Fema Smart DCM, Smart SN Operating Instructions Manual

® U.S Registered Trademark Copyright © 2007 Honeywell Inc. All Rights Reserved MU2B-0328GE51 R0207A
Smart DCM/SN
ELECTRONIC PRESSURE SWITCHES AND TRANSMITTERS
OPERATING INSTRUCTIONS
GENERAL
BEFORE PROCEEDING!
VALIDITY
These Operating Instructions pertain to measuring systems containing Smart SN Pressure Transmitters / DCM Pressure Switches. Device software must be version 1.30 or higher.
QUALIFIED PERSONNEL AND USAGE
Use only these Operating Instructions (and the corresponding Mounting Instructions) to set up and operate the device. Only qualified personnel are permitted to install, commission, operate, and maintain the device. This device may be used only in applications and under operating conditions described in these Operating Instructions.
TECHNICAL DATA
Materials
Parts contacting medium Stainless steel (1.4571) Chemical resistance 4C4 as per EN 60721-3-4 HMI PA66 GF25 Total weight 300 g without, 350 g with HMI
Ambient (operating) temperature and humidity
Versions (non-HMI) -20...+80 °C Versions (HMI) -20...+70 °C Humidity 0...95% r.h., non-condensing Temperature of medium -30...+100 °C ( 16 bar models)
-40...+100 °C (> 16 bar models)
Storage temperature
Versions (non-HMI) -40...+80 °C ( 16 bar)
-40...+100 °C (> 16 bar)
Versions (HMI) -30...+80 °C
Climate class
Indoors 4K4H as per EN 60721-3-4 Outdoors 3K8H as per EN 60721-3-3
Mechanical stability
Vibration 20 g as per IEC 68-2-6 (up to
2000 Hz)
Mechanical shock 100 g as per IEC 68-2-27
Device resistance / accuracy (combined non-linearity, hysteresis, and repeatability at 20 °C)
P 16 bar P > 16 bar
overpressure safety 2x P
nominal
2x P
nominal
burst pressure 4x P
nominal
10x P
nominal
sensor type piezo thin-film
accuracy
max. ±0.8% FS ±0.5% FS (typ.)
max. ±1% FS ±0.6% FS (typ.)
Pressure meas. range 0…40 bar (rel.), -1…1 bar (vac.) Cycle time 100 ms
EMC according to EN 61326 Protection class 2 as per EN 61010 Protection rating (non-HMI) IP67 as per EN 60529-2 Protection rating (HMI) IP65 as per EN 60529-2 Process connection G1/2" external thread Electrical connection 4-prong A-coded M12x1 plug
Switch
Output, high level V
SUPPLY
minus 2 V (min.) Output, low level GND plus 0.5 V (max.) Reaction time max. 300 ms
WARN output voltage passive: V
SUPPLY
- 2 V
active: ≤ 0.5 V
Transmitter (analog) output
Current (2-wire) 4…20 mA Voltage / current (3-wire) 0/2...10 V, 0/4...20 mA V
SUPPLY
(2-wire) 18…35 Vdc
V
SUPPLY
(3-wire) 18…35 Vdc, 24 Vac +10%/-20%,
max. 50 mA
Current output (max. load) (V
SUPPLY
- 16 V) / 22 mA
(max. error ±0.25% FS) Voltage output (min. load) 15 k (max. error ±0.25% FS) Transient response approx. 200 ms
Span, offset, and long-term drift (within temperature compensation range of 0…80 °C)
max. typical
temp. effect on span ±0.3% FS / 10 K ±0.2% FS / 10 K temp. effect on offset ±0.3% FS / 10 K ±0.2% FS / 10 K long-term drift* ±0.3% FS / year ±0.2% FS / year
SMART DCM SWITCH – OPERATING INSTRUCTIONS
MU2B-0328GE51 R0207A
2
DCM SWITCH
SEQUENCE OF SCREENS
MONITOR FUNCTION
OUTPUTSET-PT RESET-PT
AUTO-0 SET ZERO RESET 0
PRESSURE,
STATE
SET-PT.
WELCOME
RESET-PT. MONITOR FUNCTION DROP-IN DROP-OUT
MESSAGE MESSAGE
DROP-IN DROP-OUT
PEAKS
UNIT LANGUAGE BACKLIGHT REFRESH ROTATE CONTRAST
DISPLAY
CLEARMIN. MAX. TEMP. SIMUL. SET CODE RESET
EXTRAS
ENTER CODE
GO TO
CONFIRM
A
LL
SETTINGS
PLAUSIBLE
?
NO
Y
ES
SET-PT. RESET-PT. MONITOR F UNCTION DROP-IN DROP-OUT CODE SIMUL. STORING...
DISPLAY LEVEL
PARAMETRIZATION LEVEL
CODE
ERROR
START
CONFIRMATION LEVEL
Fig. 1. Sequence of screens - Overview (DCM)
Devices equipped with an HMI (Human-Machine-Interface) feature pushbuttons and a display, allowing easy configuration by means of a menu structure. The menu structure is divided into the following segments:
The START SCREEN;
The DISPLAY LEVEL (where information including the
current pressure and parameterized values are shown but cannot be edited);
The CODE area (where you will have to enter the correct four-digit CODE in order to proceed any further);
The PARAMETRIZATION LEVEL (where you can edit various different parameters);
A ERROR-CHECKING area (where the device will check the plausibility of your values and, if necessary, redirect you back to the PARAMETRIZATION LEVEL); and
The CONFIRMATION LEVEL (where you can review your edited values before permanently storing them).
START SCREEN
Within 10 seconds of powering-up the device, an initial screen – the START SCREEN - will appear briefly (see Fig. 2).
Startup
Fig. 2. Start screen
You will then be automatically directed to the DISPLAY LEVEL.
DISPLAY LEVEL
In the DISPLAY LEVEL, you can view the current pressure as well as the various different user-settings currently in force.
Reset-pt.
Monitor Function
Drop in
delay
0s
Drop
out delay
0s
4.00bar Window N.C.
MENU MENU MENU MENU MENU
-0.90
bar
Closed
MENU
NEXT
PREVIOUS
NEXT
NEXT
NEXT
NEXT
NEXT
PREVIOUS
PREVIOUS
PREVIOUS
PREVIOUS
PREVIOUS
Set-pt.
5.00bar
MENU
NEXT
PREVIOUS
ESCAPE ESCAPE ESCAPE ESCAPE ESCAPE ESCAPE
Fig. 3. DISPLAY LEVEL
ENTERING THE ENTRY CODE
In order to gain access to the PARAMETRIZATION LEVEL (where you can edit values), it is first necessary to show that you have the requisite authorization by entering the correct four-digit ENTRY CODE (default: 0000).
CODE
NOT
V
ALID
Put code
0000
OK
-
+
0
Put code
0000
-
+
8
Put code
0000
-
+
9
Put code
0009
-
+
0
Put code
0009
-
+
1
Put code
0009
-
+
4
Put code
0009
-
+
5
ESCAPE
OK OK
LEFT LEFT LEFT
OK OK OK OK
Put code
0000
-
+
1
OK
LEFT
LEFT LEFT LEFT LEFT
Fig. 4. Entering the ENTRY CODE
SMART DCM SWITCH – OPERATING INSTRUCTIONS
MU2B-0328GE51 R0207A
3
PARAMETRIZATION LEVEL
Once you have successfully entered the ENTRY CODE and thus gained access to the PARAMETRIZATION LEVEL, you can edit values and reconfigure the device.
NOTE: The currently set option (e.g. "yes," "no," "window
monitor", etc.) is always marked in the display screen with a small dot to the left (see Fig. 5).
Monitor
Max.
OK
Window
ESCAPE
Monitor
Max.
Window
ESCAPE
OK
DOT
Fig. 5. Dot indicating present setting
SET-PT.
In this screen, you can select the set-point. This is defined as the pressure at which you want the device to switch. The default setting is 60% of full-scale.
ERROR MESSAGE: "VALUE OUT OF RANGE"
If you have entered a set-point outside of the device's specified pressure measurement range or which is for any other reason not rational, this error message will appear, whereupon you should then enter a correct value.
RESET-PT.
In this screen, you can select the reset-point. This is defined as the pressure at which you want the device to switch back. The default setting is 40% of full-scale.
ERROR MESSAGE: "VALUE OUT OF RANGE"
If you have entered a reset-point outside of the device's specified pressure measurement range or which is for any other reason not rational, this error message will appear, whereupon you should then enter a correct value.
OUTPUT
MONITOR
Here, you can choose between three types of monitors: min., max., and window.
Min.;
Max.;
Window;
See Fig. 7 on page 5 for an explanation of the meanings of these different settings. The default setting is "Max."
FUNCTION
Here, you can choose the type of action you want the DCM Switch to have:
N.O.: Normally-open switch (meaning: when the switch is activated, it will CLOSE); or
N.C.: Normally-closed switch (meaning: when the switch is activated, it will OPEN).
See Table 2 and Fig. 7 on page 5 for more information. The default setting is "N.O."
AUTO ZERO
The purpose of the auto zero function is to allow the user to adjust the device to local ambient atmospheric pressure and
to compensate for drift. To use this function properly, the device must be mounted in the application and the pressure sensor exposed to local ambient atmospheric pressure (i.e. 0 bar relative pressure).
Yes: The device takes the current local ambient atmospheric pressure as its zero.
No: The device setting remains unchanged.
The default setting is "No".
SET ZERO
The difference between the pressure value you enter in this screen and the pressure which the device is currently measuring will be taken as the offset. This offset can be reset to zero using the reset zero option (see section "Reset Zero" below). The default setting is the pressure which the device is currently measuring (meaning that the offset is then zero).
ERROR MESSAGE: "VALUE OUT OF RANGE"
If you have set a zero outside the permissible range (±25% full-scale), this error message will appear, whereupon you should then enter a correct value.
RESET ZERO
Here, you can reset the zero:
Yes: The pressure offset will be set to zero.
No: The device setting remains unchanged.
The default setting is "No".
DROP-IN
Here, you can select the drop-in value. See also Fig. 8. Possible values range from 0 to 99 seconds. The default setting is "0" seconds.
DROP-OUT
Here, you can select the drop-out value. See also Fig. 8. Possible values range from 0 to 99 seconds. The default setting is "0" seconds.
PEAKS
Here, you can view the historical max. and min. measured pressures as well as the max. measured temperature (historical = measured since the device has been put into operation / since the last time the peaks were cleared). If desired, by proceeding to "Clear" and choosing "yes," you can also permanently erase all such values. All such peaks will then be erased and the recording of peaks will be re­initiated.
DISPLAY
Here, you can select/alter various modes of displaying screen information.
UNIT
Here, you can choose the units in which the device displays pressures:
bar: All pressures will be displayed in bars.
Pa: All pressures will be displayed in Pascals.
Psi: All pressures will be displayed in pounds / in2.
The default setting is "bar".
LANGUAGE
English is the only supported language.
SMART DCM SWITCH – OPERATING INSTRUCTIONS
MU2B-0328GE51 R0207A
4
BACKLIGHT
Here, you can select how the device's screen backlight should operate:
Always: The backlight will remain ON at all times.
Demand: The backlight will come ON whenever the
device's keys are operated, and remain ON for 25 s.
Never: The backlight is shut OFF permanently. The default setting is "Never".
REFRESH
Here, you can set how often (in seconds) the screen contents should be refreshed (i.e. refilled with freshly-measured data). Possible values range from 1 to 9 seconds. The default setting is "1" sec.
ROTATE
Here, you can permanently rotate (by 0°, 90°, 180°, or 270°) the orientation in which the screen's contents are displayed. This is for easier viewing / enhanced legibility. The default setting is "0" degrees (i.e. screen contents vertical when device mounted in upright position).
CONTRAST
Here, you can choose the degree of contrast with which the screen's contents are displayed:
Min.: The contrast is decreased to its minimum value;
Mean: The contrast is set to its mean value;
Max.: The contrast is increased to its maximum value.
The default setting is "Mean".
EXTRAS
SIMUL. (= SIMULATION MODE)
The simulation mode allows the user to test the device within the application without actually applying pressure. When the simulation mode is initiated, the device's diagnostic features are not active, and use of the device in an active safety application is impossible. After leaving the simulation mode and returning to the normal operating mode, the device is again ready for use in safety applications.
Yes: The simulation mode is started.
No: The device remains in its normal operating mode.
The default setting is "No".
WARNING
After you have completed testing in the simulation mode, do not forget to return to this screen and re-instate the active operating mode.
SET CODE
Here, you can change the ENTRY CODE. After leaving the PARAMETRIZATION LEVEL and proceeding through the CONFIRMATION LEVEL, the new ENTRY CODE will then be in effect.
RESET
Here, you can re-instate all factory (i.e. default) settings:
Yes: All factory settings are re-instated.
No: currently-set values are retained.
PLAUSIBILITY CHECK
Upon attempting to leave the PARAMETRIZATION LEVEL, the device will determine two checks to determine the plausibility of your values.
ERROR MESSAGE: "MIN. DISTANCE BETW. SET-PT. AND RESET-PT. IS 0.5% FS. PLEASE CORRECT PARAMS"
The difference between the set-point and the reset-point will be checked. If the distance is too small (i.e. less than 0.5% of the full-scale), this error message will appear.
ERROR MESSAGE: "OFFSET MUST BE BETWEEN -25%FS & +25%FS. PLEASE CORRECT"
The offset will also be checked. If the offset is not within 25% of the full-scale, this error message will appear.
CONFIRMATION LEVEL
Here, you have the opportunity of once again viewing all of the device's settings (including any changes you may have made) in a quick overview. If you reject any settings, you will be automatically redirected to the PARAMETRIZATION LEVEL. If you accept all settings, these values will be permanently stored, and you will be automatically redirected to the DISPLAY LEVEL.
IMPORTANT
You should be completely satisfied with the correctness of the settings displayed in the CONFIRMATION LEVEL. As soon as you complete the CONFIRMATION LEVEL, all of these settings will become effective.
SMART DCM SWITCH – OPERATING INSTRUCTIONS
MU2B-0328GE51 R0207A
5
OUTPUT DESCRIPTION
1
2
4
3
L+
L-
OC PNP
1 2 3
4
P
L+
L-
OC PNP
WARN
WARN
Fig. 6. Pin assignment of A-coded M12 plug
NOTE: The unit and any field devices (actuators, sensors,
etc.) to which it is electrically connected must be provided with a common ground via pin 3.
The initial conditions of the device's signal outputs are as follows:
Table 1. DCM Switch signal outputs after power-up
WARN (pin 2) POWER OUTPUT (pin 4)
passive -- open
NOTE: The WARN output (pin 2) is an auxiliary output
used for signaling errors. It cannot be used to drive high loads.
DCM SWITCH BEHAVIOR IN OVERCURRENT CONDITIONS
In order to prevent damage of the device electronics, the device measures the current flowing into the load. If the current flowing from the switch output to the load exceeds 250 mA, the load is automatically disconnected and the WARN output is set to < 0.5 V for 5 sec. The load is then reconnected, the current is measured again, and the WARN output is set to the power supply voltage. If the current is still greater than 250 mA, the load is disconnected and the WARN output is set to < 0.5 V… in a loop.
Table 2. DCM Switch functions and definitions
definition function
equa-
tion
"active" = "inactive" =
max. monitor N.O.
1 closed open
max. monitor N.C.
1 open closed
min. monitor N.O.
1 open closed
min. monitor N.C.
1 closed open
window monitor N.O.
2 closed open
window monitor N.C.
2 open closed
Equation 1 (min./max. monitor):
active x ≥ USP y
n+1
= inactive x LSP
y
n
otherwise
Equation 2 (window monitor):
active LSP ≤ x ≤ USP inactive x ≤ LSP minus (0.5%
±
range)
Inactive x ≥ LSP plus (0.5%
±
range)
y
n+1
=
yn otherwise
Where
y
n
is the analog output value as determined in the
previous cycle,
y
n+1
is the analog output value as determined in the current
cycle, and
x is the current measured pressure.
USP
USP
USP
LSP
LSP
LSP
NORMALLY-OPEN NORMALLY-CLOSED
time
time
time
p
p
p
closed
closed
closed
open
open
open
time
time
time
p
p
p
closed
closed
closed
open
open
open
USP
USP
USP
LSP
LSP
LSP
MAX. MONITORMIN. MONITORWINDOW MONITOR
Fig. 7. DCM Switch output (max./min./window monitor)
USP
LSP
time
p
closed
open
N.O. MAX. MONITOR (OR N.C. MIN. MONITOR)
T
1
T
3
T
2
T
4
LEGEND:
T less than drop-in time T greater than or equal to drop-in time T less than drop-out time T greater than or equal to drop-out time
1 2 3 4
Fig. 8. Drop-in / drop-out time
SMART SN TRANSMITTER – OPERATING INSTRUCTIONS
MU2B-0328GE51 R0207A
6
SN TRANSMITTER
SEQUENCE OF SCREENS
MODE FUNCTION
OUTPUTSTART-PT END-PT
AUTO-0 SET ZERO RESET 0
PRESSURE,
STATE
START-PT.
WELCOME
END-PT. MODE FUNCTION ATTENUATION
MESSAGE MESSAGE
ATTENUATION
PEAKS
UNIT LANGU AGE BACKLIGHT REFRESH ROTATE CONTRAST
DISPLAY
CLEARMIN. MAX. TEMP. SIMUL. SET CODE RESET
EXTRAS
ENTER CODE
GO TO
CONFIRM
A
LL
SETTINGS
PLAUSIBLE
?
NO YES
START-PT. END-PT. MODE FUNCTION ATTENUATION CODE SIMUL. STORING...
DISPLAY LEVEL
PARAMETRIZATION LEVEL
CODE
ERROR
START
CONFIRMATION LEVEL
Fig. 9. Sequence of screens – Overview (SN)
Devices equipped with an HMI (Human-Machine-Interface) feature pushbuttons and a display, allowing easy configuration by means of a menu structure. The menu structure is divided into the following segments:
The START SCREEN;
The DISPLAY LEVEL (where information including the
current pressure and parameterized values are shown but cannot be edited);
The CODE area (where you will have to enter the correct four-digit CODE in order to proceed any further);
The PARAMETRIZATION LEVEL (where you can edit various different parameters);
A ERROR-CHECKING area (where the device will check the plausibility of your values and, if necessary, redirect you back to the PARAMETRIZATION LEVEL); and
The CONFIRMATION LEVEL (where you can review your edited values before permanently storing them).
START SCREEN
Within 10 seconds of powering-up the device, an initial screen – the START SCREEN - will appear briefly (see Fig. 10).
Startup
Fig. 10. Start screen
You will then be automatically directed to the DISPLAY LEVEL.
DISPLAY LEVEL
In the DISPLAY LEVEL, you can view the current pressure as well as the various different user-settings currently in force.
Function
A
tt. filter
Non-inv. 10%
MENU
NEXT
PREVIOUS
End
pressure
10.00bar
Mode
2-wire
4..20mA
Start
pressure
0.00bar
MENU
NEXT
PREVIOUS
ESCAPE ESCAPE
MENU
NEXT
PREVIOUS
ESCAPE
NEXT
PREVIOUS
ESCAPE
MENU
NEXT
PREVIOUS
ESCAPE
MENU
0.22
bar
4.35mA
MENU
NEXT
PREVIOUS
Fig. 11. DISPLAY LEVEL (example: SN 2-Wire)
Function
Att. filter
Non-inv. 10%
MENU
NEXT
PREVIOUS
End
pressure
10.00bar
Mode 3-wire
0..10V
Start
pressure
0.00bar
MENU
NEXT
PREVIOUS
ESCAPE ESCAPE
0.22
bar
0.21V
MENU
NEXT
PREVIOUS
MENU
NEXT
PREVIOUS
ESCAPE
NEXT
PREVIOUS
ESCAPE
MENU
NEXT
PREVIOUS
ESCAPE
MENU
Fig. 12. DISPLAY LEVEL (example: SN 3-Wire)
ENTERING THE ENTRY CODE
In order to gain access to the PARAMETRIZATION LEVEL (where you can edit values), it is first necessary to show that you have the requisite authorization by entering the correct four-digit ENTRY CODE (default: 0000).
SMART SN TRANSMITTER – OPERATING INSTRUCTIONS
MU2B-0328GE51 R0207A
7
CODE
NOT
V
ALID
Put code
0000
OK
-
+
0
Put code
0000
-
+
8
Put code
0000
-
+
9
Put code
0009
-
+
0
Put code
0009
-
+
1
Put code
0009
-
+
4
Put code
0009
-
+
5
ESCAPE
OK OK
LEFT LEFT LEFT
OK OK OK OK
Put code
0000
-
+
1
OK
LEFT
LEFT LEFT LEFT LEFT
Fig. 13. Entering the ENTRY CODE
PARAMETRIZATION LEVEL
Once you have successfully entered the ENTRY CODE and thus gained access to the PARAMETRIZATION LEVEL, you can edit values and reconfigure the device.
NOTE: The currently set option (e.g. "yes," "no,"
"4…20 mA", etc.) is always marked in the display screen with a small dot to the left (see Fig. 5).
Function
N.O.
OK
N.C.
ESCAPE
Function
N.O.
N.C.
ESCAPE
OK
DOT
Fig. 14. Dot indicating present setting
START-PT.
In this screen, you can select the start-point. This is defined as the pressure at which you want the device to begin providing an analog output signal. The default setting is "0".
ERROR MESSAGE: "VALUE OUT OF RANGE"
If you have entered a start-point outside of the device's specified pressure measurement range or which is for any other reason not rational, this error message will appear, whereupon you should then enter a correct value.
END-PT.
In this screen, you can select the end point. This is defined as the pressure at which you want the device to stop providing an analog output signal. The default setting is 100% of full-scale.
ERROR MESSAGE: "VALUE OUT OF RANGE"
If you have entered an end-point outside of the device's specified pressure measurement range or which is for any other reason not rational, this error message will appear, whereupon you should then enter a correct value.
OUTPUT
MODE
Here, you can set the device's mode. Four different modes are possible:
0…10V: the voltage range is set to 0…10 V;
0…20mA: the current range is set to 0…20 mA;
2…10V: the voltage range is set to 2…10 V;
4…20mA: the current range is set to 4…20 mA (default).
NOTE: The only mode supported by the SN 2-Wire Trans-
mitter is "4…20 mA". However, it can be inverted to "20…4 mA" (see section "Function" below).
FUNCTION
Here, you can invert the device's function (see also Fig. 15):
Non-invert.: the mode (current range or voltage range, as the case may be) is set to 0/4…20 mA or 0/2…10 V (as the case may be) (default);
Inverted: the mode (current range or voltage range, as the case may be) is set to 20…0/4 mA or 10…0/2 V (as the case may be).
The default setting is "non-invert."
U/I
MAX MAX
U/I
MAX MAX
U/I
MIN MIN
U/I
MIN MIN
output U/I output U/I
NORMAL OPERATION INVERTED OPERATION
pressure pressure
pressure
start
pressure
start
pressure
end
pressure
end
Fig. 15. SN Transmitter output (normal/inverted)
AUTO ZERO
The purpose of the auto zero function is to allow the user to adjust the device to local ambient atmospheric pressure and to compensate for drift. To use this function properly, the device must be mounted in the application and the pressure sensor exposed to local ambient atmospheric pressure (i.e. 0 bar relative pressure).
Yes: The device takes the current local ambient atmospheric pressure as its zero.
No: The device setting remains unchanged.
The default setting is "No".
SET ZERO
The difference between the pressure value you enter in this screen and the pressure which the device is currently measuring will be taken as the offset. This offset can be reset to zero using the reset zero option (see section "Reset Zero" below). The default setting is the pressure which the device is currently measuring (meaning that the offset is then zero).
ERROR MESSAGE: "VALUE OUT OF RANGE"
If you have set a zero outside the permissible range (±25% full-scale), this error message will appear, whereupon you should then enter a correct value.
RESET ZERO
Here, you can reset the zero:
Yes: The pressure offset will be set to zero.
No: The device setting remains unchanged.
The default setting is "No".
ATT. FILTER
Here, you can attenuate (dampen) the outputted portion of the peak. Possible values range from 0 to 99%. The default setting is "10" percent. The formula for calculating the attenuation is as follows:
1
100
)
100
1(
+=
nnn
y
nattenuatio
x
nattenuatio
y
SMART SN TRANSMITTER – OPERATING INSTRUCTIONS
MU2B-0328GE51 R0207A
8
Where y
n
is the analog output value
x
n
is the measured offset-compensated pressure in this
cycle
y
n-1
is the analog output value generated in the previous
cycle
PEAKS
Here, you can view the historical max. and min. measured pressures as well as the max. measured temperature (historical = measured since the device has been put into operation / since the last time the peaks were cleared). If desired, by proceeding to "Clear" and choosing "yes," you can also permanently erase all such values. All such peaks will then be erased and the recording of peaks will be re­initiated.
DISPLAY
Here, you can select/alter various modes of displaying screen information.
UNIT
Here, you can choose the units in which the device displays pressures:
bar: All pressures will be displayed in bars.
Pa: All pressures will be displayed in Pascals.
Psi: All pressures will be displayed in pounds / in2.
The default setting is "bar".
LANGUAGE
English is the only supported language.
BACKLIGHT
Here, you can select how the device's screen backlight should operate:
Always: The backlight will remain ON at all times.
Demand: The backlight will come ON whenever the
device's keys are operated, and remain ON for 25 sec.
Never: The backlight is shut OFF permanently. The default setting is "Never"
NOTE: The only backlight option supported by the SN 2-
Wire Transmitter is "Never."
REFRESH
Here, you can set how often (in seconds) the screen contents should be refreshed (i.e. refilled with freshly-measured data). Possible values range from 1 to 9 seconds. The default setting is "1" sec.
ROTATE
Here, you can permanently rotate (by 0°, 90°, 180°, or 270°) the orientation in which the screen's contents are displayed. This is for easier viewing / enhanced legibility. The default setting is "0" degrees (i.e. screen contents vertical when device mounted in upright position).
CONTRAST
Here, you can choose the degree of contrast with which the screen's contents are displayed:
Min.: The contrast is decreased to its minimum value;
Mean: The contrast is set to its mean value;
Max.: The contrast is increased to its maximum value.
The default setting is "Mean".
EXTRAS
SIMUL. (= SIMULATION MODE)
The simulation mode allows the user to test the device within the application without actually applying pressure. When the simulation mode is initiated, the device's diagnostic features are not active, and use of the device in an active safety application is impossible. After leaving the simulation mode and returning to the normal operating mode, the device is again ready for use in safety applications.
Yes: The simulation mode is started.
No: The device remains in its normal operating mode.
The default setting is "No".
WARNING
After you have completed testing in the simulation mode, do not forget to return to this screen and re-instate the active operating mode.
SET CODE
Here, you can change the ENTRY CODE. After leaving the PARAMETRIZATION LEVEL and proceeding through the CONFIRMATION LEVEL, the new ENTRY CODE will then be in effect.
RESET
Here, you can re-instate all factory (i.e. default) settings:
Yes: All factory settings are re-instated.
No: currently-set values are retained.
PLAUSIBILITY CHECK
Upon attempting to leave the PARAMETRIZATION LEVEL, the device will perform two checks to determine the plausibility of your values.
ERROR MESSAGE: "MIN. DISTANCE BETW. START-PT. AND END-PT. IS 50% FS. PLEASE CORRECT PARAMS"
The difference between the set-point and the reset-point will be checked. If the distance is too small (i.e. less than 50% of the full-scale), this error message will appear.
ERROR MESSAGE: "OFFSET MUST BE BETWEEN -25%FS & +25%FS. PLEASE CORRECT"
The offset will also be checked. If the offset is not within 25% of the full-scale, this error message will appear.
CONFIRMATION LEVEL
Here, you have the opportunity of once again viewing all of the device's settings (including any changes you may have made) in a quick overview. If you reject any settings, you will be automatically redirected to the PARAMETRIZATION LEVEL. If you accept all settings, these values will be permanently stored, and you will be automatically redirected to the DISPLAY LEVEL.
IMPORTANT
You should be completely satisfied with the correctness of the settings displayed in the CONFIRMATION LEVEL. As soon as you complete the CONFIRMATION LEVEL, all of these settings will become effective.
Loading...
+ 16 hidden pages