GE3
4
Cod. 3540Z970 - 09/2011 (Rev. 00)
2.02 Dimensions and technical data (fi g. 2 - tab. 1)
Fig. 2
Key
a1 Flow 1 1/4"
a2 Return 1 1/4"
a3 Boiler drain 1/2"
a4 Flue connection 120-130 mm
a5 Burner hole 105 mm
Tab. 1
Model
Heat and D.H.W.
(net) gas+oil
Max.
Heat and
D.H.W. output
Max.
N°
element
Water capacity
dm
3
Combustion
chamber lenght
mm
GE 3 - 25 27,8 25,0 3 13 350
GE 3 - 35 38,8 35,0 4 17 450
GE 3 - 45 49,9 45,0 5 21 550
GE 3 - 55 59,6 54,1 6 25 650
Model
Working
pressure
bar
ABC
Combustion
chamber
load loss
∆p mbar
Combustion
chamber
volume
dm
3
Water load losses
Weight
of unit
kg
∆t 10 ∆t 20
GE 3 - 25 6 400 750 380 0,1 20,15 1,8 - 115
GE 3 - 35 6 400 750 480 0,15 28,21 4,2 1 145
GE 3 - 45 6 400 750 580 0,15 36,27 7,2 1,6 175
GE 3 - 55 6 400 750 680 0,2 52,39 11 2,3 205
N.B.: - Max. water temperature for the heating system is 90° C. - Min. water temperature for the heating
system is 45° C.
EnglishFrançais