Fenway DH-60 User Manual

2-Wire Air Duct Smoke Detector
TM
Effective: May 2007
Protection Systems
R
F-70.06
FEATURES
Approvals/Listing
UL 268A Listed File S1064
Factory Mutual Approved
CSFM Listed #3240-1076:121
NYC MEA Listed #134-95-E
City of Los Angeles Approved #RR8318
24 Vdc Operation
Connects to Fire Alarm Control Panel Initiating Cir­cuit
Compatible with Fenwal Advanced Smoke Detectors
In-place Sensitivity Measurement (in % per foot obscuration)
Remote Indication, Test and Reset Capabilities
Easily Mounts to Round or Rectangular Ducts
Wide Range of Duct Sizes and Air Velocities
Clear Lexan Cover for Easy Viewing of Smoke Detec­tor Status and Cleanliness
DESCRIPTION
The Fenwal Series DH-60 (2W) Air Duct Smoke Detector is designed for detecting particles of combustion in air handling systems. The DH-60 (2W) Duct Detector hous­ing accepts the Fenwal Advanced CPD-7054D Ionization and PSD-7157D Photoelectric Smoke Detector Heads.
The DH-60 (2W) Detector connects to the Initiating Cir­cuit of a UL Listed compatible Fire Alarm Control Panel and upon detection of pre-set smoke levels, puts the panel in a state of alarm. The panel may then control a variety of devices, such as HVAC fans and dampers to prevent the spread of smoke throughout the facility. A transparent Lexan cover over the detection chamber allows visual inspection of the duct detector’s chamber and the internal smoke detector status. Sampling is accomplished by sampling tubes that extend into the HVAC duct. Outputs provided can accommodate remote alarm and power indication, remote test and remote reset. Fenwal offers a range of remote accessories that operate in conjunction with the duct detectors.
APPLICATION
The Fenwal Series DH-60 Duct Detectors are suited for use with HVAC systems in commercial, industrial and institutional fire alarm applications.
The DH-60 is easily mounted to both rectangular and round ducts from 8 inches (200 mm) to 12 feet (3.6 m) wide and is compatible with all ducts with air velocities between 500 and 4000 feet per minute (2.5 to 20 m/s).
A UTC Fire & Security Company
The Ionization and Photoelectric Smoke Detector heads listed above operate over this entire air velocity range.
SAMPLING TUBES
The operation of the DH-60 (2W) Duct Detector is based upon an air sampling principle. Two tubes extend into the HVAC duct to transport air from inside the duct into the duct detector sensing chamber and back out to the duct. If the sampled air contains a concentration of smoke greater than or equal to the alarm threshold of the inter­nal smoke detector, the unit will alarm. The duct detector inlet supply sampling tube is selected according to the size of the HVAC duct. A separate exhaust tube is not required since an integral exhaust tube is molded into the housing to simplify installation.
REMOTE INDICATORS/CONTROLS
A series of easily installed remote indicators are available to add versatility and flexibility to the Fenwal Series DH­60 (2W) Duct Detectors. These attractive and functional devices provide convenient status information along with remote Test/Reset capabilities. The remote indicators are helpful when the detector is out of view or located in rela­tively inaccessible locations. Figure 2 shows the face­plates of the RA 911 and RA 914 remote indicator controls.
FUNCTIONAL TESTING AND SENSITIVITY MEASUREMENT
The Fenwal DH-60 (2W) Duct Detectors should be tested upon installation and once a year thereafter as stated in NFPA 72. All alarm signal devices, releasing devices, and extinguishing systems, as applicable should be dis­engaged before the test is performed and re-engaged at the conclusion of testing.
The DH-60 Duct Detector may be functionally tested either by introducing smoke into the detector or activating the magnet test. Two separate magnet-locating slots are provided on the outside of the duct detector housing.
Further, as stated in NFPA 72, Detector sensitivity should be checked within one year of installation and every alter­native year thereafter. Fenwal offers the Model DST-003 handheld wireless infrared sensitivity tester that allows the sensitivity of installed operating detectors to be mea­sured from the floor level. For details, please refer Fen­wal Document 06-236524-001.
ENCLOSURE
END PLUG
EXHAUST TUBE (MOLDED INTO ENCLOSURE)
MTG. SCREW
AND O-RING
DETECTOR HEAD
ION OR PHOTO
Figure 1. DH-60 (2W) Parts Breakdown
COVER
COVER/TERMINAL DESIGNATION PLATE
INLET TUBE (SUPPLY)
DUCT DETECTOR
MODEL DH-60
FENWAL
DETECTOR VIEW PORT
ALARM
INDICATOR
MODEL RA-911
REMOTE ALARM INDICATOR
Figure 2. Remote Alarm Indicators
ALARM
TEST
MODEL RA-914
REMOTE ALARM INDICATOR
WITH TEST
- 2 -