The LW-401 is a microprocessor based fire
and life safety system with four conventional
initiating device circuits (up to 8 with the
addition of the optional LWZE-4A or
LWZE-8A zone expander). All basic alarm
and trouble functions are annunciated and
controlled from the LW-401 front panel (See
Figure 1) which consists of:
• Seven segment numeric display
• Four user-control switches
• Red and yellow LEDs for each of the
eight zones
• Six system status LEDs
Key features of the LW-401 are:
• 2 Class B (Style Y) +24 VDC notification
appliance circuits (NACs) rated at 1.5
amps each.
LW-401 Operation, Installation, and Maintenance ManualLW-401
Figure 1
LW-401 Control Panel
• Alarm Coding (March Time, Temporal, or
Simplified Zone Code) and NonSilenceable output option.
• Easy-to-use built-in diagnostics.
• 24 hour re-sound for Alarm and Trouble
conditions that are not restored to normal
after being acknowledged.
• Optional LWZE-8A module converts the
system to four Class A (Style D) Initiating
Device Circuits and two Class A (Style
Z) Notification Appliance Circuits and
also provides four additional Class A
(Style D) Initiating Device Circuits.
• Optional LWZR-8 module provides eight
programmable Form C relays.
• Optional LWRA-8B/W module provides
remote annunciation for eight zones with
16 LEDs. Up to two may be used.
• Optional LWCT-1 module provides
Leased Line/Municipal Tie connection.
1
Page 5
LW-401
Operation, Installation, and Maintenance Manual
Standard Components
A standard four zone LW-401 has one
module—the main board. An expander
board is added to provide four additional
zones, when needed.
MAIN BOARD
The Main board of the LW-401 contains the
intelligence for the system and performs all
of the input/output processing as listed
below:
• Two supervised Notification ApplianceCircuits provide 24 VDC at 1.5 amps.
Each circuit operates Class B (Style Y)
and can be independently programmed
to operate a number of different ways
(Non-Coded, March Time, Temporal, or
Simple Zone Code).
• Two Form C relays rated at 30 VDC at
1 amp resistive, 30 VAC at 500mA
resistive. These relays are for Alarm and
Trouble operation.
• A dual mode battery charger that
provides float and constant current
modes of charging sealed lead acid
batteries (15 Amp-Hour maximum).
• Nonvolatilestorageofsystem configu-ration so that configuration remains
intact during loss of system power.
• Four supervised power limitingInitiating Device Circuits. Each circuit
operates Class B (Style B) and can be
independently programmed to operate
as an Automatic Alarm input, a Verified
Alarm input, a Supervisory input, or a
Generic input. Each initiating device
circuit can use an unlimited number of
manual shorting-type devices.
• CPU Fail LED.
DISPLAY
The LW-401 display, shown in Figure 2,
provides the user with the necessary interface to operate the fire detection system in
Normal, Test, and Program modes.
2
Figure 2
LW-401 Front Panel
Page 6
FRONT PANEL FUNCTIONS
The front panel of the LW-401 is comprised
of a seven segment display, function keys,
and LEDs. Their functions are described
below (Refer to Figure 2):
The LEDs
The green Power LED remains on steady when
AC power is connected and pulses when the unit
is operating from batteries.
The red Alarm LED pulses when an alarm is
detected until it is acknowledged. Then it remains
on steady until the alarm condition is reset.
The yellow Supervisory LED pulses when a
supervisory condition is detected until it is acknowledged. Then it remains on steady until the
supervisory condition is reset. Note that the
pulsing rates of the trouble and supervisory
conditions are different.
The yellow Trouble LED pulses when a trouble
condition is detected until it is acknowledged.
Then it remains on steady until the trouble
condition is reset. Note that the pulsing rates of
the trouble and supervisory conditions are
different.
The yellow Bypass/Alarm Silence LED is on
steady when a zone in the system is bypassed
and it pulses when a notification circuit is silenced. When an initiating device zone is bypassed, the appropriate yellow zone trouble LED
is on.
The Test/Program LED is on steady when the
Test mode is selected and it pulses when the
Program mode is selected.
The Sounder
CONDITIONRATE OF PULSATION
SYSTEM ALARMSounds steady
TROUBLEPulses at 50% duty cycle
SUPERVISORYPulses at 25% duty cycle
CPU FAILUREPulses once every 2 seconds
LW-401 Operation, Installation, and Maintenance ManualLW-401
CODEDESCRIPTION
1AC power fail
2NAC 1 trouble
3NAC 2 trouble
4Ground fault
5Municipal tie fault
6Battery fault
7System Configuration fault
8Auxiliary port fault
9Outputs bypassed
0Hardware failure
troubles, and supervisory conditions. In general
the LEDs change from pulsing to steady to
indicate that the condition was acknowledged.
The SILENCE key silences the notification
appliance circuits that are configured as
silenceable. Pressing the SILENCE key a
second time causes the NACs to re-sound.
The RESET key resets the LW-401 and all of
the smoke detectors.
The DRILL key activates all of the notification
appliance circuits.
The yellow zone status LEDs indicate
a trouble or supervisory condition existing on a
particular input. Pulsing indicates the condition
was not acknowledged; on steady indicates it
was acknowledged.
The seven segment display indicates the
various system troubles and the programming and
test modes. The numbers and symbols that appear
on this display are described in the following chart.
The red zone status LEDs provide an
indication of the status of a particular zone.
Pulsing indicates an alarm condition in that
zone. When the alarm is acknowledged, the
LED remains on steady until the panel is reset.
3
Page 7
LW-401
Operation, Installation, and Maintenance Manual
4
Page 8
2
INSTALLATION
Unpacking the Equipment
The LW-401 is shipped in two cartons;
one of the cartons contains the LW-401
enclosure. The other carton contains the
LW-401 electronics, the transformer, and
the mounting hardware. Follow the proce-
dure below to unpack the LW-401 equipment.
LW-401 Operation, Installation, and Maintenance ManualLW-401
Remove the packing material, and
inspect the electronics for damage.
Note: If the PC board is damaged,
contact the shipping carrier
immediately to report the damage.
1. Locate and open the shipping carton
containing the LW41-EN enclosure.
Remove the packing material and inspect
the enclosure for damage.
Note: If the enclosure is damaged,
contact the shipping carrier
immediately to report the damage.
2. Locate and open the shipping carton
containing the LW-401 electronics.
3. Check that the following items are inside
the carton:
• Mounting hardware for the LW41-MB
and transformer
• Main board
• Power transformer
Note: If any of the above items are
missing, contact the distributor
from whom you ordered the unit.
Figure 3
LW-401 Enclosure
5
Page 9
LW-401
Operation, Installation, and Maintenance Manual
Installing the Control Panel
Remove all system power before
installation, first battery and then AC.
(To power up, connect the
AC first, then the battery.)
All wiring must comply with
national and local codes.
Install the LW-401 control panel by following
the steps listed below.
1. Install the enclosure. Fasten the
enclosure securely to a clean, dry, shock
and vibration free surface. Consider the
following placement factors when
mounting the enclosure: height as it
relates to the front panel, weight and
size of the enclosure, and local mounting
codes. Refer to the
and Power Limited Wiring Instructions,
P/N 446107, for further information.
LW41-EN Installation
2. Fasten the power transformer to the
inside of the enclosure. Mount the
transformer on the four studs in the
upper left-hand corner of the LW41-EN
enclosure, as shown in Figure 4, using
the hardware provided.
3. Pull all field wiring into the enclosure.
Dress the wiring to the approximate
location to which it will go on the
LW41-MB.
4. Install the PC Board mounting metal
hex standoffs and plastic spacers.
Mount the six PC Board metal hex standoffs and two plastic round spacers, as
shown in Figure 5.
5. Install the Main board. Mount the Main
board to the standoffs in the center of
the enclosure (Refer to Figure 6).
a. Fasten two of the six screws provided
in the PC board mounting hardware in
the two bottom metal hex standoffs
Figure 4
Transformer Mounting
6
Figure 5
Mounting the Standoffs and Spacers
Page 10
labeled A in Figure 6, leaving a 1/4
inch gap between the standoff and
the head of the screw.
b. Place the slots on the bottom of the
LW41-MB on the two screws.
c. Secure the board in place by fasten-
ing the remaining four screws labeled
B to the metal hex standoffs.
d. Tighten the bottom two screws.
6. Optional modules. Refer to the specific
optional module Installation Instruction
sheet for the appropriate installation.
7. Before connecting any wire to its
screw terminal, refer to the Checkout
Procedure (page 27) and the LW-401
Connection Diagram, P/N 315-
096185FA. Prior to connecting wiring to
the Main board, ensure compliance to
maximum resistance in accordance with
the Field Wiring Checkout procedure,
page 27. Make sure that all power is off
before connecting leads.
8. Install power wiring. The LW-401 is
designed to operate from a 120 VAC, 60
Hz power source.
LW-401 Operation, Installation, and Maintenance ManualLW-401
Use a dedicated circuitbreaker. Wire in
accordance with local codes and/or
Article 760 of the National Electrical
Code, NFPA 72, latest edition.
a. Run Earth Ground from a suitable
source to the Earth Ground stud on
the chassis (See Figure 6 for the
location of the stud). Secure in place
using the two #8 nuts provided.
Check local requirements. Conduit is
not an acceptable ground.
b. Connect the 120 VAC source and the
BLACK transformer wire leads
to TB1.
c. Connect the BROWN transformer
wire leads to TB6.
Figure 6
Mounting the LW41-MB
7
Page 11
LW-401
Operation, Installation, and Maintenance Manual
8
Page 12
3
OPERATING MODES
LW-401 Operation, Installation, and Maintenance ManualLW-401
The LW-401 annunciates the following
modes of operation:
• Alarm
• Supervisory
• Trouble
• Normal
• Program/Test
Alarm
The LW-401 Display board lights the
appropriate red alarm LED and the general
ALARM LED to indicate to the user that an
Alarm condition exists on an initiating device
circuit (IDC).
Supervisory
A Supervisory alarm condition is indicated on
the LW-401 by the SUPERVISORY LED
flashing along with the appropriate yellow
zone LED.
Zone Trouble
A Trouble condition is displayed by a
flashing TROUBLE LED along with the
appropriate yellow zone LEDs.
For a further description of the system fault
codes, see System Fault Troubleshooting
(Table 3, page 25).
Normal
The Normal Mode is the absence of any
alarm, supervisory, or trouble condition. The
POWER LED is lit in Normal mode when the
system has AC power. The Alarm, Trouble,Supervisory, Bypass, and Zone status
LEDs are off, and the internal sounder is off.
Program/Test
The Program/Test Mode is used for system
configuration, test, and maintenance func-
When the LW-401 is in Program
tions.
Mode, it does not indicate alarm or supervisory conditions.
The System resets to normal mode after 2
minutes of front panel inactivity. When the
LW-401 is in the One Person System Test
Mode, it automatically returns to normal
mode after 20 minutes of inactivity.
Responding to a Fire Alarm
System Trouble (Fault) Codes
A number is displayed in the seven segment
display to indicate System Trouble (Fault)
Codes. They are:
Code 1: AC Power Fail/Brownout
Code 2: Notification Appliance Circuit 1
Code 3: Notification Appliance Circuit 2
Code 4: Ground Fault
Code 5: Municipal Tie Fault
Code 6: Battery Fault
Code 7: System Configuration Fault
Code 8: Auxiliary Port Fault
Code 9: Output Bypassed
Code 0: Hardware Failure
How the System Annunciates Fire Alarms
When a fire is detected on one of the initiating device circuits (IDCs), the LW-401
causes the System ALARM LED and the
appropriate Zone ALARM LED on the front
panel to flash and the system’s internal
audible to sound.
NOTE: Follow the response plan approved
by the local authority having
jurisdiction.
9
Page 13
LW-401
Operation, Installation, and Maintenance Manual
To Acknowledge Alarms
1. Unlock and open the door.
2. Press ACK to acknowledge (Block
Acknowledge) all alarms and other
conditions. The system ALARM and the
Zone ALARM LEDs on the front panel
stop flashing and remain on. The
system’s internal audible silences.
To Silence The Notification Appliance
Circuits
Press SILENCE after all alarms are acknowledged. The BYPASS LED on the front panel
flashes. The following four conditions are
checked before the Notification Appliance
Circuit(s) can be silenced:
1. If either NAC is programmed as NON-SILENCEABLE, it will not silence.
2. If the NAC inhibit timer has been programmed (see
Set System Timing
on
page 13), the NAC will not silence until
the inhibit time delay has expired (6
seconds to 5 minutes.)
3. If either NAC is programmed for temporal
coding, it will complete sending out
the entire current temporal round before
silencing.
4. If either NAC is programmed for ZONECODING, all coded rounds for each
zone in alarm must be sent out before
the NAC will silence.
Once the NACs have silenced, pressing the
SILENCE a second time causes the Notification Appliance Circuits to re-sound, and the
BYPASS LED to turn off.
Responding to a Supervisory
Condition
How the System Annunciates
Supervisories
When a supervisory condition is detected, the
system causes the SUPERVISORY LED and
one of the yellow Zone TROUBLE LEDs on
the front panel to flash and the system’s
internal audible to sound.
To Acknowledge Supervisories
1. Unlock and open the door.
2. Press ACK to acknowledge (Block
Acknowledge) all supervisory and other
conditions. The system SUPERVISORY
and the Zone TROUBLE LEDs on the
front panel stop flashing and remain on
and the system’s internal audible silences.
To Reset
Press RESET. (The system will not reset
until all alarms, supervisories, and troubles
are acknowledged and all conditions are
returned to normal.)
Responding to a Trouble Condition
How the System Annunciates Troubles
When a trouble is detected, the system
causes the TROUBLE LED and the appropriate yellow Zone TROUBLE LEDs on the
front panel to flash and the system’s internal
audible to sound. Troubles will clear prior to
Acknowledge if the condition which caused
the trouble returns to normal.
To Reset
Press RESET. (The system will not reset
until all alarms, supervisories, and troubles
are acknowledged and all conditions are
returned to normal.)
10
Note: Exceptions are Class A zone troubles
which always latch.
System troubles are also annunciated by the
appropriate trouble code in the 7-segment
Page 14
LW-401 Operation, Installation, and Maintenance ManualLW-401
display. If an alarm occurs after the trouble is
annunciated, the 7-segment display will clear.
To Acknowledge Troubles
1. Unlock and open the door.
2. Press ACK to acknowledge (Block
Acknowledge) all troubles and other
conditions. The system TROUBLE LED
and the Zone TROUBLE LEDs on the
front panel stop flashing and remain on.
The system’s internal audible silences.
To Reset
Press RESET. (The system will not reset
until all alarms, supervisories, and troubles
are acknowledged and all conditions are
returned to normal.)
System Features
In addition to the standard modes of operation for reporting system conditions, the
LW-401 has user-programmable features
that are described below. Each topic identifies the Program Level used to select these
features. Refer to the Programming section
of this manual for instructions on how to
activate these features in your LW-401
System.
Initiating Device Circuit (Zone) Types
(Program Level 3)
The LW-401 has the following 4 zone types.
• General Alarm
• Alarm Verified Zones
• Supervisory Zones
• Generic Zones
General Alarm is the default setting for all
zones. Alarm Verified Zone and Generic
Zone operation are described below.
• Shorting-type input devices and smoke
detectors are compatible with all zone
types.
• Manual fire alarm stations and smoke
detectors can be mixed on zones where
local codes allow.
• On verified zones, the manual station
reports alarms when activated, without
delay.
Alarm Verification
The Alarm Verification Feature provides the
LW-401 with a way to verify an alarm from
area-type smoke detectors. This feature can
be used to reduce incidences of false
alarms.
A detector supervised with Alarm Verification
is turned off by the System immediately after
it reaches an alarm threshold. The trouble
LED for that detector's zone turns on. The
detector is verified for a length of time which
must not exceed 60 seconds. After power is
restored to the device, and for the next 60
seconds, if the detector once again reaches
the alarm threshold the system will report an
alarm condition. If after 60 seconds the
detector has not alarmed, any detector which
again reaches the alarm threshold will restart
the verification cycle. See Figure 7, page 12,
for a graphic illustration of the Alarm Verification Time cycle.
CAUTION:
Use only detectors which are subjected to
air velocities of less than 100 feet per
minute with Alarm Verification. Under dynamic air velocity conditions, smoke may
be swept from a smoke detector after the
initial alarm. That may cause a long delay
before verification. Do not select Alarm
Verification for such applications.
11
Page 15
LW-401
Operation, Installation, and Maintenance Manual
Figure 7
Line Graph of Alarm Verification
3. March Time Code
4. Simple Zone Code
A steady tone is the default choice for each
circuit. A nonsilenceable NAC has a steady
tone. Temporal Code is as defined by NFPA
72. (Simple Zone Code is explained below.)
Please note that while it is possible to pro-
gram the two NACs with different, nonsteady codes, it is not permitted by any
authority. Use only one nonsteady code in
your LW-401 system.
Alarm Verification in the LW-401 is applied
globally to all selected zones. Therefore,
when a detector reaches its alarm threshold
and begins the Alarm Verification Time cycle,
any detector on any alarm verified zone will
react to smoke conditions as if its own Alarm
Verification Cycle had begun with the first
detector.
Generic Zone
The generic zone is activated (or alarmed)
by the output from another control panel.
This output should be made with a contact
device connected across the Generic zone.
When activated, it causes the notification
appliance circuits to sound and the appropriate initiating Zone LED to light. When the
input is deactivated, the NACs will silence.
The System alarm contacts do not change
state.
Notification Appliance Circuit (NAC or
Bell Circuit) Type (Program Level 4)
The LW-401 has two Notification Appliance
Circuits, each circuit is rated at 1.5 amps.
The Notification Appliance Circuits can each
be programmed for one of the following four
code choices:
1. Steady NAC
2. Temporal Code
When distributing power in the system,
remember that there are 3 amps available
between the two NACs and the auxiliary
output. Do not exceed 3 amps total current
draw from the system.
Simple Zone Code
Notification Appliance Circuits programmed
for simple zone code follow a pre-programmed code pattern. Devices are turned
on and off once for Zone 1 alarms, twice for
Zone 2 alarms, three times for Zone 3 alarms,
etc. The first alarm’s code is repeated for the
number of rounds programmed in the system, then the next alarm is reported. The
minimum allowable number of rounds is
three.
When all zones in alarm complete their
specified number of rounds in turn, the entire
sequence begins again with the first zone in
alarm. This sequence is repeated until the
system is silenced or reset.
The system operator cannot silence the
appliances, or reset the system, until the
programmed number of rounds of code have
been completed for each alarm. After silencing the appliances, the system reports a new
alarm via its particular code, followed by a
resound of all previously silenced alarms.
12
Page 16
LW-401 Operation, Installation, and Maintenance ManualLW-401
Set Output Control Matrix (Program
Level 5)
The LWZE-4A Zone/Output Expander module has four output relays and four open
collector outputs. The LWZR-8 Relay module
has eight output relays. Initiating Device
Circuits can be mapped to these outputs. Any
number of zones can be mapped to any
output. The first zone in alarm will turn the
output on. Also, any zone can be mapped to
any number of outputs. When the zone
alarms, all mapped outputs will turn on.
The outputs on the LWZE-4A and the
LWZR-8 are linked. The outputs are numbered 1 through 8. If a zone is mapped to an
output, for example output number 1, the first
output on the LWZE-4A and LWZR-8 will
turn on if both modules are in use.
Bypass Zones and Outputs (Program
Levels 1 and 2)
The LW-401 can bypass both Initiating
Device Circuits and relays or open collector
outputs on the LWZE-4A Zone/Output Expander module and the LWZR-8 Relay module.
• When a circuit is bypassed, the system
reports a trouble condition and the
Bypass LED will be on.
• When a zone is bypassed, the zone
trouble LED will also be on.
• When an output is bypassed, and both
the LWZE-4A and the LWZR-8 are in
use, the respective output on both cards
will be bypassed.
Set System Timing (Program Level 6)
The LW-401 has the following four timing
functions:
1. Verification Retard/Reset Timer
2. NAC Inhibit Timer
3. NAC Cutoff Timer
4. Simplified Zone Code Rounds
The Alarm Verification Retard/Reset time
establishes the delay time required to provide
an alarm verification cycle as determined by
the system owner or the local authority.
(Complete instructions for the proper selection of this timer follow.)
The NAC Inhibit and Cutoff Timers provide
automatic control of evacuation signals.
• The inhibit timer prevents any user from
silencing the notification appliances
before the selected time expires.
• The cutoff timer automatically turns off
all notification appliances after the
selected time expires.
Each timer has eight separate selections.
When the cutoff timer is set at
minutes), there is no automatic cutoff and
the appliances are energized until silenced
or reset.
The last timing function sets the number of
rounds of code for those systems using
Simple Zone Coding. (Please see the above
discussion of NAC types for a full explanation of Simple Zone Coding.) The minimum
number of rounds is 3 and the maximum
programmable number of rounds is 8.
The selection of the Alarm Verification
feature results in a delay of the system alarm
signal to the affected circuits. The total
allowable delay is 60 seconds. This delay,
the Alarm Verification time, is the sum of a
built-in 6 second system delay and the
programmed Retard/Reset time. The Retard/
Reset time can be set between 15 and 50
seconds, with 15 seconds being the programmed default. (See the definition of zone
types above for a further definition of the
Alarm Verification Time cycle.)
13
Page 17
LW-401
Operation, Installation, and Maintenance Manual
1. To select the proper Retard/Reset time,
begin with the Alarm Verification time
required by the system owner or local
authority.
2. Subtract the built-in 6 second system
delay. Make sure that the result is equal
to, or greater than the Detector Start-up
Delay from the Table below. If not, the
Alarm Verification Time must be lengthened, or a new detector must be selected
for the installation.
3. Select the Retard/Reset time from the
programming instructions on page 18
which is closest to your result.
Example:
1. Alarm Verification Time required
by building owner =30 seconds
2. Subtract the built-in, 6 second
system delay
3. Result =24 seconds
Select a Retard/Reset Time of 25 seconds from the
table on page 18 of the programming instructions.
NOTE: All detectors in the table below, except the
8854/8843, can be used for this application.
The 8854/8843 Delay Startup is longer than
the Retard/Reset time and therefore would
cause the Alarm Verification time to exceed
30 seconds.
-6 seconds
putratSyaleD
rotceteD
)sdnoceS(
1098/00985
3098/20985
5098/40985
Set AC Fail Signal Delay (Program
Level 8)
Underwriters Laboratories, Inc. requires all
fire protection systems which communicate
to a Central Station to delay the transmission
of AC Fail Trouble Signals by a predetermined length of time. The system default is a
6 hour delay. The other option, no delay, is
used when the system does not report to a
Central Station.
Enable System Option Cards (Program
Level 9)
The LW-401 system has the capacity to
support the following option cards:
• Either the LWZR-8 Relay module or the
LWCT-1 Municipal Tie module
plus
• Either the LWZE-4A or the LWZE-8A
Zone/Output Expander module
plus
• 1 or 2 Model LWRA-8B/W Remote
Annunicators
The optional modules must be enabled in
the LW-401 program or they will not function.
One Person System Test (Test Level 1)
This feature allows one person to test the
system by disabling it, activating initiating
devices, and listening for the building
audibles to sound. After the notification
appliances sound, the system will reset and
wait for the next device to be activated.
3488/458805
Set System Password
(Program Level 7)
The System Password consists of four digits
using the four system keys: ACK, RESET,
DRILL, SILENCE. The password can be any
4-digit sequence of these keys.
14
The system can also be tested without the
notification appliances. A second person
must watch the system display for indication
of activated zones. If the system is left inactive during the test, the system will reset to its
normal operating mode after 20 minutes.
NOTE: Supervisory zones will appear as alarm
zones during this test and the zone
alarm LED will turn on.
Page 18
LW-401 Operation, Installation, and Maintenance ManualLW-401
Last Event Record (Test Level 4)
This feature records the zone in which the
last event occurred in each of four categories: Alarms, Troubles, Verified Alarms, and
Supervisories. This can be used for troubleshooting one-time reports of events.
Program Mode
The program mode allows the user to
change the configuration of the LW-401
system. The program mode has nine levels.
Each level allows the user to configure a
different function within the LW-401.
When the program mode is enabled, the
current programming levels and sublevels
display in turn on the seven segment display.
The order of the display is as follows:
1. the program level is displayed first
2. then a hyphen (-) is displayed
3. then the sublevel is displayed
4. then the display is blank.
The entire sequence then repeats.
In the programming mode, the four function
keys operate differently than they do in the
normal mode. Their functions are as follows:
The Acknowledge key toggles between the
Test mode, the Program mode, and the
Leave mode. The seven segment display
shows t, P, and L, respectively, to indicate
these modes.
The Reset key is used to select program
levels and options inside the programming
levels.
The Drill key selects options and toggles
options on and off.
The Silence key selects different sublevels.
Pressing silence when the seven segment
display shows L exits the user from the
program/test mode.
PROGRAM LEVEL DESCRIPTIONS
Level 1:Bypass or enable the LWZE-4A or
LWZE-8A Zone Expander card.
Level 2:Bypass or enable the Relay and/or
the Open Collector Outputs on the
optional LWZE-4A, or LWZE-8A
and LWZR-8 cards.
Level 3:Allows configuration of the Initiat-
ing Zone Circuits to any one of
the following types: Initiating,
Verified Initiating, Supervisory,
and Generic Input.
Level 4:Allows configuration of the Notifi-
cation Appliance Circuits to NonSilenceable and any one of the
following types: Steady, Tempo-
ral, March Time, and Simplified
Zone Code.
Level 5:Allows programming of the out-
puts on the optional LWZE-4A or
LWZE-8A Zone/Output Expander
card and the LWZR-8 Relay card
to follow Alarms on the Initiating
Zone Circuits.
Level 6:Allows programming of timer and
counter values:
• the Verification Timer between
15 and 50 seconds.
•
the Inhibit and Cutoff Timers
of the Notification Appliance
Circuits.
• the Round Count ranging from
3 to 8 for Simplified Zone Coding.
Level 7:Allows programming of the 4-digit
Password.
Level 8:Allows programming of the AC
Fail Trouble Signal Delay.
Level 9:Enable/Disable the LWZR-8;
LWRA-8B/W, Addresses 1 and 2;
LWCT-1; and LWZE-4A/
LWZE-8A.
15
Page 19
LW-401
Operation, Installation, and Maintenance Manual
ENABLING THE PROGRAM MODE
Enter Password
1. Press the RESET key and hold it down
while simultaneously pressing the
DRILL key. The System TROUBLE LED
turns on steady and the letter E flashes
on the seven segment display.
2. Enter the password by pressing the
appropriate keys (ACK = 1, RESET = 2,
DRILL = 3, SILENCE = 4); then press the
SILENCE key.
For example,
the default password is
1111. To enter the default password,
press the ACK key four times and then
press the SILENCE key.
The seven segment display either
displays F to indicate an incorrect
password, or A to indicate the password
is accepted. If the letter F appears,
repeat steps 1 and 2; if the letter A
appears, continue on.
Reading the LW-401 Display
As the system is programmed, the 7-segment display shows the current program
level and sublevel. When a program level is
selected, the program level number is shown
in the 7-segment display. When the sublevel
is selected, the 7-segment display shows the
program number followed by a hyphen, then
by the sublevel number.
The red zone LEDs are used to indicate
which programmed options have been
selected. The zone LEDs correspond to the
charts in the following programming and
testing instructions for each feature. The
yellow zone LED acts as a pointer when
changing the current programming.
To Select Program Mode
Press the ACK key once. The PROGRAM/
TEST LED flashes and the seven segmentdisplay shows the letter P.
To Exit Program Mode
The user can exit the Program mode at any
time by pressing the ACK key until the
Program/Test status LED turns off and the
letter L appears in the seven segment display. Then press the SILENCE key to save
the system Configuration (only in the Program Mode) and exit the Program/Test Mode.
Program Level 1 - Bypass Zones
1. Press the Reset key once to select
Program Level 1.
2. Press the Silence key to select the Zone
to be bypassed.
Example
: 1-1 bypasses or enables Zone 1.
3. The red zone LED for the selected zone
will be on if the zone is enabled and off if
bypassed.
4. Press the Drill Key to change the state of
the zone.
5. Press the Silence key to select another
Zone to be bypassed and return to Step 3.
6. Press the ACK key when done.
Program Level 2 - Bypass Outputs
1. Press the Reset key twice to select
Program Level 2.
2. Press the Silence key to select the
Output to be bypassed.
Example:
Output Relay 1.
The Outputs on each card are organized
as indicated in the following table:
LW-401 Operation, Installation, and Maintenance ManualLW-401
3. The red zone LED for the selected Output
will be on if the Output is enabled and off
if bypassed.
4. Press the Drill key to change the state of
the Output.
5. Press the Silence key to select another
Output to be bypassed and return to
Step 3.
6. Press the ACK key when done.
Program Level 3 - Set Zone Types
1. Press the Reset key 3 times to select
Program Level 3.
2. Press the Silence key to select the Zone
to be programmed.
Example:
for Zone 1.
3. The selected Zone Type is shown by the
red zone LED indicated in the following
table:
Zone 1 LED=Initiating Zone Type
Zone 2 LED=Verified Alarm Zone Type
Zone 3 LED=Supervisory Zone Type
Zone 4 LED=Generic Zone Type
4. Press the Reset key to advance the
pointer (yellow zone LED) to the desired
Zone Type.
5. Press the Drill key to activate the desired
Zone Type.
3-1 programs the Zone Type
3. The selected NAC type is shown by the
red zone LED indicated in the following
table:
Zone 1 LED=Steady NAC
Zone 2 LED=Temporal Code
Zone 3 LED=March Time Code
Zone 4 LED=Simple Zone Code
Zone 5 LED=Non-Silenceable Output
4. Press the Reset key to advance the
pointer (yellow zone LED) to the desired
NAC type.
5. Press the Drill key to activate the desired
NAC type.
6. Press the Silence key to select the other
NAC to be programmed and return to
Step 3.
7. Press the ACK key when done.
Program Level 5 - Output Control
Matrix
1. Press the Reset key 5 times to select
Program Level 5.
2. Press the Silence key to select the Zone
to be programmed.
Ex: 5-1 allows mapping Zone 1 to
Outputs.
3. The selected Zone Map is shown by the
red zone LEDs indicated in the following
table:
6. Press the Silence key to select another
Zone to be programmed and return to
Step 3.
7. Press the ACK key when done.
Program Level 4 - Set NAC Types
1. Press the Reset key 4 times to select
Program Level 4.
2. Press the Silence key to select the NAC
to be programmed.
Example:
the first Bell Circuit.
4-1 programs the NAC type for
Zone 1 LED=Zone Mapped to Output 1
Zone 2 LED=Zone Mapped to Output 2
Zone 3 LED=Zone Mapped to Output 3
Zone 4 LED=Zone Mapped to Output 4
Zone 5 LED=Zone Mapped to Output 5
Zone 6 LED=Zone Mapped to Output 6
Zone 7 LED=Zone Mapped to Output 7
Zone 8 LED=Zone Mapped to Output 8
4. Press the Reset key to advance the
pointer (yellow zone LED) to the desired
Output.
17
Page 21
LW-401
Operation, Installation, and Maintenance Manual
5. Press the Drill key to map the selected
Zone to the desired Output.
6. Press the Silence key to select another
Zone to be programmed and return to
Step 3.
7. Press the ACK key when done.
Program Level 6 - Set System Timing
1. Press the Reset key 6 times to select
Program Level 6.
2. Press the Silence key to select one of
the four timing functions to be
programmed as indicated in the following
table:
1. The selected Retard/Reset Time is
shown by the red zone LEDs according to the following table:
Zone 1 LED=15 seconds
Zone 2 LED=20 seconds
Zone 3 LED=25 seconds
Zone 4 LED=30 seconds
Zone 5 LED=40 seconds
Zone 6 LED=50 seconds
Zone 7 LED=50 seconds
Zone 8 LED=50 seconds
2. Press the Reset key to advance the
pointer (yellow zone LED) to the
desired time.
3. Press the Drill key to activate the
desired time.
4. Press the ACK key when done.
Level 6-2 - Set NAC Inhibit Timer
1. The selected Inhibit Time is shown by the
red zone LEDs as indicated in the
following table:
Zone 1 LED=0 minutes
Zone 2 LED=6 seconds
Zone 3 LED=30 seconds
Zone 4 LED=1 minutes
Zone 5 LED=90 seconds
Zone 6 LED=2 minutes
Zone 7 LED=3 minutes
Zone 8 LED=5 minutes
2. Press the Reset key to advance the
pointer (yellow zone LED) to the desired
time.
3. Press the Drill key to activate the desired
time.
4. Press the ACK key when done.
Level 6-3 - Set NAC Cutoff Timer
1. The selected Cutoff Time is shown by the
red zone LEDs as indicated in the
following table:
Zone 1 LED=No Cutoff
Zone 2 LED=1 minutes
Zone 3 LED=2 minutes
Zone 4 LED=5 minutes
Zone 5 LED=10 minutes
Zone 6 LED=15 minutes
Zone 7 LED=20 minutes
Zone 8 LED=25 minutes
2. Press the Reset key to advance the
pointer (yellow zone LED) to the desired
time.
3. Press the Drill key to activate the desired
time.
4. Press the ACK key when done.
18
Page 22
LW-401 Operation, Installation, and Maintenance ManualLW-401
Level 6-4 - Set Simplified Zone Code
Rounds
1. The selected number of rounds is shown
by the red zone LEDs as indicated in the
following table:
Zone 3 LED=3 rounds
Zone 4 LED=4 rounds
Zone 5 LED=5 rounds
Zone 6 LED=6 rounds
Zone 7 LED=7 rounds
Zone 8 LED=8 rounds
2. Press the Reset key to advance the
pointer (yellow zone LED) to the desired
time.
3. Press the Drill key to activate the
desired time.
4. Press the ACK key when done.
Program Level 7 - Set System
Password
1. Press the Reset key 7 times to select
Program Level 7.
2. Press the Silence key to select the
Password digit to be programmed.
Example: 7-1 programs the first digit of
your password.
3. The selected digit choice is shown by the
red zone LED as indicated in the
following table:
Zone 1 LED=ACK (1)
Zone 2 LED=RESET (2)
Zone 3 LED=DRILL (3)
Zone 4 LED=SILENCE (4)
4. Press the Reset key to advance the
pointer (yellow zone LED) to the desired
digit choice.
5. Press the Drill key to activate the
desired digit choice.
6. Press the Silence key to select another
digit to be programmed and return to
Step 3.
7. Press the ACK key when done.
Program Level 8 - Set the AC Fail
Signal Delay
1. Press the Reset key 8 times to select
Program Level 8.
2. Press the Silence key to select this
programming function. There is no other
function to be selected.
Note: 8-1 programs the AC Fail Signal
Delay.
3. A six-hour delay is activated when the
red zone LED for zone 1 is on. If the LED
is off, there is no delay.
4. Press the Drill key to activate or
deactivate the delay.
5. Press the ACK key when done.
Program Level 9 - Enable System
Option Cards
1. Press the Reset key 9 times to select
Program Level 9.
2. Press the Silence key to select this
programming function. There is no other
function to be selected.
Note: 9-1 enables the System Option
Cards.
3. The selected Option Cards are shown by
the red zone LED as indicated in the
following table:
Zone 1 LED = LWZR-8 Enabled
Zone 2 LED = LWRA-8B/W, Addr 1 Enabled
Zone 3 LED = LWRA-8B/W, Addr 2 Enabled
Zone 4 LED = LWCT-1 Enabled
Zone 5 LED = Zone Expansion Enabled
19
Page 23
LW-401
Operation, Installation, and Maintenance Manual
4. Press the Reset key to advance the
pointer (yellow zone LED) to the desired
Option Card.
5. Press the Drill key to activate the desired
Option Card.
6. Press the ACK key when done.
Test Mode
The test mode allows the user to test that the
LW-401 is operating correctly. There are six
levels to the test mode. Each level tests
different functions within the LW-401.
Reading the LW-401 Display
As the system is tested, the 7-segment
display shows the current test level and
sublevel. When a test level is selected, the
test level number is shown in the 7-segment
display. When the sublevel is selected, the
7-segment display shows the test number
followed by a hyphen, then by the sublevel
number.
• Level 5:Performs Local Display and
Remote (LWRA-8B/W) Lamp
test.
• Level 6:Clears the panel's history
events (Alarm, Trouble, and
Supervisory).
ENABLING THE TEST MODE
Enter Password
1 . Press the RESET key and hold it down
while simultaneously pressing the DRILL
key. The System TROUBLE status LED
lights steady, and the letter E flashes on
the seven segment display.
2. Enter the password by pressing the
appropriate keys (ACK = 1, RESET = 2,
DRILL = 3, SILENCE = 4); then press the
SILENCE key. The seven segment
display either displays F to indicate an
incorrect password, or A to indicate the
password is accepted. If the letter F
appears, repeat steps 1 and 2; if the
letter A appears, continue on.
TEST LEVEL DESCRIPTIONS
• Level 1:Enables the One Person
System Test Function.
• Level 2:Tests the Main board Alarm
and Trouble relays and NAC
relays.
• Level 3:Tests the Optional Module
Relays and Open Collector
Output Drivers.
• Level 4:Displays the Alarm, Trouble,
and Supervisory history on
the Initiating Device Circuit
Zone status LEDs.
20
To Select Test Mode
Press the ACK key twice.The PROGRAM/
TEST status LED on the front panel lights
steady and the seven segment display
shows the letter t.
To Exit Test Mode
The user can exit the Test mode at any time
by pressing the ACK key until the Program/Test status LED turns off and the letter L
appears in the seven segment display. Then
press the SILENCE key to exit the Program/
Test Mode.
Page 24
Test Level 1—One Person System Test
Important
Inform the person in charge of the LW-401
fire alarm system that a One Person Test is
to be performed and that part or all of the
fire detection system will be disabled. It is
also advisable (or may be required) to notify
the fire department of the test.
LW-401 Operation, Installation, and Maintenance ManualLW-401
LevelFeature
2-1Test System Alarm Relay
2-2Test NAC 1 Relay
2-3Test System Trouble Relay
2-4Test NAC 2 Relay
3. Press the Drill key to change the state of
the selected relay. Please note that
testing the NAC relays will activate the
appliances on that circuit.
The One Person Test feature allows the
installer to test the system in the following
two ways.
• When a device is alarmed, the system
notification appliances sound and the
appropriate IDC alarm LED lights for 2
seconds.
• When a device is alarmed, the sounding
of the appliances is eliminated—only
the system display annunciates.
1. Press the Reset key once to select Test
Level 1.
2. Press the Silence key once or twice to
select the type of test you wish to
perform.
Example:
1-1 enables test with
notification appliances;
1-2 enables test without
appliances.
4. Press the ACK key when done.
Test Level 3 - Test Optional Outputs
1. Press the Reset Key 3 times to select
Test Level 3.
2. Press the Silence Key to select one of
the eight outputs to be tested as
indicated in the following table:
3. Press the Drill key to change the state of
the selected output.
4. Press the ACK key when done.
Test Level 4 - Last Event Record
1. Press the Reset key 4 times to select
Test Level 4.
2. Press the Silence key to select the event
to be reviewed per the following table:
Example:
alarm.
LevelFeature
4-1Review Last Alarm
4-2Review Last Zone Trouble
4-3Review Last Verification
4-4Review Last Supervisory
3. The Zone Alarm LED for the last zone in
alarm will be on. Similarly, the Zone
Trouble LED will be on for the last zones
in supervisory and trouble conditions.
4-1 reviews the last zone in
Test Level 6 - Clear the Last Event
Record
1. Press the Reset key 6 times to select
Test Level 6.
2. Press the Silence key to select this
function. There is no other function to be
selected.
3. Press the Drill key to clear the event
record.
4. Press the ACK key when done.
4. Press the ACK key when done.
Test Level 5 - Lamp Test
1. Press the Reset key 5 times to select
Test Level 5.
2. Press the Silence key to select the
lamps to be tested as indicated in the
following table:
Example:
LevelFeature
5-1Test the Local Display
5-2Test Remote Annunciators
5-1 tests Local Display.
3. Press and hold the Drill key to turn
the lamps on.
4. Press the ACK key when done.
22
Page 26
LW-401 Operation, Installation, and Maintenance ManualLW-401
LW-401 Operation, Installation, and Maintenance ManualLW-401
CHECKOUT PROCEDURE
Prior to installing devices on bases and
applying power to the LW-401 system, follow
the Field Wiring Checkout Procedure
(Refer to Table 5, page 27).
On completion of installation, the system
should be thoroughly tested. Check supervision functions and the functional operation of
each external circuit, as well as the basic
system control panel functions.
yalpsiDedoCtluaFelbuorTesuaCelbissoP
1liaFrewoPCAecruoSrewoPCAkcehC
2ecnailppAnoitacifitoN
tluaF1tiucriC
3ecnailppAnoitacifitoN
tluaF2tiucriC
Maintenance
PERIODIC INSPECTION AND TESTING
To insure proper and reliable operation,
inspect and test the system to the latest
edition of NFPA 72
SERVICING
If troubleshooting and servicing guidance is
needed, contact your local Cerberus Pyrotronics Authorized Service Representative.
available for the NAC
circuits and auxiliary
port must be derated
to keep the total alarm
current below 3.5 amps.
26
Page 30
LW-401 Operation, Installation, and Maintenance ManualLW-401
TABLE 5TABLE 5
TABLE 5
TABLE 5TABLE 5
FIELD WIRING CHECKOUT PROCEDUREFIELD WIRING CHECKOUT PROCEDURE
FIELD WIRING CHECKOUT PROCEDURE
FIELD WIRING CHECKOUT PROCEDUREFIELD WIRING CHECKOUT PROCEDURE
MEASURE RESISTANCE BETWEEN
TERMINAL AND TERMINAL
Meter connection for Field Wiring Checkout Procedure Steps 1 and 2:
Positive lead connected to BL1-1 or BL2-1 and negative lead connected to BL1-2 or BL2-2.
Before making resistance measurements, short the End of Line Resistor (10K ohms).
BL1-1
BL2-1
BL1-2
BL2-2
<3.0 ohms
<3.0 ohms
Line open
Line too long
2. Measure Notification Appliance Circuit End of Line Resistance
Before making resistance measurements, remove the short from the previous step.
BL1-1
BL2-1
BL1-2
BL2-2
10K ohms
10K ohms
Line shorted; Line open
Wrong End of Line Resistor value
NAC Device wired backward
NAC Device not polarized
3. Check for Ground Fault
BL1-1
BL1-2
BL2-1
BL2-2
Meter connection to Field Wiring Checkout Procedure Steps 4, 5, and 6:
Positive lead connected to IDC + and negative lead connected to IDC -. Do not connect initiating devices to the
ID loop for resistance measurements in Field Wiring Checkout Procedure Steps 4, 5, and 6.
To all other Main Control module
terminals excluding NAC 1
To all other Main Control module
terminals excluding NAC 2
WARNING: This equipment generates, uses, and can radiate radio
frequency energy and if not installed and used in accordance with
the instructions manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a
Class A computing device pursuant to Subpart J of Part 15 of FCC
Rules, which are designed to provide reasonable protection against
such interference when operated in a commercial environment.
Operation of this equipment in a residential area is likely to cause
interference in which case the user at his own expense will be
required to take whatever measures may be required to correct the
interference.
Page 35
P/N 315-095997FA-2
(446106)ww
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.