Faraday MPC-6000, RND-2, MPC-7000 Programming Manual

Page 1
MPC-6000 / MPC-7000 / RND-2
Fire Alarm System Control Unit
Programming Manual
Siemens Building Technologies, Inc. 8 Fernwood Road • Florham Park, NJ 07932 Tel: (973) 593-2600 • Fax: (973) 593-6670 Web: www.faradayfirealarms.com
P/N 315-049403FA-6 (3.23.06)
Page 2
Page 3
Table Of Contents
Introduction............................................................................................................................. 1
The Access levels..................................................................................................................... 1
User Level ..............................................................................................................1
Maintenance Level..................................................................................................2
Technician Level.....................................................................................................2
The Operator Interface ..........................................................................................................3
Interface for User and Maintenance Levels ............................................................3
Interface for the Technician Level...........................................................................4
Entering Alphanumeric Characters.........................................................................5
QUICK START....................................................................................................................... 6
Automatic programming of a new system...............................................................6
Manual programming of a system ..........................................................................7
Programming Concepts.......................................................................................................... 9
Program Memory....................................................................................................9
The programming model of the system ................................................................10
Automatic Programming .......................................................................................11
User Level.............................................................................................................................. 14
Activating a General Alarm ...................................................................................14
Activating an Alert.................................................................................................14
Activating a Drill ....................................................................................................14
Activating a Recall ................................................................................................15
Performing a Lamp Test .......................................................................................15
Viewing the Event History.....................................................................................15
Accessing Maintenance Functions .......................................................................16
Accessing Technician Functions ..........................................................................16
Maintenance Level................................................................................................................ 17
Enabling/Disabling Devices ..................................................................................17
Enabling/Disabling Input Groups ..........................................................................17
Enabling/Disabling Applications............................................................................17
Enabling/Disabling PAS........................................................................................18
Enabling/Disabling the Output Zones ...................................................................18
Enabling/Disabling NACs......................................................................................18
Enabling/Disabling City Tie...................................................................................18
Enabling/Disabling the DACT ...............................................................................19
Enabling/Disabling the Status Relays...................................................................19
Enabling/Disabling the Open Collector Circuits ....................................................19
Enabling/Disabling the Releasing Circuits ............................................................20
Changing the Maintenance Password ..................................................................20
Setting the Time....................................................................................................20
Setting the Time Format .......................................................................................21
Enabling Daylight Savings Time Adjustment ........................................................21
Setting the Date....................................................................................................21
Setting the Date Format........................................................................................22
Clearing the History ..............................................................................................22
Printing the History ..............................................................................................22
Page 4
Printing the Sensitivity Levels ...............................................................................23
Editing the System Label ......................................................................................23
Editing the Device Labels .....................................................................................23
Starting Quick Test ...............................................................................................23
Configuring NAC sound time for Quick Test .........................................................24
Configuring the printer during Quick Test .............................................................24
Programming a Device .........................................................................................24
Technician Level ................................................................................................................... 25
Activating the Releasing Application Features......................................................25
Configuring the Releasing Application Features...................................................25
Editing a Device Configuration .............................................................................26
Editing an Input Group Configuration....................................................................29
Editing a System Group Configuration..................................................................31
Configuring the NACs ...........................................................................................31
Configuring the Remote Relays (SRUs) ...............................................................32
Configuring the Remote LEDs (SLUs)..................................................................32
Configuring the Remote LCDs (RDC-2s)..............................................................33
Configuring Panel Relays .....................................................................................33
Installing the DACT.............................................................................................334
Configuring the DACT Accounts...........................................................................34
Configuring the Coder...........................................................................................35
Setting System Timers..........................................................................................35
Configuring the City Tie Activation........................................................................36
Setting Trouble Ack Required...............................................................................36
Setting the System Reporting Type ......................................................................36
Copying the Primary to the Backup ......................................................................36
Printing the Primary/Backup Configuration ...........................................................37
Validating the Backup Configuration.....................................................................37
Activating the Backup ...........................................................................................37
Hard Reset ...........................................................................................................37
Changing Access Passwords ...............................................................................37
Enabling the Network Connection to the Panel ....................................................38
Setting the Node Number .....................................................................................38
Setting the Printer.................................................................................................38
Setting the Total Number of Nodes.......................................................................39
Enabling Accepting/Sending Global Commands ..................................................39
Assigning a Message to a Network Link ...............................................................40
Creating the Notify Link and the Observe Link .....................................................40
Exiting the Technician Level .................................................................................40
APPENDIX A: GLOSSARY................................................................................................ 41
APPENDIX B: REFERENCES........................................................................................... 45
APPENDIX C: COMPATIBLE DEVICES FOR FDLC.................................................. 46
APPENDIX D: TYPICAL PROGRAMMING MODEL.................................................. 47
Page 5
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Introduction
The MPC-6000/7000/RND-2 Fire Alarm Control Panels are completely field programmable. Although programming requires no special software skills, a thorough working knowledge of Fire Alarm Control Panels and devices is assumed. There are two ways to program an MPC-6000/7000/RND-2 fire alarm system control unit from the front panel keypad:
1. Auto Program. Using Auto Program will quickly configure the FACP in a General Alarm configuration.
2. Manual Program. Editing the program manually using the keypad.
Both methods require that the Technician password be entered so that the Technician functions may be accessed. Jump to the Quick Start section if you need to get a system up and running quickly.
Note: All references to the Releasing Application programming options are available on the MPC-6000 panel only.
The Access levels
The MPC-6000/7000/RND-2 system has three functional levels as follows:
•
User Level, no password is required to access these functions.
•
Maintenance Level, accessed using the Maintenance password, allows access to the
maintenance menu functions.
•
Technician Level, accessed using the Technician password, allows access to trained
technician menu functions.
User Level
The User Level functions accessible to the system user are protected from unauthorized use by the lock on the front of the cabinet. Pressing the Menu button on the lower right of the operator interface accesses the user functions. The functions available to the User are as follows:
•
Activate a General Alarm
•
Activate an Alert event
•
Activate a Recall event
•
Activate a Lamp Test
•
Activate a Drill
•
View event history
•
Go to Maintenance Level (with the password)
•
Go to Technician Level (with the password)
1
Page 6
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Maintenance Level
The Maintenance Level is accessed via the User Menu and the correct password. The functions accessible in the Maintenance Level are as follows:
•
Enable or disable devices, outputs, groups, zones, status relays and option modules
•
Configure and run a Quick Test
•
Print History (For Diagnostics Only)
•
Print Detector Levels (For Diagnostics Only)
•
Edit Device and system labels
•
Set the system time and date
•
Change the Maintenance Level access password
•
Program a device
•
Clear event history
•
Enable or disable application
Technician Level
The Technician Level is accessed via the User Menu and entering the correct password. The functions accessible in the Technician Level are as follows:
•
Configure devices, outputs, groups, zones and option modules
•
Set System parameters (i.e., automatic silence, alarm silence inhibit, reset inhibit, etc.)
•
Configure MPCnet network options
•
Configure bell codes
•
Validate the backup configuration
•
Swap the primary and backup configuration
•
Copy the primary to the backup configuration
•
Print the primary and backup configuration (For Diagnostics Only)
•
Change the Technician Level access password
2
Page 7
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
The Operator Interface
Interface for User and Maintenance Levels
The operator interface for configuring and programming the MPC-6000/7000 uses the 4 line by 20 character LCD display, the M1 through M4 buttons on the left and right of the display and sixteen push buttons at the bottom of the interface. User Level and Maintenance Level utilize the LCD display and the four buttons (two on each side of the display) to navigate and alter the basic operation of the panel. The display will show messages in the four corners of the display that will be adjacent to the four buttons M1 through M4. The message on the display adjacent to the button indicates the action that will occur when the button is pressed. Therefore pressing M1 will cause the function labeled as “Menu 1” to be pressed.
M1 or 1 M3 or A
M2 or * M4 or D
Note: When programming in Technician Level, M1=1 on the keypad, M2=* on the keypad, M3=A on the keypad and M4=D on the keypad.
For example, in the following figure, menu item 1 (Lamp Test) is described as having an
Action of ‘Run Lamp Test’. If the button next to Lamp Test is depressed, Lamp Test will
be performed. Menu item 2 (View History) will cause the first event in the event history to be displayed on the screen.
Action: Run Lamp Test Returns to the top of the
Will display panel go to the next screen History
Menu 1 Menu 3
Menu 2 Menu 4
Lamp Test Esc
View History More
list or to the level up
3
Page 8
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Interface for the Technician Level
When the Technician Level is accessed using the password, the LCD display and the keypad are used to program the panel, and to view the programming if desired. The display acts as a menu and the keypad allows the user to navigate through the menu of functions and change or print the programming. The following figure describes the navigation used in this context:
A-esc: will backup to previous screen
Each menu item is associated with "A", "B", "C", or "D" buttons on the keypad. Pressing
one of these keys will cause the panel to go to the function associated with the button.
For example
ZNxxx P Aesc ZoneType:PRESIG B+20 Timer:___ Sec Cmor To Zone #:___ D +1
Aesc Bfn1 Cfn2 Dnxt
B-fn1: will perform function 1 C-fn2: will perform function 2 D-Nxt: will step to the next screen
A-Esc, will backup to previous screen B-+20 Jumps ahead 20 devices C-mor shows further options in list D-+1, Jumps ahead 1
4
Page 9
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Entering Alphanumeric Characters
Entry of alphanumeric data using the keypad is as follows:
•
Each character is entered using a two-keystroke sequence on the keypad.
•
Numerals are entered using the sequence 0x, where x is the numeral to be entered.
•
Letters are entered using 1x, 2x, 3x, and 4x sequences, based on the letters appearing
above the numbers on the keypad, where the first digit (1, 2, 3 or 4) is the position of the letter and the second digit is the numerical key on which that letter appears. For example, to enter the letter “A” use the sequence “12”. To enter the letter “N” use the sequence “26”. Exceptions are the letters “Q” and “Z” which do not appear on the keypad. The letter "Q" is entered using the sequence "27", as though "Q" appears on the "7" between "P" and "R". The letter "R" is entered as "37" and "S" as "47". Similarly, "Z" is entered as "49", as though "Z" appears on the "9" key. Punctuation marks are entered using 5x, 6x, 7x, and 8x sequences, as shown below:
CHARACTER SEQUENCE CHARACTER SEQUENCE
<space> 50 > 70
! 51 ? 71
" 52 @ 72 # 53 [ 73 $ 54 ¥ 74
% 55 ] 75
& 56 ^ 76
´ 57 _ 77
( 58 ` 78
) 59 { 79
* 60 | 80 + 61 } 81
, 62 → 82
- 63 ¦ 83
. 64
/ 65
: 66
; 67 < 68 = 69
•
Insert and overwrite modes can be toggled using the "C" key.
•
Entering the same letter into a position in overwrite mode will change the case of the letter
(i.e., if a position contains the letter "f", and the user enters "33" in overwrite mode, the "f" will change to "F").
•
A character may be deleted by pressing the “9” key.
•
Pressing the * key will move the cursor back one space; pressing the # key will move the
cursor forward one space.
5
Page 10
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
QUICK START
Automatic programming of a new system
This is the quickest way to get a system operational. After all of the devices, notification appliances and option modules have been programmed and installed, check all wiring for grounds, shorts and opens. Connect SLUs, SRUs, NACs and any other field wiring to the panel.
Automatic programming is selected from the Technician Level. Below are the steps to access the Technician Level.
Step Action Description
1 Press “Menu” and then press “More” until
the option “Tech. Level” is displayed.
2 Press “Tech. Level”. The display will show the entry
3 Enter the password on the keypad. The
default is “0 1 2 3 4 5”.
4 Press “Enter” or “D”. The display will show the starting
Once the Technician Level has been accessed, following are the steps to activate the autoprogram function.
Step Action Description
1 Select “Edit” by pressing “4”. The display will show the first
2 Select “Autoprgm” by pressing “7”. The display will show the
3 Start the autoprogram by pressing the “D”
key.
screen for the technician level access password. The password will be displayed as “* * * * * *”.
screen of the Technician Level.
screen of the Edit functions with “Auto Pgm” as one of the options.
Autoprgm screen. The display will show all of the addresses being checked as the auto program is performed. This could take several minutes. As each new device is found, the display will allow the installer to chose whether to include the found device. When the autoprogram is finished, the screen will return to the Edit options.
6
Page 11
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Step Action Description
Note NOTE #1: The backup configuration will now contain a configuration as follows:
all input points in group #241 (General Alarm). The General Alarm System group is pre-programmed to activate all output zones. Any Remote LCD displays that were connected at the time of Auto Program will also be activated. However remote relay (SRUs) and remote Led modules (SLUs) will not be detected and so will not be in the configuration.
4 At the EDIT BACKUP screen, press “A”
and escape back to TECH LEVEL
screen.
5 Use “C” to get to the next set of functions
and select “validate”.
6 Press the “*” key followed by the "C" key
when prompted. This action will cause the autoprogrammed configuration to be swapped into the primary memory and the panel will be restarted. (You now have as the primary configuration the result of the Auto Program. In other words, a General Alarm system.)
The display will show the starting technician menu.
This will cause the data in the backup configuration to be checked. Correct any errors found before continuing. The panel will reset and reinitialize.
Manual programming of a system
Manual programming is a much more involved operation and requires knowledge of the operation of the system before proceeding. The basic steps to programming a system configuration are as follows:
Step Number
1 System configuration Set a number of overall system parameters. 2 Loops Set up each loop, one in the case of the 6000
3 Input groups/system
Configure Description
and (up to) four in the case of the 7000. Set up the behavior of the input group or system
groups
groups--the bell codes it will activate and the output zones that will be activated by this input group. Note that an input group must be configured to activate an output group to cause any output activations.
NOTE: If the releasing input group type is selected and it is using coded signals, all other input group types must be configured for Steady-On only code type.
7
Page 12
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Step Number
4 Devices Set the address and other parameters for each
5 Notifications
Optional 6 RDC-2 Annunciators If there are any remote RDC-2 displays, set
Optional 7 Remote LEDs If there are any remote LED modules, configure
Optional 8 Remote Relays If there are any remote Relay modules,
Optional 9 DACT line/DACT
Optional 10 Releasing Application If configured in the system parameters,
11 Validate Run validate and fix any errors that are reported. 12 Activate Swap the backup configuration with the primary
Configure Description
of the devices that will be installed into the system. Configure the input group of each device. Note that devices must be connected to an input group for any output to be activated. If the panel is networked, also setup the network group that this device will activate. Configure the behavior of the NACs and the
appliance circuits
account
output zone that will activate each NAC. Note that a NAC must be configured as connected to an output zone or it will not activate.
whether installed.
each of the remote LEDs. Select the Output zone that will activate the LED.
configure each of the remote Relays. Note that the Relays must be connected to an Output Zone in order to activate. If a dialer is installed, configure the line and account data.
configure the releasing features parameters.
configuration.
IMPORTANT NOTE: Special considerations apply to programming an RND-2 panel as
opposed to either an MPC-6000 or MPC-7000 panel. No devices (inputs or outputs), no NACs, no SLUs nor any SRUs can be connected or programmed. Only the MPC-DACT DACT board or the CT-1K City Tie board, the RDC-2 Annunciator and the network may be connected and programmed to an RND-2 panel.
8
Page 13
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Programming Concepts
Program Memory
The program memory consists of two components, the PRIMARY (active) configuration and the BACKUP (editable) configuration. The primary configuration is the active
(running) configuration that determines the current function of the FACP. The backup configuration is the configuration that is edited to make changes or additions to the existing active panel program. This allows the program to be edited while the FACP operates normally.
Before the backup configuration is activated, it first must be validated to make sure that the configuration follows the installation rules. The validation process ensures no values or operating parameters are out of limits.
When the edited configuration is activated, all changes are implemented at once by swapping the primary and backup configurations. The backup configuration becomes the primary (running) configuration and the configuration that was running becomes the backup configuration.
NOTE: At this point it is advisable to copy the primary configuration to the backup so that both configurations are identical. There is a copy feature that allows the operato copy the primary configuration to the backup.
r to
9
Page 14
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
The programming model of the system
The following diagram shows the programming model of the MPC-6000 and MPC-7000 systems.
Input devices
can belong to
one local input
group.
1
Input group
Each input device can be configured for type of operation, i.e., alarm, manual pull,
22
T
T
T
32
T
12
waterflow, sil waterflow, trouble, supervisory, non­fire, panel reset, alarm silence, acknowledge.
GC
The input group may be configured for different activation, i.e., none, fire zone, cross zone, PAS, pre signal, wildcard, releasing.
Output Zones
up to 255
An input group can activate any or all Output Zones.
up to 240 input
groups
System groups: general alarm
Each LED and remote
relay can have its
output behavior configured, i.e.,
Alarm active, trouble,
supervisory, pre-alarm.
drill
recall
alert
trouble
quick test
Each output can be set
for the control behavior,
supervisory, pre-alarm,
GC
GC
GC
GC
i.e., non-silencable,
trouble active,
silenceable, trouble
silence, supervisory
silence.
Can set various behaviors depending on the type of system group. (Mainly output coding.)
Releasing Circuit, NACs and
Audible bases can connect to
one and only one output Zone.
Each relay can have its output behavior configured, i.e., non-silencable, trouble active, supervisory, pre­alarm, silenceable, trouble silence, supervisory silence.
Remote relays and remote
LEDs connect to output zones.
Monitor modules and detector
base relays can connect to one
and only one output zone.
The MPC-6000 and MPC-7000 programming model
10
Page 15
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
The basic concept is that loop devices are configured and grouped into input groups. The input groups are set to have a certain behavior and activate output zones. The output devices―whether relay bases, audible bases, NACs, serial LEDs or Serial relays―are configured and connected to Output Zones.
Automatic Programming
Auto-program can be done with a new, non-configured control unit or to augment an existing configuration. Augmenting an existing program adds new points but leaves previously programmed points unaffected. Discrepancies in the configuration will be presented individually for acceptance. Again, auto program writes information into the backup and must be validated before becoming the primary operating configuration.
Auto Program will recognize the types of devices connected and will set up different parameters depending on the devices it finds. The following tables show the settings for the different device types.
Smoke and thermal detectors
Parameter Description
Label Generic label identifying the detector by loop number and address. Application If FireSmart detectors are found, the application will not be changed in the
device. Factory default is none.
Sensitivity The sensitivity of the detectors will be left as found. The factory default is
3.00%. ROR Rate of rise will be off. Led off LED will be defaulted to ON. Pre-alarm Pre-alarm will be off. Verification Verification will be as found in the detector. Input Usage The input usage will be defaulted to Alarm. Input Group All detectors will be defaulted to input group 241 (General Alarm). Network Group This will not be set and will need to be set manually. (Future use) Relays and Audible bases
Monitor Modules, Manual Stations and Conventional Zone modules
Parameter Description
Label Generic label identifying the detector by loop number and address. Led off LED will be defaulted to ON. Input Usage Input usage will be defaulted to alarm. Input Group All inputs will be defaulted to input group 241 (General Alarm). Network Group This will not be set and will need to be set manually. (Future use)
Will be defaulted to auto activation. The relay or audible base will activate when the device activates.
11
Page 16
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Monitor Modules with relay and single input
Parameter Description
Label Generic label identifying the detector by loop number and address. Led off LED will be defaulted to ON. Input Usage Input usage will be defaulted to alarm. Input Group Inputs will be defaulted to input group 241 (General Alarm). Network Group This will not be set and will need to be set manually. (Future use) Output Type Will be defaulted to non-silenceable. Output Zone Will be defaulted to 1.
Intelligent LEDs
Parameter Description
Label Generic label identifying the detector by loop number and address. Output Type Will be defaulted to non-silenceable. Output Zone Will be defaulted to 1.
NACs
Parameter Description
Notification
Set to Audible. Device Type Output Type Will be defaulted to silenceable. Output Zone Will be defaulted to 1. Always On Will be no. Wire Class Will be defaulted as Class B. Default Times ON time delay will be defaulted to no delay.
OFF time delay will be defaulted to no delay. The ON time and OFF time refer to the time delays in which the NAC delays its activation and
deactivation.
System Parameter
Parameter Description
Label Set to “FARADAY AUTO Prgrmd” Drill Enable ON Auto Silence Timer Off Alarm Silence Inhibit Off Panel Reset Inhibit Off Auto Alarm silence Off Trouble Reminder 12 hours NAC sound time 5 seconds Quick test exit 30 minutes City Tie Activation Not changed Global Commands Not changed Printer ESC Not changed Releasing Not installed. If installed, this activates releasing application features.
•
The presence of RDC-2 Annunciators is detected and their address is programmed
automatically when the system is initialized.
12
Page 17
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Not included in auto-program
The following devices cannot be detected automatically:
•
Bell Codes
•
Serial Remote Processor LEDs
•
Serial Remote Processor Relays
•
DACT
•
City Tie
•
Releasing Module
Programming of these points is not changed by Auto-Program and must be done manually in the panel's Technician Level.
13
Page 18
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
User Level
Pressing the menu button displays the User Level functions. The user menu allows the operator to activate General Alarm, Alert, Drill, Recall or Lamp Test. It also allows for viewing the Event History. The Maintenance Level programming and Tech Level programming can be accessed from the User menu as well.
Following are the various functions that may be performed at the User level.
Activating a General Alarm
It is possible to sound a general alarm from the keypad using the following steps:
Action Result
1. Press “Menu”.
2. Press “General Alarm”. Display requests “Yes/No” confirmation of the
General Alarm.
3. Press “Yes” to activate a General Alarm. The display will return to normal indicating
General Alarm has been activated.
4. Press “System Reset” or “Alarm Silence” to stop. NOTE: System Reset is required if audibles are non-silenceable.
Activating an Alert
It is possible to sound an Alert from the keypad using the following steps:
Action Result
1. Press “Menu”.
2. Press “Alert”. Display requests “Yes/No” confirmation of the
Alert.
3. Press “Yes” to activate an Alert. The display will return to normal indicating an
Alert has been activated.
4. Press “System Reset” to stop.
Activating a Drill
It is possible to sound a drill from the keypad using the following steps:
Action Result
1. Press “Menu”.
2. Press “More”.
3. Press “Drill”. Display requests “Yes/No” confirmation of the
Drill.
4. Press “Yes” to activate a Drill. The display will indicate Drill has been
activated.
5. Press “System Reset” to stop. Returns to system normal display.
14
Page 19
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Activating a Recall
It is possible to sound a Recall from the keypad using the following steps:
Action Result
1. Press “Menu”.
2. Press “More”.
3. Press “Recall”. Display requests “Yes/No” confirmation of the
Recall.
4. Press “Yes” to activate a Recall. The display will indicate Recall has been
activated.
5. Press “System Reset” to stop. Returns to system normal display.
Performing a Lamp Test
It is possible to perform a lamp test of the LEDs on the front of the Panel by following the steps below:
Action Result
1. Press “Menu”.
2. Press “More”.
3. Press “More.”
4. Press “Lamp Test”. LEDs in the front panel will be lit for
approximately 3 seconds.
Viewing the Event History
The Event History screen displays the last 2000 events reported to a panel. The information displayed includes the date and time, the type of event (TRB, ALM, SUP etc.), the device reporting the event and the event reported.
Action Result
1. Press “Menu”.
2. Press “More”.
3. Press “More.”
4. Press “View History”. The display will show the most recent event.
5. Press the two buttons to the left of the display to scroll forward and backward through the events.
6. Press the upper right hand button (M3) to escape back to the user menu.
(Press M1 to go to an older event, press M2 to go to a more recent event.)
15
Page 20
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Accessing Maintenance Functions
There are other functions available after the maintenance password has been entered. Follow the steps below to access the maintenance functions:
Action Result
1. Press “Menu”.
2. Press “More”.
3. Press “More.”
4. Press “More”.
5. Press “Maint. Level”. The display will show the screen to enter the
four-digit maintenance password.
6. Enter the four-digit password (default is 0 1 2 3) and press “Enter”.
Accessing Technician Functions
There are other functions available after the technician password has been entered. Follow the steps below to access the technician functions:
Action Result
1. Press “Menu”.
2. Press “More”.
3. Press “More”.
4. Press “More”.
5. Press “Tech. Level”. The display will show the screen to enter the
six-digit technician password.
6.
Enter the six-digit password (default is 0 1 2 3 4 5)
and press “Enter”.
16
Page 21
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Maintenance Level
Following are the details of the Maintenance level functions.
Enabling/Disabling Devices
The disable / enable screens allow the operator to disable or enable devices and components of the system. System Inputs, Outputs, etc., can be disabled / enabled. NOTE: When a device is already enabled, the disable option is displayed.
Action Result
1. Press “Disable/Enable”.
2. Press “Inputs”.
3. Press “Devices”. The display will show a screen for the address
of the device.
4. Enter the address through the keypad. When the address is entered, the status of the
device will be displayed.
5. Use the “Disable(Enable)” button to change the state of the device.
Enabling/Disabling Input Groups
The input group may be disabled/enabled as follows:
Status will toggle on the display.
Action Result
1. Press “Disable/Enable”.
2. Press “Inputs”.
3. Press “Groups”. The display will show a screen for the address
of the group.
4. Enter the address through the keypad. When the address is entered, the status of the
group will be displayed.
5. Use the “Disable(Enable)” button to change the state of the group.
Status will toggle on the display.
Enabling/Disabling Applications
The applications in the FireSmart detector that prevent false activation often make it difficult to test the detectors using canned smoke. This function allows the Applications in the detectors to be turned off for testing. A trouble is posted as a reminder to reset them later.
Action Result
1. Press “Disable/Enable”.
2. Press “Appl”. The display will show the current status of the
applications.
3. Use the “Disable(Enable)” button to change the status of the applications in the
FireSmart detectors.
Status will toggle on the display.
17
Page 22
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Enabling/Disabling PAS*
PAS (Positive Alarm Sequence) may be disabled/enabled as follows:
Action Result
1. Press “Disable/Enable”.
2. Press “More”.
3. Press “PAS”.
4. Use the “Disable(Enable)” button to change the state of PAS
.
*Refer to page 30 for information on PAS.
The display will show the current status of PAS. Status will toggle on the display.
Enabling/Disabling the Output Zones
The output zones may be disabled/enabled as follows:
Action Result
1. Press “Disable/Enable”.
2. Press “Outputs”.
3. Press “Zones”. The display will show a screen for the address
of the zone.
4. Enter the address through the keypad. When the address is entered, the status of the
zone will be displayed.
5. Use the “Disable(Enable)” button to change the state of the zone.
Status will toggle on the display.
Enabling/Disabling NACs
The Notification Appliance Circuits may be disabled/enabled as follows:
Action Result
1. Press “Disable/Enable”.
2. Press “Outputs”.
3. Press “NACs”. The display will show a screen for the number
of the NAC.
4. Enter the number through the keypad and press “Enter”.
5. Use the “Disable(Enable)” button to change the state of the NAC.
When the address is entered, the display will show the current state of the NAC. Status will toggle on the display.
Enabling/Disabling City Tie
The City Tie Circuit may be disabled/enabled as follows:
Action Result
1. Press “Disable/Enable”.
2. Press “Outputs”.
3. Press “More”.
4. Press “City Tie”. The display will show the status of the City Tie.
5. Use the “Disable(Enable)” button to change the state of the City Tie.
Status will toggle on the display.
18
Page 23
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Enabling/Disabling the DACT
The DACT (Digital Alarm Communication Transmitter) may be disabled/enabled as follows:
Action Result
1. Press “Disable/Enable”.
2. Press “Outputs”.
3. Press “More”.
4. Press “DACT”. The display will show the status of the DACT.
5. Use the “Disable(Enable)” button to change the state of the DACT.
Status will toggle on the display.
Enabling/Disabling the Status Relays
The Status Relays may be disabled/enabled as follows:
Action Result
1. Press “Disable/Enable”.
2. Press “Outputs”.
3. Press “More”.
4. Press “More”.
5. Press “Status Relays”.
6. Use the keypad to enter the address. The display will show the state of the Status
Relays.
7. Use the “Disable(Enable)” button to change the state of the Status Relays.
Status will toggle on the display.
Enabling/Disabling the Open Collector Circuits
The Open Collector Circuits may be disabled/enabled as follows:
Action Result
1. Press “Disable/Enable”.
2. Press “Outputs”.
3. Press “More”.
4. Press “More”.
5. Press “OC Ckts”.
6. Use the keypad to enter the address (01-04) and press “Enter”.
7. Use the “Disable(Enable)” button to change the state of the OC Circuit.
The display will show the state of the OC Circuit. Status will toggle on the display.
19
Page 24
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Enabling/Disabling the Releasing Circuits
The Releasing Circuits may be disabled/enabled as follows:
Action Result
1. Press “Disable/Enable”.
2. Press “Outputs”.
3. Press “More”.
4. Press “More”.
5. Press “Rel Ckts”.
6. Use the keypad to enter the address (01-02) and press “Enter”.
7. Use the “Disable(Enable)” button to change the state of the Releasing Circuit.
The display will show the state of the Releasing Circuit. Status will toggle on the display.
Changing the Maintenance Password
The password for access to the Maintenance level menus may be changed as follows from the Maintenance starting screen:
Action Result
1. Press “More”.
2. Press “More”.
3. Press “More”.
4. Press “Change Password”. The display will show “change maintenance
password”.
5. Use the keypad to change the password and press “Enter”.
Setting the Time*
The time and the time format are adjustable.
Action Result
1. Press “More”.
2. Press “More”.
3. Press “More”.
4. Press “Time/Date”.
5. Press “Time”.
6. Press “Set Time”. The display will show the time with the cursor
under the hours.
7. Use the keypad to enter new time. Pressing “Clr” will clear the entry. Pressing “Set” will set the time.
*The time for a networked system can be set from any point in the system. It can take up to one minute before all of the points on the system are in sync.
20
Page 25
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Setting the Time Format
The time and the time format are adjustable.
Action Result
1. Press “More”.
2. Press “More”.
3. Press “More”.
4. Press “Time/Date”.
5. Press “Time”.
6. Press “Set Time Format”. The display will show the current time format.
7. Use the “12 hour”, “24 hour” buttons to set the time format.
Enabling Daylight Savings Time Adjustment
The MPC-6000/MPC-7000/RND-2 can adjust for daylight savings automatically. Follow the steps below to enable or disable the automatic daylight savings adjustment feature:
Action Result
1. Press “More”.
2. Press “More”.
3. Press “More”.
4. Press “Time/Date”.
5. Press “Time”.
6. Press “DST Adjust”. The display will show whether the DST
automatic adjustment is enabled or disabled.
7. Use the “Disable(Enable)” button to change the status.
The state will toggle on the display.
Setting the Date
The date and the date format are adjustable.
Action Result
1. Press “More”.
2. Press “More”.
3. Press “More”.
4. Press “Time/Date”.
5. Press “Date”.
6. Press “Set Date”. The display will show the current date.
7. Use the keypad to enter new date. Pressing “Clr” will clear the entry. Pressing “Set” will set the date.
21
Page 26
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Setting the Date Format
The date and the date format are adjustable.
Action Result
1. Press “More”.
2. Press “More”.
3. Press “More”.
4. Press “Time/Date”.
5. Press “Date”.
6. Press “Set Date Format”. The display will show the current date format.
7. Use the two date format buttons to select the desired date format.
Clearing the History
The panel can store the last 2000 events in the event history. The information displayed includes the date and time, the type of event (TRB, ALM, SUP, etc.), the device reporting the event and the event reported. This event history may be cleared using the following steps.
Action Result
1. Press “More”.
2. Press “More”.
3. Press “More”.
4. Press “Clear History”. The display will then request a “yes” or “no”
confirmation.
5. Press “Yes” to clear the event history. The display will flash a short message to
indicate the history has been cleared.
Printing the History (For Diagnostics Test Only)
The panel can store the last 2000 events in the event history. The information displayed includes the date and time, the type of event (TRB, ALM, SUP, etc.), the device reporting the event and the event reported. This event history may be printed using the following steps.
Action Result
1. Press “More”.
2. Press “Print Hist”. The display will show the “Print Fwd” and “Print
Reverse” options.
3. Select the direction of printing that is desired. The display will show a message that history is
being printed.
22
Page 27
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Printing the Sensitivity Levels (For Diagnostics Test Only)
The sensitivity levels of all of the detectors in the system may be printed. Follow the steps below:
Action Result
1. Press “More”.
2. Press “Print Sensor Levels”. The display will indicate that the sensor levels
are being printed.
Editing the System Label
The system label may be changed as follows:
Action Result
1. Press “More”.
2. Press “More”.
3. Press “Edit Labels”.
4. Press “System”. The display will show the system label.
5. Use the keypad text. Pressing Bsav will save the changes.
keys to change the
system label
Editing the Device Labels
The device labels may be changed as follows:
Action Result
1. Press “More”.
2. Press “More”.
3. Press “Edit Labels”.
4. Press “Device”.
5. Enter the Loop and Device address, then press Dnxt.
6. Use the keypad text. Pressing Bsav will save the changes.
keys to change the
device label
The display will show the label for the device at this address.
Starting Quick Test
The Quick Test mode allows quick and easy testing of the installation. It will allow the devices to be activated and the NACs to sound for an adjustable time of from 1-30 minutes.
Action Result
1. Press “Quick Test”.
2. Press “Start”. The display will prompt for a “Yes” or “No”
confirmation to start Quick Test.
3. Press “Yes” to start Quick Test. The display will show NAC sound time, the
status of the printer and the time until autoexit.
4. Press “Stop” to reset the panel. Note: A test will reset the autoexit time to its original setting.
23
Page 28
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Configuring NAC sound time for Quick Test
The period of time that the NACs will be active after each event in Quick Test is set as follows:
Action Result
1. Press “Quick Test”.
2. Press “Configure”.
3. Press “NAC time”. The display will indicate the time in seconds
that the NACs will sound during Quick Test.
4. Use the “Inc” and “Dec” buttons to set the time either to “off” or from 1 to 30 seconds.
Configuring the printer during Quick Test (For Diagnostics Test Only)
Printing may be enabled or disabled during Quick Test as follows:
Action Result
1. Press “Quick Test”.
2. Press “Configure”.
3. Press “Printer”. The display will indicate whether the printer is
enabled or disabled during Quick Test.
4. Use the “Disable(Enable)” button to change state.
The display will toggle to indicate the state.
Programming a Device
It is possible to program a device address without the programming tool. Following is the procedure that is used when adding a single new device to the loop.
Action Result
1. Press “More”.
2. Press “More”.
3. Press “Program device”. The panel will display a message as it is
looking for the new device. When a new device has been found, the display will show a screen to enter a device address.
4. Use the keypad and “Program” buttons to enter the address and program the new device. Pressing “Clr” will clear the entry.
24
Page 29
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Technician Level
The Technician level allows complete programming of the MPC-6000/MPC-7000/RND-
2. See the User level functions for the method to access the Technician level. The steps below assume that the Technician level has been accessed and that the panel is displaying the starting screen of the Technician level.
Activating the Releasing Application Features
During initial power-up, the releasing application features are defaulted to NOT INSTALLED state and need to be activated to use the panel for releasing application. When this feature is activated, it allows the user to select releasing application features at various levels of programming.
Action Result
1. From Tech Level Screen, select “Edit”. Enter the Edit Backup Screen.
2. Select “Manual Pgm”. Enter the Manual Programming Screen.
3. Select “Cmor,” then select “Sys Params.” Enter the System Parameter Programming
Screen.
4. Select “Cmor” three times then select “Releasing.”
5. Press Bsav to save the selection. Saves the selection to the Backup program.
Configuring the Releasing Application Features
After the releasing application features have been activated, its parameters need to be configured.
Action Result
1. From Tech Level Screen, select “Edit”. Enter the Edit Backup Screen.
2. Select “Manual Program.” Enter the Manual Programming Screen.
3. Select “Cmor,” then select “Releasing.” Enter the Releasing Parameter Programming
4. After configuring the Releasing Application Parameters, press Bsav to save the selections.
The following provides a description of the releasing application parameters.
Enter the Releasing Application Prompt. Select YES to enable the releasing application feature.
Screen Saves the selection to the Backup program.
.
Parameters Sublevel Description
Agent Rel Delay
Shutoff Period
Abort Type
Enter the desired time using the numeric keypad in 5 sec. Increments.
Enter the desired time using the numeric keypad in 5 sec. increments. ULI
IRI
*
AHJ NYC
This parameter sets the time delay before the releasing circuits activate once the releasing set thresholds are met. 90 seconds.
This parameter sets the time the releasing circuit is active. This timer starts as soon as releasing circuit activates. (Default – 60 sec.) Range: 20-60 seconds.
This parameter determines the action of the panel when the abort switch is initiated while the system is in Pre-Discharge condition.
ULI - Abort condition is initiated during Pre­Discharge condition only. Pre-Discharge delay counts down or restores to 10 sec. then holds if abort is pressed and resumes countdown if abort switch is released.
(Default – 30 sec.) Range: 0-
25
Page 30
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Parameters Sublevel Description
IRI* – Abort condition is initiated if the abort
switch is held during 1 before the panel enters the Pre-Discharge condition. The Pre-Discharge delay will countdown to 10 sec. and hold if the abort switch is held. Pressing abort switch during Pre­Discharge condition does not initiate an abort condition.
AHJ – Abort condition is initiated during Pre­Discharge condition only. Pre-Discharge delay is restored to its programmed value every time the abort switch is pressed and will not start the countdown until the abort switch is released.
NYC – Abort condition that meets New York City requirement for releasing application. Abort condition is initiated during Pre-Discharge condition only. If abort switch is pressed during Pre-Discharge delay countdown, a 90 sec. investigation time delay is added before Pre­Discharge delay countdown initiates again. NOTE: Abort condition will still be honored even when initiated before 1
condition. Open Col Ckts
Releasing Circuit
*This feature is supported for UL 864 9
Use the keypad to configure the parameters of each open collector circuit.
Use the keypad to configure the parameter of each releasing circuit.
th
Edition.
This selection enters the Open Collector Circuit
Programming Screen. This is similar to
programming the NAC device where the
following parameters have to be configured:
Open Collector Circuit #
Output Installed: Select YES if circuit is used
Output Zone: Enter zone the circuit will belong to
Output Type: Select output type where the output
will activate when the condition is met.
This screen selects if the releasing circuit is
being used. Select INSTALLED if the releasing
circuit is used.
Editing a Device Configuration
A device’s configuration may be edited as follows:
st
Alarm condition only
st
Alarm or Pre-Discharge
Action Result
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Select “Devices”.
4. Enter the device address. The user may now navigate through screens
The loop devices are addressed using a four-digit address. The first (left-most digit) is the loop number while the next three digits specify the address on the loop. The setup of an input device will vary depending on the type of device installed at that address.
which allow setting of the various parameters for a device.
26
Page 31
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
The types of devices that can be installed in the system are listed in Appendix C on page 46.
The parameters that may be set for AutoOutput Activation are shown in the following table.
Parameter Description Applies to
DvOut
(Device Output Type)
AutoOutput If enabled, the detector can activate its own output
Device Zone The Output Zone to which the output device is
On Delay Delay in seconds between when the zone activates
Off Delay Delay in seconds between when the zone activates
Type of event that will cause activation of the output. Also, whether or not it is silenceable.
device. Otherwise, the device will only activate when its Output Zone is activated.
assigned.
and when the output device activates.
and when the output device de-activates. When used with the On Delay, this parameter can be used to turn an output device on only for a certain period of time when its zone is activated. If this parameter is set to zero, the device will not deactivate (0=infinite).
8710, 8712, 8713, 8704, 8726, 8706 8710, 8712, 8713
8710, 8712, 8713, 8704, 8726, 8706 8710, 8712, 8713, 8704, 8726, 8706
8710, 8712, 8713, 8704, 8726, 8706
27
Page 32
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Below are the different parameters that may be set for each of the different devices:
FireSmart
Smoke
Detector
Thermal Detector
Photo
Smoke
Detector
station
Pull
Loop Devices
Single
input monitor module
Dual
input monitor module
Single
input monitor module
Conven-
tional Zone
module
LED
output
Intelligent
Point
Control
(See note 4)
with relay
Parameter
8713 8712 8710 8700-Single
8700-Dual
8700-Metal
8701 8702
8703 8704 8705 8726 8706
Label X X X X X X X X X X Application X - - - - - - - - ­Sensitivity
ROR
When app
off
-
- X - - - - - - -
X - - - - - - - ­Led off X X X - X X X X - X Pre-alarm
Verification
When app
off
When app
off *
- X - - - - - - -
- X - - - - X** - -
Alarm X X X X X X X X - ­Waterflow - - - - X X X X - ­Sil. Waterflow - - - - X X X X - ­Trouble - - - - X X X - - X**** Supervisory X - X - X X X X - ­Panel reset - - - - X X X - - ­Alarm silence - - - - X X X - - ­Acknowledge - - - - X X X - - ­Test - - - - X X*** X - - ­Manual Pull - - - - - - X - -
2, 3
Abort Man. Release
- - - - X X X - - -
1, 3
- - - X X X X - - -
Thermal1 - X - - X X X - - -
* Except when used in DUCT application. *** Available only for first input usage. ** Except when used for manual pull station. **** Input usage inherently set to trouble.
1
Thermal and manual release usage devices generate an alarm condition.
2
Abort usage devices will only generate an abort condition when initiated during a Pre-discharge
condition.
3
These features are only available with releasing operations.
4
8706 modules can only be assigned to addresses 1-60.
NOTE: When programming requires yes or no, press 1 for YES and 0 for NO.
The following table provides a description of the parameters that may be set for each device.
Parameter Description
Label Each device may have a forty character label assigned to it to describe the input. This label
will be displayed when the input becomes active.
Application The FireSmart detectors have internal algorithms that may be set for different environments.
A setting of “none” turns off the algorithms and allows the detector sensitivity to be set manually and verification to be selected.
Sensitivity This sets the level of smoke that will cause the device to generate an alarm. This is only
appropriate for smoke detectors. Norm Open Relay contact are normally open. EOL is required. This applies to 8702, 8703 and 8704. Norm Clos
Relay contacts are normally closed. No EOL is required. This applies to 8702, 8703 and 8704.
28
Page 33
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Parameter Description
ROR Rate of rise thermal alarm. This is used for the FireSmart detector and the thermal detector
when the temperature rises at a rate of 15 degrees/minute. Led off Used to disable the LED on the device so that it does not indicate polling. It will still flash red
for alarm. Pre-alarm Selected when an early warning of a fire alarm is required. The LED will flash yellow if the
device is in trouble. Verification This is selected to cause the device to go through the UL defined verification cycle to
eliminate false alarms.
The following table provides a description of the usages that may be set for each device.
Usage Description
Alarm This usage is selected for fire alarm causing devices. Waterflow Selection for devices connected to Waterflow sensors in sprinkler systems. Generates a non
silenceable alarm event. Sil. Waterflow If connected to Waterflow sensors in sprinkler systems but the alarm is silenceable. Trouble Activation of this device will cause a trouble event in the system. Supervisory Activation of this device will cause a supervisory event in the system. Panel reset An input with this usage will cause the panel to reset. Alarm silence An input with this usage will silence the alarm on the panel. Acknowledge An input with this usage will acknowledge the event on the system. Test An input with this usage will cause all the logic associated with a device─typically a duct
detector─to activate along with all its associated output zones. Input Group Each loop input device must belong to one and only one local input group. This is a way of
allowing multiple detectors in one area to be grouped together to provide a common action.
Editing an Input Group Configuration
An input group’s configuration may be edited as follows:
Action Result
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Select “Groups”.
4. Select “Input Groups”.
5. Enter the input group number. The user may now navigate through screens
that allow setting of the various parameters for a group.
Input Groups
The loop devices must be grouped together (a group of one is possible). There are 240 input groups on the MPC-6000 and MPC-7000 that can be programmed as one of the following types:
Group Type Description
Fire Typical fire group. Activates selected output zones when an event occurs in the
group.
Counting Used for Counting Zone operation. In this mode of operation, at least the number of
devices given on the Activation Threshold screen must be active before the corresponding Output Zones will activate.
29
Page 34
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Group Type Description
NFPA 72 National Fire Alarm Code requires the following for Counting Zone:
1) There shall be at least two automatic detectors in each protected space.
2) The alarm verification feature shall not be used.
3) The detectors shall be installed at spacing determined in NFPA 72, when used to initiate fire safety functions or fire extinguishing systems.
4) The detectors shall be installed at a linear spacing not more than 0.7 times the linear spacing determined in NFPA 72, when used to activate public mode notification.
PAS Positive Alarm Sequence group as defined by NFPA. The alarm signal from a device
selected for positive alarm sequence operation will activate selected output zones of the PAS Group. The signal shall be acknowledged within 15 seconds in order to initiate the alarm investigation phase. If the signal is not acknowledged within 15 seconds then selected output zones of the associated Timeout Group will activate. The Timeout Group must be a Fire Group that activates an audible NAC.
The investigation phase (Timer) can be programmed from 60 to 180 seconds. If the system is not reset during this period, the Timeout Group will activate.
If a second PAS alarm occurs during the investigation phase, the selected output zones of the associated Timeout Group will activate.
If PAS is disabled, then the initial alarm signal will activate the selected output zones of the PAS Group and the output zones of the associated Timeout Group.
Pre-Signal Pre-signal as defined by NFPA allows initial Fire Alarm signals to sound only in
department offices, control rooms, fire brigade stations or other constantly attended central locations for which human action is subsequently required to activate general alarm or a feature that allows the control equipment to delay the general alarm by more than 1 minute after the start of alarm processing. If there is a connection to a remote location, the transmission of the alarm signal to the supervising station shall activate upon the initial alarm signal.
On the initial alarm, the selected output zones associated with the pre-signal group will activate. The delay of activation of additional output zones can be programmed from 60 to 180 seconds. If the system is not reset during this period, the output zones of the associated Timeout Group will activate. The Timeout Group must be a Fire Group.
Wild Card
Wild Card zone for non-fire operation allows monitoring of critical functions with logging
or control function. The event will latch and will not reset until the panel is reset. Releasing Group
This group type is the only input group that can activate the releasing circuit. When
this type is selected, the following parameters have to be configured:
- Releasing Group Threshold setting: This sets the threshold to initiate a
Pre-Discharge condition and can be selected from the following: Any 1
alarm, Any 2 alarms, Any 1 smoke detector and Any 1 thermal device.
- Releasing Circuit Activation: This selects the releasing circuit that will
activate when this Group is initiated.
- Releasing Circuit Code Selection: This screen allows the user to select
the type of pre-defined signal for the releasing NAC type to play if the
condition has been met. 1
st
Alarm, Discharge and Pre-discharge are
defaulted to activate Steady ON.
Output Zone:
-
This sets the output zones that the releasing group activates. NOTE: Any alarm condition that is initiated from the releasing input group will generate a general alarm condition.
Notes:
1. Zone Coding signals are not allowed to be associated with the Releasing Input Group.
2. When the Releasing Input Group utilizes the predefined signal codes on its releasing NAC outputs, all other Input Group type NAC outputs must be set to Steady On only.
3. Releasing should be enabled before selecting a releasing group.
4. 8701, 8702, 8703 and 8704 devices assigned to “Drill,” “Alert” or “Recall” system groups should have their usage set to supervisory.
30
Page 35
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Pre-alarm, supervisory and trouble bell codes must always be Steady On. For Counting Zone, the 1st Alarm bell code can be a predefined bell code, but it is only allowed to be Steady On if a releasing group is in the configuration.
st
For a Releasing Input Group, the 1
Alarm and Pre-Discharge can use predefined bell codes. No zone coding is allowed, and bell codes of all other input groups must be Steady On if a releasing group is in the configuration. NAC1 must have a 1 Discharge output type and NAC2 must have a Discharge output type. 1st Discharge, Discharge output types are only allowed to be in Output Zone 1.
st
Alarm/Pre-
Alarm/Pre-
The
Discharge bell code must be Steady On.
An input Group may also be configured to activate 1 or all of the 255 Output Zones.
Editing a System Group Configuration
There are a number of system groups, which may be configured as follows:
Action Result
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Select “Groups”.
4. Select “System Groups”.
5. Select the system group to be edited. The user may now navigate through screens that allow
setting the bell codes that the system group will use and the outputs which this system group will activate.
Configuring the NACs
There are a number of parameters that may be configured for the NACs.
Action Result
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Select “Outputs”.
4. Select “NACs”.
5. Enter the number of the NAC to be configured. The user may now navigate through screens
that allow setting the parameters of the NACs.
The parameters that may be set for the NACs are shown in the following table.
Parameter Description
Notification device type Either Audible, Strobe or Horn/Strobe. Output Zone Which output Zone activates this NAC. Output Set to indicate if the NAC is operating or not. On Delay Delay in seconds before the NAC turns on. Special Feature This selection allows the NAC to be configured for special application.
- Always ON: Select YES only if the NAC circuit is used to power the output of the 8706.
Wiring Class Select YES if NAC wiring is configured as Class A.
31
Page 36
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Parameter Description
Output Type Alarm Silenceable, Alarm Non-Silenceable, Pre-Alarm Silenceable,
Pre-Alarm Non-Silenceable, Trouble Silenceable, Trouble Non­Silenceable, Supervisory Silenceable, Supervisory Non-Silenceable, Releasing NAC. Note:
Use Trouble or Supervisory NAC output type only where required. If the Output Type Releasing NAC is selected, another screen will open to prompt the user if this particular releasing NAC will activate on 1 Alarm, Discharge or Pre-Discharge. Select ON if the NAC is to activate. When 1 is selected, all other NAC outputs must be configured as Steady-On only bell code.
st
Alarm/Pre-Discharge NAC
st
Configuring the Remote Relays (SRUs)
Following are the steps that need to be followed to configure the remote relay units.
Action Result
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Select “Outputs”.
4. Select “SRUs”.
5. Enter the address of the relay to be configured
6. Enter a “1” to enable the relay. The user may now navigate through screens that allow setting the parameters of the address relay.
The relays in the serial relay unit must be logically connected to an output zone in order to operate. When the selected output zone becomes active, the relay will become active based on the type of activation that has been selected, i.e., alarm, trouble, supervisory, pre-alarm. Set the output type and the output zone that will activate this relay.
Configuring the Remote LEDs (SLUs)
Following are the steps that need to be followed to configure the remote LED units.
Action Result
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Select “Outputs”.
4. Select “SLUs”.
5. Enter the address of the LED to be configured.
6. Enter a “1” to enable the LED. (Use the * and #
buttons to navigate left and right.)
The LEDs in the serial LED unit must be logically connected to an output zone in order to activate. When the addressed output zone becomes active, the LED will become active depending on the type of activation that has been selected, i.e., alarm, trouble, supervisory, pre-alarm. Set the output type and the output zone that will activate this LED.
The user may now navigate through screens that allow setting the parameters of the address LED.
32
Page 37
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Configuring the Remote LCDs (RDC-2s)
Following are the steps that need to be followed to configure the remote LCD units.
Action
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Use “Cmor” and select “RS-485 NW”.
4. Select “RDC
5. Enter a “1” in the map to enable the RDC at
the selected address. (Use the * and # buttons to navigate left and right.)
6. Press Bsav to save the selection.
Annciatrs”.
Configuring the Panel Relays
Panel relays are set by default as follows:
Relay 1: Alarm, Non-silenceable, no on- or off- delays Relay 2: Pre-alarm, Non-silenceable, no on- or off- delays Relay 3: Supervisory, Non-silenceable, no on- or off- delays Relay 4: Trouble, Non-silenceable, no on- or off- delays
In the default configuration, any Alarm, Trouble, etc., on the system will activate the corresponding relay.
Following are the steps that need to be followed to configure the panel relays differently than the default settings.
Action
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Select “Cmor”.
4. Select “Cmor”.
5. Select “Prgm Relays”.
6. Follow the screen prompts to set up the panel relays.
7. Press Bsav to save the selection.
These are the parameters that need to be set when configuring panel relays.
Installed Select yes to program independently. Output Zone Enter the number of the output zone that activates this circuit. Output Type Select the type of event and whether or not it can be silenced. Delay Timers Allows the setting of activation and deactivation times for the relay. The On delay
sets the time after the event that the relay will activate. The Off delay determines
how long it will stay on after it activates. The times are in seconds. NOTE: When a programmable relay is set for “AC Power Fail,” the system trouble group must activate the same output zone assigned to the relay.
33
Page 38
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Installing the DACT
Setting the System Reporting Type must be selected before installing the DACT. See
page 36. Following are the steps that need to be followed to install the DACT.
Action
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Select “Outputs”.
4. Use “Cmor” and select “Option Mods”.
5. Select “
6. Follow the screen prompts to set up the DACT.
DACT CFG”.
These are the parameters that need to be set when installing the DACT.
Test Time The time that the DACT will regularly call in to the central station to check the
connection. Select the line number The DACT can connect to two lines. Select which one is to be configured. Select the
dialing method
The DACT can dial using pulse or tone. Select which is needed.
Configuring the DACT Accounts
Following are the steps that need to be followed to configure the DACT Accounts.
Action
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Select “Outputs”
4. Use “Cmor” and select
5. Select “DACT ACCTS”.
6. Follow the screen prompts to set up the DACT Accounts.
“Option Mods”.
The following information is set up for the two possible DACT accounts.
Format This is the format that is used to report to the Central station. The options are
SIADCS8, SIADCS20, ADEMCO, 4/2-1400, 3/1-1400, 3/1-2300, 4/2-2300. Number of attempts Must report event type
Account number CIC prefix The prefix used by the DACT to dial through a PBX to access a line. Phone number
This is the number of times that the DACT will attempt to dial the account before
trying the next account.
When selected yes, the DACT must report these events to the selected account “x”.
If not selected and the DACT cannot report the event to account “x” for whatever
reason, it will try a different account “y”. If it successfully reports it to account “y”, it
will not go back to account “x” and try again. If Must Report is selected, it will keep
trying to report to account “x” until it is successful, whether or not it has already
successfully reported it to a different account.
The number to identify the account at the central station.
The phone number which the DACT will dial for this account.
34
Page 39
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Configuring the Coder
Following are the steps that need to be followed to configure the Coder.
Action
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Select “Outputs”
4. Select “Cmor”
5. Select “Cmor”.
6. Follow the screen prompts to set up the Coder.
twice
and select
“Option Mods”.
These are the parameters that need to be set when configuring the coder.
NOTE: The Coder is not available if Releasing Group is being used.
None If none is selected, only the predefined bell codes (Steady on, March Time,
Temporal, California, Three-pulse Temporal and Alert) may be selected for the
Alarm Bell Code for any input group. Zone Coder If selected, coder may be selected for the Alarm Bell Code for any input group in
addition to the predefined bell codes. Master Coder If selected, this code will be used for the Alarm Bell Code for all input groups.
Predefined and user configured bell codes will not be available for the Alarm Bell
Codes. Play after Code Master Code These are the digits used in the Master Code. Up to four code digits may be
Rounds Number of rounds of a bell code that will be played (3, 4 or Continuous). If “3
This is the bell code (MTB, Temporal, Steady, None) that will be played after the
Master Code.
entered. Zero is used as an “end of code” indicator. For example, to set the code to
2-4, enter “2” for the first digit, “4” for the second and “0” for the third.
rounds” is selected, the bell code will play three times then will change to the code
selected in Play after Code. If “Continuous” is selected, the bell code will play
continuously until silenced.
Setting System Timers
Following are the steps to set system timers.
Action
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Use “Cmor” and select
4. Use “Cmor” and select “Timers”.
5. Use “Cmor” to select the timers to be set.
“Sys Params”.
Below is a list of the timers and their functions:
Parameter Description
Alarm Silence Inhibit The period of time that the alarm will sound before it can be silenced. Panel Reset Inhibit The period of time that the panel is prevented from being reset after an
alarm is annunciated. Trouble Reminder The time period before a trouble will come back to remind the installer. Quick test NAC time The length of time that the NACs will sound in Quickest. Quick test exit The time that Quick test will exit automatically after inactivity.
35
Page 40
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Configuring the City Tie Activation
Setting the System Reporting Type must be selected before configuring the City Tie
activation. See page 36. The City Tie, once installed, may be activated by a trouble, a supervisory or both.
Action
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Use “Cmor” and select
4. Select
5. Use the screen to select which activation is required and press “Bsav”.
“CityTrbActvn”.
“Sys Params”.
Setting Trouble Ack Required
Troubles and supervisory events are normally self-restoring; however, if it is required that they need to be acknowledged before clearing, follow the procedure below:
Action
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Use “Cmor” and select
4. Select “Trb Ack Req”.
5. Press 1 for yes and then press “Bsav”.
“Sys Params”.
Setting the System Reporting Type
Depending on the type of system configured, the panel will report power failure in different periods of time. (No reporting for Local, Auxiliary, 6 hours for Central Station and 15 hours for Remote Station.)
Action
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Use “Cmor” and select
4. Select “System Type”.
5. Use the screen to select which system type is required and press “Bsav”.
“Sys Params”.
Copying the Primary to the Backup
Once the primary configuration has been checked out and is running correctly, it is a good idea to copy the configuration into the backup. This is accomplished as follows:
Action Result
1. Select “Edit”.
2. Select “Copy Primary”.
3. Select “Cyes” to start the copy. The screen will indicate the copy is in progress.
It will take several minutes.
36
Page 41
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Printing the Primary/Backup Configuration (For Diagnostics Test Only)
The primary/backup configurations may be printed via the printer port on the panel.
Action Result
1. Select “Print Configs”.
2. Select “Print”.
3. Select “Print Primary” or “Print Backup”. The configuration will be printed on the printer
connected to the panel printer port.
Validating the Backup Configuration
The validation process will check to see that the configuration in the backup memory is correct.
Action Result
1. Use “Cmor” and select
Display will show invalid settings in the
“Validate”.
The display will indicate running
configuration if found.
that the validity check is
Activating the Backup*
When the configuration is correct it may be made the primary configuration as follows:
Action Result
1. Use “Cmor” and select
2. Select “Cyes” to switch to the backup configuration.
“Activate”.
The display will show the swap in progress.
*Refer to Programming Concepts on page 9 for a description of Primary and Backup configurations.
Hard Reset
This function re-initializes the panel in the same way as power up:
Action Result
1. Use “Cmor” and select “Hard Reset”. The panel will re-initialize.
Changing Access Passwords
The passwords used to access the Maintenance and Technician Levels may be changed as follows:
Action
1. Use “Cmor” and select ”Change PWs”.
2. Change the maintenance and technician passwords as needed and press “Bsav”.
37
Page 42
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Enabling the Network Connection to the Panel
This setting is used when the control panel is to be connected to a network. The networking communications in the panel must be enabled as follows:
Action Result
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Press “Cmor” twice to select “Network Setup”.
4. Select “1” to install the network or “0” to remove the network setting.
When “1” is selected, Dnxt appears so other network settings can be made.
Setting the Node Number
If the panel is networked, it must have its network node number set as follows:
Action Result
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Press “Cmor” twice to select “Network Setup”.
4. Select “Dnxt”. Type in the Node number. Be certain to enter leading zeros for nodes 1-9.
A maximum of 99 nodes can be entered.
5. Select “Dnxt” to continue to next setting or “Bsav” to save the setting.
When “Dnxt” is selected, the screen for the printer setting displays. When “Bsav” is selected, the Network Connection screen displays.
Setting the Printer*
If the printing of events from this node printer is required on the network, then it must be set as follows:
Action Result
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Press “Cmor” twice to select “Network Setup”.
4. Select “Dnxt”.
5. Select “Dnxt”.
6. To Print Events for the node, select “1” for yes or “0” for no.
7. Select “Dnxt” to continue to next setting or “Bsav” to save the setting.
*For an MPC-6000 / MPC-7000, the default setting for the printer is OFF (Diagnostics test only). For an RND-2, the default setting for the printer is ON.
When “Dnxt” is selected, the screen for the Total Number of Nodes displays. When “Bsav” is selected, the Network Connection screen displays.
38
Page 43
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Setting the Total Number of Nodes
Follow the steps below to set the total number of nodes (panels, RNDs and printers) in the network.
Action Result
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Press “Cmor” twice to select “Network Setup”.
4. Select “Dnxt”.
5. Select “Dnxt”.
6. Select “Dnxt”. The setting for the Total Number of Nodes
displays.
7. Type in the Total Number of Nodes. Be certain to enter leading zeros if the total
number of nodes is from 1-9. A maximum of 99 nodes can be entered.
8. Select “Dnxt” to continue to next setting or “Bsav” to save the setting.
When “Dnxt” is selected, the screen for Accepting/Sending Global Commands displays. When “Bsav” is selected, the Network Connection screen displays.
Enabling Accepting/Sending Global Commands
Allows the panel to accept/send commands from a network annunciator, i.e., RND-2.
Action Result
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Press “Cmor” twice to select “Network Setup”.
4. Select “Dnxt”.
5. Select “Dnxt”.
6. Select “Dnxt”.
7. Select “Dnxt”. The setting for Accepting Global Commands
displays.
8. Select “1” to enable the panel to accept global commands or select “0” and the panel will not accept global commands.
9. Press the # key to move to the setting for sending global commands.
10. Select “1” to enable the panel to send global commands or select “0” and the panel will not send global commands.
11. Press the * key to move back to the setting for accepting global commands, if desired.
12. Select “Bsav” to save the setting. When “Bsav” is selected, the Network
When “1” is selected, the panel can accept global commands.
When “1” is selected, the panel can send global commands and control other panels.
Connection screen displays.
39
Page 44
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Assigning a Message to a Network Link
This setting only appears when a network connection has been enabled. The network link in the panel can be assigned a text message as follows:
Action Result
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Press “Cmor” twice to select “Network Link”.
4. Type in the number of the node to which this panel will report.
5. A custom message can be assisgned to this link. Follow the instructions on page 5 of this manual for entering alphanumeric characters.
6. Press Bsav to save the settings.
The default setting is 01. The maximum setting is 99. Assignments can be made in the Input Group Configuration to have this link observe or control activity.
Creating the Notify Link and the Observe Link
This setting is used to create the Notify link and Observe link.
Action Result
1. Select “Edit”.
2. Select “Manual Pgm”.
3. Selectr “Groups”.
4. Select “Input Groups”.
5. Select “Fire”, then Dnxt.
6. Select “Coding”, then Dnxt.
7. Select “Output Zones”, then Dxnt.
8. Type in the number of the link that you wish this input group to notify.
9. Select Dxnt .
10. Type in the number of the link that you wish this input group to observe.
11. Select Bsav to save the setting.
Be certain to enter leading zeros if the total number of nodes is from 1-9. The maximum node number is 255; 0 = none.
Be certain to enter leading zeros if the total number of nodes is from 1-9. The maximum node number is 255; 0 = none.
Exiting the Technician Level
Follow the steps below to exit the Technician Level and return to User Level:
Action Result
1. Use “Cmor” and select ”Exit Tech LvL”. The Display will return to the user level.
40
Page 45
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
APPENDIX A: GLOSSARY
Abort Condition. Condition in which the abort function is pressed during 1st-Alarm (IRI type only) or during Pre-Discharge condition.
Abort Function. Defines an event that is manually initiated during the proper releasing event sequence that will indefinitely prevent the releasing circuit from activating.
AC Power Fail. Refers to a condition in which AC power loss is detected by the system.
Agent Release Delay. Same as Pre-Discharge Delay.
Alarm Signal. A signal indicating an emergency requiring immediate action, such as an alarm for fire from a manual station, a waterflow alarm, an automatic smoke detector, etc.
Alarm Silence Inhibit. An option that prevents a human operator from silencing the notification
appliances for a preset period of time.
Alarm System. A combination of compatible initiating devices, control units and notification appliances designed and installed to produce an alarm signal in the event of a fire or other condition, as designed.
Alarm Verification. A preset option that causes the control unit to verify alarms originated by smoke detectors before indicating an alarm.
Annunciator. A remotely located, electrically powered display, separate from the control unit, containing LCDs, LEDs or lamps to indicate the states of the fire alarm system.
Audible Signal. A sound made by one or more audible notification appliances, such as bells or horns, in response to the operation of an initiating device.
Authority Having Jurisdiction (AHJ). The organization, office, or individual responsible for approving equipment, installation or procedures.
Auxiliary Relays. Control relays that energize only during alarm conditions that are used to either apply power to or remove power from other equipment during an alarm condition.
City Tie. Provides connections for shunt, local energy, central station or remote station.
Class A Circuit. An initiating device or notification appliance circuit within which all components
remain fully functional, even though a single open or ground exists in the circuit.
Class B Circuit. An initiating device or notification appliance circuit within which some or all components may be disabled when a single open or ground exists in the circuit.
DACT. Digital Alarm Communicator Transmitter (see NFPA 72).
Detector - FireSmart™. An intelligent fire detector that blends photoelectric, thermal and neural network technologies for superior protection without false alarms.
Detector - Smoke, Photoelectric Type. A detector employing the photoelectric principle of
reflection or obstruction of light by smoke.
Detector - Thermal Type. An addressable thermal sensor that is programmable as either a fixed temperature (135° F) or as a rate of rise detector.
41
Page 46
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Discharge Condition. Refers to the condition in which the releasing circuit is activated. Discharge Output Type. Defined as the output type associated with a releasing group and
activated if the panel proceeds to the Discharge event.
Discharge Period. Defined as the time period in which the releasing circuit will remain active
before automatically deactivating.
Enable / Disable. Refers to the state of individual circuits (inputs and outputs) or logic functions
regardless of the presence of its corresponding modules.
EOLR. End-of-line resistor, used for termination purposes. FACP. Fire Alarm Control Panel. General Alarm. A term usually applied to the simultaneous operation of all the notification
appliances on a system.
Ground Fault. A trouble condition in which a low resistance has been detected between the
system wiring and conduit ground.
Group 1st –Alarm. Refers to the condition in which the releasing input group meets at least
one of the threshold requirements to activate the releasing circuit. This does not refer to the pre­alarm condition detected by the smoke detector.
Initiating Device. A manually or automatically operated device such as a manual pull station,
smoke detector, heat detector, waterflow switch or tamper switch.
Input Group. Detectors and devices are grouped together for convenience into input groups.
This will usually represent an area in the building, for instance “the first floor”.
Labeled. Equipment or materials to which have been attached a label, symbol, or other
identifying mark of an organization acceptable to the authority having jurisdiction and concerned with product evaluation, that maintains periodic inspection of the production of such labeled equipment or materials, and by whose labeling the manufacturer indicates compliance with appropriate standards or performance in a specified manner.
Listed. Equipment or materials included in a list published by an organization acceptable to the
authority having jurisdiction and concerned with product evaluation, that maintains periodic inspection of production of listed equipment or materials, and whose listing states either that the equipment or material meets appropriate standards or has been tested and found suitable for use in a specified manner.
Manual Release Function. Defines an event that is manually initiated in which the releasing
circuit activates regardless of the condition of the system. This function is ignored if the releasing circuit has already activated and the Discharge Period has elapsed.
NEC. National Electrical Code, also published as NFPA 70. National Fire Alarm Code. Also published as NFPA 72. Notification Appliance. An electrically operated appliance used to indicate the system status,
such as a bell, horn, strobe light or speaker.
Notification Appliance Circuit (NAC). A circuit to which notification appliances are connected.
42
Page 47
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Output Zone. There may be 255 output zones. Normally used to specify an area of the building
for signaling. The output devices such as notification appliances, audible bases, relay bases, SLUs and SRUs are connected to these output zones so that when the output zones become active the devices will become active.
PAS. Positive Alarm Sequence group as defined by NFPA. The alarm signal from a device
selected for positive alarm sequence operation will activate selected output zones of the PAS Group. The signal shall be acknowledged within 15 seconds in order to initiate the alarm investigation phase. If the signal is not acknowledged within 15 seconds then selected output
zones of the associated Timeout Group will activate. The Timeout Group must be a Fire Group. Power Supply. That portion of the fire alarm control unit that provides the power needed to
operate all control unit modules, as well as that needed to operate all electrically powered initiating devices and all notification appliances.
Pre-Alarm. A pre-alarm condition is annunciated by pre-alarm LEDs and buzzers on the control
panel and LCD annunciators and remote processors. The LEDs flash and buzzers are on steady until acknowledgment.
Pre-discharge Condition. Refers to the condition in which the Pre-discharge delay has been
activated.
Pre-discharge Delay. The time period delay before the activation of the releasing circuit when the releasing condition is met.
Pre-Signal. Pre-signal as defined by NFPA allows initial Fire Alarm signals to sound only in
department offices, control rooms, fire brigade stations or other constantly attended central locations for which human action is subsequently required to activate general alarm or a feature that allows the control equipment to delay the general alarm by more than one minute after the start of alarm processing. If there is a connection to a remote location, the transmission of the alarm signal to the supervising station shall activate upon the initial alarm signal.
Programming Tool. Refers to an external proprietary software package that allows the user to
program the panel (CIS-4 for the MPC-6000 / MPC-7000 panels).
Quick Test. A term pertaining to the test mode of the system that automatically resets after a
service tech tests initiating devices.
Releasing Group Threshold. Defined as a set of conditions which the input releasing group has to meet in order to initiate a pre-discharge event.
Releasing Input Group. The only input group type that can be associated with the releasing circuits.
Releasing NAC. NAC associated with releasing input group type that annunciates Releasing
Group 1st Alarm and Pre-discharge associated with the releasing application.
Reset Condition. Condition in which the panel is forced to return to its normal state, usually
performed by pressing the “SYTEM RESET” button after all known events / conditions are
cleared.
43
Page 48
MPC-6000 / MPC-7000 / RND-2 PROGRAMMING MANUAL
Signaling Line Circuit (SLC). A circuit to which intelligent devices are connected. Also called a
detection loop. A detection loop in the case of the MPC-6000 and MPC-7000 may contain up to 252 detectors or devices, all of which may have outputs. Each detection loop will be driven by an FDLC (Faraday device loop card).
Supervisory Alarm. A signal indicating the operation of a supervisory device. Supervisory Device. A device that monitors the condition of a sprinkler system such as a gate-
valve switch, water level switch, low pressure switch, low temperature switch or fire pump monitor.
Trouble Signal. An audible signal indicating trouble of any nature, such as a circuit break or
ground, occurring in the device or wiring associated with a fire alarm signal.
Waterflow Switch. An assembly approved for service and so constructed and installed that any
flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler head will result in activation of this switch and subsequent indication of an alarm condition.
Wild Card. Wild card zone for non-fire operation allows monitoring of critical functions with
logging or control function. The event will latch and will not reset until the panel is reset.
Zone. A designated area of a building. Commonly, zone, is interchanged with initiating device
circuit.
44
Page 49
MPC-6000/MPC-7000/RND-2 PROGRAMMING MANUAL
APPENDIX B: REFERENCES
• NFPA 72: National Fire Alarm Code (National Fire Protection Association)
• NFPA 70: National Electrical Code (Delmar Publishers)
• MPC-6000 / MPC-7000 / RND-2 Faraday Fire Alarm Control Panel Owner's
Manual, P/N 315-447309
• Faraday web site: http://www.faradayfirealarms.com
45
Page 50
MPC-6000/MPC-7000/RND-2 PROGRAMMING MANUAL
APPENDIX C: COMPATIBLE DEVICES FOR SIGNALING LINE CIRCUITS (FDLC)
Model Description
8700-S Single action pull station 8700-D Dual action pull station 8700-M Metal manual pull station 8701 Single input mini monitor module 8702 Single input monitor module 8703 Dual input monitor module 8704 Monitor module with single input and relay 8705 Conventional zone input module 8706 Intelligent Point Control 8710 Faraday photo detector 8712 Faraday thermal detector 8713 Faraday FireSmart detector with algorithms 8726C1 Ceiling mounted intelligent LED 8726W1 Wall mounted intelligent LED
1
The 8726(C/W) is a device that is assigned to an output zone only. When an input group that is “connected to” its output zone becomes active, the 8726 will blink red, provided the event that occurred in the group is the same as the Output Type selected for the 8726W.
46
Page 51
MPC-6000/MPC-7000/RND-2 PROGRAMMING MANUAL
APPENDIX D: TYPICAL PROGRAMMING MODEL
One Hazard (Releasing Zone) Area and One Fire (Building Fire Protection) Area
Input Devices
Manual Release Switch
Abort Switch
Input Devices
Manual Pull Stations
Releasing Input
Group 1
General Alarm
Group
Output Zone 1
Output Zone 2
Any Alarm condition from the releasing input group will annunciate a general
alarm condition
NAC1
1st Alarm/
Pre-Discharge
Coded or
Steady Only
NOTE: The General Alarm Input Group must have an audible NAC Association.
47
NAC2
Discharge
Steady-On or
Strobe Only
NAC3 Alarm
Steady-On or
Strobe Only
NAC4
Alarm or
Trouble
Steady-On or
Strobe Only
Page 52
MPC-6000/MPC-7000/RND-2 PROGRAMMING MANUAL
48
Page 53
Page 54
Page 55
Page 56
Siemens Building Technologies, Inc. 8 Fernwood Road • Florham Park, NJ 07932 Tel: (973) 593-2600 • Fax: (973) 593-6670 Web: www.faradayfirealarms.com