Ferroli HMW 35.1 Series, HMW 30.1 Series, HMW 50.1 Series, HMW 55.1 Series, HMW 40.1 Series Technical Manual

...
Page 1
HMW
WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION
TECHNICAL MANUAL
R
E
R
I
G
E
R
A
N
T
G
A
S
E
C
O
-
F
R
I
E
N
D
L
Y
Page 2
2
The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual, if due to printing or typing mi-
stakes. The manufacturer reserves the right to apply changes and improvements to the products at any time without notice.
Page 3
3
TABLE OF CONTENTS
GENERAL FEATURES ..................................................................................4
Unit description ......................................................................................5
Unit identification code ................................................................................5
Description of components .............................................................................6
Control system ......................................................................................7
Options ............................................................................................8
Accessories .......................................................................................10
TECHNICAL DATA AND PERFORMANCES ................................................................11
Technical data......................................................................................11
NOMINAL performances - VERY HIGH TEMPERATURE plants ...............................................12
NOMINAL performances - HIGH TEMPERATURE plants ....................................................13
NOMINAL performances - RADIANT plants...............................................................14
NOMINAL performances - STANDARD plants .............................................................15
HEATING performances..............................................................................16
COOLING performances .............................................................................17
Plant side hydraulic performances ......................................................................18
Source side hydraulic performances ....................................................................20
Performances DESUPERHEATER......................................................................22
Operating limits.....................................................................................23
Electrical data ......................................................................................24
Noise levels .......................................................................................25
Weights...........................................................................................26
Overall dimensions ..................................................................................27
Minimum operating area ..............................................................................27
Page 4
4
Page 5
5
IH 40.1 VB AB 0 M 5
GENERAL FEATURES
Unit description
Unit identification code
The codes that identify the units and the meaning of the letters used are described below.
Unit type
IH - Units suitable for hydronic plant in­stallation operating as heat pumps IP - Units suitable for hydronic plant installation operating as reversible heat pumps
Power supply
1 - 230V - 1 - 50 Hz 5 - 400V - 3 - 50 Hz
Operating range
H - High temperature. The unit is suitable to produce water at high temperature
Refrigerant type
0 - R410A
Unit version
VB - Base version VD - Desuperheater version
N° compressors
Unit model
Acoustic setting up
AB - Base setting up AS - Low noise setting up
This series of water-water heat pumps satises the heating, cooling and domestic hot water production requirements of au­tonomous or centralized residential plants of medium and large size.
All the units are suitable for indoor installation and can be ap­plied to fan coil plants, radiant oor plants and high efciency radiators plants.
As source both water (from well, river, lake…) or brine solutions (from geothermic probes) can be used.
The control system allows to manage not only the refrigerant circuit but the whole plant with the possibility to choose different solutions both for the heating and cooling plant and for the do­mestic hot water management. The possibility of solar panels or other heating sources integration is also available.
The heating function optimizes the ow water temperature ac­cording both to the ambient temperature and to the outdoor tem­perature through climatic curves adaptable to the building featu­res. It’s possible to manage a storage tank and two independent circuits (a direct one and a mixed one).
The domestic hot water management allows to control the th­ree way valve, the storage tank and the anti-legionella cycles (if necessary).
The cooling function can be realized through “passive cooling” (free cooling), through “active cooling” (refrigerant circuit inver­sion) or through both systems actuated in sequence. When the unit is used in radiant oor plants, to avoid condensate gene-
ration, a room humidity sensor can be installed. During cooling mode operation a part of the heating power in excess can be recovered for the domestic hot water production (VD version).
The internal programmer clock allows to dene different daily switching programs for heating, cooling and domestic hot water production.
The refrigerant circuit is equipped with scroll compressor mounted on damper supports, brazed plate heat exchangers, electronic expansion valve and reverse cycle valve (for rever­sible units). The circuit is protected by high and low pressure
switches and ow switches on both the exchangers.
In the low noise setting up units (AS) the outdoor structure is thermally and acoustically insulated in order to reduce sound propagation and to allow the installation in domestic places.
All the hydraulic pipes are thermally insulated to avoid conden­sate generation.
All the units are supplied with phase sequence and voltage con­troller and with an outdoor temperature sensor in order to realize the climatic control.
All the units are accurately built and individually tested in the factory. Only electric and hydraulic connections are required for installation.
HMW
Page 6
6
GENERAL FEATURES
Description of components
External structure. Basement, supporting structure and panels
are made of galvanized and painted sheet-steel to guarantee good resistance to atmospheric agents. Accessibility to internal parts is possible removing the frontal and lateral panels. For extraordinary manteinances also the rear panel can be removed.
In the units with low noise acoustic setting up the basement, the supporting structure and the panels are completely insulated in order to minimize noise emissions in the surroundings.
Refrigerant circuit. It is contained inside a compartment easily accessible to simplify maintenance and control operations.
The hermetic scroll compressor (1) is mounted on damper supports and is protected against overtemperatures and overcurrents.
The heat exchangers on the plant side (2) and on the source side (3) are realized with brazed stainless steel plates, properly insulated to avoid condensate generation and to minimize thermal losses, and protected by a flow switch that detects whatever water flow lack. The expansion device (4), an electronic expansion valve, allows the unit to adjust itself to the different operating conditions keeping steady the set superheating. The refrigerant circuit of each unit contains moreover solid core hermetic filter dryer (5) to restrain impurity and moisture residuals that could be present in the circuit, high and low pressure switches in order to assure the compressor to operate inside the permitted limits, 4 way reverse cycle valve (6) to allow operating mode change reversing the refrigerant flow (only for reversible heat pumps), pressure connections SAE 5/16” - UNF 1/2” - 20 equipped with pin, gasket and blind nut, as required for the use of R410A refrigerant (they allow the complete check of the refrigerant circuit : compressor inlet pressure, compressor outlet pressure, thermostatic expansion valve upstream pressure and pressure drops accross the filter). All the pipes of the refrigerant
circuit are properly insulated to avoid condensate generation and to minimize thermal losses.
Hydraulic circuit. Both the hydraulic circuits on the plant side and on the source side are equipped with expansion vessel, air vents and drain valves. The circuit on the plant side is moreover equipped with pressure safety valve. All the pipes are thermally insulated to avoid condensate generation and minimize thermal losses. The circuit on the plant side can be equipped with a circulation pump (option) while the circuit on the source side can be equipped with a circulation pump (option) or with a two way valve (option).
Electrical panel. It contains all the power, control and security components necessary to guarantee the unit to work properly. The unit is managed by a microprocessor controller to which all the electrical loads and the control devices are connected. The user interface, placed on the frontal part of the unit, allows to view and to modify, if necessary, all the parameters of the unit.
All the units are supplied with an outdoor temperature sensor, to be installed outside, in order to realize the climatic control.
1
2
3
4
5
6
Page 7
7
GENERAL FEATURES
Control system
The microprocessor controller is able to manage not only the unit itself but also all that components of the plant which allow to realize a complete system.
The main functions of the control system are :
- room temperature control according to the outdoor temperature (climatic control)
- domestic hot water production (management of 3 way valve, storage tank, anti legionella cycles…)
- management of a heating and/or cooling mixed circuit (pump and 3 way mixing valve)
- management of a heating direct circuit (only pump)
- management of a storage tank for heating and/or cooling
- management of electrical heaters for heating and domestic hot water (3 steps logic)
- solar panels integration
- passive cooling
- room humidity control for cooling with radiant systems
- internal programmer clock (for heating, cooling and domestic hot water)
- digital input for electrical energy low tariff
- alarm memory management and diagnostic
- compressor and pump operating hour counter
- possibility to manage more units in cascade (maximum 16)
Besides the standard user interface present on all the units, wired or wireless remote thermostats are available which allow to control all the operating parameters of the unit and to acquire the temperature in the different zones in order to realize a more precise and comfortable control.
The unit controller is able to manage a lot of different plant solutions enabling automatically the necessary control algorythms according to the components which have been connected.
The management of such components is possible through ad­ditional expansion modules which communicate with the unit by means of an internal bus and provide all the inputs and outputs
required to full a complete system.
The controller is able to manage up to two zones in heating (one by means of a mixed circuit and the other by means of a direct circuit) and one zone in cooling (by means of a mixed circuit).
It’s possible to realize more complex plants connecting to the heat pump controller further expansion modules in order to extend without limits the number of zones to be managed.
For each zone the following parameters can be set :
- set point
- daily or weekly operating time table
- climatic control curve
- room control sensor : it can be in common with the other zones or independent (in that case it’s necessary to install an additional room thermostat)
Page 8
8
GENERAL FEATURES
Options
The controller flexibility and the big number of options available allow to get, for each model, a lot of different configurations that integrate inside the heat pump many components of the plant and allow to realize compact and tested installations.
In order to select the right configuration it is necessary to define the type of plant to which the heat pump will be connected, both for what concerning the heating and cooling circuits, and for what concerning the domestic hot water management.
Not reversible heat pump (IH) without options Reversible heat pump (IP) without options
Version VD - Desuperheater version
Allows to recover a part of the available heating power (and otherwise not used during cooling operating mode) for the domestic hot water production.
Acoustic setting up
AS - Low noise acoustic setting up
Allows to reduce the noise produced by the unit by means of the refrigerant circuit vane acoustic insulation and sound jackets on the compressors.
Plant side
ow rate
management
Pump (standard, high head or modulating)
Allows the circulation of the water on the plant side.
With the modulating pump is possible to control the ow rate in order to keep
constant the temperature difference between inlet and outlet.
Source side
ow rate
management
Pump (standard, high head or modulating)
Allows the circulation of the water on the source side.
With the modulating pump is possible to control the ow rate in order to keep
constant the temperature difference between inlet and outlet.
2 way valve
Modulates the water ow rate on the source side when the water circulation is
assured by an external pump.
Domestic hot water production
3 way valve
Allow to divert the hot water produced by the heat pump from the heating circuit to the domestic hot water circuit.
Passive cooling
Allows to use the source to cool down the plant water without activating the compressor.
Soft starter Reduces the compressor start current.
Option "Version" : “VD - Desuperheater version"
1
3
4
2
1
3
4
2
1
3
4
7
6
2
Page 9
9
GENERAL FEATURES
In this configuration the heat pump can be coupled to a domestic hot water tank equipped with a coil designed for a maximum water temperature between 55°C and 60°C.
The anti legionella cycles have to be performed by means of electrical heaters placed on the heat pump outlet (see option “Integrative electrical heaters”) or directly inside the tank.
Option “Domestic hot water production”
3 way valve
Option “Source side flow rate management”
Pump 2 way valve
Option “Passive cooling”Option “Plant side flow rate management”
Pump
1
3
4
2 1
3
4
2
1
3
5
4
2
1
3
4
2
1
3
4
2
Page 10
10
GENERAL FEATURES
Accessories
Rubber vibration dampers
Allow to reduce the transmission to the unit support plane of the mechanical vibrations generated by the compressor and by the pumps in their normal operating mode.
3 way valve for domestic hot water
Allow to divert the hot water produced by the heat pump from the heating circuit to the domestic hot water circuit.
Remote thermostat (wired or wireless)
Allows operating mode selection and set point adjustment. The on board temperature sensor can be used in order to realize a climatic control.
Remote control (wired or wireless)
Replicates all the control and visualization functionalities of the controller installed on the unit. The on board temperature sensor can be used in order to realize a climatic control.
LPB bus interface Connected to the unit controller, allows to communicate on the LPB bus, required for the cascade management.
Wireless transmitter
Connected to the unit controller, allows to communicate with the wireless remote control and the wireless outdoor temperature sensor.
BSB wireless transmitter
Connected to the communication bus (BSB) of the unit controller, allows to communicate with the wireless remote control and the wireless outdoor temperature sensor.
Wireless repeater Extends wireless operating range.
Wireless adaptor for outdoor temperature sensor
Allows to transform the wired outdoor temperature sensor, standard for all the units, in a wireless sensor.
Condensate sensor In cooling mode it allows the minimum ow temperature control when condensate generation occurs.
Room hygrostat In cooling mode it allows the minimum ow temperature control according to the room humidity.
Room humidity sensor (with or without display)
In cooling mode it allows the minimum ow temperature control according to the room dew point, calculated from
the measured room humidity.
Transformer 230V / 24V - 3VA
It assures the correct power supply for the condensate sensor and for the room humidity sensor.
Page 11
11
TECHNICAL DATA AND PERFORMANCES
Technical data
Frame
1
Model
30.1 35.1 40.1 45.1 50.1 55.1
U.M.
Power supply
400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz
Refrigerant
Type
R410A -
Compressor
Type
scroll -
Quantity
1
Oil charge
1,8 3,4 3,4 3,4 3,4 3,4 kg
Refrigerant circuit
Number of circuits
1 1 1 1 1 1 -
Power steps
0 - 100 0 - 100 0 - 100 0 - 100 0 - 100 0 - 100 %
Plant side heat exchanger
Type
stainless steel brazed plates -
Quantity
1
Water volume
4,18 4,18 5,14 5,14 5,89 5,89 l
Source side heat exchanger
Type
stainless steel brazed plates -
Quantity
1
Water volume
4,18 4,18 5,14 5,14 5,89 5,89 l
Plant side hydraulic circuit
Safety valve set point
6 6 6 6 6 6 bar
Expansion vessel volume
12 12 12 12 12 12 l
Source side hydraulic circuit
Expansion vessel volume
12 12 12 12 12 12 l
Plant side pump - standard and modulating (option)
Type
centrifugal
pump
centrifugal
pump
centrifugal
pump
centrifugal
pump
centrifugal
pump
centrifugal
pump
-
Quantity
1 1 1 1 1 1
Installed power
0,7 0,7 1,2 1,2 1,2 1,2 kW
Plant side pump - high head (option)
Type
centrifugal
pump
centrifugal
pump
centrifugal
pump
centrifugal
pump
centrifugal
pump
centrifugal
pump
-
Quantity
1 1 1 1 1 1
Installed power
1,2 1,2 2,0 2,0 2,0 2,0 kW
Source side pump - standard and modulating (option)
Type
centrifugal
pump
centrifugal
pump
centrifugal
pump
centrifugal
pump
centrifugal
pump
centrifugal
pump
-
Quantity
1 1 1 1 1 1
Installed power
0,7 0,7 1,2 1,2 1,2 1,2 kW
Source side pump - high head (option)
Type
centrifugal
pump
centrifugal
pump
centrifugal
pump
centrifugal
pump
centrifugal
pump
centrifugal
pump
-
Quantity
1 1 1 1 1 1
Installed power
1,2 1,2 2,0 2,0 2,0 2,0 kW
Page 12
12
TECHNICAL DATA AND PERFORMANCES
IH
Heating W10W65 ( source : water in 10°C out 7°C / plant : water in 55°C out 65°C )
Heating capacity - - - - - -
kW
Power input - - - - - -
kW
COP - - - - - -
-
Water flow rate plant side - - - - - -
l/h
Pressure drops plant side - - - - - -
kPa
Water flow rate source side - - - - - -
l/h
Pressure drops source side - - - - - -
kPa
Heating B0W65 ( source : brine in 0°C out -3°C / plant : water in 55°C out 65°C )
Heating capacity - - - - - -
kW
Power input - - - - - -
kW
COP - - - - - -
-
Water flow rate plant side - - - - - -
l/h
Pressure drops plant side - - - - - -
kPa
Water flow rate source side - - - - - -
l/h
Pressure drops source side - - - - - -
kPa
IP
Heating W10W65 ( source : water in 10°C out 7°C / plant : water in 55°C out 65°C )
Heating capacity - - - - - -
kW
Power input - - - - - -
kW
COP - - - - - -
-
Water flow rate plant side - - - - - -
l/h
Pressure drops plant side - - - - - -
kPa
Water flow rate source side - - - - - -
l/h
Pressure drops source side - - - - - -
kPa
Heating B0W65 ( source : brine in 0°C out -3°C / plant : water in 55°C out 65°C )
Heating capacity - - - - - -
kW
Power input - - - - - -
kW
COP - - - - - -
-
Water flow rate plant side - - - - - -
l/h
Pressure drops plant side - - - - - -
kPa
Water flow rate source side - - - - - -
l/h
Pressure drops source side - - - - - -
kPa
Data declared according to EN 14511. The values are referred to units without options or accessories. Brine = water with 30% ethylene glycol.
NOMINAL performances - VERY HIGH TEMPERATURE plants
Frame
1
Model
30.1 35.1 40.1 45.1 50.1 55.1
U.M.
Power supply
400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz
Page 13
13
TECHNICAL DATA AND PERFORMANCES
IH
Heating W10W55 ( source : water in 10°C out 7°C / plant : water in 47°C out 55°C )
Heating capacity 24,0 27,5 32,5 36,4 41,0 48,0
kW
Power input 7,17 8,17 9,72 10,8 12,2 14,1
kW
COP 3,35 3,37 3,34 3,37 3,36 3,40
-
Water flow rate plant side 2615 2996 3541 3966 4468 5219
l/h
Pressure drops plant side 6 8 7 9 9 12
kPa
Water flow rate source side 4840 5569 6561 7376 8319 9777
l/h
Pressure drops source side 20 25 24 29 28 39
kPa
Heating B0W55 ( source : brine in 0°C out -3°C / plant : water in 47°C out 55°C )
Heating capacity 19,1 21,8 25,8 28,9 32,5 38,0
kW
Power input 6,89 7,83 9,32 10,3 11,6 13,4
kW
COP 2,77 2,78 2,77 2,81 2,80 2,84
-
Water flow rate plant side 2081 2375 2811 3149 3541 4141
l/h
Pressure drops plant side 4 5 5 6 6 8
kPa
Water flow rate source side 3904 4470 5272 5949 6681 7890
l/h
Pressure drops source side 14 18 16 21 20 27
kPa
IP
Heating W10W55 ( source : water in 10°C out 7°C / plant : water in 47°C out 55°C )
Heating capacity 23,5 27,0 31,9 35,6 40,1 47,1
kW
Power input 7,09 8,07 9,61 10,7 12,0 14,0
kW
COP 3,31 3,35 3,32 3,33 3,34 3,36
-
Water flow rate plant side 2561 2942 3476 3879 4369 5121
l/h
Pressure drops plant side 6 7 7 9 8 11
kPa
Water flow rate source side 4717 5452 6418 7176 8090 9548
l/h
Pressure drops source side 19 24 23 28 27 37
kPa
Heating B0W55 ( source : brine in 0°C out -3°C / plant : water in 47°C out 55°C )
Heating capacity 18,6 21,4 25,2 28,3 31,8 37,3
kW
Power input 6,81 7,75 9,21 10,2 11,5 13,3
kW
COP 2,73 2,76 2,74 2,77 2,77 2,80
-
Water flow rate plant side 2027 2332 2746 3084 3465 4064
l/h
Pressure drops plant side 4 5 4 6 5 7
kPa
Water flow rate source side 3767 4368 5113 5790 6490 7699
l/h
Pressure drops source side 13 17 15 20 19 26
kPa
Data declared according to EN 14511. The values are referred to units without options or accessories. Brine = water with 30% ethylene glycol.
NOMINAL performances - HIGH TEMPERATURE plants
Frame
1
Model
30.1 35.1 40.1 45.1 50.1 55.1
U.M.
Power supply
400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz
Page 14
14
TECHNICAL DATA AND PERFORMANCES
NOMINAL performances - Standard plants
Data declared according to EN 14511. The values are referred to units without options or accessories. Brine = water with 30% ethylene glycol.
IH
Heating W10W45 ( source : water in 10°C out 7°C / plant : water in 40°C out 45°C )
Heating capacity 26,5 30,4 35,9 40,2 45,2 52,9
kW
Power input 6,21 7,14 8,47 9,47 10,7 12,5
kW
COP 4,27 4,26 4,24 4,24 4,22 4,23
-
Water flow rate plant side 4588 5266 6222 6952 7821 9141
l/h
Pressure drops plant side 17 23 21 26 25 34
kPa
Water flow rate source side 5835 6718 7919 8874 9977 11721
l/h
Pressure drops source side 28 36 34 42 40 54
kPa
Heating B0W45 ( source : brine in 0°C out -3°C / plant : water in 40°C out 45°C )
Heating capacity 20,6 23,6 27,9 31,2 35,1 41,0
kW
Power input 6,04 6,90 8,19 9,12 10,2 12,0
kW
COP 3,41 3,42 3,41 3,42 3,44 3,42
-
Water flow rate plant side 3580 4084 4831 5405 6083 7108
l/h
Pressure drops plant side 11 14 13 16 16 21
kPa
Water flow rate source side 4670 5338 6299 7079 7969 9353
l/h
Pressure drops source side 19 25 23 29 28 37
kPa
IP
Heating W10W45 ( source : water in 10°C out 7°C / plant : water in 40°C out 45°C )
Heating capacity 26,0 29,8 35,1 39,3 44,3 51,9
kW
Power input 6,14 7,05 8,35 9,34 10,5 12,3
kW
COP 4,23 4,23 4,20 4,21 4,22 4,22
-
Water flow rate plant side 4501 5162 6083 6795 7664 8968
l/h
Pressure drops plant side 17 22 20 25 24 32
kPa
Water flow rate source side 5709 6567 7716 8642 9757 11464
l/h
Pressure drops source side 27 35 32 40 38 52
kPa
Heating B0W45 ( source : brine in 0°C out -3°C / plant : water in 40°C out 45°C )
Heating capacity 20,1 23,2 27,3 30,6 34,4 40,3
kW
Power input 5,97 6,82 8,10 9,01 10,1 11,8
kW
COP 3,37 3,40 3,37 3,40 3,41 3,42
-
Water flow rate plant side 3493 4015 4727 5301 5961 6986
l/h
Pressure drops plant side 10 14 13 16 15 20
kPa
Water flow rate source side 4530 5233 6134 6916 7779 9163
l/h
Pressure drops source side 18 24 22 27 26 36
kPa
Cooling W30W7 ( source : water in 30°C out 35°C / plant : water in 12°C out 7°C )
Cooling capacity 23,2 26,6 31,4 35,2 39,6 46,2
kW
Power input 5,13 5,87 6,96 7,77 8,71 10,2
kW
EER 4,52 4,53 4,51 4,53 4,55 4,53
-
Water flow rate plant side 3999 4582 5406 6058 6813 7963
l/h
Pressure drops plant side 14 18 16 20 19 26
kPa
Water flow rate source side 4899 5604 6621 7403 8325 9707
l/h
Pressure drops source side 20 26 24 29 28 38
kPa
Cooling B30W7 ( source : brine in 30°C out 35°C / plant : water in 12°C out 7°C )
Cooling capacity 23,0 26,3 31,1 34,8 39,2 45,9
kW
Power input 5,15 5,90 7,00 7,82 8,77 10,3
kW
EER 4,47 4,46 4,44 4,45 4,47 4,46
-
Water flow rate plant side 3947 4531 5354 5989 6744 7911
l/h
Pressure drops plant side 13 17 16 20 19 26
kPa
Water flow rate source side 5263 6029 7132 7963 8964 10483
l/h
Pressure drops source side 24 31 29 35 34 46
kPa
Frame
1
Model
30.1 35.1 40.1 45.1 50.1 55.1
U.M.
Power supply
400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz
Page 15
15
TECHNICAL DATA AND PERFORMANCES
NOMINAL performances - Radiant plants
Data declared according to EN 14511. The values are referred to units without options or accessories. Brine = water with 30% ethylene glycol.
IH
Heating W10W35 ( source : water in 10°C out 7°C / plant : water in 30°C out 35°C )
Heating capacity 28,8 33,0 39,0 43,6 49,1 57,6
kW
Power input 5,20 6,02 7,11 8,02 8,99 10,7
kW
COP 5,54 5,48 5,49 5,44 5,46 5,38
-
Water flow rate plant side 4970 5698 6719 7516 8468 9906
l/h
Pressure drops plant side 20 26 24 30 29 39
kPa
Water flow rate source side 6813 7825 9211 10326 11641 13657
l/h
Pressure drops source side 37 48 45 56 54 73
kPa
Heating B0W35 ( source : brine in 0°C out -3°C / plant : water in 30°C out 35°C )
Heating capacity 22,1 25,4 30,0 33,6 37,8 44,2
kW
Power input 5,09 5,84 6,92 7,74 8,68 10,2
kW
COP 4,34 4,35 4,34 4,34 4,35 4,33
-
Water flow rate plant side 3827 4381 5178 5801 6529 7620
l/h
Pressure drops plant side 12 16 15 19 18 24
kPa
Water flow rate source side 5469 6274 7400 8323 9369 10970
l/h
Pressure drops source side 26 34 31 39 37 50
kPa
IP
Heating W10W35 ( source : water in 10°C out 7°C / plant : water in 30°C out 35°C )
Heating capacity 28,2 32,4 38,2 42,7 48,1 56,4
kW
Power input 5,13 5,93 7,01 7,90 8,86 10,5
kW
COP 5,50 5,46 5,45 5,41 5,43 5,37
-
Water flow rate plant side 4866 5594 6598 7360 8295 9715
l/h
Pressure drops plant side 20 26 24 29 28 38
kPa
Water flow rate source side 6655 7670 9031 10089 11378 13368
l/h
Pressure drops source side 36 47 43 53 51 70
kPa
Heating B0W35 ( source : brine in 0°C out -3°C / plant : water in 30°C out 35°C )
Heating capacity 21,6 24,9 29,4 32,9 37,0 43,4
kW
Power input 5,02 5,76 6,84 7,64 8,57 10,1
kW
COP 4,30 4,32 4,30 4,31 4,32 4,30
-
Water flow rate plant side 3741 4295 5074 5680 6390 7481
l/h
Pressure drops plant side 12 16 14 18 17 23
kPa
Water flow rate source side 5326 6134 7231 8122 9140 10744
l/h
Pressure drops source side 25 32 30 37 36 48
kPa
Cooling W30W18 ( source : water in 30°C out 35°C / plant : water in 23°C out 18°C )
Cooling capacity 30,5 34,9 41,2 46,0 51,8 60,6
kW
Power input 5,18 5,97 7,07 7,95 8,90 10,6
kW
EER 5,89 5,85 5,83 5,79 5,82 5,72
-
Water flow rate plant side 5276 6052 7138 7983 8983 10518
l/h
Pressure drops plant side 23 30 28 34 33 44
kPa
Water flow rate source side 6146 7040 8314 9284 10444 12204
l/h
Pressure drops source side 30 39 37 45 43 58
kPa
Cooling B30W18 ( source : brine in 30°C out 35°C / plant : water in 23°C out 18°C )
Cooling capacity 30,1 34,5 40,8 45,6 51,3 60,1
kW
Power input 5,22 6,04 7,15 8,06 9,02 10,7
kW
EER 5,77 5,71 5,71 5,66 5,69 5,62
-
Water flow rate plant side 5207 5983 7069 7897 8897 10431
l/h
Pressure drops plant side 22 29 27 33 32 43
kPa
Water flow rate source side 6598 7569 8953 9987 11247 13157
l/h
Pressure drops source side 36 47 44 54 52 70
kPa
Frame
1
Model
30.1 35.1 40.1 45.1 50.1 55.1
U.M.
Power supply
400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz
Page 16
16
TECHNICAL DATA AND PERFORMANCES
HEATING performances
Inlet temperature - source side [°C] Inlet temperature - source side [°C]
COP ( brine )
Inlet temperature - source side [°C] Inlet temperature - source side [°C]
COP ( water )
Power input ( brine and water )
Inlet temperature - source side [°C]
Heating capacity Heating capacity ( water )
The graphs allow to get the corrective factors to be applied to the nominal performances in order to obtain the real performances in the selected operating conditions.
The reference nominal conditions are :
WATER-WATER units : W10W35
source : water in 10°C out 7°C
plant : water in 30°C out 35°C
BRINE-WATER units : B0W35
source : brine in 0°C out -3°C
plant : water in 30°C out 35°C
Outlet temperature
plant side :
A = 65°C
B = 55°C
C = 45°C
D = 35°C
E = 25°C
B
B
B
B
B
C
C
C
C
C
D
D
D
D
D
E
E
E
E
E
Page 17
17
TECHNICAL DATA AND PERFORMANCES
COOLING performances
The performances of the units, when used as brine - water, are referred to applications in which the source side uid is a solution of
water and 30% ethylene glycol by volume. Such a concentration guarantees a freezing temperature of about -15°C and allows the unit to work inside the declared operating limits.
The graphs allow to get the corrective factors to be applied to the nominal performances in order to obtain the real performances in the selected operating conditions.
The reference nominal conditions are :
WATER-WATER units : W30W7
source : water in 30°C out 35°C
plant : water in 12°C out 7°C
BRINE-WATER units : B30W7
source : brine in 30°C out 35°C
plant : water in 12°C out 7°C
Outlet temperature
plant side :
A = 24°C
B = 18°C
C = 12°C
D = 7°C
Cooling capacity ( brine and water )
Inlet temperature - source side [°C]
Inlet temperature - source side [°C] Inlet temperature - source side [°C]
Power input ( brine and water ) EER ( brine and water )
A
A
A
B
B
B
C
C
C
D
D
D
Page 18
18
TECHNICAL DATA AND PERFORMANCES
Plant side hydraulic performances
The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).
Pressure drops - unit without options
Flow rate [ l/h ]
Flow rate [ l/h ]
Available static head - unit with option “Plant side flow rate management” : “Standard pump” or "modulating pump"
Pressure drops [ kPa ]Available static head [ kPa ]
0
40
80
120
160
200
240
02000 4000 6000 8000 10000 12000
0
20
40
60
80
100
120
02000 4000 6000 8000 10000 12000
30.1
35.1
40.1
45.1
50.1
55.1
55.1
50.1
45.1
40.1
35.1
30.1
Page 19
19
TECHNICAL DATA AND PERFORMANCES
A = unit with option “Domestic hot water production” : “3 way valve”
B = unit with option “Passive cooling”
Flow rate [ l/h ]
Pressure drops to be added
Pressure drops [ kPa ]
Available static head - unit with option “Plant side flow rate management” : “High head pump”
Flow rate [ l/h ]
Available static head [ kPa ]
The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).
0
20
40
60
80
100
120
0 2000 4000 6000 8000 10000 12000
A
0
60
120
180
240
300
360
02000 4000 6000 8000 10000 12000
30.1
35.1
40.1
45.1
50.1
55.1
55.1
50.1
45.1
40.1
35.1
30.1
B
Page 20
20
TECHNICAL DATA AND PERFORMANCES
Source side hydraulic performances
The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).
Pressure drops - unit without options
Flow rate [ l/h ]
Flow rate [ l/h ]
Available static head - unit with option “Source side flow rate management” : “Standard pump” or "modulating pump"
Pressure drops [ kPa ]Available static head [ kPa ]
0
40
80
120
160
200
240
0 2000 4000 6000 8000 10000 12000
0
20
40
60
80
100
120
0 2000 4000 6000 8000 10000 12000
30.1
35.1
40.1
45.1
50.1
55.1
55.1
50.1
45.1
40.1
35.1
30.1
Page 21
21
TECHNICAL DATA AND PERFORMANCES
B = unit with option “Passive cooling”
Flow rate [ l/h ]
Pressure drops to be added
Pressure drops [ kPa ]
Available static head - unit with option “Source side flow rate management” : “High head pump”
Flow rate [ l/h ]
Available static head [ kPa ]
The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).
0
60
120
180
240
300
360
0 2000 4000 6000 8000 10000 12000
55.1
50.1
45.1
40.1
35.1
30.1
0
20
40
60
80
100
120
0 2000 4000 6000 8000 10000 12000
30.1
35.1
40.1
45.1
50.1
55.1
B
Page 22
22
TECHNICAL DATA AND PERFORMANCES
Performances DESUPERHEATER
The graphs are referred to units operating with water at the temperature of 10°C (density 1000 kg/m3).
Flow rate [ l/h ]
Pressure drops desuperheater - unit "VD - Desuperheater version"
Pressure drops [ kPa ]
IP
Cooling W30W7-W45
( source : water in 30°C out 35°C / plant : water in 12°C out 7°C / heat recovery : water in 40°C out 45°C )
Cooling capacity 23,8 27,3 32,2 36,0 40,6 47,4
kW
Power input 5,04 5,76 6,84 7,63 8,56 10,0
kW
EER 4,72 4,74 4,71 4,72 4,74 4,74
-
Water flow rate plant side 4102 4702 5543 6195 6985 8169
l/h
Pressure drops plant side 14 18 17 21 20 27
kPa
Water flow rate source side 4986 5704 6737 7516 8468 9882
l/h
Pressure drops source side 21 26 25 30 29 39
kPa
Heating capacity (desuperheater) 4,35 4,98 5,88 6,57 7,39 8,62
kW
EER with heat recovery 5,59 5,60 5,57 5,58 5,61 5,60
-
Water flow rate desuperheater side 756 865 1022 1142 1284 1498
l/h
Pressure drops desuperheater side 0,1 0,4 0,5 0,7 0,7 1,0
kPa
Frame
1
Model
30.1 35.1 40.1 45.1 50.1 55.1
U.M.
Power supply
400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz
Data declared according to EN 14511. The values are referred to units with the only option "VD - Desuperheater version".
0
5
10
15
20
25
30
0100020003000 4000 5000 6000
30.1
35.1
40.1
45.1
50.1
55.1
Page 23
23
TECHNICAL DATA AND PERFORMANCES
Operating limits
Temperature difference between unit inlet and outlet Plant side Source side
DT max Maximum value 11 5
°C
DT min Minimum value 3 1
°C
Passive
cooling
HEATING
Inlet temperature - source side [°C]
The graphs reported below show the operating area inside which the correct working of the unit is guaranteed. The dotted lines show the operating area when brine solutions in the source side hydraulic circuit are used.
COOLING
Inlet temperature - source side [°C]
Outlet temperature - plant side [°C]Outlet temperature - plant side [°C]
Page 24
24
TECHNICAL DATA AND PERFORMANCES
Electrical data
Unit
Frame
1
Model
30.1 35.1 40.1 45.1 50.1 55.1
U.M.
Power supply
400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz
F.L.A. Maximum total current input 16,1 18,1 20,2 22,1 26,1 30,2
A
F.L.I. Maximum total power input 10,2 11,5 12,8 14,0 16,6 19,2
kW
M.I.C.
Maximum total start current 115 131 138 145 160 194
A
Maximum total start current with soft starter (option)
56 65 69 73 82 102
A
Power supply
400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz
F.L.A. Maximum total current input 1,2 1,2 2,0 2,0 2,0 2,0
A
F.L.I. Maximum total power input 0,7 0,7 1,2 1,2 1,2 1,2
kW
Plant side pump - standard or modulating (option)
Power supply
400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz
F.L.A. Maximum total current input 2,0 2,0 3,4 3,4 3,4 3,4
A
F.L.I. Maximum total power input 1,2 1,2 2,0 2,0 2,0 2,0
kW
Plant side pump - high head (option)
Power supply
400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz
F.L.A. Maximum total current input 1,2 1,2 2,0 2,0 2,0 2,0
A
F.L.I. Maximum total power input 0,7 0,7 1,2 1,2 1,2 1,2
kW
Source side pump - standard or modulating (option)
Power supply
400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 400 - 3 - 50 V-ph-Hz
F.L.A. Maximum total current input 2,0 2,0 3,4 3,4 3,4 3,4
A
F.L.I. Maximum total power input 1,2 1,2 2,0 2,0 2,0 2,0
kW
Source side pump - high head (option)
Page 25
25
TECHNICAL DATA AND PERFORMANCES
Noise levels
Reference conditions
Performances referred to units operating in heating mode at nominal conditions W10W35. Unit placed in free field on reflecting surface (directional factor equal to 2). The sound power level is measured according to ISO 3744 standard. The sound pressure level is calculated according to ISO 3744 and is referred to a distance of 1 meter from the external surface of the unit.
Base acoustic setting up (AB)
Modello
Livelli di potenza sonora [dB]
per bande d'ottava [Hz]
Livello di
potenza sonora
Livello di pressione sonora
a 1 metro a 5 metri a 10 metri
63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)] [dB(A)] [dB(A)] [dB(A)]
30.1
62,5 61,6 61,8 61,2 57,0 55,5 51,1 40,2 68 63 47 37 32
35.1
63,5 62,6 62,8 62,2 58,0 56,5 52,1 41,2 69 64 48 38 33
40.1
64,5 63,6 63,8 63,2 59,0 57,5 53,1 42,2 70 65 49 39 34
45.1
65,5 64,6 64,8 64,2 60,0 58,5 54,1 43,2 71 66 50 40 35
50.1
66,5 65,6 65,8 65,2 61,0 59,5 55,1 44,2 72 67 51 41 36
55.1
67,5 66,6 66,8 66,2 62,0 60,5 56,1 45,2 73 68 52 42 37
Reference conditions
Performances referred to units operating in heating mode at nominal conditions W10W35. Unit placed in free field on reflecting surface (directional factor equal to 2). The sound power level is measured according to ISO 3744 standard. The sound pressure level is calculated according to ISO 3744 and is referred to a distance of 1 meter from the external surface of the unit.
Low noise acoustic setting up (AS)
Model
Sound power levels [dB]
by octave bands [Hz]
Sound power
level
Sound pressure
at 1 meter at 5 meters at 10 meters
63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)] [dB(A)] [dB(A)] [dB(A)]
30.1
51,2 54,9 58,5 57,4 52,0 42,1 29,7 22,3 63 57 41 31 26
35.1
52,2 55,9 59,5 58,4 53,0 43,1 30,7 23,3 64 58 42 32 27
40.1
53,2 56,9 60,5 59,4 54,0 44,1 31,7 24,3 65 59 43 33 28
45.1
54,2 57,9 61,5 60,4 55,0 45,1 32,7 25,3 66 60 44 34 29
50.1
55,2 58,9 62,5 61,4 56,0 46,1 33,7 26,3 67 61 45 35 30
55.1
56,2 59,9 63,5 62,4 57,0 47,1 34,7 27,3 68 62 46 36 31
Page 26
26
TECHNICAL DATA AND PERFORMANCES
Weights
Components weights
Frame
1
Model
30.1 35.1 40.1 45.1 50.1 55.1
U.M.
Transport weights
Operating weights
Unit without options 379 397 407 407 419 420
kg
Options
Version Desuperheater version (VD) 10 10 10 13 13 13
kg
Acoustic setting up
Low noise setting up (AS) 50 50 50 50 50 50
kg
Plant side flow rate management
Standard pump 16 16 16 16 16 16
kg
High head pump 20 20 20 20 20 20
kg
Modulating pump 24 24 24 24 24 24
kg
Source side flow rate management
Standard pump 16 16 16 16 16 16
kg
High head pump 20 20 20 20 20 20
kg
Modulating pump 24 24 24 24 24 24
kg
2 way valve 15 15 15 15 15 15
kg
Domestic hot water production
3 way valve 15 15 15 15 15 15
kg
Passive cooling 25 25 32 32 32 32
kg
Unit without options 388 406 416 416 428 429
kg
Options
Version Desuperheater version (VD) 10 10 10 13 13 13
kg
Acoustic setting up
Low noise setting up (AS) 50 50 50 50 50 50
kg
Plant side flow rate management
Standard pump 16 16 16 16 16 16
kg
High head pump 20 20 20 20 20 20
kg
Modulating pump 24 24 24 24 24 24
kg
Source side flow rate management
Standard pump 16 16 16 16 16 16
kg
High head pump 20 20 20 20 20 20
kg
Modulating pump 24 24 24 24 24 24
kg
2 way valve 15 15 15 15 15 15
kg
Domestic hot water production
3 way valve 15 15 15 15 15 15
kg
Passive cooling 25 25 32 32 32 32
kg
Unit without options 401 419 433 433 449 450
kg
Options
Version Desuperheater version (VD) 12 12 12 16 16 16
kg
Acoustic setting up
Low noise setting up (AS) 50 50 50 50 50 50
kg
Plant side flow rate management
Standard pump 23 23 23 23 23 23
kg
High head pump 27 27 27 27 27 27
kg
Modulating pump
31 31 31 31 31 31
kg
Source side flow rate management
Standard pump 24 24 24 24 24 24
kg
High head pump 28 28 28 28 28 28
kg
Modulating pump 32 32 32 32 32 32
kg
2 way valve 23 23 23 23 23 23
kg
Domestic hot water production
3 way valve 19 19 19 19 19 19
kg
Passive cooling 33 33 45 45 45 45
kg
Page 27
27
TECHNICAL DATA AND PERFORMANCES
1 Source return 1”1/2 M
2 Source flow 1”1/2 M
3 Plant return 1”1/2 M
4 Plant flow 1”1/2 M
5 Domestic hot water flow 1”1/2 M
6 Desuperheater inlet 1”1/4 M
7 Desuperheater outlet 1”1/4 M
Rispect the free area around the unit as shown in figure in order to guarantee a good accessibility and facilitate maintenance and control operations.
A 600 mm
B 600 mm
Overall dimensions
Minimum operating area
1150
790
100 100 100
1552
100 100 100
100
100153
93
1
5
4
3
2
6
7
A
B
Page 28
28
Cod. 3QE37361
Loading...