Ferraz Shawmut A60Q User Manual

D 18
AC: 5-40A
600VAC, 200kA I.R.
DC: 5-40A
600VDC, 100kA I.R. L/R = 10ms
Ratings
A60Q Amp-trap
Form 101 Semiconductor Protection fuses feature the only 600 volt AC/DC rating in the industry of similar size (1-1/2" x 13/32") fuses protecting semiconductors. A60Q also has the lowest l2t of all similar fuses and excellent cycling ability. Applications include inverters and small equipment requiring extremely fast response to faults, without the need to carry sustained heavy overloads.
Approvals
HIGHLIGHTS:
600VAC/DC RatedExtremely Fast Acting Current LimitingLowest l
2
t
Excellent Cycling
Ability
APPLICATIONS:
Protection of small
inverters and drives, and equipment requiring the highest degree of protection
A 60 Q 30 - 2
Amp-trap®Fuse
Rated Volts - 600
Style
Amperes
Mounting Type
Ferrule, midget dims. (1-1/2” x 13/32”)
Catalog Numbering System
A
60
Q
30
2
FUSE HOLDERS FOR A60Q FUSES
USM Series . . . .ULTRASAFETMFuse Holders
303 Series
. . . . .Midget Fuse Blocks
1-1/2”
(38.1 mm)
13/32”
(10.3 mm)
Features/Benefits
Lowest l2t of any fuse this size for greater protection
Excellent cycling ability gives advantage in equipment design
600V AC/DC rated
AMP-TRAP®–Form 101
A60Q SEMICONDUCTOR PROTECTION FUSES
AMPERE CATALOG AMPERE CATALOG
RATING NUMBER RATING NUMBER
5 A60Q5-2 20 A60Q20-2 6 A60Q6-2 25 A60Q25-2
8 A60Q8-2 30 A60Q30-2 10 A60Q10-2 35 A60Q35-2 12
A60Q12-2 40 A60Q40-2
15 A60Q15-2
Standard Fuse Ampere Ratings, Catalog Numbers
For amper
e ratings and styles not listed, call T
echnical Services.
UL Recognized
Component
AC: UL Guide JFHR2
File E60314
DC: UL File E60314
查询A60Q25-2供应商
D
D
19
AMP-TRAP®–Form 101
A60Q SEMICONDUCTOR PROTECTION FUSES
Melting Time – Current Data, 600V Fuses
Time in Seconds
Current in Amperes
AMPERE MELTING
I2t CLEARING I2t
RATING (A2s) (A2s)
55 60
8 6.5 70 10 10 110 12 17 150 15 26 180 20 41 330 25 69 440 30 132 860 35
197 1300
40 276 1800
I2t at 600VAC, 100kA
AMPERE
CLEARING I2t
RATING (A2s)
540 842
10
70 12 90 15 110 20
200
25
260 30 520 35 780 40 1100
I2t at 600VDC,100kA, L/R = 10 ms
Available Current in RMS Symmetrical Amperes
Max. Instantaneous Peak Let-Thru Amperes
Peak Let-Thru Current Data – A60Q5 to 40, 600 Volts AC
A60Q5 to 40
AMPERE WATTS LOSS @ WATTS LOSS @
RATING 80% RATING (W) 100%RATING (W)
5 0.5 0.7
8 0.7 1.1 10 0.9 1.5 12 1.3 2.0 15 1.9 3.0 20 2.6 4.4 25 2.9 5.3 30 3.0 5.8 35 3.3 6.4 40 3.6 7.0
Watts Loss Data