Federal Signal Corporation 120 Series Installation, Operation And Maintenance Manual

120 Series
Loudspeaker, ISMT Loudspeaker,
Powered Loudspeaker, and Sounder
25 Watts
(Model Type ES4 and ES5)
2562192D REV. D 612 Printed in U.S.A.
Installation, Operation,
and Maintenance
2
Federal Signal Corporation Integrated Systems 2645 Federal Signal Drive University Park, IL 60484-3167, U.S.A.
Warranty – Seller warrants all goods for ve years on parts and 2-1/2 years
on labor, under the following conditions and exceptions: Seller warrants that all goods of Seller's manufacture will conform to any descriptions thereof for speci-
cations which are expressly made a part of this sales contract and at the time
of sale by Seller such goods shall be commercially free from defects in material
or workmanship. Seller reserves the right at the Seller’s discretion to “Repair and Return” or “Replace” any item deemed defective during the warranty period.
This warranty does not cover travel expenses, the cost of specialized equipment for gaining access to the product, or labor charges for removal and reinstal­lation of the product. This warranty shall be ineffective and shall not apply to goods that have been subjected to misuse, neglect, accident, damage, improper maintenance, or to goods altered or repaired by anyone other than Seller or its authorized representative, or if ve years have elapsed from the date of ship­ment of the goods by Seller with the following exceptions: lamps and strobe tubes are not covered under this warranty. Outdoor warning sirens and control­lers manufactured by Federal Warning Systems are warranteed for two years on parts and one year on labor. No agent, employee, representative or distributor
of Seller has any authority to bind the Seller to any representation, afrmation, or warranty concerning the goods and any such representation, afrmation or
warranty shall not be deemed to have become a part of the basics of the sales
contract and shall be unenforceable. THE FOREGOING WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES OR MERCHANT­ABILITY, FITNESS FOR PURPOSE AND OF ANY OTHER TYPE, WHETHER EXPRESS OR IMPLIED. These warranties shall not apply unless Seller shall
be given reasonable opportunity to investigate all claims for allegedly defective goods. Upon Seller's instruction a sample only of allegedly defective goods shall be returned to Seller for its inspection and approval. The basis of all claims for al­leged defects in the goods not discoverable upon reasonable inspection thereof pursuant to paragraph 8 hereof must be fully explained in writing and received by Seller within thirty days after Buyer learns of the defect or such claim shall be deemed waived.
3
Contents
Safety Message to Installers, Operators, and
Maintenance Personnel .......................................................................5
An Overview of the 120 Series ............................................................6
Product Detail .........................................................................................7
Special Conditions for Safe Use .............................................................9
Condições especiais para o Uso Seguro: ...........................................10
Installing the Product ......................................................................... 11
Accessing the Terminals and Glands ................................................... 11
Earthing ................................................................................................12
Greasing Holes for the Mounting Face and Screws .............................13
Wiring the ES4/MS4 Multi-Tone Sounder .........................................14
For 240 Vac Operation .........................................................................14
For 110 Vac Operation ..........................................................................14
For 24 Vdc 2-Wire Operation................................................................14
For 24 Vdc 3-to-5-Wire Operation ........................................................16
For AC 4-to-6-Wire Operation...............................................................17
240 Vac Operation: .........................................................................17
110 Vac Operation: .........................................................................17
Routine Maintenance .........................................................................18
Technical Service and Support .........................................................19
Ordering Replacement Parts .............................................................19
Figures
Figure 1 Loudspeaker dimensions........................................................9
Figure 2 Dimensions of mounting bracket ..........................................11
Figure 3 Side and rear views ..............................................................12
Figure 4 Tapping .................................................................................12
Figure 5 Speaker wiring diagram ........................................................13
Figure 6 Sounder wiring diagram........................................................15
Figure 7 Voltage selector for multi-tone sounder ................................15
4
120 Series Loudspeakers and Sounder
Tables
Table 1 Tone chart for 240 Vac, 110 Vac, and
24 Vdc two-wire operation ...................................................... 16
Table 2 Tone chart for 24 Vdc 3-to-5 wire
and AC 4-to-6 wire operation ............................................................... 18
Table 3 Replacement parts ................................................................ 19
5
120 Series Loudspeakers and Sounder
Safety Message to Installers, Operators, and Maintenance Personnel
It is important to follow all instructions shipped with this product. This device is to be installed by a trained electrician who is thoroughly familiar with local codes.
The selection of the mounting location for the device, its controls and the routing of the wiring is to be accomplished under the direction of the facilities engineer and the safety engineer. In addition, listed below are some other important safety instructions and precautions you should follow:
Read and understand all instructions before installing or
operating this equipment.
Do not connect this unit to the system while the power is on.
All effective warning speakers produce loud sounds, which
may cause in certain situations, permanent hearing loss. You should take appropriate precautions such as wearing hearing protection.
All effective warning speakers produce loud sounds, which may
cause, in certain situations, permanent hearing loss. The device should be installed far enough away from potential listeners to limit their exposure while still maintaining its effectiveness.
After installation, test the sound system to ensure that it operates
properly.
After testing is complete, provide a copy of these instructions to
all operating personnel.
Establish a procedure to routinely check the speaker installation
for integrity and proper operation. Any maintenance must be performed by a trained electrician in accordance with NEC guidelines and local codes.
Failure to follow all safety precautions and instructions may result in property damage, serious injury, or death.
6
120 Series Loudspeakers and Sounder
An Overview of the 120 Series
The Federal Signal 120 Series Loudspeaker complies with the ATEX
Directive for operation in gaseous hazardous areas classied as Zone 1 with a temperature classication of –20 °C to +70 °C T4, –20 °C to +55 °C T5, and –20 °C to +40 °C T6.
The loudspeakers are designed for use in industrial public address
and general alarm applications where ATEX certication is required.
They are available in either an ATEX Zone 1 explosion-proof version or a CE compliant, marine-grade industrial version.
The Model 120 Series Loudspeaker, including the marine versions (loudspeaker and MS1), has a main enclosure with dual gland entries and an FLP end cap. The model is tted with a nose cone, outer and
inner horn, driver, and an adjustable mounting bracket. The compo­nents within the main enclosure—transformer, transformer and PCB Assembly, PCB—vary depending on the model.
The 25-watt loudspeakers provide an appropriate amount of sound for the ambient environment. Each speaker is transformer-coupled to
ne tune the sound output for each application and balance the audio
load. Available audio inputs are 100 Vrms, 70 Vrms, and 8 ohms.
A stainless-steel ratcheted mounting bracket locks the sounder in
position at a specic angle without slipping. The bottom surface of
the mounting bracket also contains three mounting holes, to adapt to a variety of surfaces.
The loudspeaker is rated for IP66/67 according to EN60529 through
the use of a neoprene O-ring seal. All exterior cast aluminum surfac­es are nished in powder coat paint and external hardware is manu­factured from stainless steel to resist corrosion.
Loading...
+ 14 hidden pages