Ferroli HGP 45.2, HGP 55.2, HGP 65.2, HGP 95.2, HGP 85.2 Technical Manual

...
HGP
AIR-WATER HEAT PUMPS FOR INDOOR INSTALLATION
TECHNICAL MANUAL
R
E
R
I
G
E
R
A
N
T
G
A
S
E
C
O
-
F
R
I
E
N
D
L
Y
2
The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual, if due to printing or typing mi-
stakes. The manufacturer reserves the right to apply changes and improvements to the products at any time without notice.
3
TABLE OF CONTENTS
GENERAL FEATURES ..................................................................................5
Unit description ......................................................................................5
Unit identification code ................................................................................5
Description of components .............................................................................6
Control system ......................................................................................7
Options ............................................................................................8
Accessories ........................................................................................9
TECHNICAL DATA AND PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Technical data......................................................................................10
NOMINAL performances - HIGH TEMPERATURE plants ....................................................11
NOMINAL performances - STANDARD plants .............................................................12
NOMINAL performances - RADIANT plants...............................................................13
HEATING performances..............................................................................14
COOLING performances .............................................................................15
Plant side hydraulic performances ......................................................................16
Source side aeraulic performances .....................................................................18
DESUPERHEATER performances......................................................................19
Operating limits.....................................................................................20
Electrical data ......................................................................................21
Noise levels .......................................................................................22
Weights...........................................................................................23
Overall dimensions ..................................................................................24
Minimum operating area ..............................................................................24
4
5
GENERAL FEATURES
Unit description
This series of air-water heat pumps satises the heating, coo- ling and domestic hot water production requirements of autono­mous or centralized residential plants of medium and large size. All the units are suitable for indoor installation and can be ap­plied to fan coil plants, radiant oor plants and high efciency radiators plants. The control system allows to manage not only the refrigerant circuit but the whole plant with the possibility to choose different solutions both for the heating and cooling plant and for the do­mestic hot water management. The possibility of solar panels or other heating sources integration is also available. The heating function optimizes the ow water temperature ac­cording both to the ambient temperature and to the outdoor tem­perature through climatic curves adaptable to the building featu­res. It’s possible to manage a storage tank and two independent circuits (a direct one and a mixed one). The domestic hot water management allows to control the th­ree way valve, the storage tank and the anti-legionella cycles (if necessary). The cooling function can be realized through “active cooling” (refrigerant circuit inversion). When the unit is used in radiant
oor plants, to avoid condensate generation, a room humidity
sensor can be installed. During cooling mode operation a part of the heating power in excess can be recovered for the domestic hot water production (VD version). The internal programmer clock allows to dene different daily switching programs for heating, cooling and domestic hot water production.
The refrigerant circuit, contained in a box repaired from the air
ow to simplify the maintenance operations, is equipped with
two scroll compressors mounted on damper supports, brazed plate heat exchangers, electronic expansion valve, reverse
cycle valve, centrifugal fans (plug fans), nned coil realized with copper pipes and alluminium ns. The circuit is protected by high and low pressure switches and ow switches on the plate heat
exchanger. The compressors are arranged in tandem on a single refrigerant circuit and allow the capacity modulation according to the plant requests in order to guarantee a high seasonal efficiency. The plate heat exchanger and all the hydraulic pipes are ther­mally insulated in order to avoid condensate generation and re­duce thermal losses. The plug fans with electronic control of the rotational speed gua­rantee high efficiencies and low noise in all the operating condi­tions and allow to install the unit indoor (with ducted air inlet and outlet). It is moreover possible to reduce the noise level during the night. All the units are provided with a phase sequence and correct sequence controller device and with an outdoor temperature sensor in order to realize the climatic control. All the units are accurately built and individually tested in the factory. Only electric and hydraulic connections are required for installation.
IP 75.2 VB AB 0 M 5
Unit identification code
The codes that identify the units and the meaning of the letters used are described below.
Unit type
IP - Units suitable for hydronic plant in­stallation operating as reversible heat pumps
N° compressors
Unit model
Unit version
VB - Base version VD - Desuperheater version
Power supply
1 - 230V - 1 - 50 Hz 5 - 400V - 3 - 50 Hz
Operating range
M - Medium temperature. The unit is suitable to produce water at medium temperature
Refrigerant type
0 - R410A
Acoustic setting up
AB - Base setting up AS - Low noise setting up
HGP
6
GENERAL FEATURES
External structure. Basement, supporting structure and lateral
panels are made of galvanized and painted sheet-steel to guarantee good resistance to atmospheric agents. Accessibility to internal parts is possible removing the frontal and lateral panels. For extraordinary manteinances also the other panels can be removed.
Refrigerant circuit. It is contained inside a compartment separated from the air flow to simplify maintenance and control operations.
The scroll compressors (1) are mounted on damper supports and are protected against overtemperatures and overcurrents. Each compressor is equipped with an electrcal heater, that is activated when the compressor turns off, to keep the compressor crankcase oil temperature high enough to prevent migration of the refrigerant during winter stops and to evaporate any liquid present in the crankcase, in order to prevent possible liquid rushes on starting.
The plant side heat exchanger (2) is a brazed stainless steel plate heat exchanger, properly insulated to avoid condensate generation and to minimize thermal losses, and protected by a flow switch that detects whatever water flow lack.
The source side heat exchanger (3) is a finned coil realized with grooved copper pipes and hydrophilic aluminium fins with waved profile to increase the heat exchange coefficient. A tray is placed under the coil to collect the condensate generated in heating mode.
The expansion device (4), an electronic expansion valve, allows the unit to adjust itself to the different operating conditions keeping steady the set superheating.
The refrigerant circuit of each unit contains moreover solid core hermetic filter dryer (5) to restrain impurity and moisture residuals that could be present in the circuit, high and low pressure switches in order to assure the compressor to operate inside the permitted limits, 4 way reverse cycle valve
(6) to allow operating mode change reversing the refrigerant flow, liquid receiver (7) to compensate the different refrigerant charge required in heating and in cooling mode and pressure connections SAE 5/16” - UNF 1/2” - 20 equipped with pin, gasket and blind nut, as required for the use of R410A refrigerant (they allow the complete check of the refrigerant circuit: compressor inlet pressure, compressor outlet pressure and expansion valve upstream pressure). All the pipes of the refrigerant circuit are properly insulated to avoid condensate generation and minimize thermal losses.
The plug fans (8) are equipped with an high efficiency electronically commutated (EC) motor and guarantee enough available static pressure to allow the indoor ducted installation besides high efficiencies in all the operating conditions.
Hydraulic circuit. All the pipes are thermally insulated to avoid condensate generation and minimize thermal losses. The circuit can be equipped with a standard, high head or modulating circulation pump (option). The circuit is always equipped also with expansion vessel, safety valve and air vents.
Electrical panel. It contains all the power, control and security components necessary to guarantee the unit to work properly. The unit is managed by a microprocessor controller to which all the electrical loads and the control devices are connected. The user interface, to be placed indoor, allows to view and to modify, if necessary, all the parameters of the unit.
All the units are supplied with an outdoor temperature sensor, to be installed outside, in order to realize the climatic control.
Description of components
4
6
3
8
1
2
7
7
GENERAL FEATURES
The microprocessor controller is able to manage not only the unit itself but also all that components of the plant which allow to realize a complete system. The main functions of the control system are :
- room temperature control according to the outdoor temperatu­re (climatic control)
- domestic hot water production (management of 3 way valve, storage tank, anti legionella cycles…)
- management of a heating and/or cooling mixed circuit (pump and 3 way mixing valve)
- management of a heating direct circuit (only pump)
- management of a storage tank for heating and/or cooling
- management of electrical heaters for heating and domestic hot water (3 steps logic)
- solar panels integration
- room humidity control for cooling with radiant systems
- internal programmer clock (for heating, cooling and domestic hot water)
- digital input for electrical energy low tariff
- alarm memory management and diagnostic
- compressor and pump operating hour counter
- possibility to manage more units in cascade (maximum 16)
Besides the user interface of the unit to be placed indoor, wi­red or wireless remote thermostats are available which allow to control all the operating parameters of the unit and to acquire the temperature in the different zones in order to realize a more precise and comfortable control.
The unit controller is able to manage a lot of different plant so­lutions enabling automatically the necessary control algorythms according to the components which have been connected. The management of such components is possible through additional expansion modules which communicate with the unit by means of an internal bus and provide all the inputs and outputs required to fulfil a complete system.
Room temperature
20.5 C
18:28
The controller is able to manage up to two zones in heating (one by means of a mixed circuit and the other by means of a direct circuit) and one zone in cooling (by means of a mixed circuit).
It’s possible to realize more complex plants connecting to the heat pump controller further expansion modules in order to extend without limits the number of zones to be managed.
For each zone the following parameters can be set :
- set point
- daily or weekly operating time table
- climatic control curve
- room control sensor : it can be in common with the other zones or independent (in that case it’s necessary to install an additional room thermostat)
Control system
FS
8
GENERAL FEATURES
Options
Version VD - Desuperheater version
Allows to recover a part of the available heating power (and otherwise not used during cooling operating mode) for the domestic hot water production.
Acoustic setting up
AS - Low noise acoustic setting up
Allows to reduce the noise produced by the unit by means of the refrigerant circuit vane acoustic insulation and sound jackets on the compressors.
Plant side
ow rate
management
Standard pump Allows the circulation of the water on the plant side.
High head pump
Allows the circulation of the water on the plant side and guarantees a higher available static head.
Modulating pump
Allows the circulation of the water on the plant side keeping constant the temperature difference between inlet and outlet.
Domestic hot water production
3 way valve
Allow to divert the hot water produced by the heat pump from the heating circuit to the domestic hot water circuit.
Soft starter Reduces the compressor start current.
The controller flexibility and the big number of options available allow to get, for each model, a lot of different configurations that integrate inside the heat pump many components of the plant and allow to realize compact and tested installations.
In order to select the right configuration it is necessary to define
the type of plant to which the heat pump will be connected, both for what concerning the heating and cooling circuits, and for what concerning the domestic hot water management.
Option “Plant side flow rate management”
Pump (standard or high head or modulating)
Reversible heat pump (IP) without options Opzione "Version" : "Desuperheater version (VD)"
9
GENERAL FEATURES
3 way valve
Option “Domestic hot water production”
In this configuration the heat pump can be coupled to a domestic hot water tank equipped with a coil designed for a maximum water temperature between 55°C and 60°C.
The anti legionella cycles have to be performed by means of electrical heaters placed on the heat pump outlet (see option “Integrative electrical heaters”) or directly inside the tank.
Accessories
Rubber vibration dampers
Allow to reduce the transmission to the unit support plane of the mechanical vibrations generated by the compressor and by the fans in their normal operating mode.
Coil protection grilles Protect the external surface of the nned coil.
3 way valve for domestic hot water
Allow to divert the hot water produced by the heat pump from the heating circuit to the domestic hot water circuit.
Remote thermostat (wired or wireless)
Allows operating mode selection and set point adjustment. The on board temperature sensor can be used in order to realize a climatic control.
Remote control (wired or wireless)
Replicates all the control and visualization functionalities of the controller installed on the unit. The on board temperature sensor can be used in order to realize a climatic control.
Wireless transmitter
Connected to the unit controller, allows to communicate with wireless remote control and wireless outdoor temperature sensor.
Wireless repeater Extends wireless operating range.
Wireless adaptor for outdoor temperature sensor
Allows to transform the wired outdoor temperature sensor, standard for all the units, in a wireless sensor.
Condensate sensor In cooling mode it allows the minimum flow temperature control when condensate generation occurs.
Room hygrostat In cooling mode it allows the minimum ow temperature control according to the room humidity.
Room humidity sensor (with or without display)
In cooling mode it allows the minimum ow temperature control according to the room dew point, calculated from
the measured room humidity.
Transformer 230V / 24V - 3VA
It assures the correct power supply for the condensate sensor and for the room humidity sensor.
Loading...