 77 77
kg
Pipes for solar panels connection 2 2 2 2 2
kg
Refrigerant circuit box 50 54 56 65 68
kg
Components weights
Transport weights
Operating weights
Unit without options 148 152 154 163 166
kg
Options
Source side flow rate management
Pump 3 3 3 3 3
kg
2 way valve 2 2 2 2 2
kg
Domestic hot water production
3 way valve 3 3 3 3 3
kg
3 way valve with primary heat exchanger
9 9 9 9 9
kg
3 way valve with secondary heat exchanger
10 10 10 10 10
kg
Passive cooling 5 5 5 5 5
kg
Integrative electrical heaters 5 5 5 5 5
kg
Accessories
Integrated tank 95 95 95 95 95
kg
Pipes for solar panels connection 3 3 3 3 3
kg
Refrigerant circuit box 52 56 58 67 70
kg
Unit without options 133 137 139 148 152
kg
Options
Source side flow rate management
Pump 4 4 4 4 4
kg
2 way valve 3 3 3 3 3
kg
Domestic hot water production
3 way valve 5 5 5 5 5
kg
3 way valve with primary heat exchanger
13 13 13 13 13
kg
3 way valve with secondary heat exchanger
14 14 14 14 14
kg
Passive cooling 8 8 8 8 8
kg
Integrative electrical heaters 6 6 6 6 6
kg
Accessories
Integrated tank 202 202 202 202 202
kg
Pipes for solar panels connection 5 5 5 5 5
kg
Page 22
22
TECHNICAL DATA AND PERFORMANCES
Overall dimensions
Minimum operating area
Rispect the free area around the unit as shown in figure in order to guarantee a good accessibility and facilitate maintenance and control operations.
A 600 mm
B 300 mm
1 Plant return 1” M
2 Plant flow 1” M
3 Domestic hot water return 1” M
4 Domestic hot water flow 1” M
5 Source return 1” M
6 Source flow 1” M
7 Solar panel return 18 mm
8 Solar panel flow 18 mm
Unit with accessory “Integrated tank”
Unit with accessory
“Integrated tank”
1 2 3 4 5 6
1 2 3 4 5 6
78
A
B
A
B
Page 23
23
CONNECTIONS
Hydraulic connections
To design properly the hydraulic system respect the local safety regulations in force.
It is always necessary to guarantee an appropriate water flow through the plate heat exchangers of the unit even if on both the hydraulic circuits (source side and plant side) is installed, as standard, a flow switch that stops the unit if the water flow rate is too low.
To adjust the water flow rate through the heat exchangers modify the speed of the pump by means of the 3 speed selector. For a more accurate adjustment it is reccomended the installation of a valve on the outlet of each circuit.
It is also reccomended to install a filter on the inlet of each circuit in order to avoid the entrance of foreign substances.
The hydraulic circuit on the plant side is equipped with safety valve and expansion vessel. To mantain the circuit under pressure a self-filling group, that automatically fills the circuit, can be installed.
The hydraulic circuit on the source side is equipped with expansion vessel. If it is used as a closed circuit it is necessary to install an adequate safety valve (maximum setting 3 bar).
Suggestions for the hydraulic plant realization
Prepare the pipes with the minimum possible number of bends in order to minimize pressure losses, and suitably support them to prevent excessive stresses at the connections of the unit.
Install shut-off valves near the components that need maintenance, to allow their replacement without having to drain the system.
Provide manual or automatic valves in the highest part of the circuit to vent the air.
Make sure there are no leaks before insulating the pipes and filling the system.
In order to avoid condensate generation insulate all the pipes on the source side (and also on the plant side for reversible heat pumps) using steam barrier type material.
Brine solutions
When the unit is used as a brine-water heat pump, the source side hydraulic circuit must be filled with a brine solution able to guarantee a freezing temperature lower than the minimum expected operating temperature. In order to guarantee the unit to work inside the whole operating range declared, a freezing temperature not higher than -15°C is required.
The brine solution must be mixed before filling the circuit.
All the components used on the source side hydraulic circuit must be suitable to work with the brine solution adopted.
Galvanized steel pipes are not to be used.
Expansion vessels setting
All the units are equipped with expansion vessels (source side and plant side).
The precharge pressure of the expansion vessel must be adequate to the total volume of the hydraulic circuit at which the unit is connected.
The factory setting (pVE-std = 0,5 bar g) is the minimum value necessary to avoid the presence of zones with a negative relative pressure inside the hydraulic circuit and the risk of pump cavitation, supposing that no parts of the plant are placed at a higher level than the one at which the unit is installed. In that case the precharge pressure must be increased proportionally to the elevation of the highest part of the plant according to the following relation :
pVE = p
VE-std
+ H
max
/ 9,81
pVE : expansion vessel precharge pressure [bar g]
Hmax elevation of the highest part of the plant referred to the unit installation level [m]
The maximum value of the precharge pressure is equal to the safety valve pressure set.
Increasing the precharge pressure, the maximum plant volume supported by the expansion vessel of the unit is reduced :
VI = VVE · Ce · [ 1 - ( 1 + pVE ) / ( 1 + pVS ) ]
VI : plant volume supported by the expansion vessel [l]
VVE : expansion vessel volume [l]
Ce : expansion coefficient
pVS : safety valve pressure set [bar g]
If the real plant volume is higher than such calculated volume, it is necessary to install an additional expansion vessel of appropriate volume.
Once the hydraulic circuit has been filled, the pressure at the expansion vessel must be slightly higher than the precharge pressure.
If parts of the plant are placed at a lower level than the one at which the unit is installed, verify that the components can withstand the maximum pressure that can be present.
Acqua
Ethylene glycol
(percentage by volume)
Propylene glycol
(percentage by volume)
10% 20% 30% 40% 10% 20% 30% 40%
Freezing temperature [°C] 0 -3,8 -8,9 -15,7 -24,9 -3,4 -7,4 -13,1 -21,5
C
e
Plant side (T
min
= 5°C , T
max
= 60°C) 58,63 47,80 45,24 42,82 40,61 45,47 39,96 35,82 32,88
Source side (T
min
= 5°C , T
max
= 45°C) 101,46 73,28 68,84 64,77 61,08 69,42 60,41 53,91 49,03
Source side (T
min
= -10°C , T
max
= 45°C) - - - 51,85 48,57 - - 42,67 38,50
Page 24
24
CONNECTIONS
Electrical connections
The electrical wirings must be carried out by qualified personnel according to the regulations in force at the installation time in the country of installation. Before starting any work on the electrical circuit make sure that the unit power supply line is disconnected at the start.
NB Refer to the electrical diagram enclosed in the unit.
Power supply system
The power cables of the heat pump power supply line must be connected to :
- for single phase power supply : from a single phase voltage system provided with neutral conductor and separated earth wire :
V = 230 V ± 10 %
f = 50 Hz
- for three phase power supply : from a symmetrical three phase voltage system provided with neutral conductor and
separated earth wire :
V = 400 V ± 10 %
f = 50 Hz
The units are shipped completely factory wired and arranged for the connection to the power supply.
The power cables must enter the unit through the holes on the rear panel and must be connected to the power supply terminals of the unit.
The integrative electrical heaters (option) must be supplied by a dedicated power supply line to be connected to the power supply terminals inside the electrical board of the unit.
Heat pump power supply
The power supply cables must have an adequate section for the power absorbed by the unit and must be chosen in conformity with the regulations in force. Design the power supply line, always referring to the total FLI and FLA values of the unit, taking into account the selected options (except the integrative electrical heaters) and the installed accessories.
Integrative electrical heaters power supply
The power supply cables must have an adequate section for the power absorbed by the only integrative electrical heaters and must be chosen in conformity with the regulations in force.
It is possible to connect the integrative electrical heaters either to a single phase power supply or to a three phase power supply.
If a three phase power supply is used, connecting to the terminal R the same phase used to supply the heat pump, the current absorbed by the electrical heaters on that phase is never added to the current absorbed by the heat pump.
Upstream protection
An automatic switch suitable for ensuring protection against overcurrents and indirect contacts must be installed upstream each power supply line.
Coordination between line switch must be carried out observing the regulations in force on electrical safety, regarding the type of installation and the installation ambient conditions.
Connections available for the user
The electrical board of the heat pump contains some terminals dedicated to the connection of temperature probes, humidity probes, pumps, valves ...
Carry out all the necessary connections in order to realize the desired plant following the instructions reported in the section “Inputs and outputs”.
ATTENTION
Carry out all the connections outside the heat pump avoiding the power cables and the probe cables to be coupled.
Integrative electrical heaters connection
with single phase power supply
Integrative electrical heaters connection
with three phase power supply
Integrative
electrical heaters
Single phase
heat pump
Integrative
electrical heaters
Single phase
heat pump
Page 25
25
RECEIVING AND POSITIONING
Receiving
Check on receiving
As soon as the unit is received verify accurately the correspon­dance of the load to what was ordered to make sure that all the material has been delivered. Check carefully that the load has not been damaged. In case of goods with visible damages inform promptly the haulage contractor reporting on the delivery note the phrase “Collected with reserves owing to evident damage”. Delivery ex works implies reimbursement of any da­mage on charge of the insurance company as established by law.
Safety instructions
Observe the safety regulations in force concerning the equip­ment to use for unit handling or the operating formalities to fol­low.
Handling
Before handling the unit, check the weight of the unit , reported both on the dataplate and on the technical documentation. Make sure the unit to be handled with care avoiding any kind of colli­sion that could damage the operating parts of the unit. On the packaging of the unit are reported all the instructions necessary for a corect handling during storing and installation.
The unit is supplied on a pallet suitable for the transport. It is advisable to place protective material between the truck and the unit to avoid damages to the unit. Prevent the unit or parts of it from falling down.
Storing
The units must be stored in a dry place, repaired from sun, rain, sand or wind. Do not stack the units. Maximum temperature = 60 °C Minimum temperature = -20 °C Humidity = 90 %
Packaging removal
Remove the packaging taking care not to damage the unit. Check for any visible damage. Get rid of the packaging material sending them to specialized recycling centres (observe the regulations in force).
Positioning
The units are suitable for indoor installation. Verify that the support surface can bear the weight of the selec­ted unit and is perfectly horizontal. In order to limit the vibrations transmitted by the unit it is possible to place, between the unit base and the support surface, a strip of hard rubber or, if a hi­gher level of insulation is required, vibration dampers.
In any case it is not advisable to place the unit near private offi­ces, bedrooms or zones where very low noise levels are requi­red. Respect the minimum operating area and verify that the installa­tion place is not subject to flooding.
Page 26
26
START UP
Start up
The following operations must be carried out only by properly trained personnel. To make the contractual warranty effective, start up must be carried out by authorized service centres. Before calling the service centre it is advisable to make sure that all the installation steps have been completed (positioning, electrical connections, hydraulic connections...).
Preliminary checks before turning on
1. Verify that :
- the unit has not suffered visible damages due to transport or positioning
- the unit is placed on an horizontal surface able to bear its weight
- the minimum operating area are respected
- the ambient conditions comply with the provided operating limits
- the hydraulic and electrical connections has been carried out correctly
2. Disconnect the unit power suply line at the start and make sure that :
- the unit power supply line complies with the regulations in force
- the screws, fastening the electrical cables to the components inside the electrical panel of the unit, are well tightened (vibrations
during transport phases could have caused some loosening)
3. Connect the unit power supply line and verify that :
- the voltage of the power supply line complies with the the nominal one of the unit
- for three phase power supply units, the unbalance between the phases is lower than 2% (a higher value produces an excesive
current input on one or more phases causing possible damages to the electrical components of the unit)
NOTE. Example of phase unbalance calculation
- Read the value of the three line voltages using a voltmeter :
line voltage between phases L1 and L2 : V
1-2
= 390 V
line voltage between phases L2 and L3 : V
2-3
= 397 V
line voltage between phases L3 and L1 : V
3-1
= 395 V
- Calculate the difference between the maximum and minimum value of the measured line voltages :
ΔV
max
= max ( V
1-2
; V
2-3
; V
3-1
) - min ( V
1-2
; V
2-3
; V
3-1
) = V
2-3
- V
1-2
= 397 - 390 = 7 V
- Calculate the average line voltage value :
Δ
average
= ( V
1-2
+ V
2-3
+ V
3-1
) / 3 = ( 390 + 397 + 395 ) / 3 = 394 V
- Calculate the percentage unbalance value :
ΔV
max
/ V
average
x 100 = 7 / 394 x 100 = 1,78 % < 2 %
Turning on
Press the unit switch on button placed on the frontal panel of the unit. Start all the plant components necessary to guarantee an adequate water flow rate on the plant and source side hydraulic circuit. Activate the unit in heating or in cooling mode operating on the user interface or on the remote controls and insert a set point suitable to require the unit to work.
Page 27
27
CONTROL SYSTEM
Control system configuration
The control system can be configured in different ways in order to adapt itself to the user needs and to the kind of plant managed by the heat pump.
The simpler configuration consists of unit controller (A), user in­terface (E) and outdoor air temperature sensor (B). Such components are always supplied with the unit and allow to realize a climatic control based only on the outdoor air tem­perature.
The communication between the devices of the control system can be carried out through wired or wireless connections. To realize a wireless network are available, as accessories : wireless transmitter (F) to be connected to the heat pump controller, wireless adaptor for outdoor temperature sensor (G) , wireless remote control (H) and wireless repeater (I) to be used to amplify the signal when the distance between the devices is large.
The remote control, supplied as an accessory, can be used, besides as user interface, also as room unit for the management of a zone both in heating and in cooling. The temperature sensor contained inside the remote control allows to detect the room tempera­ture and to realize a climatic control based on the outdoor air temperature and on the room temperature.
If the heat pump controller manages a further heating zone, in order to realize a climatic control based on the outdoor air temperature and on the room temperature, it is necessary to add a remote thermostat (D) dedicated to that zone.
User
interface
Outdoor
air sensor
Heat pump
controller
Outdoor
air sensor
Outdoor
air sensor
Heat pump
controller
Heat pump
controller
Remote
control zone 1
Remote
thermostat
zone 2
Remote
control zone 1
Remote
control zone 2
User
interface
User
interface
Page 28
28
CONTROL SYSTEM
Heating and cooling circuits
The controller of the heat pump is able to manage up to two zones :
- zone 1 : heating and cooling
- zone 2 : only heating
The management of further zones, possibile by means of additional zone controllers, is not treated in this manual.
For each zone can be set :
- set point
- daily or weekly operating time table
- climatic curve
- room control sensor
The management of such zonesis performed by means of three independent distribution circuits.
The heating circuit 1 and the cooling circuit 1 control the same plant components (pump and mixing valve). Such circuits can be ma­naged either as unmixed circuits or as mixed circuits (in this case for the mixing valve management the installation of a temperature sensor on the flow of the circuit is necessary).
Function Distribution circuit
Zone 1
Heating and cooling
HC1 Heating circuit 1 mixed
CC1 Cooling circuit 1 mixed
Zone 2 Heating HCP Heating circuit P NOT mixed
Zone 1
HC1/CC1 HCP
Zone 2
Remote control
40 Room unit 1
42 HC1
Remote thermostat
ru 3 (HCP)
Zone 1
HC1/CC1 HCP
Zone 2
Remote
thermostat
Remote
control
User
interface
User interface
40 Operator unit 1
42 HC1 + HCP
- Climatic control based only on the outdoor air temperature
The management of each zone can be realized by means of :
The room temperature detection is not required. The plant ma­nagement is realized only through the unit user interface. The flow water temperature of each circuit is calculated by means of independent climatic curves for each distribution circuit.
- Climatic control based on the outdoor air temperature and on the room temperature
A room unit (a remote control or a remote thermostat) is requi­red for each zone in order to detect the room temperature and to modify the flow water temperature of each circuit, calculated according to the climatic curves, with the possibility to define a relative weight to the influence of the outdoor air temperature and of the room temperature.
Page 29
29
CONTROL SYSTEM
min. 10 cm
Control system devices installation
REMOTE THERMOSTAT AND REMOTE CONTROL ( WIRED OR WIRELESS )
They should be located in the main room of the zone they manage taking into account the following criteria :
- the place of installation should be chosen so that the sensor can
measure the room temperature as accurately as possible without being influenced by the direct solar radiation or by other hot or cold sources (about 1,5 meters above the floor);
- in the case of wall mounting, enough clearance above the device
must remain, enabling it to be fitted and removed.
The power supply of the remote thermostat and of the remote control is supplied by the mounting base. When the devices are re­moved from their base, power is cut off and the devices are out of operation. The wireless remote control is powered by three 1,5 V alkaline batteries type AA (LR06).
Remote thermostat
Remote control
1 CL+ BSB data
2 CL- BSB ground
1 CL+ BSB data
2 CL- BSB ground
3 G+ Power supply
Wired
Wireless
96
9
6
9
1
4
7
1 2
4,2
65
06
56 60
42
5 8 1
0 0 1
82
4,2
9
56
60
001
80
11
93
76
Page 30
30
CONTROL SYSTEM
A
B
C
A LED
B Button
A LED
B Button
C Connector X60
A LED
B Button
OUTDOOR AIR SENSOR
The device must be installed outside the building. The sensor is con­nected to the controller of the unit or to the wireless adaptor through a two wire cable ( the wires are interchangeable ).
WIRELESS ADAPTOR FOR OUTDOOR TEMPERATURE SENSOR
The device must be installed inside the building. The device is powered by two 1,5 V alkaline batteries type AAA (LR03). The outdoor air sensor is connected to the adaptor through a two wire cable ( the wires are interchangeable ).
WIRELESS TRANSMITTER
The transmitter must be connected to the X60 terminal of the heat pump controller. Before connecting the transmitter, the controller must be disconnected from power. Do NOT install the transmitter inside metal casing.
WIRELESS REPEATER
The device must be installed inside the building. The device is powered through the mounting base by the power pack supplied with the device ( the wires are interchangeable ).
90
001
32
12
4,2
65
06
56
60
B
A
28,8
43
71
66,5
55,8
H
H
2
/
1
N
N-W
3
m 5,2nim
1
2
4
79,8
6,19
49,7
3
5,5
Ø 14,1
2524,5
49,5
4
5,5
6
AAA
AAA
B
A
90
001
32
12
4,2
65
06
56
60
Page 31
31
CONTROL SYSTEM
Wireless devices connection
WIRELESS REMOTE CONTROLLER
WIRELESS ADAPTOR FOR OUTDOOR TEMPERATURE SENSOR
WIRELESS REPEATER
The wireless devices should be located in such a way that the transmission is as interference free as possible. The following criteria must be observed :
- do not place the devices in the vicinity of electrical cables,
strong magnetic fields or equipments as PC, televisions, mi­cro wave ovens...
- do not place the devices near large metal structures or con-
structional elements with fine meshes as special glass or special concrete;
- the distance of the devices from the transmitter should not
exceed 30 meters or 2 floors.
In order to fulfill the connection two stages are necessary.
Connection establishment : wireless devices are connected to the controller of the heat pump. This stage must be done before installing the devices so that all the parts are within easy reach.
Connection test : the signal quality is checked. The devices must be already installed in their final position. If the test fails it’s necessary to modify the position of the devices or to add a wireless repeater in order to extend wireless operating range.
Connection establishment
Verify if the wireless transmitter is connected to the heat pump controller and that the controller is powered. Verify if the batteries of the wireless remote controller are pro­perly installed. Press the button on the wireless transmitter for at least 8 secon­ds. The led starts blinking at high frequency. Press the OK button on the wireless remote controller to enter the menu PROGRAMMING. Press the INFO button for at least 3 seconds, select the opera­ting level COMMISSIONING and press OK. Select the menu WIRELESS and press OK. Set the parameter 40 “USED AS” according to the use of the component and press OK. Select YES with the knob and press OK. The process of opening the connection is started. The display shows the progress of opening the connection in %. The process can take 2 to 120 seconds.
The connection is established when “DEVICE READY” appears and the led on the wireless transmitter extinguishes.
Connection test
Press the OK button on the wireless remote controller to enter the menu PROGRAMMING. Press the INFO button for at least 3 seconds, select the opera­ting level COMMISSIONING and press OK. Select the menu WIRELESS and press OK. Set the parameter 121 “TEST MODE” as ON and press OK. The digits on the left show the telegrams sent, the digits on the right the telegrams received. The test will be ended after 24 te­legrams. The test is considered successful when at least 50% of the telegrams sent have been received.
Connection establishment
Verify if the wireless transmitter is connected to the heat pump controller and that the controller is powered. Verify if the batteries of the wireless adaptor are properly instal­led. Press the button on the wireless transmitter for at least 8 secon­ds. The led starts blinking at high frequency. Press the button on the wireless adaptor for at least 8 seconds. Also the led on the adaptor starts blinking at high frequency. The connection is established when the led on the wireless tran­smitter extinguishes. Press briefly the button on the wireless adaptor until also the led on the wireless adaptor extinguishes.
Connection test
Press the button on the wireless adaptor for a maximum of 8 seconds. The led on the adaptor starts blinking at low frequency. If the connection works correctly the led on the wireless transmit­ter flashes briefly at 10 second intervals. After the test press briefly the button on the wireless adaptor until the led on the adaptor extinguishes. The test can be aborted pressing the ESC button.
Connection establishment
Verify if the wireless transmitter is connected to the heat pump controller and that the controller is powered. Verify if the wireless repeater is properly powered. Press the button on the wireless transmitter for at least 8 secon­ds. The led starts blinking at high frequency. Press the button on the wireless repeater until also the led on the repeater starts blinking at high frequency. The connection is established when the led on the wireless tran­smitter extinguishes. Press briefly the button on the wireless repeater until also the led on the wireless repeater extinguishes.
Connection test
Press the button on the wireless repeater for a maximum of 8 se­conds. The led on the repeater starts blinking at low frequency. If the connection works correctly the led on the wireless transmit­ter flashes briefly at 10 second intervals. After the test press briefly the button on the wireless repeater until the led on the repeater extinguishes. The test can be aborted pressing the ESC button.
Page 32
32
CONTROL SYSTEM
Control system use
The user interface, placed on the frontal panel, allows the com­plete control of the system permitting to visualize and modify all the operating parameters of the unit. The remote control (wired or wireless) replicates all the functions available through the user interface. The only differences com­pared to the user interface are the presence of a temperature
sensor to measure the room temperature of the zone managed by the remote control and the replacement of the “Reset” button with the “Occupancy” button. The remote thermostat contains a temperature sensor to me­asure the room temperature but allows the access to a limited number of functions.
DHW button
ESC button
KNOB
INFO button
KNOB
OCCUPANCY button
OPERATING MODE button
COOLING button
OCCUPANCY button
OK button
OPERATING MODE button
20.5 C
Room temperature
20.5 C
18:28
Room temperature
20.5 C
18:28
DHW button
ESC button
KNOB
OPERATING MODE button
OK button
INFO button
COOLING button
RESET button
BSB port
Page 33
33
CONTROL SYSTEM
OPERATING MODE button
Allows to select the active heating mode (indicated by a bar under the corresponding symbol).
Heating mode Automatic
- room temperature controlled according to the set time table (switching between Comfort and Reduced set point)
- protective functions active
- ECO functions active (automatic summer/winter changeover and automatic 24 hour heating limit)
Heating mode Comfort
- room temperature controlled according to Comfort set point
- protective functions active
- ECO functions not active (automatic summer/winter changeover and automatic 24 hour heating limit)
Heating mode Reduced
- room temperature controlled according to Reduced set point
- protective functions active
- ECO functions active (automatic summer/winter changeover and automatic 24 hour heating limit)
Heating mode Frost Protection
- room temperature controlled according to Frost Protection set point
- protective functions active
- ECO functions active (automatic summer/winter changeover and automatic 24 hour heating limit)
COOLING button
Allows to select the cooling mode (indicated by a bar under the corresponding symbol).
Cooling mode Automatic
- room temperature controlled according to the set time table (switching between Comfort set point and OFF)
- protective functions active
- cooling enabled according to the outdoor temperature
Cooling mode OFF
- protective functions active
REMOTE THERMOSTAT DISPLAY
USER INTERFACE AND REMOTE CONTROL DISPLAY
Heating : Comfort set point
Heating : Reduced set point
Heating : Frost Protection set point
Cooling : Comfort set point
Wait
Change batteries
Holiday function active
Reference to heating circuit
Alarm message
Maintenance messages
Info level
Programming level
ECO functions active
Xxxxxxxxxxxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxxxxxxxxxxx
Xxxxxxxxxxxxxxxxxxxxxxxxxxx
Page 34
34
CONTROL SYSTEM
DHW button
Allows to select the domestic hot water heating mode (indicated by a bar under the corresponding symbol).
Domestic hot water heating mode ON
- domestic hot water temperature controlled according to the set time table
- protective functions active
Domestic hot water heating mode OFF
- protective functions active
Domestic hot water heating mode FORCED Pressing for at least 3 seconds the DHW button the domestic hot water tank forced charging function is activated.
RESET button
Permette di cancellare messaggi di errore pendenti e di ignorare i ritardi previsti alla partenza evitando tempi di attesa indesiderati durante l’installazione o la ricerca di guasti. Questa funzione NON dovrebbe essere utilizzata nel normale funzionamento.
OCCUPANCY button
When a room is not used for a short period of time, pressing the OCCUPANCY button is possible to lower the room temperature in order to save energy. When the room is occupied again, pressing again the OCCUPANCY button, normal operation is restored. The function is active only in automatic heating mode or in automatic cooling mode :
- in heating : changeover from Comfort heating to Reduced heating
- in cooling : changeover from Comfort cooling to cooling OFF
The function remains active until the next operating mode change set through the time table program.
KNOB
Allows to modify the Comfort set point (in heating or in cooling according to the active operating mode). Press the OK button to confirm. Allows moreover to select the different parameters inside the menu and to select the values of each parameter.
INFO button
Pressing the INFO button various informations about the operating status of the system can be displayed. The list of informations changes according to the type of unit, the plant configuration and the active operating mode. When error or maintenance messages are displayed, pressing the INFO button further details about the event are pro­vided.
ECO FUNCTIONS
Automatic summer/winter changeover
This function is used to switch on or off the heating mode in the course of the year according to the outdoor air temperature. It is possible to extend or to shorten the period of time during which the heating mode is active modifying the threshold of the outdoor air temperature at which the changeover takes place. The threshold set is independent for each circuit (parameter 730 for heating circuit 1, parameter 1330 for heating circuit P). Increasing the threshold the heating mode will be switched on earlier and switched off later. To take into account the building thermal inertia the outdoor temperature is attenauted.
Automatic 24 hour heating limit
This function is used to switch on or off the heating mode in the course of the day according to the outdoor air temperature. This fun­ction allows, in the intermediate seasons (spring and autumn), to respond to sudden changes of the outdoor air temperature. It is possible to extend or to shorten the period of time during which the heating mode is active modifying the temperature threshold at which the changeover takes place. The threshold is calculated adding to the Comfort set point a differential. The differential set is independent for each circuit (parameter 732 for heating circuit 1, parameter 1332 for heating circuit P). Increasing the differential the heating mode will be switched on earlier and switched off later. To take into account the building thermal inertia the outdoor temperature is attenauted.
Page 35
35
CONTROL SYSTEM
Control system programming
Menu structure
The settings that can not be modified directly through the buttons of the user interface and of the remote controls are accessible through the programming parameters, grouped inside the various programming menus. The menus concerning functions which are not active are automatically hidden. It is possible to enter the programming menus with different user names. Each user has different authorizations concerning the pos­sibility to visualize and modify the parameters :
- End user E
- Commissioning I
- Heating engineer F
The programming menus are accessible only through the user interface and the remote control.
To enter the programming menus :
- return to the main display (from whatever position press repeatedly the ESC button)
- press the OK button
- press the INFO button for at least 3 seconds
- select the user name with the knob and press the OK button
- select the desired menu and press OK
To modify the parameters inside the menus :
- select the desired parameter with the knob
- press the OK button to modify the parameter
- select the new value with the knob
- press the OK button to confirm the new value or the ESC button to cancel
Menu Level Parameter Function
Hour and date
E 1
Hour / minutes
E 2
Day / Month
E 3
Year
Operator section
E 20
Language
Time table 1
Heating circuit 1
E 500
Preselection
E 501
Phase 1 on
E 502
Phase 1 off
E 503
Phase 2 on
E 504
Phase 2 off
E 505
Phase 3 on
E 506
Phase 3 off
E 516
Default values
Time table 3
Heating circuit P
E 540
Preselection
E 541
Phase 1 on
E 542
Phase 1 off
E 543
Phase 2 on
E 544
Phase 2 off
E 545
Phase 3 on
E 546
Phase 3 off
E 556
Default values
Time table 4
Domestic hot water
E 560
Preselection
E 561
Phase 1 on
E 562
Phase 1 off
E 563
Phase 2 on
E 564
Phase 2 off
E 565
Phase 3 on
E 566
Phase 3 off
E 576
Default values
Page 36
36
CONTROL SYSTEM
Menu Level Parameter Function
Time table 5
Cooling circuit 1
E 600
Preselection
E 601
Phase 1 on
E 602
Phase 1 off
E 603
Phase 2 on
E 604
Phase 2 off
E 605
Phase 3 on
E 606
Phase 3 off
E 616
Default values
Holidays program
Heating circuit 1
E 642
Start
E 643
End
E 648
Operating level
Holidays program
Heating circuit P
E 662
Start
E 663
End
E 668
Operating level
Heating circuit 1
E 710
Comfort set point
E 712
Reduced set point
E 714
Frost Protection set point
E 720
Climatic curve slope
E 730
Summer/winter changeover temperature
Cooling circuit 1
E 901
Operating mode
E 902
Comfort set point
E 907
Release
Heating circuit P
E 1300
Operating mode
E 1310
Comfort set point
E 1312
Reduced set point
E 1314
Frost Protection set point
E 1320
Climatic curve slope
E 1330
Summer/winter changeover temperature
Domestic hot water
E 1610
Nominal set point
Service
Special operations
E 7120
Economy mode
E 7141
Emergency operation
Diagnostic
heat source
E 8410
Heat pump return temperature
E 8412
Heat pump ow temperature
E 8427
Source return temperature
E 8429
Source ow temperature
Diagnostic consumers
E 8700
Outdoor temperature
E 8701
Minimum outdoor temperature
E 8702
Maximum outdoor temperature
E 8740
Room temperature heating circuit 1
E 8741
Set point room temperature heating circuit 1
E 8743
Flow temperature heating circuit 1
E 8756
Flow temperature cooling circuit 1
E 8800
Room temperature heating circuit P
E 8803
Set point ow temperature heating circuit P
E 8830
Temperature 1 Domestic Hot Water
E 8980
Temperature 1 Buffer
E 8982
Temperature 2 Buffer
E 9031
Relay output QX1
E 9032
Relay output QX2
E 9033
Relay output QX3
E 9034
Relay output QX4
E 9035
Relay output QX5
E 9036
Relay output QX6
E 9037
Relay output QX7
E 9038
Relay output QX8
Page 37
37
CONTROL SYSTEM
Remote thermostat programming
Remote control (wired o wireless) programming
Functions available for the user
The configuration parameters of the remote thermo­stat must be set on the device itself. A long press (longer than 3 seconds) on the OC­CUPANCY button allows to enter the Programming menu from which is possible to modify the parame­ters listed in the table. When a parameter is selected the current value blin­ks. Use the knob to adjust the value of the parame­ter. Press briefly the OCCUPANCY button to select the following parameter. Press the HEATING button to escape from the Pro­gramming menu.
The configuration parameters of the remote control must be set on the device itself. Entering the “Operator section” menu it is possible to adjust the parameters listed in the table.
Heat pump type setting
It is possible to set the type of heat pump (water-water or brine-water) modifying the parameter 5800.
Hour, date and language setting
In order to set hour and date enter the “Hour and date” menu and modify the parameters 1, 2 and 3. It is possible to select the desired language for the user interface and for each remote control through the “Operator section” menu (parameter 20).
Time tables setting
When the selected operating mode is “Automatic”, the circuits are activated according to the set time tables. It is possible to set the time table independently for each circuit (heating circuit 1, heating circuit P, domestic hot water circuit, cooling circuit 1).
For the cooling circuit 1 it is possible to select, through the parameter 907, whether :
- keep the circuit always activated (24 hour per day)
- activate the circuit according to time table 5
- activate the circuit according to heating circuit 1 time table
For each time table it is possible to specify the program to use in the different days of the week :
- daily (a different program for each day of the week)
- weekly (same program for all the days of the week)
- week end (a program from Monday to Friday and another program from Saturday to Sunday)
For each program it is possible to specify 3 different operating phases per day (6 switch on or switch off events per day).
Holidays setting
It is possible to set a holidays period for the heating circuit 1 and for the heating circuit P. For each period it is possible to specify the start and the end date and the set point to be adopted during the holidays period.
For details on the settings of parameters 40, 42, 44 and 46 see paragraph “Heating and cooling circuits”. The room temperature sensor contained inside the remote control can be calibrated adding an offset (parmeter 54) to the value read.
Parameter Function
ru
Remote thermostat used as
ru = 1 management heating circuit 1 ru = 3 management heating circuit P
P1
SSave settings
P1 = 1 save pressing HEATING button or for timeout P1 = 2 save pressing HEATING button
P2
Operation lock
P2 = 0 lock disabled P2 = 1 all the buttons are locked (access to Programming menu
granted)
Menu Level Parameter Function
Operator section
E 20
Language
F 22
Informations
F 26
Operation lock
F 27
Programming lock
I 28
Save settings
I 40
Renote control use
I 42
Heating circuits assignment
I 46
Operation heating circuit P
I 48
Action OCCUPANCY button
F 54
Room temperature sensor offset
Page 38
38
CONTROL SYSTEM
Comfort
Reduced
Frost Protection
Operating mode selection for heating and cooling circuits
Heating circuit 1 : through the Heating button on the remote control Heating circuit P : through the Heating button on the remote thermostat Cooling circuit 1 : through the Cooling button on the remote control or through the parameter 901
Set point setting
For each heating circuit 3 set points can be set : Comfort, Reduced and Frost Protecion. For each cooling circuit only one set point can be set : Comfort. The set points of the heating circuits are related one each other : the Comfort set point can not be lower than the Reduced set point, the Reduced set point can not be lower than the Frost Protection set point and the Frost Protection set point can not be lower than 4°C.
All the set points can be adjusted through the parameters. The Comfort set points of the heating circuit 1 and of the cooling circuit 1 can also be adjusted by means of the knob of the user interface. The Comfort set point of each circuit can also be adjusted by means of the knob of the remote control or of the remote thermostat assigned to that circuit (if present).
Heating integration with external heating source
It is possible to manage the activation of an external heating source to integrate the heating capacity supplied by the heat pump. The external source can be enabled only when the outdoor temperature is lower than a fixed limit (parameter 3700) in order to realize a bivalent operation.
Heating circuits climatic curves setting
The climatic curves allow to calculate the flow temperature set point of each circuit according to the outdoor air tempera­ture in order to keep the room temperature as near as possi­ble to the set value. The curves are referred to a room set point of 20°C . If the set point is modified, the curve automatically change to adapt themselves to the new value. It is possible to modify the parameters of the climatic curves in order to fit the features of the plant and of the building. The higher the slope of the curve, the higher is the change of the flow temperature set point for low values of the outdoor air temperature. If the room temperature is correct for high outdoor air tem­perature but is lower than the set point for low outdoor air temperature, the slope of the curve must be increased and vice versa. If on the other hand the room temperature is always lower or higher than the set point the curve must be translated without modifying its slope.
Heating circuit 1 Heating circuit P Cooling circuit 1
Comfort set point parameter 710 parameter 1310 parameter 902
Reduced set point parameter 712 parameter 1312 -
Frost Protection set point parameter 714 parameter 1314 -
Maximum Comfort set point parameter 716 parameter 1316 40 °C
Minimum Comfort set point - - 15 °C
Heating circuit 1
Heating circuit P
Climatic curve slope parameter 720 parameter 1320
Climatic curve displacement parameter 721 parameter 1321
0 2 4 6 8 10 12 14 16 18 20 22 °C
Page 39
39
CONTROL SYSTEM
Inputs and outputs
The following table shows the list of the inputs and outputs available on the controller of the heat pump along with the expected use. Some inputs and outputs can be configured in a different way by the user in order to manage other plant components which are not contained inside the heat pump.
ID Use Description Features
Available
for the user
ingressi
B9 B9 outdoor air temperature temperature sensor NTC 1K B91 B91 source heat exchanger inlet temperature temperature sensor NTC 10K B92 B92 source heat exchanger outlet temperature temperature sensor NTC 10K B71 B71 plant heat exchanger inlet temperature temperature sensor NTC 10K B21 B21 plant heat exchanger outlet temperature temperature sensor NTC 10K
B3 B3 domestic hot water buffer temperature temperature sensor NTC 10K
B1 B1 heating circuit 1 ow temperature temperature sensor NTC 10K
BX1 B4 plant buffer temperature temperature sensor NTC 10K x BX2 B41 plant buffer temperature - bottom temperature sensor NTC 10K x BX3 B31 domestic hot water buffer temperature - bottom temperature sensor NTC 10K x (1) BX4 B38 instantaneous domestic hot water ow temperature temperature sensor NTC 10K x (1) BX5 B6 solar collector temperature temperature sensor NTC 10K x
H1 H1 instantaneous domestic hot water ow switch voltage free digital input
H3 H3 room humidity sensor
voltage free digital input 0-10 Vdc input
x
E9 E9 Low pressure switch 230 Vac digital input E10 E10 High pressure switch 230 Vac digital input
EX1 E15 Source ow switch 230 Vac digital input EX2 E24 Plant ow switch 230 Vac digital input EX3 E5 Low tariff 230 Vac digital input x EX4 E6 Electrical power supply lock 230 Vac digital input x EX5 - - 230 Vac digital input x EX6 - - 230 Vac digital input x EX7 - - 230 Vac digital input x
uscite
K1 K1 Compressor 2 A - 230 Vac
Q2 Q2 Heating circuit 1 pump 2 A - 230 Vac Q3 Q3 Domestic hot water 3 way valve 2 A - 230 Vac
Q8 Q8
Source pump Source 2 way valve
2 A - 230 Vac
Q9 Q9 Plant pump 2 A - 230 Vac QX1 K25 Integrative electrical heaters - step 1 2 A - 230 Vac x (2) QX2 K26 Integrative electrical heaters - step 2 2 A - 230 Vac x (2) QX3 Y28 Passive cooling 3 way valve 2 A - 230 Vac x (3)
QX4
Q33 Q34
Domestic hot water pump Instantaneous domestic hot water pump
2 A - 230 Vac x (1)
QX5 Y22 Reversing cycle valve 2 A - 230 Vac x (4)
QX6
Q20Q5Heating circuit P pump
Solar collector pump
2 A - 230 Vac x
Y1/Y2 Y1/Y2 Heating circuit 1 3 way mixing valve 2 A - 230 Vac x
UX - - 0-10 Vdc x
(1) Available for the user only if as “Domestic hot water production” option has not been chosen “3 way valve with primary heat
exchanger” or “3 way valve with secondary heat exchanger”. (2) Available for the user only if the “Integrative electrical heaters” option has not been chosen. (3) Available for the user only if the “Passive cooling” option has not been chosen. (4) Available for the user only for not reversible heat pumps (IH).
Page 40
40
CONTROL SYSTEM
The controller diagnostic takes into account, besides the alarms reported in the table, many other alarm codes the meaning of which is indicated on the unit display when the corresponding alarm becomes active. Such alarms are not critical and don’t lock the heat pump operation.
Note: (1) A = automatic reset , M = manual reset , A / M = manual reset only if the number of events in an hour is higher than 3. (2) Only for brine-water units (3) Only for water-water units
Code
Alarm Reset
(1)
Input Heat pump lock
10 Outdoor air temperature sensor A B9 No
33 Plant side flow temperature sensor A B21 No
35 Source side return temperature sensor A B91 Yes
(2)
44 Plant side return temperature sensor A B71 No
45 Source side flow temperature sensor A B92 Yes
(3)
106 Sorce side temperature too low M - Yes 201 Plant side frost protection alarm A B21 Yes 222 High pressure during heat pump operating A / M E10 Yes 223 High pressure during heating circuit start M E10 Yes 224 High pressure during domestic hot water circuit start M E10 Yes 225 Low pressure A / M E9 Yes 228 Source side flow switch A / M E15 Yes 355 Phase sequence controller A / M E21 - E23 Yes 356 Plant side flow switch A / M E24 Yes
Alarms
Alarms table
Alarms activation and reset
The controller is able to perform a complete diagnosis of the unit detecting all the operating faults and notifying different alarms. The activation of an alarm implies :
- involved consumers locked
- alarm icon shown on the display
- event recorded in the alarm history
To show the details about the active alarm press the INFO but­ton.
Alarms that can damage the unit or the plant require a manual reset that implies that the operator has to reset manually the controller. It is advisable to verify accurately the cause that ori­ginated the alarm and to make sure that the problem has been solved before restarting the unit. In any case the unit will restart only if the cause of the alarm has disappeared. For the manual reset alarms, pressing the INFO button, along with the details about the alarm, also the message “Reset ?” will appear. Press the OK button. When the message “Yes” blinks press again the OK button to confirm the alarm reset.
The less critical alarms have an automatic reset. As soon as the minimum compressor switch off time has elapsed the controller tries to reset the alarm. If the cause that originated the alarm has disappeared, the unit starts working again and the alarm icon is
no more shown on the display. Some of these alarms become manual reset alarms if the number of events in an hour exceeds a fixed threshold.
It is possible to reset the active alarms also through the RESET button or the parameter 6711 that activates the RESET function. In that case the scheduled delays at the unit switch on are igno­red avoiding undesired waiting times during commissioning or fault tracing. This function should NOT be used in normal ope­ration.
Alarm history
The controller allows to save the last 10 alarms occured during the unit operation. For each event the following details are re­corded :
- alarm code
- hour
- date
Such details can be displayed entering the “Errors” menu (para­meters from 6800 to 6819). When the number of saved events is higher than 10 the following events are saved deleting the oldest alarms.
Page 41
41
CONTROL SYSTEM
Controller technical data
Power supply
230 Vac (+10% / -15%)
50 Hz / 60 Hz
max 11 VA
Safety class (EN 60730) II Degree of protection (EN 60529) IP 00 Operating room temperature (not condensing) -20°C ... 50°C Storing room temperature -20°C ... 65°C
Power supply bus BSB
Communication
wired BSB bus
2 wire connection not interchangeable (200m max)
Safety class (EN 60730) III Degree of protection (EN 60529) IP 20 Operating room temperature (not condensing) 0°C ... 50°C Storing room temperature -20°C ... 65°C
Room temperature sensor
Range : 0°C ... 50°C
Resolution : 0,1°C
Tolerance : 1,0°C
Power supply 3 alkaline batteries 1,5 V type AA (LR06)
Communication
wireless BSB bus
frequency 868 MHz
Safety class (EN 60730) III Degree of protection (EN 60529) IP 20 Operating room temperature (not condensing) 0°C ... 50°C Storing room temperature -20°C ... 30°C
Room temperature sensor
Range : 0°C ... 50°C
Resolution : 0,1°C
Tolerance : 1,0°C
Power supply
5,5 Vdc (X60 terminal of the controller)
max 0,11 VA
Communication 6 wire connection not interchangeable (1,5m max)
Safety class (EN 60730) III Degree of protection (EN 60529) IP 40 Operating room temperature (not condensing) 0°C ... 50°C Storing room temperature -20°C ... 65°C
Controller
Remote thermostat and wired remote control
Comando remoto wireless
Wireless transmitter
Power supply bus BSB
Communication
wired BSB bus
5 wire connection not interchangeable (3m max)
Safety class (EN 60730) III Degree of protection (EN 60529) IP 20 Operating room temperature (not condensing) 0°C ... 50°C Storing room temperature -20°C ... 65°C
User interface
Page 42
42
CONTROL SYSTEM
Power supply
230 Vac (+10% / -15%)
50 Hz (+6% / -6%)
max 0,5 VA
Communication
wireless BSB bus
frequency 868 MHz
Safety class (EN 60730) III Degree of protection (EN 60529) IP 20 Operating room temperature (not condensing) 0°C ... 50°C Storing room temperature -20°C ... 65°C
Power supply 2 alkaline batteries 1,5 V type AAA (LR03)
Communication
wireless BSB bus
frequency 868 MHz
Safety class (EN 60730) III Degree of protection (EN 60529) IP 20 Operating room temperature (not condensing) 0°C ... 50°C Storing room temperature -20°C ... 30°C Outdoor temperature sensor cable length max 5m
Wireless repeater
Wireless adaptor for outdoor temperature sensor
Sensors features
The temperature sensors used in the hydraulic circuit are type NTC 10K (10 k at 25°C).
The outdoor air sensor is type NTC 1K (1 k at 25°C).
When the sensor is at the temperature of 25°C the electrical resi­stance measured at the sensor ends is 1 kW for the NTC 1K sensor and 10 k for the NTC 10K sensors. The thermistor of these sensors has a negative temperature coef­ficient : the electrical resistance value decreases when the tempe­rature increases.
In order to verify if a sensor is faulty or interrupted, check the corre­spondence between the resistance value in k and the temperature of the sensor in °C according to the table.
For a reliable check it is not necessary to control each single value, but some sample values are enough. If the instrument shows an infinite resistance the sensor is interrupted.
NTC 1K NTC 10K
Temperature
[°C]
Resistance
[kΩ]
Resistance
[kΩ]
-20 7,578 96,360
-15 5,861 75,502
-10 4,574 55,047
-5 3,6,00 42,158 0 2,857 32,555 5 2,284 25,339
10 1,840 19,873 15 1,492 15,699 20 1,218 12,488 25 1,000 10,000 30 0,827 8,059 35 0,687 6,535 40 0,575 5,330 45 0,483 4,372 50 0,407 3,605 55 - 2,989 60 - 2,49 65 - 2,084 70 - 1,753 75 - 1,481
Page 43
43
Maintenance
IMPORTANT
BEFORE CARRYING OUT MAINTENANCE OR CLEANING OPERATIONS MAKE SURE THE UNIT POWER SUPPLY IS DISCON­NECTED. ANY ORDINARY OR EXTRAORDINARY MAINTENANCE OPERATION MUST BE CARRIED OUT BY SPECIALIZED AND AUTHORIZED PERSONNEL IN ORDER TO ENSURE COMPLIANCE WITH THE SAFETY REGULATIONS IN FORCE.
NB. The unit switch on button placed on the frontal panel of the unit do NOT exclude the electrical voltage to all the circuits contained inside the electrical panel of the unit. Always make sure that the power supply lines (of the heat pump and of the integrative electrical heaters) are disconnected at the start before carrying out any maintenance operation.
This section is extremely important for the efficient operation of the unit during the years. A few operations carried out periodically can avoid the need to call specialized personnel. The operations to be carried out do not require particular technical knowledge and consist of simple checks of the components of the unit. Contact an authorized service center if maintenance is required.
Structure
To prevent noises and strange vibrations to rise make sure that the various steel parts are well fastened together and that the inspec­tion panels are properly fixed to the unit. In case of oxidation, treat with paints, suitable to avoid or reduce the problem, the parts of the unit affected.
Hydraulic plant
Visually check that the hydraulic plant is leaks free and is pressurized. Verify there is no air in the circuit (acting on the air vents). Verify that the filters in the plant are clean.
Electrical plant
Verify that the power supply cable that connects the unit to the distribution panel is not affected by cuts, cracks or alterations that could compromise the insulation. Contact an authorized service center if maintenance is required. After a first period of time from the first start up and at every stop or seasonal start up carefully check that each electrical connection is well fixed.
MAINTENANCE
Page 44
44
SAFETY AND POLLUTION
Accessing the unit
The access to the unit must be granted exclusively to qualified personnel trained to operate on this type of units and provided with the necessary protection equipment. Moreover such personnel, to operate, must be authorized by the owner of the unit and recognized by the Manufacturer.
Residual risks
The unit are designed and built in such a way to minimize risks for people and for the place where the unit is installed. The residual risks, impossible to eliminate during the design process, are reported in the following table along with the indications necessary for their neutralization.
Considered part Residual risk Mode Precautions Compressor Burns Contact Use protective gloves
Refrigerant circuit pipes
Burns Contact Use protective gloves
Cold burns
Contact or refrigerant outflow
Use protective gloves
Electrical circuit
Electrocutions Burns
Contact with live parts
Verify the unit earth connection Disconnect the power supply line before carrying out any operation inside the unit
General considerations
Pollution
The unit contains refrigerant gas and lubricating oil. During discarding such fluids must be recovered and eliminated according to the regulations in force in the country where the unit is installed. The unit must not be abandoned during discarding.
Refrigerant safety card
1 SUPPLIER COMPANY AND PRODUCT IDENTIFICATION
Card No. FRIG 8 Product R-410A Supplier company identification RIVOIRA SpA
2 COMPOSITION / INFORMATION ON INGREDIENTS
Substance / Preparation Preparation Components / Impurities Contains the following components : Difluoromethane (R32) 50 % in weight Pentafluoroethane (R125) 50 % in weight EEC No. Non-applicable for mixtures Trade-name / /
3 IDENTIFICATION OF HAZARDS
Identification of hazards Liquefied gas. The vapours are heavier than air and can cause suffocation, reducing the oxygen available for brea-
thing. Rapid evaporation of the fluid can cause freezing. Can cause cardiac arrhythmia.
4 FIRST-AID MEASURES
Inhalation Do not administer anything if the person has fainted. Take the person outdoors. Use oxygen or artificial respiration if necessary. Do not administer adrenaline or similar substances. Contact with eyes Rinse thoroughly with plenty of water for at least 15 minutes and see a doctor. Contact with skin Wash immediately with plenty of water. Immediately remove all contaminated garments. Swallowing
5 FIRE-PREVENTION MEASURES
Specific hazards Increase in pressure. Dangerous fumes Halogen acids, traces of carbonyl halides. Fire-extinguishing means usable All the known fire-extinguishing means can be used. Specific methods Cool the containers/tanks with water sprays. Special protection equipment Use self-contained breathing apparatus in confined spaces.
6 MEASURES AGAINST ACCIDENTAL SPILLING OF THE PRODUCT
Personal protection Evacuate personnel to safe areas. Provide for adequate ventilation. Use personal protection equip-
ment Protection for the environment It evaporates. Product removal methods It evaporates.
7 HANDLING AND STORAGE
Handling and storage Ensure an adequate air change and/or extraction in the workplaces. Only use well-ventilated rooms.
Do not breathe vapours or aerosols. Carefully close the containers and keep them in a cool, dry and
well-ventilated place. Keep in the original containers. Incompatible products Explosives, flammable materials, organic peroxides.
8 CONTROL OF EXPOSURE / PERSONAL PROTECTION
Personal protection Ensure adequate ventilation, especially in closed areas. Control parameters Difluoromethane (R32): Recommended exposure limits: AEL (8h and 12h TWA) = 1000 ml/m3 Pentafluoroethane (R125): Recommended exposure limits: AEL (8h and 12h TWA) = 1000 ml/m3
Page 45
45
SAFETY AND POLLUTION
Respiratory tract protection For rescue and for maintenance works in tanks, use self-contained breathing apparatus. The vapours
are heavier than air and can cause suffocation, reducing the oxygen available for breathing. Eye protection Total protection glasses. Hand protection Rubber gloves. Hygiene measures Do not smoke.
9 CHEMICAL-PHYSICAL PROPERTIES
Relative density, gas (air=1) Heavier than air. Solubility in water (mg/l) Not known, but deemed very low. Appearance Colourless liquefied gas. Odour Similar to ether. Fire point Does not ignite.
10 STABILITY AND REACTIVITY
Stability and reactivity No decomposition if used according to the special instructions. Materials to be avoided Alkali metals, alkali-earth metals, granulated metal salts, Al, Zn, Be, etc. in powder. Hazardous products of decomposition Halogen acids, traces of carbonyl halides.
11 TOXICOLOGICAL INFORMATION
Local effects Concentrations substantially above the value TLV (1000 ppm) can cause narcotic effects. Inhalation
of highly concentrated products of decomposition can cause respiratory insufficiency (pulmonary
oedema). Long-term toxicity No carcinogenic, teratogenic or mutagenic effects have been recorded in experiments on animals. Specific effects Rapid evaporation of the fluid can cause freezing. Can cause cardiac arrhythmia.
12 ECOLOGICAL INFORMATION
Effects linked to ecotoxicity Pentafluoroethane (R125) Potential global warming with halocarbides; HGWP (R-11 = 1) = 0.84 Potential impoverishment of the ozone; ODP (R-11 = 1) = 0
13 CONSIDERATIONS ON DISPOSAL
General Do not dispose of where accumulation can be hazardous.
Usable with reconditioning.
The depressurised containers must be returned to the supplier.
Contact the supplier if instructions for use are deemed necessary.
14 INFORMATION FOR TRANSPORT
Designation for transport LIQUEFIED GAS N.A.S. ( DIFLUOROMETHANE, PENTAFLUOROETHANE ) UN No. 3163 Class/Div 2.2 ADR /RID No. 2, 2nd A ADR/RID hazard no. 20 ADR label Label 2 : non-toxic non-flammable gas. CEFIC Groupcard 20g39 - A Other information for transport Avoid transport on vehicles where the loading zone is not separate from the cab. Make sure the driver is informed about the potential risk of the load and knows what to do in case of
accident or emergency. Before starting transport, make sure the load is properly secured and : make sure the valve of the container is closed and does not leak; make sure the blind cap of the valve (when provided) is correctly fitted; make sure the cap (when provided) is correctly fitted and that there is an adequate ventilation passage; ensure compliance with the current provisions.
15 INFORMATION ON REGULATIONS
The product must not be labelled according to Directive 1999/45/EC. Comply with the regulations given below, and the relevant applicable updates and amendments. Circulars no. 46/79 and 61/81 of the Ministry of Labour : Risks related to the use of products containing aromatic amines Leg. Decree no. 133/92 : Regulations on the discharge of hazardous substances in waters Leg. Decree no. 277/91 : Protection of workers against noise, lead and asbestos Law 256/74, Decree 28/1/92, Leg. Decree no. 52 dated 3/2/97, Decree dated 28/4/97 as amended : Classification, packing and labelling of hazardous substances and preparations Decree no. 175/88, as amended : Activities with significant accident risks (Seveso Law) Decree no. 203/88 : Emissions into the atmosphere Decree no. 303/56 : Work hygiene Decree no. 547/55 : Regulations on accident prevention Leg. Decree no.152 dated 11/5/99 : Protection of waters
16 OTHER INFORMATION
Recommended uses Refrigerant Can cause suffocation in high concentration. Keep in a well-ventilated place. Do not breathe the gas. The risk of suffocation is often underestimated and must be clearly explained during the training of operators. Ensure compliance with all the national and regional regulations. Before using this product in any new process or trial, an in-depth study on safety and compatibility of the product with the materials must be carried out. The above information is based on our current know-how and describes the product according to the safety requirements. It does not however repre­sent a guarantee and assurance of the qualities in a legal sense. Each person responds personally for compliance with such regulations.
Page 46
46
The manufacturer declines all responsibility for any inaccuracies in this manual due to printing or typing errors.
The reserves the right to modify the products contents in this catalogue without previous notice.
Page 47
47
Page 48
Ferroli spa ¬ 37047 San Bonifacio (Verona) Italy ¬ Via Ritonda 78/A tel. +39.045.6139411 ¬ fax +39.045.6100933 ¬ www.ferroli.it
COD. 3QE24784
Loading...