General instructions
• Read the warnings given in this manual thoroughly. They provide important information for safe installation, use and maintenance.
• Keep the manual carefully for future consultation.
• The instruction manual is an integral and essential part of the product and must be kept by the user.
• If the appliance is sold or transferred to another owner or if the owner moves, leaving the appliance behind, always ensure that the manual is kept with the appliance for consultation by the new owner and/or installer.
• Incorrect installation or poor maintenance absolves the manufacturer from all liability for damage to people or things.
• Installation and maintenance must be carried out in conformity with current legislation, according to the manufacturer's instructions and by qualified personnel.
• Before cleaning or maintenance, disconnect the appliance from the mains via the switch on the appliance or a suitable isolating device.
• In the event of malfunction or faulty operation, deactivate the appliance. Do not attempt to repair or carry out any other operation on the appliance directly. Contact qualified personnel only.
• To guarantee efficient operation, the appliance must be serviced once a year by an authorised service centre.
• The appliance may not be used for purposes other than those for which it was explicitly designed. Any other use is considered improper and therefore dangerous.
• Incorrect installation and use or failure to follow the instructions provided by the manufacturer absolve the manufacturer from all liability for damage.
• After unpacking, check that the contents are whole and undamaged.
• Keep packaging out of reach of children as it is potentially hazardous.
• To clean external parts, use a damp cloth moistened with soapy water if necessary. Avoid using abrasive cleaning products and solvents.
• Repairs or the replacement of components must be carried out exclusively by qualified personnel using original spare parts only. Failure to respect the above may compromise the safety of the appliance.
Mars
The CE mark indicates that the appliance satisfies all the essential requisites of the gas appliance directive (90/396/CEE) and the technical standards referred to.
2
Page 3
Supplied By www.heating spares.co Tel. 0161 620 6677
Index
1. T echnical infor mations ........................................................................................................................... 4
2. Dimensions and technical data ............................................................................................................. 5
3. Packing and shipment ........................................................................................................................... 6
4. Installation ............................................................................................................................................. 7
5. T esting ...................................................................................................................................................8
6. Service ...................................................................................................................................................9
3
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
1. TECHNICAL INFORMATIONS
1.01 Introduction
GN1 N boiler is a new heating generator with high efficiency, for central heating system as well sanitary hot water
production suitable for burners using oil or gas. The boiler body is built by cast iron sections joined togheter by mean of biconical nipples and tie rods. Sections fins
are especially developed to achieve the best efficiency of the boiler in order to save on fuel consumption. The boiler body insulation is provided by mineral high density fibers that minimizes the body heat lost.
1 3 452
Key
1 Timer sochet 2 Thermomanometer 3 Security thermostat manual resetting 4 Main switch 5 Control thermostat
Fig. 1
1.02 Control and securities devices operation
Regulating thermostat, manual resetting 3 (fig. 1)
It operates when the boiler temperature, during the heating mode reach such a level that can use a danger situation. Before resetting this thermostat ask for Qualified Serviceman to inspect the appliance.
Central thermostat 5 (fig. 1) It allows to control the boiler temperature by mean of its knobs.
This thermostat controls the burner.
Room thermostat (not supplied) This device is not supplied, but can be fitted by installer, it is connected in series to the control thermostat and it
manages both the burner and the circulating pump during the heating mode. The use of such appliance is advised to get a better comfort as well on energy saving.
4
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
2. DIMENSIONS AND TECHNICAL DATA
2.01 Dimensions and technical data (fig. 2 - tab. 1)
400
Ø
850
B
270
A
a1
1” 1/2
711
542
1” 1/2
1/2”
80
64
Key
a1 Flow 11/2" a2 Return 11/2" a3 Boiler drain 11/2"
Heat and
D.H.W.
Model
(gross)
gas
Max.
GN1 N 02 GN1 N 03 GN1 N 04 GN1 N 05 GN1 N 06 GN1 N 07 GN1 N 08
Model
GN1 N 02 GN1 N 03 GN1 N 04 GN1 N 05 GN1 N 06 GN1 N 07 GN1 N 08
28,6
43 57,3 71,6 86,1
100,4 114,7
Working pressure
bar
4 4 4 4 4 4 4
Heat and
D.H.W.
(net)
gas+oil
Max.
25,8 38,7 51,6 64,5 77,5 90,4
103,3
300 400 500 600 700 800 900
A
Heat and
D.H.W. output
Max.
23,3 34,9 46,5 58,1 69,8 81,4 93,0
105 105 105 105 125 125 125
Fig. 2
Heat and
B
D.H.W. (gross)
gas
Min.
18,2 18,2 39,3 49,1 59,1 68,8 78,6
130 130 130 180 180 180 180
Heat and
Ø
D.H.W.
(net)
gas+oil
Min.
16,4 16,4 35,4 44,2 53,2 62,0 70,8
Combustion
chamber load loss p mbar
0,2 0,2 0,2 0,2 0,2 0,2 0,2
Heat and
D.H.W. output
Min.
15,0 15,0 32,5 40,5 48,8 57,0 65,0
N°
element
2 3 4 5 6 7 8
Combustion
chamber
volume
3
dm
12,09 20,15 28,21 36,27 52,39 60,45 68,51
Water
capacity
dm
11 14 17 20 23 26 29
a2
3
t 10
1 1,8 4,2 7,2
11 15 20
85
Combustion
chamber
lenght
mm
286 386 486 586 686 786 886
Water
load losses
a3
Combustion
chamber
dimension
Ømm
260x310 260x310 260x310 260x310 260x310 260x310 260x310
Weight of unit
t 20
-
-
1 1,6 2,3 3,3 4,5
kg.
100 125 150 175 200 225
75
N.B.: - Max. water temperature for the heating system is 90° C. - Min. water temperature for the heating system is 45° C.
5
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
2.02 Pressure drop (fig. 3) Pressure drops according to the boiler size are specified on the following diagram and refer to temperature
difference between flow and return comprises between 10 and 20°C.
Fig. 3
3. PACKING AND SHIPMENT
Boiler is delivered complete assembled in a wood crate.
6
Fig. 4
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
4. INSTALLATION
It is law that all gas appliances are installed by Competent Persons, in accordance with the regulations. Failure to install appliances correctly lead to prosecution, it is your own interest, and that of safety, to ensure that the law is coplied with. Manufacturers instructions must NOT be taken in any way as over-riding statutory obligations, special care must be paid to conform with law and regulation concerning building and location of the chimney.
4.01 Electrical connection
Proceed to wire pump, burner and optional room thermostat. According to the wiring diagrams (fig.5) and to the directions attached to the cables. It is recommended to install a two-pole switch between the power supply and the boiler. The switch contacts must have a clearance of at least 3 mm and fuses of 5 A max must be provided.
N.B. - Appliance must be earthed.
It is recommended to connect the boiler to a good electric earth system.
FERROLI could not be considered responsable for any kind of damage to Persons or things caused by failure of earthing the system.
159
98
a
13
c
d
4
63
C
2
1
49
2
c
123 4 56 7 8 9 101112
123 4 56 7 8 9 101112
LN
230V 50Hz
160
32
72
L1
Key
32 Central heating pump 49 Overheat cut-off thermostat 63 C.H. boiler thermostat 72 Room thermostat (not fitted) 98 Switch 159 Test knob 160 Auxiliary contact 189 Boiler shut down warming 211 Burner connector
Fig. 5a
Note = Dotted lines indicate connections to be performed during installation
14192345678 1011 12 13
15 16
189
N
S3T1
B4
T2
211
7
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
Electrical diagram
1
L
230V 50Hz
1a
1
9
160
10
11
72
12
10
11
159
98
4
N
2
3C
3
63
d
C
4
2
1
2
16
3
4 5
189
2
49
c
13
5
14
15
7
B4 S3 T2 T1
N
L1
32
211
8
6
Key
32 Central heating pump 49 Overheat cut-off thermostat 63 C.H. boiler thermostat 72 Room thermostat (not fitted) 98 Switch 159 Test knob 160 Auxiliary contact 189 Boiler shut down warming 211 Burner connector
Fig. 5b
Note = Dotted lines indicate connections to be performed during installation
4.02 Hydraulic connections
Boiler must be connected to the system according to boiler back part indications and those provided at fig. 2. Pipe must be free of any kind of strain and security valves must be provided in both central heating system and domestic hot water system location of such security valves be as close is possible to the boiler and between the boiler and valve no obstructions or gate valves must be placed.
The boiler is not supplied with expansion tank it has to be provided during the boiler installation. It is advised that the pressure in the hydraulic system has to be between 0,5 and 1 bar measured in cold water condition.
4.03 Connection to the chimney
It is recommended to connect the boiler to a good working chimney built according to the regulations. The connection between boiler and chimney must be done by using suitable material proof against high temperature and corrosion. Where flue sections have to be connected it is advised pay attention to avoid leaking and provided good insulation through all the flue length to avoid condensing problem.
8
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
5. TESTING
5.01 Before the first light of the boiler
Before the first light of the boiler follow these check list:
a) check the system is filled with water at the right pressure; b) check against any leakage of water fuel; c) check that the correct electric power is supplied to the unit; d) check size and perfect flue installation; e) check against any type of flammable materials where the boiler is installed; f) check the burner has the right heat input according to the boiler size; g) control that the water valves are open.
5.02 First lighting
After the boiler preliminaries checking , the appliance can be lights in the following way;
1) Open the fuel gate valve.
2) Set the regulating thermostat at the required temperature level.
3) Give electric power to the boiler and switch on the main switch 4 (fig. 1) on the boiler control panel.
After above operations the burner will start to run and the boiler will begin to work.
5.03 After the first lighting
After the first lighting it is advisable check: burner works properly, this checking must be done by appropriate instruments. Thermostats operate correctly. Water flows through the system. Smoke gases evacuate through the flue duct.
5.04 Switch off
To turn off the unit for a short period it is enough to switch off the switch 4 (fig. 1) on the control panel.
If the boiler has to be stopped for long period beside to act by the switch 4, it is necessary to cut the supply of fuel by mean of the gate valve, in winter season, to avoid damages due to the frost it is necessary to add the antifrost liquid in the system or to drain it completely.
9
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
6. SERVICE
The after sale service must be carried out only Qualified Plumbers. It is advise to service the boiler at least once a year, before the winter season. Check must include the boiler cleaning, the perfect operation of the controls and the burner.
Furthermore the flue duct conditions have to be inspected.
6.01 Boiler cleaning
Cut out electric power. The front panels 1, 2, 3 (fig. 6). Clean the boiler internal parts. Check the flue duct and if necessary clean it. The burner service must be done according the Manufacture Instructions.
Tube Brush
Fig. 6
1
2
3
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
ALL SPECIFICATIONS SUBJECT TO CHANGE Please note - to avoid incurring unnecessary expense, in the event of a boiler shut down, check this in not caused by lack of electricity supply, gas supply or low water pressure before calling
our Customer Service Helpline.
Lichfield Road, Branston Industrial Estate, Burton Upon Trent, Staffordshire DE14 3HD
Tel. 08707 282 885 - Fax 08707 282 886
Loading...