User’s Manual S40-T
FEMA ELECTRÓNICA - Page 8
Input Menu
The input menu selects the input signal range. Options available are Pt100/RTD 2 or 3 wires, and thermocouples J, K, T,
E, S, R, N, C, L and X.
Note - Thermocouple X is a linear signal at 10uV/ºC.
The instrument manages up to 4 alarms. Each alarm is
controlled by the condition “display higher (or lower) than
the congured setpoint”. The front leds are controlled by
the activation / deactivation of the related alarm. The relays
installed on Option1 and/or Option2 are controlled by Alarm1
and Alarm2.
Active (Act) - Value “On/Off”. Denes if the instrument has to
manage this alarm or not. Select “Off” for alarm not managed.
Type (tyPE) - Value “Max/Min”. Denes the behavior of the
alarm as maximum or minimum alarm. The alarms cong-
ured as maximum are activated when the display value is
equal or higher than the setpoint. The alarms congured as
maximum are deactivated when the display is lower than
the setpoint. The alarms congured as minimum have the
inverse behavior.
Setpoint (SEt) - Value from “9999” to “-1999”. Alarm set point.
Hysteresis (hySt) - Value from “0” to “9999”. Points of hyster-
esis. The hysteresis applies on the deactivation of the alarm.
Delay (dEL) - Value from “0.0” to “99.9” seconds. Delay to be
applied to the relay activation and deactivation. Relays are
activated and deactivated X seconds after the activation /
deactivation of the alarm. The delay affects only to the relays.
The delay does not affect to the front leds.
Setpoint2 (SEt2) - Value from “-1999” to “9999”. Second
setpoint. The second setpoint allows for the creation of acti-
vation windows. If the alarm is congured as maximum with
setpoint 1000 and setpoint2 is congured at 1500, the alarm
will be activated between 1000 and 1500 and the alarm will
be deactivated when display is <1000 and >1500. Setpoint2
is affected on the same way as the setpoint with hysteresis
and delays.
Display Menu
Functions on this menu allow for conguration of the visualization.
Steps (StEP) - Display changes on predened steps. Values
are 1, 2, 5, 10, 20 and 50. The display is made in steps of X
counts. For example, select a step of 20 will make the display
to change in steps of 20 (1420, 1440, 1460, ...).
Maximum (MAX) - Memory of maximum display. Indicates
the maximum value of display since the last reset of the
memory. Memory is reset on the following cases : manual
reset from the Conguration Menu (Maximum), change on
the input signal (Input), modication on the scaling (Scaling),
change on the decimal point (dP), modication of the linear-
ization segments, or instrument power-down.
Minimum (MIn) - Memory of minimum display. Indicates the
minimum value of display since the last reset of the memory.
Memory is reset on the following cases : manual reset from
the Conguration Menu (minimum), change on the input
signal (Input), modication on the scaling (Scaling), change
on the decimal point (dP), modication of the linearization
segments, or instrument power-down.
AlarmX Menu
Temperature Conguration Menu
The temperature conguration menu sets the function parameters for Pt100/RTD and thermocouple sensors.
Degrees (dEG) - Value “ºC/ºF”. Select the temperature to be
displayed in celsius or fahrenheit degrees.
Pt100/RTD resolution (P.rES) - Value “1º/0.1º”. Resolution
for the Pt100/RTD. Select to display with degree or tenth of
degree resolution.
Offset (oFFS) - Value from “-1999” to “9999” counts. Offset
to be added to the reading. Both for Pt100/RTD and thermocouples.
Thermocouple Cold Junction Compensation (t.cJc) - Val ue “On/Off”. Select “On” for automatic CJC compensation in
the instrument. Select “Off” to disable the CJC compensation.
On break (on.bk) - Value “to_h/to_l”. Select “To L” to make
the reading go to minimum, in case of probe broken. Select
“To H” to make the reading go to maximum in case of probe
broken.
Alpha (ALPh) - Value “385/390”. Select “385” or “390” according to your PT100/RTD sensor.