Ferroli 20-V, 30-V, 40-V, FCP 20-V, FCP 30-V Installation And Operation Manual

...
INSTALLATION AND OPERATION MANUAL
GB
FCP 20-V - 30-V - 40-V
Wall-mounted Fan coil
18
°C
Dear customer, Thank you for having purchased a FERROLI air conditioner. It is the result of lengthy experience, dedicated planning research and has been made with top-quality materials and avant-garde technologies. Moreover, the CE marking gua­rantees that the appliance complies with the European Machine Directive governing safety matters. The quality level is constantly supervised, thus FERROLI products stand for Safety, Quality and Reliability. Ask the Dealer from whom you purchased the appliance for the address of our nearest Assistance Service if you do not already know it. The information in this manual may be subjected to modifications following product improvements.
Thank you once again
FERROLI S.p.A
3
TABLE OF CONTENTS
GENERAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
WHEN THE MACHINE ARRIVES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
FOREWORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
DECLARATION OF CONFORMITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
OVERALL DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
SAFETY REGULATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
MACHINE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
PACKING AND STORAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
ELECTRICAL CONNECTION OF THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
INSTALLATION OF THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
OTHER POSITIONS FOR INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
WET CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
CONDENSATION DRAINAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
AIR VENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
SETTING AT WORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
USE OF THE REMOTE CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
INDICATOR “LED” OF THE INDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
PROBE AUTODIAGNOSIS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
DESCRIPTION
OF THE OPERATING MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
TIMER PROGRAMMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
EMERGENCY KEY OF THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
ROUTINE MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
HOW TO CLEAN THE FILTERS OF THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
HOW TO CLEAN THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
4
DECLARATION OF CONFORMITY
The company hereby declares that the machine in question complies with the matters prescribed by the following Directives:
Machine Directive 98/37 EEC
Low voltage Directive 73/23 EEC
Electromagnetic compatibility Directive EMC 89/336 EEC
GENERAL SPECIFICATIONS
WHEN THE MACHINE ARRIVES
As soon as the machine arrives, it is essential to check to make sure that all the materials listed in the shipping document have been consi­gned and that none of the parts has sustained damage due to trans­port. If damage is discovered, immediately notify the haulage contractor of its entity and inform our customer management office. Only in this way will you be able to receive the missing mate­rials or reimbursement of damages in the fastest possible way.
FOREWORD
The conditioner is a machine that has been exclusively designed and built for air conditioning and must only be used for that purpose. The machine can only operate well and be used in a profitable way if it is used correctly and kept in a fully efficient condition. Please read this instruction manual carefully and consult it whenever difficulties or doubts arise when the conditioner is used. Please remember that our assistance service, organized in collaboration with our dealers, is always at your disposal for advice and direct interventions when necessary.
5
GENERAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS
OVERALL DIMENSIONS
18
°C
AC
B
Mod. UM 20-V 30-V 40-V
A mm 790 1030 1030 B mm 270 310 310 C mm 190 205 205
NOTES: (1) Operation in the Heating mode. The data refer to:
- Inlet Water temperature: 70°C , Δt water 10°C
- Ambient Air temperature 20°C D.B. (2) Operation in Heating mode. The data refer to:
- Inlet Water temperature 50°C, Δt water 5°C
- Ambient Air temperature 20°C D.B.
(3) Operation in the Cooling mode. The data refer to:
- Inlet Water temperature: 7°C , Δt water 5°C
- Ambient Air temperature 27°C D.B., 19°C W.B. (4) Sound pressure in a 100 m
3
room with 0.5 sec. reverberation time. (NOTE): the water pressure drops on the wet side are inclusive of los­ses from the valve.
MOD. UM 20 30 40
Heating capacity
(1)
max. [W] 3400 4500 6600 med. [W] 2900 3800 5500
min [W] 2550 3300 4800
Water flow rate
(1)
[l/h] 292 387 568
Water pressure drop on wet side
(1)
[Kpa] 14,0 17,0 24,0
Heating capacity
(2)
max. [W] 2500 3400 5000
Water pressure drop on wet side
(2)
[Kpa] 14,0 18,0 31,0
Cooling capacity
(3)
max. [W] 1800 2700 3700 med. [W] 1400 2250 3100
min [W] 1200 2000 2700
Water flow rate
(3)
[l/h] 310 464 636
Dehumidification at max speed
(3)
[g/h] 400 850 1110
Sensible cooling capacity at max speed
(3)
[W] 1530 2100 2960
Water pressure drop on wet side
(3)
[Kpa] 17 21 37
Air flow rate
max. [m³/h] 380 500 730 med. [m³/h] 260 410 600
min [m³/h] 200 350 520
N° fans 1 1 1
Sound pressure
(4)
max. [dB(A)] 41 42 47 med. [dB(A)] 35 40 45
min [dB(A)] 32 37 43
Power input [W] 30 36 46
Wet connections F [ " ] 1/2" F 1/2" F 1/2" F Condensation drain pipe diameter F [mm] 16 16 16
three-way valve connection
Type - electronic ON-OFF
Ø [ " ] 1/2" 1/2" 1/2"
Packaging dimension
L mm 865 1100 H mm 285 290 D mm 340 380
Net weight indoor unit
kg 8 14
Gross weight indoor unit
kg 10 15
6
SAFETY REGULATIONS
Strictly comply with the following regulations to prevent injuries to the operator or damage to the machine.
·The machine must be installed in compliance with the laws in force in the country of use.
· This installation manual, the operating instructions and the wiring diagrams are an integral part of the machine.
They must be kept with care and be ready to hand for consultation when required.
· Failure to comply with the instructions in this manual and inadequate installation of the conditioner may void the war-
ranty. Moreover, the Manufacturer shall not be liable for any direct and/or indirect damages due to incorrect installa­tion.
· All supplementary maintenance operations must be carried out by specialized and authorized personnel.
· Work in a clean, uncluttered place when installing the appliance.
· It is absolutely forbidden to touch moving parts or to get between the same.
· Before starting the conditioner, make sure that the various components and the entire system are in perfect and safe
conditions.
· Strictly comply with the routine maintenance operations.
· If parts need changing, insist on genuine spares. Failure to do so will void the warranty.
· Do not remove or tamper with the safety devices.
· Disconnect the electric power source before proceeding with any work on the machine.
· The coil surface is sharp. Do not touch it without protective gloves.
· Carefully read the stickers on the machine. Never cover them. Replace them immediately should they be damaged.
· Do not use the machine in an explosive atmosphere.
· The power line must be regularly grounded.
· If the power cable has been damaged, stop the machine if it is operating, and have the flex immediately replaced
by an authorized electrician.
· The machine must be stored at a temperature between -25°C and 55°C.
· Use a powder extinguisher in the event of a fire outbreak. Do not use water.
· If the power cable has been damaged, stop the machine if it is operating, and have the flex immediately replaced
by an authorized electrician.
· All supplementary maintenance operations must be carried out by specialized and authorized personnel.
· The appliance must not be dumped if it is to be scrapped since it contains materials that must be recycled or dispo-
sed of by authorized centers.
· Do not wash the machine with direct or pressurized jets of water or with corrosive substances.
· The temperature of the cold water must not be less than 5°C (to prevent condensation from forming). The tempera-
ture of the water must not exceed 70°C. The water must be clean and with a pH between 6.5 and 7.5.
· When the unit remains at a seasonal standstill, the coils must be filled with water to reduce the risk of oxidation. The
appliance must be protected against freezing temperatures during winter.
The Manufacturer and dealer network are at your disposal and will provide prompt and accurate technical assi­stance to ensure that your conditioner always operates in the best and most efficient way.