Fedders A*PB24A1, A*PB24B1, A*PC60A1 Series, A*PB36A1 Series, A*PC48A1 Series Instruction Manual

...
Electric Air Handler
TABLE OF CONTENTS
SERIES NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . .1
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS .1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
INSPECTION AND UNPACKING . . . . . . . . . . . . . . . . . . . .2
NOTES TO INSTALLER
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Power Considerations . . . . . . . . . . . . . . . . . . . . . . .2
Electric Heat Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Upflow Application . . . . . . . . . . . . . . . . . . . . . . . . .3
Horizontal Applicaton . . . . . . . . . . . . . . . . . . . . . . .4
Downflow Application . . . . . . . . . . . . . . . . . . . . . . .5
Connect Refrigerant Piping . . . . . . . . . . . . . . . . . . .6
Factory and Field installed Expansion Valves . . . . .6
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Return Air Ducting . . . . . . . . . . . . . . . . . . . . . . . . . .7
Return Air Platform Height . . . . . . . . . . . . . . . . . . .7
LINE VOLTAGE CONNECTIONS . . . . . . . . . . . . . . . . . . . .7
24 VOLT CONTROL SYSTEM . . . . . . . . . . . . . . . . . . . . . .8
CONDENSATE PLUMBING
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
BLOWER SPEED/STATIC OPERATION TABLE . . . . . . . .11
ELECTRIC HEAT KIT . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Heating Specifications . . . . . . . . . . . . . . . . . . . . . .13
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
. . . . . . . . . . . . . . . . . . . . . . . .
8
NOTE:
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS EQUIPMENT. READ THE ENTIRE INSTRUCTION MANUAL THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION.
1
SERIES NOMENCLATURE
roduct Type
P
= Air handler
A
Brand Identifier
Motor
B = 43 3/8” H x 18” W x 22” D C = 48 1/8” H x 22” W x 26” D
18 = 18,000 BTU/H (5.28 kW) 24 = 24,000 BTU/H (7.03 kW) 30 = 30,000 BTU/H (8.79 kW)
6 = 36,000 BTU/H (10.55 kW)
3 42 = 42,000 BTU/H (12.31 kW) 48 = 48,000 BTU/H (14.07 kW) 60 = 60,000 BTU/H (17.58 kW)
Chassis Size
Nominal BTUH
= ECM
E
P
= PSC
A L P B 24 A 1 * A
evision Letter
R
Electrical Designation
1 = 208 / 230 Volts, 1Phase, 60 Hz
= 230 Volts, 1 Phase, 50 Hz
2 3 = 208 / 230 Volts, 3 Phase, 60 Hz 4 = 460 Volts, 3 Phase, 60 Hz
= 230 Volts, 3 Phase, 50 Hz
5 6 = 380 Volts, 3 Phase, 50 Hz
Design Series
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
What You Need To Know About Safety Instructions
Warning and Important Safety Instructions appearing in this manual are not meant to cover all possible conditions and situations that may occur. Common sense, caution and care must be exercised when operating or cleaning tools and equipment.
Always contact your dealer, distributor, service agent or manufacturer about problems or conditions you do not understand.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
WARNING
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY, PROPERTY DAMAGE OR LOSS OF LIFE. READ THIS MANUAL COMPLETELY BEFORE BEGINNING ANY WORK AND FOLLOW ALL SAFETY PRECAUTIONS.
A QUALIFIED INSTALLER MUST PERFORM INSTALLATION AND SERVICE.
DO NOT DESTROY THIS MANUAL. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS COMPONENT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE, POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
BEFORE PERFORMING ANY WORK ON THIS EQUIPMENT, POWER SUPPLY MUST BE TURNED OFF AT THE HOUSEHOLD SERVICE BOX TO AVOID THE POSSIBILITY OF SHOCK, INJURY, DAMAGE TO EQUIPMENT, OR DEATH.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS, OR OTHER COMBUSTIBLE MATERIALS IN THE VICINITY OF THIS AIR HANDLER OR ANY OF ITS MATCHING SYSTEM COMPONENTS (CONDENSING UNIT, HEAT PUMP OR FURNACE).
1
NOTES TO INSTALLER
The words “SHALL” and “MUST” indicate a requirement which is essential to satisfactory and safe product performance. The words “SHOULD” and “MAY” indicate a recommendation or advice which is not essential and not required but which may be useful or helpful.
The instructions are for the use of qualified individuals specially trained and experienced in the installation of this type equipment and related system components.
Installation and service personnel are required by some locales to be licensed. Persons not qualified shall not install this equipment nor interpret these instructions.
INTRODUCTION
Models A*PB and Plare designed for flexibility and can be used for upflow, horizontal or downflow applications. These units are available for systems of 18,000 through 60,000 BTUH nominal cooling capacity. Factory authorized electric heater kits are available in 5 kW through 20 kW sizes. See product specifications for available accessory kits.
INSPECTION AND UNPACKING
A thorough inspection of the shipping container must be made immediately upon receiving your unit. Look for any punctures or openings, and if it appears damage has occurred, note it on the freight bill before signing. Contact delivering carrier immediately to inspect damage. Do not begin installation work should begin until this inspection is completed.
INSTALLATION
Codes
The installer must comply with all local, state and federal codes and/or regulations pertaining to this type of equipment and its installation. Such codes and/or regulations shall take precedent over any recommendations contained herein. If there are no local codes on the subject, installations shall be made in accordance with the National Electrical Code (NEC) and recommendations made by the National Board of Fire Underwriters.
Power Considerations
The installer shall check available power to make certain it matches the unit name plate rating and that constant voltage can be maintained on the unit. Unsatisfactory performance or a possible hazard could otherwise result. The local power company should be contacted with questions concerning power supply.
Electric Heater Kits
Only EEB/EEC series electric heater kit may be installed into the air handler. See Electric Heat section on page 12 for more information.
Location
All models are approved for alcove, closet, and attic installation in the upflow, downflow or horizontal position. Refer to the
pplicable section of this manual on pages 3-5 for specific
a installation instructions on each position.
The air handler must be installed in a level position and should be located for ease in connecting air duct with proper air distribution.
xterior surface of cabinet may sweat when unit is installed in
E
on-air-conditioned space such as attic or garage. Installer must
n provide protection such as full-size auxiliary drain pan on all units. Be sure to allow for filter access for periodic user servicing. In addition, caulking must be applied around the power and control wires entering the control box. This will prevent air leakage into and condensate from forming inside the control box.
Clearances
Clearances from the air handler to the combustibles are zero inches from all sides, top, and bottom; one inch from discharge air plenum; and the duct within 36 inches of the plenum.
Provide adequate space for servicing the air handler; at least 30 inches. All service and maintenance can be performed from the front access doors of the air handler.
WARNING
DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN DUCTWORK TO ANY OTHER HEAT-PRODUCING DEVICE SUCH AS FIREPLACE INSERT, STOVE, ETC. UNAUTHORIZED USE OF SUCH DEVICES MAY RESULT IN FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PERSONAL INJURY, OR PROPERTY DAMAGE.
2
Upflow Applicaton
D
ISCHARGE DUCT (600 FPM)
24” MINIMUM
RETURN DUCT WITH A MINIMUM OF
1/2” FIBERGLASS DUCT LINER (500 FPM).
REFER TO LOCAL CODES.
AIR
HANDLER
(MAY ALSO BE
DOWNFLOW)
DISCHARGE DUCT (600 FPM)
24” MINIMUM
RETURN DUCT WITH A MINIMUM OF
1/2” FIBERGLASS DUCT LINER (500 FPM).
REFER TO LOCAL CODES.
AIR
HANDLER
(MAY ALSO BE
DOWNFLOW)
DISCHARGE DUCT (600 FPM)
24” MINIMUM
RETURN
GRILLE
(500FPM)
RETURN PLATFORM LINED WITH
1” FIBERGLASS INSULATION.
REFER TO LOCAL CODES.
CLOSET
AIR HANDLER
In an upflow application normally a duct is employed as a return air means as shown in Figure 1 below
r a platform is installed as in Figure 2.
o
111
Upflow Installation With Return Duct
112
Upflow Installation With Return Platform
3
SUPPLY
AIR
SERVICE
PLATFORM
CEILING
JOISTS
AIR HANDLER SUPPORTS
(FIELD SUPPLIED)
AUXILIARY DRAIN PAN
(FIELD FABRICATED)
P-TRAP
PRIMARY
DRAIN LINE
RETURN AIR
AUXILIARY DRAIN LINE
Horizontal Application
This type of position is usually used in an attic or crawl space. The air
andler may be laid on the left or right side for horizontal applications.
h The factory-installed coil is intended for left-side-down installation.
This type of installation requires a return air duct to be attached to the air handler inlet. The opposite end of the return air duct is then routed to a return air grille mounted to the ceiling or wall. This duct MUST be no smaller than the inlet opening of the air handler.
or Horizontal Right Application:
F
1. Remove front panels from the air handler.
2. Remove coil assembly from the air handler.
3. Remove horizontal drain pan from left hand side of air handler and
re-install on right hand side. Change splash baffle location from left hand to right hand side of drain pan flange.
4. Remove the horizontal coil support bracket from the right hand side
of the air handler.
5. Reinstall coil assembly in the air handler.
6. Reattach coil support bracket to the left hand side of the air
handler.
7. Replace front panels.
CAUTION
Horizontal applications in unconditioned areas, such as attics above a ceiling, require special precautionary measures. An auxiliary drain pan having at least two inches overall clearance around the unit MUST be field-fabricated and installed as
hown below.
s The drain outlet and drain line for the auxiliary
drain pan need not be trapped but should be sloped to a suitable drain.
CAUTION
For optimum condensate drainage performance in horizontal installations, unit should be leveled along the length and width. Failure to follow this caution may result in product or property damage.
CAUTION
A P-type trap must be installed in the primary drain line as shown in figure 3 below.
Horizontal Installation
113
4
Loading...
+ 11 hidden pages