5
IH 40.1 VB AB 0 M 5
GENERAL FEATURES
Unit description
Unit identification code
The codes that identify the units and the meaning of the letters used are described below.
Unit type
IH - Units suitable for hydronic plant installation operating as heat pumps
IP - Units suitable for hydronic plant
installation operating as reversible heat
pumps
Power supply
1 - 230V - 1 - 50 Hz
5 - 400V - 3 - 50 Hz
Operating range
H - High temperature.
The unit is suitable to produce
water at high temperature
Refrigerant type
0 - R410A
Unit version
VB - Base version
VD - Desuperheater version
N° compressors
Unit model
Acoustic setting up
AB - Base setting up
AS - Low noise setting up
This series of water-water heat pumps satises the heating,
cooling and domestic hot water production requirements of autonomous or centralized residential plants of medium and large
size.
All the units are suitable for indoor installation and can be applied to fan coil plants, radiant oor plants and high efciency
radiators plants.
As source both water (from well, river, lake…) or brine solutions
(from geothermic probes) can be used.
The control system allows to manage not only the refrigerant
circuit but the whole plant with the possibility to choose different
solutions both for the heating and cooling plant and for the domestic hot water management. The possibility of solar panels or
other heating sources integration is also available.
The heating function optimizes the ow water temperature according both to the ambient temperature and to the outdoor temperature through climatic curves adaptable to the building features. It’s possible to manage a storage tank and two independent
circuits (a direct one and a mixed one).
The domestic hot water management allows to control the three way valve, the storage tank and the anti-legionella cycles (if
necessary).
The cooling function can be realized through “passive cooling”
(free cooling), through “active cooling” (refrigerant circuit inversion) or through both systems actuated in sequence. When the
unit is used in radiant oor plants, to avoid condensate gene-
ration, a room humidity sensor can be installed. During cooling
mode operation a part of the heating power in excess can be
recovered for the domestic hot water production (VD version).
The internal programmer clock allows to dene different daily
switching programs for heating, cooling and domestic hot water
production.
The refrigerant circuit is equipped with scroll compressor
mounted on damper supports, brazed plate heat exchangers,
electronic expansion valve and reverse cycle valve (for reversible units). The circuit is protected by high and low pressure
switches and ow switches on both the exchangers.
In the low noise setting up units (AS) the outdoor structure is
thermally and acoustically insulated in order to reduce sound
propagation and to allow the installation in domestic places.
All the hydraulic pipes are thermally insulated to avoid condensate generation.
All the units are supplied with phase sequence and voltage controller and with an outdoor temperature sensor in order to realize
the climatic control.
All the units are accurately built and individually tested in the
factory. Only electric and hydraulic connections are required for
installation.
HMW