Faraday LW401 Operation, Installation, And Maintenance Manual

Page 1
Operation, Installation, and
Maintenance Manual
LW401
Fire Alarm System Control Unit
Faraday: www.faradayfirealarms.com
Copyright 1997, Faraday, LLC All Rights Reserved
P/N 315-095997FA-2
(446106)
Page 2
Table of Contents
Section Page
1 INTRODUCTION .......................................................................................................................1
Standard Components ........................................................................................................2
MAIN BOARD ................................................................................................................................ 2
DISPLAY ....................................................................................................................................... 2
FRONT PANEL FUNCTIONS .......................................................................................................... 3
2 INSTALLATION.........................................................................................................................5
Unpacking the Equipment ..................................................................................................5
Installing the Control Panel ................................................................................................6
3 OPERA TING MODES ............................................................................................................... 9
Alarm ....................................................................................................................................9
Supervisory .........................................................................................................................9
Zone Trouble........................................................................................................................9
SYSTEM TROUBLE (FAUL T) CODES............................................................................................ 9
Normal ..................................................................................................................................9
Program/Test .......................................................................................................................9
Responding to a Fire Alarm................................................................................................9
HOW THE SYSTEM ANNUNCIA TES FIRE ALARMS...................................................................... 9
TO AC KNOW LEDG E ALAR MS .................................................................................................... 10
TO SILENCE THE NOTIFICA TION APPLIANCE CIRCUITS ......................................................... 10
TO RESET ................................................................................................................................... 10
Responding to a Supervisory Condition......................................................................... 10
HOW THE SYSTEM ANNUNCIA TES SUPERVISORIES .............................................................. 10
TO ACKNOWLEDGE SUPERVISORIES ...................................................................................... 10
TO RESET ................................................................................................................................... 10
Responding to a Trouble Condition.................................................................................10
HOW THE SYSTEM ANNUNCIATES TROUBLES ........................................................................ 10
TO ACKNOWLEDGE TROUBLES ................................................................................................ 11
TO RESET ................................................................................................................................... 11
System Features ............................................................................................................... 11
INITIA TING DEVICE CIRCUIT (ZONE) TYPES ............................................................................ 11
ALARM VERIFICA TION ............................................................................................................... 11
GENERIC ZONE ..........................................................................................................................12
NOTIFICA TION APPLIANCE CIRCUIT (NAC OR BELL CIRCUIT TYPE) ..................................... 12
Simple Zone Code...................................................................................................................
SET OUTPUT CONTROL MA TRIX ................................................................................................ 13
BYP A SS ZON ES AN D OUT PUTS.................................................................................................13
SET SYSTEM TIMING.................................................................................................................. 13
ALARM VERIFICA TION RETARD/RESET TIMER SELECTION .................................................... 13
SET SYSTEM PASSWORD......................................................................................................... 14
SET AC FAIL SIGNAL DELA Y...................................................................................................... 14
ENABLE SYSTEM OPTION CARDS ............................................................................................ 14
ONE PERSON SYSTEM TEST..................................................................................................... 14
LAST EVENT RECORD ............................................................................................................... 15
Program Mode ...................................................................................................................15
PROGRAM LEVEL DESCRIPTIONS ............................................................................................ 15
12
i
Page 3
Table of Contents (Cont.)
Section
ENABLING THE PROGRAM MODE ........................................................................................... 16
Enter Password .......................................................................................................................
Reading the LW-401 Display ...................................................................................................
To Select Program Mode .........................................................................................................
To Exit Program Mode.............................................................................................................
Test Mode...........................................................................................................................20
Reading the LW-401 Display ...................................................................................................
TEST LEVEL DESCRIPTIONS.................................................................................................... 20
ENABLING THE TEST MODE..................................................................................................... 20
Enter Password .......................................................................................................................
To Select Test Mode ................................................................................................................
To Exit Test Mode ....................................................................................................................
4 CHECKOUT PROCEDURE.....................................................................................................25
Maintenance ......................................................................................................................25
PERIODIC INSPECTION AND TESTING ..................................................................................... 25
SERVICING ................................................................................................................................. 25
FIELD WIRING CHECKOUT PROCEDURE ................................................................................. 27
Page
16 16 16 16
20
20 20 21
List of Illustrations
Figure
1. LW-401 Control Panel ...........................................................................................................1
2. LW-401 Front Panel ..............................................................................................................2
3. LW-401 Enclosure .................................................................................................................5
4. Transformer Mounting ...........................................................................................................6
5. Mounting the Standoffs and Spacers.....................................................................................6
6. Mounting the LW41-MB.........................................................................................................7
7. Line Graph of Alarm Verification..........................................................................................12
List of Tables
1. Program Mode Levels ..........................................................................................................23
2. Test Mode Levels.................................................................................................................24
3. System Fault Troubleshooting..............................................................................................25
4. Electrical Requirements for Battery Calculations and Power Management ..........................26
5. Field Wiring Checkout Procedure.........................................................................................27
6. Default Configurations .........................................................................................................28
7. Programming Sheet .............................................................................................................29
Page
ii
Page 4
1
INTRODUCTION
The LW-401 is a microprocessor based fire and life safety system with four conventional initiating device circuits (up to 8 with the addition of the optional LWZE-4A or LWZE-8A zone expander). All basic alarm and trouble functions are annunciated and controlled from the LW-401 front panel (See Figure 1) which consists of:
• Seven segment numeric display
• Four user-control switches
• Red and yellow LEDs for each of the eight zones
• Six system status LEDs
Key features of the LW-401 are:
• 2 Class B (Style Y) +24 VDC notification appliance circuits (NACs) rated at 1.5 amps each.
• Silenceable/Non-Silenceable notification appliance circuits (NACs).
• Fully supervised initiating and notification circuits.
• Initiating and notification circuits power limited.
• 4 Class B (Style B) 2 wire initiating device circuits that are expandable to 8 circuits.
• Supports up to 30 non-shorting devices per initiating device circuit.
• Selectable alarm verification option for each initiating device circuit.
• One person system test with or without audible confirmation.
• User-alterable factory installed configu­ration.
• One Form C system Alarm relay
• One Form C system Trouble relay
• Seven segment numeric status display
• Six LED status indicators
• Easy-to-use front panel function keys
LW-401 Operation, Installation, and Maintenance ManualLW-401
Figure 1
LW-401 Control Panel
• Alarm Coding (March Time, Temporal, or Simplified Zone Code) and Non­Silenceable output option.
• Easy-to-use built-in diagnostics.
• 24 hour re-sound for Alarm and Trouble conditions that are not restored to normal after being acknowledged.
• Optional LWZE-8A module converts the system to four Class A (Style D) Initiating Device Circuits and two Class A (Style Z) Notification Appliance Circuits and also provides four additional Class A (Style D) Initiating Device Circuits.
• Optional LWZR-8 module provides eight programmable Form C relays.
• Optional LWRA-8B/W module provides remote annunciation for eight zones with 16 LEDs. Up to two may be used.
• Optional LWCT-1 module provides Leased Line/Municipal Tie connection.
1
Page 5
LW-401
Operation, Installation, and Maintenance Manual
Standard Components
A standard four zone LW-401 has one module—the main board. An expander board is added to provide four additional zones, when needed.
MAIN BOARD
The Main board of the LW-401 contains the intelligence for the system and performs all of the input/output processing as listed below:
Two supervised Notification Appliance Circuits provide 24 VDC at 1.5 amps. Each circuit operates Class B (Style Y) and can be independently programmed to operate a number of different ways (Non-Coded, March Time, Temporal, or Simple Zone Code).
Two Form C relays rated at 30 VDC at 1 amp resistive, 30 VAC at 500mA resistive. These relays are for Alarm and Trouble operation.
• A dual mode battery charger that
provides float and constant current modes of charging sealed lead acid batteries (15 Amp-Hour maximum).
Nonvolatile storage of system configu- ration so that configuration remains intact during loss of system power.
Four supervised power limiting Initiating Device Circuits. Each circuit operates Class B (Style B) and can be independently programmed to operate as an Automatic Alarm input, a Verified Alarm input, a Supervisory input, or a Generic input. Each initiating device circuit can use an unlimited number of manual shorting-type devices.
CPU Fail LED.
DISPLAY
The LW-401 display, shown in Figure 2, provides the user with the necessary inter­face to operate the fire detection system in Normal, Test, and Program modes.
2
Figure 2
LW-401 Front Panel
Page 6
FRONT PANEL FUNCTIONS
The front panel of the LW-401 is comprised of a seven segment display, function keys, and LEDs. Their functions are described below (Refer to Figure 2):
The LEDs
The green Power LED remains on steady when AC power is connected and pulses when the unit is operating from batteries.
The red Alarm LED pulses when an alarm is detected until it is acknowledged. Then it remains on steady until the alarm condition is reset.
The yellow Supervisory LED pulses when a supervisory condition is detected until it is ac­knowledged. Then it remains on steady until the supervisory condition is reset. Note that the pulsing rates of the trouble and supervisory conditions are different.
The yellow Trouble LED pulses when a trouble condition is detected until it is acknowledged. Then it remains on steady until the trouble condition is reset. Note that the pulsing rates of the trouble and supervisory conditions are different.
The yellow Bypass/Alarm Silence LED is on steady when a zone in the system is bypassed and it pulses when a notification circuit is si­lenced. When an initiating device zone is by­passed, the appropriate yellow zone trouble LED is on.
The Test/Program LED is on steady when the Test mode is selected and it pulses when the Program mode is selected.
The Sounder
CONDITION RATE OF PULSATION
SYSTEM ALARM Sounds steady TROUBLE Pulses at 50% duty cycle SUPERVISORY Pulses at 25% duty cycle CPU FAILURE Pulses once every 2 seconds
LW-401 Operation, Installation, and Maintenance ManualLW-401
CODE DESCRIPTION
1 AC power fail 2 NAC 1 trouble 3 NAC 2 trouble 4 Ground fault 5 Municipal tie fault 6 Battery fault 7 System Configuration fault 8 Auxiliary port fault 9 Outputs bypassed 0 Hardware failure
E Enter password A Password accepted F Password fail P Program mode
Test mode
t
L Leave Program/Test mode
The Function Keys
The ACK key is used to acknowledge alarms,
troubles, and supervisory conditions. In general the LEDs change from pulsing to steady to indicate that the condition was acknowledged.
The SILENCE key silences the notification appliance circuits that are configured as silenceable. Pressing the SILENCE key a second time causes the NACs to re-sound. The RESET key resets the LW-401 and all of the smoke detectors. The DRILL key activates all of the notification
appliance circuits.
The yellow zone status LEDs indicate a trouble or supervisory condition existing on a particular input. Pulsing indicates the condition was not acknowledged; on steady indicates it was acknowledged.
The seven segment display indicates the various system troubles and the programming and test modes. The numbers and symbols that appear on this display are described in the following chart.
The red zone status LEDs provide an indication of the status of a particular zone. Pulsing indicates an alarm condition in that zone. When the alarm is acknowledged, the LED remains on steady until the panel is reset.
3
Page 7
LW-401
Operation, Installation, and Maintenance Manual
4
Page 8
2
INSTALLATION
Unpacking the Equipment
The LW-401 is shipped in two cartons; one of the cartons contains the LW-401 enclosure. The other carton contains the LW-401 electronics, the transformer, and the mounting hardware. Follow the proce-
dure below to unpack the LW-401 equipment.
LW-401 Operation, Installation, and Maintenance ManualLW-401
Remove the packing material, and inspect the electronics for damage.
Note: If the PC board is damaged,
contact the shipping carrier immediately to report the damage.
1. Locate and open the shipping carton containing the LW41-EN enclosure. Remove the packing material and inspect the enclosure for damage.
Note: If the enclosure is damaged,
contact the shipping carrier immediately to report the damage.
2. Locate and open the shipping carton containing the LW-401 electronics.
3. Check that the following items are inside the carton:
• Mounting hardware for the LW41-MB
and transformer
• Main board
• Power transformer Note: If any of the above items are
missing, contact the distributor from whom you ordered the unit.
Figure 3
LW-401 Enclosure
5
Page 9
LW-401
Operation, Installation, and Maintenance Manual
Installing the Control Panel
Remove all system power before
installation, first battery and then AC.
(To power up, connect the
AC first, then the battery.)
All wiring must comply with
national and local codes.
Install the LW-401 control panel by following the steps listed below.
1. Install the enclosure. Fasten the enclosure securely to a clean, dry, shock and vibration free surface. Consider the following placement factors when mounting the enclosure: height as it relates to the front panel, weight and size of the enclosure, and local mounting codes. Refer to the
and Power Limited Wiring Instructions,
P/N 446107, for further information.
LW41-EN Installation
2. Fasten the power transformer to the
inside of the enclosure. Mount the
transformer on the four studs in the upper left-hand corner of the LW41-EN enclosure, as shown in Figure 4, using the hardware provided.
3. Pull all field wiring into the enclosure.
Dress the wiring to the approximate location to which it will go on the LW41-MB.
4. Install the PC Board mounting metal hex standoffs and plastic spacers.
Mount the six PC Board metal hex stand­offs and two plastic round spacers, as shown in Figure 5.
5. Install the Main board. Mount the Main board to the standoffs in the center of the enclosure (Refer to Figure 6).
a. Fasten two of the six screws provided
in the PC board mounting hardware in the two bottom metal hex standoffs
Figure 4
Transformer Mounting
6
Figure 5
Mounting the Standoffs and Spacers
Page 10
labeled A in Figure 6, leaving a 1/4 inch gap between the standoff and the head of the screw.
b. Place the slots on the bottom of the
LW41-MB on the two screws.
c. Secure the board in place by fasten-
ing the remaining four screws labeled B to the metal hex standoffs.
d. Tighten the bottom two screws.
6. Optional modules. Refer to the specific optional module Installation Instruction sheet for the appropriate installation.
7. Before connecting any wire to its screw terminal, refer to the Checkout Procedure (page 27) and the LW-401 Connection Diagram, P/N 315-
096185FA. Prior to connecting wiring to the Main board, ensure compliance to maximum resistance in accordance with the Field Wiring Checkout procedure, page 27. Make sure that all power is off before connecting leads.
8. Install power wiring. The LW-401 is designed to operate from a 120 VAC, 60 Hz power source.
LW-401 Operation, Installation, and Maintenance ManualLW-401
Use a dedicated circuitbreaker. Wire in accordance with local codes and/or Article 760 of the National Electrical Code, NFPA 72, latest edition.
a. Run Earth Ground from a suitable
source to the Earth Ground stud on the chassis (See Figure 6 for the location of the stud). Secure in place using the two #8 nuts provided. Check local requirements. Conduit is
not an acceptable ground.
b. Connect the 120 VAC source and the
BLACK transformer wire leads to TB1.
c. Connect the BROWN transformer
wire leads to TB6.
Figure 6
Mounting the LW41-MB
7
Page 11
LW-401
Operation, Installation, and Maintenance Manual
8
Page 12
3
OPERATING MODES
LW-401 Operation, Installation, and Maintenance ManualLW-401
The LW-401 annunciates the following modes of operation:
• Alarm
• Supervisory
• Trouble
• Normal
• Program/Test
Alarm
The LW-401 Display board lights the appropriate red alarm LED and the general ALARM LED to indicate to the user that an Alarm condition exists on an initiating device circuit (IDC).
Supervisory
A Supervisory alarm condition is indicated on the LW-401 by the SUPERVISORY LED flashing along with the appropriate yellow zone LED.
Zone Trouble
A Trouble condition is displayed by a flashing TROUBLE LED along with the appropriate yellow zone LEDs.
For a further description of the system fault codes, see System Fault Troubleshooting (Table 3, page 25).
Normal
The Normal Mode is the absence of any alarm, supervisory, or trouble condition. The POWER LED is lit in Normal mode when the system has AC power. The Alarm, Trouble, Supervisory, Bypass, and Zone status LEDs are off, and the internal sounder is off.
Program/Test
The Program/Test Mode is used for system configuration, test, and maintenance func-
When the LW-401 is in Program
tions.
Mode, it does not indicate alarm or super­visory conditions.
The System resets to normal mode after 2 minutes of front panel inactivity. When the LW-401 is in the One Person System Test Mode, it automatically returns to normal mode after 20 minutes of inactivity.
Responding to a Fire Alarm
System Trouble (Fault) Codes
A number is displayed in the seven segment display to indicate System Trouble (Fault) Codes. They are:
Code 1: AC Power Fail/Brownout Code 2: Notification Appliance Circuit 1 Code 3: Notification Appliance Circuit 2 Code 4: Ground Fault Code 5: Municipal Tie Fault Code 6: Battery Fault Code 7: System Configuration Fault Code 8: Auxiliary Port Fault Code 9: Output Bypassed Code 0: Hardware Failure
How the System Annunciates Fire Alarms
When a fire is detected on one of the initiat­ing device circuits (IDCs), the LW-401 causes the System ALARM LED and the appropriate Zone ALARM LED on the front panel to flash and the system’s internal audible to sound.
NOTE: Follow the response plan approved
by the local authority having jurisdiction.
9
Page 13
LW-401
Operation, Installation, and Maintenance Manual
To Acknowledge Alarms
1. Unlock and open the door.
2. Press ACK to acknowledge (Block Acknowledge) all alarms and other conditions. The system ALARM and the Zone ALARM LEDs on the front panel stop flashing and remain on. The system’s internal audible silences.
To Silence The Notification Appliance Circuits
Press SILENCE after all alarms are acknowl­edged. The BYPASS LED on the front panel flashes. The following four conditions are checked before the Notification Appliance Circuit(s) can be silenced:
1. If either NAC is programmed as NON- SILENCEABLE, it will not silence.
2. If the NAC inhibit timer has been pro­grammed (see
Set System Timing
on page 13), the NAC will not silence until the inhibit time delay has expired (6 seconds to 5 minutes.)
3. If either NAC is programmed for temporal coding, it will complete sending out the entire current temporal round before silencing.
4. If either NAC is programmed for ZONE CODING, all coded rounds for each zone in alarm must be sent out before the NAC will silence.
Once the NACs have silenced, pressing the SILENCE a second time causes the Notifica­tion Appliance Circuits to re-sound, and the
BYPASS LED to turn off.
Responding to a Supervisory Condition
How the System Annunciates Supervisories
When a supervisory condition is detected, the system causes the SUPERVISORY LED and one of the yellow Zone TROUBLE LEDs on the front panel to flash and the system’s internal audible to sound.
To Acknowledge Supervisories
1. Unlock and open the door.
2. Press ACK to acknowledge (Block Acknowledge) all supervisory and other conditions. The system SUPERVISORY and the Zone TROUBLE LEDs on the front panel stop flashing and remain on and the system’s internal audible silences.
To Reset
Press RESET. (The system will not reset until all alarms, supervisories, and troubles are acknowledged and all conditions are returned to normal.)
Responding to a Trouble Condition
How the System Annunciates Troubles
When a trouble is detected, the system causes the TROUBLE LED and the appro­priate yellow Zone TROUBLE LEDs on the front panel to flash and the system’s internal audible to sound. Troubles will clear prior to Acknowledge if the condition which caused the trouble returns to normal.
To Reset
Press RESET. (The system will not reset until all alarms, supervisories, and troubles are acknowledged and all conditions are returned to normal.)
10
Note: Exceptions are Class A zone troubles
which always latch.
System troubles are also annunciated by the appropriate trouble code in the 7-segment
Page 14
LW-401 Operation, Installation, and Maintenance ManualLW-401
display. If an alarm occurs after the trouble is annunciated, the 7-segment display will clear.
To Acknowledge Troubles
1. Unlock and open the door.
2. Press ACK to acknowledge (Block Acknowledge) all troubles and other conditions. The system TROUBLE LED and the Zone TROUBLE LEDs on the front panel stop flashing and remain on. The system’s internal audible silences.
To Reset
Press RESET. (The system will not reset until all alarms, supervisories, and troubles are acknowledged and all conditions are returned to normal.)
System Features
In addition to the standard modes of opera­tion for reporting system conditions, the LW-401 has user-programmable features that are described below. Each topic identi­fies the Program Level used to select these features. Refer to the Programming section of this manual for instructions on how to activate these features in your LW-401 System.
Initiating Device Circuit (Zone) Types
(Program Level 3)
The LW-401 has the following 4 zone types.
• General Alarm
• Alarm Verified Zones
• Supervisory Zones
• Generic Zones
General Alarm is the default setting for all zones. Alarm Verified Zone and Generic
Zone operation are described below.
• Shorting-type input devices and smoke detectors are compatible with all zone types.
• Manual fire alarm stations and smoke detectors can be mixed on zones where local codes allow.
• On verified zones, the manual station reports alarms when activated, without delay.
Alarm Verification
The Alarm Verification Feature provides the LW-401 with a way to verify an alarm from area-type smoke detectors. This feature can be used to reduce incidences of false alarms.
A detector supervised with Alarm Verification is turned off by the System immediately after it reaches an alarm threshold. The trouble LED for that detector's zone turns on. The detector is verified for a length of time which must not exceed 60 seconds. After power is restored to the device, and for the next 60 seconds, if the detector once again reaches the alarm threshold the system will report an alarm condition. If after 60 seconds the detector has not alarmed, any detector which again reaches the alarm threshold will restart the verification cycle. See Figure 7, page 12, for a graphic illustration of the Alarm Verifica­tion Time cycle.
CAUTION:
Use only detectors which are subjected to air velocities of less than 100 feet per minute with Alarm Verification. Under dy­namic air velocity conditions, smoke may be swept from a smoke detector after the initial alarm. That may cause a long delay before verification. Do not select Alarm
Verification for such applications.
11
Page 15
LW-401
Operation, Installation, and Maintenance Manual
Figure 7
Line Graph of Alarm Verification
3. March Time Code
4. Simple Zone Code A steady tone is the default choice for each
circuit. A nonsilenceable NAC has a steady tone. Temporal Code is as defined by NFPA
72. (Simple Zone Code is explained below.) Please note that while it is possible to pro-
gram the two NACs with different, non­steady codes, it is not permitted by any authority. Use only one nonsteady code in your LW-401 system.
Alarm Verification in the LW-401 is applied globally to all selected zones. Therefore, when a detector reaches its alarm threshold and begins the Alarm Verification Time cycle, any detector on any alarm verified zone will react to smoke conditions as if its own Alarm Verification Cycle had begun with the first detector.
Generic Zone
The generic zone is activated (or alarmed) by the output from another control panel. This output should be made with a contact device connected across the Generic zone. When activated, it causes the notification appliance circuits to sound and the appropri­ate initiating Zone LED to light. When the input is deactivated, the NACs will silence. The System alarm contacts do not change state.
Notification Appliance Circuit (NAC or Bell Circuit) Type (Program Level 4)
The LW-401 has two Notification Appliance Circuits, each circuit is rated at 1.5 amps.
The Notification Appliance Circuits can each be programmed for one of the following four code choices:
1. Steady NAC
2. Temporal Code
When distributing power in the system, remember that there are 3 amps available between the two NACs and the auxiliary output. Do not exceed 3 amps total current draw from the system.
Simple Zone Code
Notification Appliance Circuits programmed for simple zone code follow a pre-pro­grammed code pattern. Devices are turned on and off once for Zone 1 alarms, twice for Zone 2 alarms, three times for Zone 3 alarms, etc. The first alarm’s code is repeated for the number of rounds programmed in the sys­tem, then the next alarm is reported. The minimum allowable number of rounds is three.
When all zones in alarm complete their specified number of rounds in turn, the entire sequence begins again with the first zone in alarm. This sequence is repeated until the system is silenced or reset.
The system operator cannot silence the appliances, or reset the system, until the programmed number of rounds of code have been completed for each alarm. After silenc­ing the appliances, the system reports a new alarm via its particular code, followed by a resound of all previously silenced alarms.
12
Page 16
LW-401 Operation, Installation, and Maintenance ManualLW-401
Set Output Control Matrix (Program Level 5)
The LWZE-4A Zone/Output Expander mod­ule has four output relays and four open collector outputs. The LWZR-8 Relay module has eight output relays. Initiating Device Circuits can be mapped to these outputs. Any number of zones can be mapped to any output. The first zone in alarm will turn the output on. Also, any zone can be mapped to any number of outputs. When the zone alarms, all mapped outputs will turn on.
The outputs on the LWZE-4A and the LWZR-8 are linked. The outputs are num­bered 1 through 8. If a zone is mapped to an output, for example output number 1, the first output on the LWZE-4A and LWZR-8 will turn on if both modules are in use.
Bypass Zones and Outputs (Program Levels 1 and 2)
The LW-401 can bypass both Initiating Device Circuits and relays or open collector outputs on the LWZE-4A Zone/Output Ex­pander module and the LWZR-8 Relay mod­ule.
• When a circuit is bypassed, the system reports a trouble condition and the Bypass LED will be on.
• When a zone is bypassed, the zone trouble LED will also be on.
• When an output is bypassed, and both the LWZE-4A and the LWZR-8 are in use, the respective output on both cards will be bypassed.
Set System Timing (Program Level 6)
The LW-401 has the following four timing functions:
1. Verification Retard/Reset Timer
2. NAC Inhibit Timer
3. NAC Cutoff Timer
4. Simplified Zone Code Rounds
The Alarm Verification Retard/Reset time establishes the delay time required to provide an alarm verification cycle as determined by the system owner or the local authority. (Complete instructions for the proper selec­tion of this timer follow.)
The NAC Inhibit and Cutoff Timers provide automatic control of evacuation signals.
• The inhibit timer prevents any user from silencing the notification appliances before the selected time expires.
• The cutoff timer automatically turns off all notification appliances after the selected time expires.
Each timer has eight separate selections. When the cutoff timer is set at minutes), there is no automatic cutoff and the appliances are energized until silenced or reset.
The last timing function sets the number of rounds of code for those systems using Simple Zone Coding. (Please see the above discussion of NAC types for a full explana­tion of Simple Zone Coding.) The minimum number of rounds is 3 and the maximum programmable number of rounds is 8.
No Cutoff
(0
Alarm Verification Retard/Reset Timer Selection (Program Level 6-1)
The selection of the Alarm Verification feature results in a delay of the system alarm signal to the affected circuits. The total allowable delay is 60 seconds. This delay, the Alarm Verification time, is the sum of a built-in 6 second system delay and the programmed Retard/Reset time. The Retard/ Reset time can be set between 15 and 50 seconds, with 15 seconds being the pro­grammed default. (See the definition of zone types above for a further definition of the Alarm Verification Time cycle.)
13
Page 17
LW-401
Operation, Installation, and Maintenance Manual
1. To select the proper Retard/Reset time, begin with the Alarm Verification time required by the system owner or local authority.
2. Subtract the built-in 6 second system delay. Make sure that the result is equal to, or greater than the Detector Start-up Delay from the Table below. If not, the Alarm Verification Time must be length­ened, or a new detector must be selected for the installation.
3. Select the Retard/Reset time from the programming instructions on page 18 which is closest to your result.
Example:
1. Alarm Verification Time required
by building owner = 30 seconds
2. Subtract the built-in, 6 second
system delay
3. Result = 24 seconds
Select a Retard/Reset Time of 25 seconds from the table on page 18 of the programming instructions.
NOTE: All detectors in the table below, except the
8854/8843, can be used for this application. The 8854/8843 Delay Startup is longer than the Retard/Reset time and therefore would cause the Alarm Verification time to exceed 30 seconds.
-6 seconds
putratSyaleD
rotceteD
)sdnoceS(
1098/00985 3098/20985 5098/40985
Set AC Fail Signal Delay (Program Level 8)
Underwriters Laboratories, Inc. requires all fire protection systems which communicate to a Central Station to delay the transmission of AC Fail Trouble Signals by a predeter­mined length of time. The system default is a 6 hour delay. The other option, no delay, is used when the system does not report to a Central Station.
Enable System Option Cards (Program Level 9)
The LW-401 system has the capacity to support the following option cards:
• Either the LWZR-8 Relay module or the LWCT-1 Municipal Tie module
plus
• Either the LWZE-4A or the LWZE-8A Zone/Output Expander module
plus
• 1 or 2 Model LWRA-8B/W Remote Annunicators
The optional modules must be enabled in the LW-401 program or they will not function.
One Person System Test (Test Level 1)
This feature allows one person to test the system by disabling it, activating initiating devices, and listening for the building audibles to sound. After the notification appliances sound, the system will reset and wait for the next device to be activated.
3488/458805
Set System Password
(Program Level 7)
The System Password consists of four digits using the four system keys: ACK, RESET, DRILL, SILENCE. The password can be any 4-digit sequence of these keys.
14
The system can also be tested without the notification appliances. A second person must watch the system display for indication of activated zones. If the system is left inac­tive during the test, the system will reset to its normal operating mode after 20 minutes.
NOTE: Supervisory zones will appear as alarm
zones during this test and the zone alarm LED will turn on.
Page 18
LW-401 Operation, Installation, and Maintenance ManualLW-401
Last Event Record (Test Level 4)
This feature records the zone in which the last event occurred in each of four catego­ries: Alarms, Troubles, Verified Alarms, and Supervisories. This can be used for trouble­shooting one-time reports of events.
Program Mode
The program mode allows the user to change the configuration of the LW-401 system. The program mode has nine levels. Each level allows the user to configure a different function within the LW-401.
When the program mode is enabled, the current programming levels and sublevels display in turn on the seven segment display. The order of the display is as follows:
1. the program level is displayed first
2. then a hyphen (-) is displayed
3. then the sublevel is displayed
4. then the display is blank.
The entire sequence then repeats. In the programming mode, the four function
keys operate differently than they do in the normal mode. Their functions are as follows:
The Acknowledge key toggles between the Test mode, the Program mode, and the Leave mode. The seven segment display
shows t, P, and L, respectively, to indicate these modes.
The Reset key is used to select program levels and options inside the programming levels.
The Drill key selects options and toggles options on and off.
The Silence key selects different sublevels. Pressing silence when the seven segment display shows L exits the user from the program/test mode.
PROGRAM LEVEL DESCRIPTIONS
Level 1: Bypass or enable the LWZE-4A or
LWZE-8A Zone Expander card.
Level 2: Bypass or enable the Relay and/or
the Open Collector Outputs on the optional LWZE-4A, or LWZE-8A and LWZR-8 cards.
Level 3: Allows configuration of the Initiat-
ing Zone Circuits to any one of the following types: Initiating,
Verified Initiating, Supervisory, and Generic Input.
Level 4: Allows configuration of the Notifi-
cation Appliance Circuits to Non­Silenceable and any one of the following types: Steady, Tempo-
ral, March Time, and Simplified Zone Code.
Level 5: Allows programming of the out-
puts on the optional LWZE-4A or LWZE-8A Zone/Output Expander card and the LWZR-8 Relay card to follow Alarms on the Initiating Zone Circuits.
Level 6: Allows programming of timer and
counter values:
• the Verification Timer between 15 and 50 seconds.
the Inhibit and Cutoff Timers of the Notification Appliance Circuits.
• the Round Count ranging from 3 to 8 for Simplified Zone Coding.
Level 7: Allows programming of the 4-digit
Password.
Level 8: Allows programming of the AC
Fail Trouble Signal Delay.
Level 9: Enable/Disable the LWZR-8;
LWRA-8B/W, Addresses 1 and 2; LWCT-1; and LWZE-4A/ LWZE-8A.
15
Page 19
LW-401
Operation, Installation, and Maintenance Manual
ENABLING THE PROGRAM MODE
Enter Password
1. Press the RESET key and hold it down while simultaneously pressing the DRILL key. The System TROUBLE LED turns on steady and the letter E flashes on the seven segment display.
2. Enter the password by pressing the appropriate keys (ACK = 1, RESET = 2,
DRILL = 3, SILENCE = 4); then press the SILENCE key.
For example,
the default password is
1111. To enter the default password, press the ACK key four times and then press the SILENCE key.
The seven segment display either displays F to indicate an incorrect password, or A to indicate the password is accepted. If the letter F appears, repeat steps 1 and 2; if the letter A appears, continue on.
Reading the LW-401 Display
As the system is programmed, the 7-seg­ment display shows the current program level and sublevel. When a program level is selected, the program level number is shown in the 7-segment display. When the sublevel is selected, the 7-segment display shows the program number followed by a hyphen, then by the sublevel number.
The red zone LEDs are used to indicate which programmed options have been selected. The zone LEDs correspond to the charts in the following programming and testing instructions for each feature. The yellow zone LED acts as a pointer when changing the current programming.
To Select Program Mode
Press the ACK key once. The PROGRAM/ TEST LED flashes and the seven segment display shows the letter P.
To Exit Program Mode
The user can exit the Program mode at any time by pressing the ACK key until the Program/Test status LED turns off and the letter L appears in the seven segment dis­play. Then press the SILENCE key to save the system Configuration (only in the Pro­gram Mode) and exit the Program/Test Mode.
Program Level 1 - Bypass Zones
1. Press the Reset key once to select Program Level 1.
2. Press the Silence key to select the Zone to be bypassed.
Example
: 1-1 bypasses or enables Zone 1.
3. The red zone LED for the selected zone will be on if the zone is enabled and off if bypassed.
4. Press the Drill Key to change the state of the zone.
5. Press the Silence key to select another Zone to be bypassed and return to Step 3.
6. Press the ACK key when done.
Program Level 2 - Bypass Outputs
1. Press the Reset key twice to select Program Level 2.
2. Press the Silence key to select the Output to be bypassed.
Example:
Output Relay 1. The Outputs on each card are organized as indicated in the following table:
Output 1 = Relay 1 Relay 1 Output 2 = Relay 2 Relay 2 Output 3 = Relay 3 Relay 3 Output 4 = Relay 4 Relay 4 Output 5 = OC 1 Relay 5 Output 6 = OC 2 Relay 6 Output 7 = OC 3 Relay 7 Output 8 = OC 4 Relay 8 Note: OC = Open Collector
2-1 bypasses or enables
LWZE-4A LWZR-8
16
Page 20
LW-401 Operation, Installation, and Maintenance ManualLW-401
3. The red zone LED for the selected Output will be on if the Output is enabled and off if bypassed.
4. Press the Drill key to change the state of the Output.
5. Press the Silence key to select another Output to be bypassed and return to Step 3.
6. Press the ACK key when done.
Program Level 3 - Set Zone Types
1. Press the Reset key 3 times to select Program Level 3.
2. Press the Silence key to select the Zone to be programmed.
Example:
for Zone 1.
3. The selected Zone Type is shown by the red zone LED indicated in the following table:
Zone 1 LED = Initiating Zone Type Zone 2 LED = Verified Alarm Zone Type Zone 3 LED = Supervisory Zone Type Zone 4 LED = Generic Zone Type
4. Press the Reset key to advance the pointer (yellow zone LED) to the desired Zone Type.
5. Press the Drill key to activate the desired Zone Type.
3-1 programs the Zone Type
3. The selected NAC type is shown by the red zone LED indicated in the following table:
Zone 1 LED = Steady NAC Zone 2 LED = Temporal Code Zone 3 LED = March Time Code Zone 4 LED = Simple Zone Code Zone 5 LED = Non-Silenceable Output
4. Press the Reset key to advance the pointer (yellow zone LED) to the desired NAC type.
5. Press the Drill key to activate the desired NAC type.
6. Press the Silence key to select the other NAC to be programmed and return to Step 3.
7. Press the ACK key when done.
Program Level 5 - Output Control Matrix
1. Press the Reset key 5 times to select Program Level 5.
2. Press the Silence key to select the Zone to be programmed. Ex: 5-1 allows mapping Zone 1 to Outputs.
3. The selected Zone Map is shown by the red zone LEDs indicated in the following table:
6. Press the Silence key to select another Zone to be programmed and return to Step 3.
7. Press the ACK key when done.
Program Level 4 - Set NAC Types
1. Press the Reset key 4 times to select Program Level 4.
2. Press the Silence key to select the NAC to be programmed.
Example:
the first Bell Circuit.
4-1 programs the NAC type for
Zone 1 LED = Zone Mapped to Output 1 Zone 2 LED = Zone Mapped to Output 2 Zone 3 LED = Zone Mapped to Output 3 Zone 4 LED = Zone Mapped to Output 4 Zone 5 LED = Zone Mapped to Output 5 Zone 6 LED = Zone Mapped to Output 6 Zone 7 LED = Zone Mapped to Output 7 Zone 8 LED = Zone Mapped to Output 8
4. Press the Reset key to advance the pointer (yellow zone LED) to the desired Output.
17
Page 21
LW-401
Operation, Installation, and Maintenance Manual
5. Press the Drill key to map the selected Zone to the desired Output.
6. Press the Silence key to select another Zone to be programmed and return to Step 3.
7. Press the ACK key when done.
Program Level 6 - Set System Timing
1. Press the Reset key 6 times to select Program Level 6.
2. Press the Silence key to select one of the four timing functions to be programmed as indicated in the following table:
Example:
6-1 programs the Alarm
Verification Retard/Reset Timer.
Level Feature
6-1 Verification Retard/Reset Timer 6-2 NAC Inhibit Timer 6-3 NAC Cutoff Timer 6-4 Simplified Zone Code Rounds
Level 6-1 - Set Verification Retard/Reset Timer
1. The selected Retard/Reset Time is shown by the red zone LEDs accord­ing to the following table:
Zone 1 LED = 15 seconds Zone 2 LED = 20 seconds Zone 3 LED = 25 seconds Zone 4 LED = 30 seconds Zone 5 LED = 40 seconds Zone 6 LED = 50 seconds Zone 7 LED = 50 seconds Zone 8 LED = 50 seconds
2. Press the Reset key to advance the pointer (yellow zone LED) to the desired time.
3. Press the Drill key to activate the desired time.
4. Press the ACK key when done.
Level 6-2 - Set NAC Inhibit Timer
1. The selected Inhibit Time is shown by the red zone LEDs as indicated in the following table:
Zone 1 LED = 0 minutes Zone 2 LED = 6 seconds Zone 3 LED = 30 seconds Zone 4 LED = 1 minutes Zone 5 LED = 90 seconds Zone 6 LED = 2 minutes Zone 7 LED = 3 minutes Zone 8 LED = 5 minutes
2. Press the Reset key to advance the pointer (yellow zone LED) to the desired time.
3. Press the Drill key to activate the desired time.
4. Press the ACK key when done.
Level 6-3 - Set NAC Cutoff Timer
1. The selected Cutoff Time is shown by the red zone LEDs as indicated in the following table:
Zone 1 LED = No Cutoff Zone 2 LED = 1 minutes Zone 3 LED = 2 minutes Zone 4 LED = 5 minutes Zone 5 LED = 10 minutes Zone 6 LED = 15 minutes Zone 7 LED = 20 minutes Zone 8 LED = 25 minutes
2. Press the Reset key to advance the pointer (yellow zone LED) to the desired time.
3. Press the Drill key to activate the desired time.
4. Press the ACK key when done.
18
Page 22
LW-401 Operation, Installation, and Maintenance ManualLW-401
Level 6-4 - Set Simplified Zone Code Rounds
1. The selected number of rounds is shown by the red zone LEDs as indicated in the following table:
Zone 3 LED = 3 rounds Zone 4 LED = 4 rounds Zone 5 LED = 5 rounds Zone 6 LED = 6 rounds Zone 7 LED = 7 rounds Zone 8 LED = 8 rounds
2. Press the Reset key to advance the pointer (yellow zone LED) to the desired time.
3. Press the Drill key to activate the desired time.
4. Press the ACK key when done.
Program Level 7 - Set System Password
1. Press the Reset key 7 times to select Program Level 7.
2. Press the Silence key to select the Password digit to be programmed. Example: 7-1 programs the first digit of your password.
3. The selected digit choice is shown by the red zone LED as indicated in the following table:
Zone 1 LED = ACK (1) Zone 2 LED = RESET (2) Zone 3 LED = DRILL (3) Zone 4 LED = SILENCE (4)
4. Press the Reset key to advance the pointer (yellow zone LED) to the desired digit choice.
5. Press the Drill key to activate the desired digit choice.
6. Press the Silence key to select another digit to be programmed and return to Step 3.
7. Press the ACK key when done.
Program Level 8 - Set the AC Fail Signal Delay
1. Press the Reset key 8 times to select Program Level 8.
2. Press the Silence key to select this programming function. There is no other function to be selected. Note: 8-1 programs the AC Fail Signal
Delay.
3. A six-hour delay is activated when the red zone LED for zone 1 is on. If the LED is off, there is no delay.
4. Press the Drill key to activate or deactivate the delay.
5. Press the ACK key when done.
Program Level 9 - Enable System Option Cards
1. Press the Reset key 9 times to select Program Level 9.
2. Press the Silence key to select this programming function. There is no other function to be selected. Note: 9-1 enables the System Option
Cards.
3. The selected Option Cards are shown by the red zone LED as indicated in the following table:
Zone 1 LED = LWZR-8 Enabled Zone 2 LED = LWRA-8B/W, Addr 1 Enabled Zone 3 LED = LWRA-8B/W, Addr 2 Enabled Zone 4 LED = LWCT-1 Enabled Zone 5 LED = Zone Expansion Enabled
19
Page 23
LW-401
Operation, Installation, and Maintenance Manual
4. Press the Reset key to advance the pointer (yellow zone LED) to the desired Option Card.
5. Press the Drill key to activate the desired Option Card.
6. Press the ACK key when done.
Test Mode
The test mode allows the user to test that the LW-401 is operating correctly. There are six levels to the test mode. Each level tests different functions within the LW-401.
Reading the LW-401 Display
As the system is tested, the 7-segment display shows the current test level and sublevel. When a test level is selected, the test level number is shown in the 7-segment display. When the sublevel is selected, the 7-segment display shows the test number followed by a hyphen, then by the sublevel number.
Level 5: Performs Local Display and Remote (LWRA-8B/W) Lamp test.
Level 6: Clears the panel's history events (Alarm, Trouble, and Supervisory).
ENABLING THE TEST MODE
Enter Password
1 . Press the RESET key and hold it down
while simultaneously pressing the DRILL key. The System TROUBLE status LED lights steady, and the letter E flashes on the seven segment display.
2. Enter the password by pressing the appropriate keys (ACK = 1, RESET = 2,
DRILL = 3, SILENCE = 4); then press the SILENCE key. The seven segment
display either displays F to indicate an incorrect password, or A to indicate the password is accepted. If the letter F appears, repeat steps 1 and 2; if the letter A appears, continue on.
TEST LEVEL DESCRIPTIONS
• Level 1: Enables the One Person
System Test Function.
Level 2: Tests the Main board Alarm and Trouble relays and NAC relays.
Level 3: Tests the Optional Module Relays and Open Collector Output Drivers.
Level 4: Displays the Alarm, Trouble, and Supervisory history on the Initiating Device Circuit Zone status LEDs.
20
To Select Test Mode
Press the ACK key twice. The PROGRAM/ TEST status LED on the front panel lights
steady and the seven segment display shows the letter t.
To Exit Test Mode
The user can exit the Test mode at any time by pressing the ACK key until the Program/ Test status LED turns off and the letter L appears in the seven segment display. Then press the SILENCE key to exit the Program/ Test Mode.
Page 24
Test Level 1—One Person System Test
Important
Inform the person in charge of the LW-401 fire alarm system that a One Person Test is to be performed and that part or all of the fire detection system will be disabled. It is also advisable (or may be required) to notify the fire department of the test.
LW-401 Operation, Installation, and Maintenance ManualLW-401
Level Feature
2-1 Test System Alarm Relay 2-2 Test NAC 1 Relay 2-3 Test System Trouble Relay 2-4 Test NAC 2 Relay
3. Press the Drill key to change the state of the selected relay. Please note that testing the NAC relays will activate the appliances on that circuit.
The One Person Test feature allows the installer to test the system in the following two ways.
• When a device is alarmed, the system notification appliances sound and the appropriate IDC alarm LED lights for 2 seconds.
• When a device is alarmed, the sounding of the appliances is eliminated—only the system display annunciates.
1. Press the Reset key once to select Test Level 1.
2. Press the Silence key once or twice to select the type of test you wish to perform.
Example:
1-1 enables test with notification appliances; 1-2 enables test without appliances.
4. Press the ACK key when done.
Test Level 3 - Test Optional Outputs
1. Press the Reset Key 3 times to select Test Level 3.
2. Press the Silence Key to select one of the eight outputs to be tested as indicated in the following table:
Example:
Level Feature
3-1 Test Output 1 3-2 Test Output 2 3-3 Test Output 3 3-4 Test Output 4 3-5 Test Output 5 3-6 Test Output 6 3-7 Test Output 7 3-8 Test Output 8
The Outputs on each card are organized according to the following table:
3-1 tests Relay Output 1.
Test Level 2 - Test System Relays
1. Press the Reset key twice to select Test Level 2.
2. Press the Silence key to select one of the four relays to be tested as indicated in the following table:
Example:
Relay.
2-1 tests the System Alarm
LWZE-4A LWZR-8
Output 1 = Relay 1 Relay 1 Output 2 = Relay 2 Relay 2 Output 3 = Relay 3 Relay 3 Output 4 = Relay 4 Relay 4 Output 5 = OC 1 Relay 5 Output 6 = OC 2 Relay 6 Output 7 = OC 3 Relay 7 Output 8 = OC 4 Relay 8 Note: OC = Open Collector
21
Page 25
LW-401
Operation, Installation, and Maintenance Manual
3. Press the Drill key to change the state of the selected output.
4. Press the ACK key when done.
Test Level 4 - Last Event Record
1. Press the Reset key 4 times to select Test Level 4.
2. Press the Silence key to select the event to be reviewed per the following table:
Example:
alarm.
Level Feature
4-1 Review Last Alarm 4-2 Review Last Zone Trouble 4-3 Review Last Verification 4-4 Review Last Supervisory
3. The Zone Alarm LED for the last zone in alarm will be on. Similarly, the Zone Trouble LED will be on for the last zones in supervisory and trouble conditions.
4-1 reviews the last zone in
Test Level 6 - Clear the Last Event Record
1. Press the Reset key 6 times to select Test Level 6.
2. Press the Silence key to select this function. There is no other function to be selected.
3. Press the Drill key to clear the event record.
4. Press the ACK key when done.
4. Press the ACK key when done.
Test Level 5 - Lamp Test
1. Press the Reset key 5 times to select Test Level 5.
2. Press the Silence key to select the lamps to be tested as indicated in the following table:
Example:
Level Feature
5-1 Test the Local Display 5-2 Test Remote Annunciators
5-1 tests Local Display.
3. Press and hold the Drill key to turn the lamps on.
4. Press the ACK key when done.
22
Page 26
LW-401 Operation, Installation, and Maintenance ManualLW-401
1ELBAT
leveLlevelbuS noitpircseD
SLEVELEDOMMARGORP
1 1
2 1
3 1
4 1
2 3 4 5 6 7 8
2 3 4 5 6 7 8
2 3 4 5 6 7 8
2
1enoZepyTtiucriCeciveDgnitaitinI 2enoZepyTtiucriCeciveDgnitaitinI 3enoZepyTtiucriCeciveDgnitaitinI 4enoZepyTtiucriCeciveDgnitaitinI 5enoZepyTtiucriCeciveDgnitaitinI 6enoZepyTtiucriCeciveDgnitaitinI 7enoZepyTtiucriCeciveDgnitaitinI 8enoZepyTtiucriCeciveDgnitaitinI
1enoZtiucriCeciveDgnitaitinIssapyB/elbanE 2enoZtiucriCeciveDgnitaitinIssapyB/elbanE 3enoZtiucriCeciveDgnitaitinIssapyB/elbanE 4enoZtiucriCeciveDgnitaitinIssapyB/elbanE 5enoZtiucriCeciveDgnitaitinIssapyB/elbanE 6enoZtiucriCeciveDgnitaitinIssapyB/elbanE 7enoZtiucriCeciveDgnitaitinIssapyB/elbanE 8enoZtiucriCeciveDgnitaitinIssapyB/elbanE
1yaleRtuptuO8-RZWLroA8-EZWL,A4-EZWLlanoitpOssapyB/elbanE 2yaleRtuptuO8-RZWLroA8-EZWL,A4-EZWLlanoitpOssapyB/elbanE 3yaleRtuptuO8-RZWLroA8-EZWL,A4-EZWLlanoitpOssapyB/elbanE 4yaleRtuptuO8-RZWLroA8-EZWL,A4-EZWLlanoitpOssapyB/elbanE
)ylno8-RZWLroA8-EZWL-5yaleRro(1tuptuOrotcelloCnepOA4-EZWLlanoitpOssapyB/elbanE )ylno8-RZWLroA8-EZWL-6yaleRro(2tuptuOrotcelloCnepOA4-EZWLlanoitpOssapyB/elbanE )ylno8-RZWLroA8-EZWL-7yaleRro(3tuptuOrotcelloCnepOA4-EZWLlanoitpOssapyB/elbanE )ylno8-RZWLroA8-EZWL-8yaleRro(4tuptuOrotcelloCnepOA4-EZWLlanoitpOssapyB/elbanE
1tiucriCecnailppAnoitacifitoNrofepyTgnilangiSsmargorP 2tiucriCecnailppAnoitacifitoNrofepyTgnilangiSsmargorP
5 1
2 3 4 5 6 7 8
6 1
2 3 4
7 1
2 3 4
8 1yaleDlangiSliaFCAtceleS
9 1 A8-EZWL/A4-EZWLelbasiD/elbanE;1-TCWLelbasiD/elbanE;W/B8-ARWLelbasiD/elbanE;8-RZWLelbasiD/elbanE
1tiucriCenoZgnitaitinIwolloFotsyaleR/rotcelloCnepOsmargorP 2tiucriCenoZgnitaitinIwolloFotsyaleR/rotcelloCnepOsmargorP 3tiucriCenoZgnitaitinIwolloFotsyaleR/rotcelloCnepOsmargorP 4tiucriCenoZgnitaitinIwolloFotsyaleR/rotcelloCnepOsmargorP 5tiucriCenoZgnitaitinIwolloFotsyaleR/rotcelloCnepOsmargorP 6tiucriCenoZgnitaitinIwolloFotsyaleR/rotcelloCnepOsmargorP 7tiucriCenoZgnitaitinIwolloFotsyaleR/rotcelloCnepOsmargorP 8tiucriCenoZgnitaitinIwolloFotsyaleR/rotcelloCnepOsmargorP
remiTnoitacifireVmralAehtsmargorP
remiTtibihnItiucriCecnailppAnoitacifitoNehtsmargorP remiTffotuCtiucriCecnailppAnoitacifitoNehtsmargorP
)egnartnuoc8ot3(tnuoCdnuoRedoCenoZehtsmargorP
1tigiDdrowssaPsmargorP 2tigiDdrowssaPsmargorP 3tigiDdrowssaPsmargorP 4tigiDdrowssaPsmargorP
23
Page 27
LW-401
Operation, Installation, and Maintenance Manual
leveLlevelbuSnoitpircseD
2ELBAT
SLEVELEDOMTSET
1 1
2
2 1
2 3 4
3 1
2 3 4 5 6 7 8
4 1
2 3 4
5 1
2
6 1droceRtnevEraelC
detavitcAstiucriCecnailppAnoitacifitoNhtiwtseTmetsySnosrePenO
decneliSstiucriCecnailppAnoitacifitoNhtiwtseTmetsySnosrePenO
yaleRmralAdraoBniaMtseT
yaleR1CANtseT
yaleRelbuorTdraoBniaMtseT
yaleR2CANtseT
1yaleRtuptuO8-RZWLroA8-EZWL,A4-EZWLlanoitpOtseT 2yaleRtuptuO8-RZWLroA8-EZWL,A4-EZWLlanoitpOtseT 3yaleRtuptuO8-RZWLroA8-EZWL,A4-EZWLlanoitpOtseT 4yaleRtuptuO8-RZWLroA8-EZWL,A4-EZWLlanoitpOtseT
)ylno8-RZWLroA8-EZWL-5yaleRro(1tuptuOrotcelloCnepOA4-EZWLlanoitpOtseT )ylno8-RZWLroA8-EZWL-6yaleRro(2tuptuOrotcelloCnepOA4-EZWLlanoitpOtseT )ylno8-RZWLroA8-EZWL-7yaleRro(3tuptuOrotcelloCnepOA4-EZWLlanoitpOtseT )ylno8-RZWLroA8-EZWL-8yaleRro(4tuptuOrotcelloCnepOA4-EZWLlanoitpOtseT
tnevEmralAtsaLyalpsiD
tnevEelbuorTtsaLyalpsiD
tnevEnoitacifireVtsaLyalpsiD
tnevEyrosivrepuStsaLyalpsiD
tseTpmaLyalpsiDlacoL
tseTpmaLyalpsiDetomeR
24
Page 28
4
LW-401 Operation, Installation, and Maintenance ManualLW-401
CHECKOUT PROCEDURE
Prior to installing devices on bases and applying power to the LW-401 system, follow the Field Wiring Checkout Procedure (Refer to Table 5, page 27).
On completion of installation, the system should be thoroughly tested. Check supervi­sion functions and the functional operation of each external circuit, as well as the basic system control panel functions.
yalpsiDedoCtluaFelbuorTesuaCelbissoP
1 liaFrewoPCAecruoSrewoPCAkcehC
2 ecnailppAnoitacifitoN
tluaF1tiucriC
3 ecnailppAnoitacifitoN
tluaF2tiucriC
Maintenance
PERIODIC INSPECTION AND TESTING
To insure proper and reliable operation, inspect and test the system to the latest edition of NFPA 72
SERVICING
If troubleshooting and servicing guidance is needed, contact your local Cerberus Pyro­tronics Authorized Service Representative.
3ELBAT
tuonworB
eriWnepO
eriWdetrohS
eriWnepO
eriWdetrohS
Signaling Systems.
GNITOOHSELBUORTTLUAFMETSYS
nepOgniriWtiucriCCA
esuFCA1FnepO
rotsiseReniLfodnEgnissiM
drawkcaBderiWeciveDCAN
deziraloPtoNeciveDCAN
rotsiseReniLfodnEgnissiM
drawkcaBderiWeciveDCAN
deziraloPtoNeciveDCAN
4 tluaFdnuorG tiucriCotdnuorGhtraEmorfmhogem1nahtsseL
5 tluaFeiTlapicinuMdeppirTsieiTlapicinuM
6 tluaFyrettaBgnissiMsiyrettaB
7 tluaFnoitarugifnoCmetsyS104-WLehterugifnoceR
8 tluaFtroPyrailixuAeniLATADnotrohS
9 dessapyBtuptuOdessapyBtuptuOlortnoCynA
0 eruliaFerawdraH deliafsahrossecorpdraobniaM104-WLehT
KNALB ylfeirBnonruTsebortS/slleB
daBsieiTlapicinuM
esuFyrettaB3FnepO
gnidnopseRtoN/tneserPtoNeludoM8-RZWL
gnidnopseRtoN/tneserPtoNeludoMW/B8-ARWL
gnidnopseRtoN/tneserPtoNeludoM1-TCWL
.draobehtecalpeR
tseTgniruDffotuhSneht
dedaolrevOsiCAN
tiucriCehtnoseciveDllafowarDtnerruCkcehC
25
Page 29
LW-401
Operation, Installation, and Maintenance Manual
4ELBAT
SNOITALUCLACYRETTABROFSTNEMERIUQERLACIRTCELE
TNEMEGANAMREWOPDNA
tnerruCdraoBniaM A011.0A021.0
:)4-1senoZ(tnerruCCDI senoZCDIforebmuN
=)ybdnatS(A900.0________
=)mralA(A021.0________
CANrepA5.1=<tnerruC:tnerruCeciveDCAN
1etoNeeS________1CAN
________2CAN A0
A5.0=<tnerruC:tnerruCtroPyrailixuA
1etoNeeSeludoM8-EZWL
A810.0tnerruCybdnatS
A810.0tnerruCmalA
syaleRdemmargorPforebmuN
=A620.0x________
A600.0tnerruCybdnatSeludoMA4-EZWL
A600.0tnerruCmralA
syaleRdemmargorPforebmuN
=A620.0x________
:)8-5senoZ(tnerruCCDI
senoZCDIforebmuN
=)ybdnatS(A900.0x________
=)mralA(A021.0x________
A600.0tnerruCybdnatSeludoMA8-EZWL
A600.0tnerruCmralA
:)8-5senoZ(tnerruCCDI
senoZCDIforebmuN
=)ybdnatS(A900.0x________
=)mralA(A021.0x________
eludoMW/B8-ARWL
seludoMW/B8-ARWLforebmuN
=)ybdnatS(A010.0x________
=)mralA(A240.0x________
eludoM1-TCWL
=ybdnatS
=mralA
latoTA______A______
=22.1x)tnerruCH-AmralA+tnerruCH-AybdnatS( eziSyrettaBH-AmuminiM
otlauqeronahtsselsnaem=<
ybdnatS
tnerruC
A______
A0
A0
A______
A0
A______
A0
A______ A0
A______
mralA
tnerruC
A0 A______
A______ A______
A______
A______
A______
A______
A0 A______
NOTE:
A______
1. In addition to deter­mining the required
A_____ A0
A0 A______
battery size, consider­ation must be given to the overall current drawn by the system. The total system
A______ A0
A0 A______
current capability is
3.5 amps at 24 volts. The total alarm
A050.0 A0
A0 A543.0
current must not exceed 3.5 amps for any combination of the basic system plus any additional
tnerruCH-AybdnatS)06ro,84,42(sruoHybdnatStnerruCybdnatSlatoT
H-A______________=__________________x___________
modules used. When installing additional modules, the current
tnerruCH-AmralA).niM5(rotcaFreilpitluMH-AtnerruCmralAlatoT
H-A______________=380.0x___________
H-A______________
available for the NAC circuits and auxiliary port must be derated to keep the total alarm current below 3.5 amps.
26
Page 30
LW-401 Operation, Installation, and Maintenance ManualLW-401
TABLE 5TABLE 5
TABLE 5
TABLE 5TABLE 5
FIELD WIRING CHECKOUT PROCEDUREFIELD WIRING CHECKOUT PROCEDURE
FIELD WIRING CHECKOUT PROCEDURE
FIELD WIRING CHECKOUT PROCEDUREFIELD WIRING CHECKOUT PROCEDURE
MEASURE RESISTANCE BETWEEN
TERMINAL AND TERMINAL
Meter connection for Field Wiring Checkout Procedure Steps 1 and 2: Positive lead connected to BL1-1 or BL2-1 and negative lead connected to BL1-2 or BL2-2.
DESIRED
RESULTS
PROBABLE CAUSE IF
RESULTS DIFFER
1. Measure Notification Appliance Circuit Loop Resistance
Before making resistance measurements, short the End of Line Resistor (10K ohms).
BL1-1 BL2-1
BL1-2 BL2-2
<3.0 ohms <3.0 ohms
Line open Line too long
2. Measure Notification Appliance Circuit End of Line Resistance
Before making resistance measurements, remove the short from the previous step.
BL1-1 BL2-1
BL1-2 BL2-2
10K ohms 10K ohms
Line shorted; Line open Wrong End of Line Resistor value NAC Device wired backward NAC Device not polarized
3. Check for Ground Fault
BL1-1 BL1-2
BL2-1 BL2-2
Meter connection to Field Wiring Checkout Procedure Steps 4, 5, and 6: Positive lead connected to IDC + and negative lead connected to IDC -. Do not connect initiating devices to the ID loop for resistance measurements in Field Wiring Checkout Procedure Steps 4, 5, and 6.
To all other Main Control module terminals excluding NAC 1
To all other Main Control module terminals excluding NAC 2
> 1 megohm
> 1 megohm
Line shorted
Line shorted
4. Measure Initiating Device Circuit Loop Resistance
Before making resistance measurements, short the End of Line Resistor (3.9K Ohms).
IDC1 + IDC2 + IDC3 + IDC4 +
IDC1 ­ IDC2 ­ IDC3 ­ IDC4 -
< 25 ohms < 25 ohms < 25 ohms < 25 ohms
Line open; Line too long
5. Measure Initiating Device Circuit End of Line Resistance
Before making resistance measurements, remove the short from the previous step.
IDC1 + IDC2 + IDC3 + IDC4 +
IDC1 ­ IDC2 ­ IDC3 ­ IDC4 -
3.9K ohms
3.9K ohms
3.9K ohms
3.9K ohms
Line shorted; Line open Wrong End of Line Resistor value
6. Check for Ground Fault
IDC1 + IDC2 + IDC3 + IDC4 +
To all other Main Control module terminals excluding the IDC -
> 1 megohm
Line shorted
IDC1 ­IDC2 ­IDC3 ­IDC4 -
To all other Main Control module terminals excluding the IDC +
> 1 megohm
Line shorted
27
Page 31
LW-401
Operation, Installation, and Maintenance Manual
6ELBAT
SNOITARUGIFNOCTLUAFED
leveLlevelbuSnoitpircseDresUyrotcaF
1 1
2 1
3 1
1enoZtiucriCeciveDgnitaitinI 2 3 4 5 6 7 8
2 3 4 5 6 7 8
1enoZ 2 3 4 5 6 7 8
2enoZ
3enoZ
4enoZ
5enoZ
6enoZ
7enoZ
8enoZ
2enoZtiucriCeciveDgnitaitinI 3enoZtiucriCeciveDgnitaitinI 4enoZtiucriCeciveDgnitaitinI 5enoZtiucriCeciveDgnitaitinI 6enoZtiucriCeciveDgnitaitinI 7enoZtiucriCeciveDgnitaitinI 8enoZtiucriCeciveDgnitaitinI
1yaleRtuptuOA4-EZWLlanoitpO 2yaleRtuptuOA4-EZWLlanoitpO 3yaleRtuptuOA4-EZWLlanoitpO 4yaleRtuptuOA4-EZWLlanoitpO
1tuptuOrotcelloCnepOA4-EZWLlanoitpO 2tuptuOrotcelloCnepOA4-EZWLlanoitpO 3tuptuOrotcelloCnepOA4-EZWLlanoitpO 4tuptuOrotcelloCnepOA4-EZWLlanoitpO
delbanE delbanE delbanE delbanE delbanE delbanE delbanE delbanE
delbanE delbanE delbanE delbanE delbanE delbanE delbanE delbanE
gnitaitinI gnitaitinI gnitaitinI gnitaitinI gnitaitinI gnitaitinI gnitaitinI gnitaitinI
delbanE delbanE delbanE delbanE delbanE delbanE delbanE delbanE
delbanE delbanE delbanE delbanE delbanE delbanE delbanE delbanE
gnitaitinI gnitaitinI gnitaitinI gnitaitinI
desutoN desutoN desutoN desutoN
4 1
2
5 1
2 3 4 5 6 7 8
6 1
2 3 4
7 1
2 3 4
8 1yaleDlangiSliaFCAteSsruoH6sruoH6
9 1;2dna1rddAW/B8-ARWL;8-RZWLlanoitpO
remiTteseRdrateR
remiTtibihnI
remiTffotuC
1tigiDdrowssaP 2tigiDdrowssaP 3tigiDdrowssaP 4tigiDdrowssaP
1tiucriCecnailppAnoitacifitoN 2tiucriCecnailppAnoitacifitoN
1tiucriCenoZgnitaitinI 2tiucriCenoZgnitaitinI 3tiucriCenoZgnitaitinI 4tiucriCenoZgnitaitinI 5tiucriCenoZgnitaitinI 6tiucriCenoZgnitaitinI 7tiucriCenoZgnitaitinI 8tiucriCenoZgnitaitinI
tnuoCdnuoRedoCenoZ
A8-EZWL/A4-EZWL;1-TCWL
ydaetS ydaetS
lortnocoN lortnocoN lortnocoN lortnocoN lortnocoN lortnocoN lortnocoN lortnocoN
sdnoces51 0 0 3
1 1 1 1
A8EZWL/A4-EZWL
delbanE
ydaetS ydaetS
lortnocoN lortnocoN lortnocoN lortnocoN lortnocoN lortnocoN lortnocoN lortnocoN
sdnoces51 0 0 3
1 1 1 1
delbasiD
28
Page 32
LW-401 Operation, Installation, and Maintenance ManualLW-401
TABLE 7
PROGRAMMING SHEET
Level Sublevel Description
1 1 Initiating Device Circuit Zone 1 Enabled Bypassed
2 Initiating Device Circuit Zone 2 Enabled Bypassed 3 Initiating Device Circuit Zone 3 Enabled Bypassed 4 Initiating Device Circuit Zone 4 Enabled Bypassed 5 Initiating Device Circuit Zone 5 Enabled Bypassed 6 Initiating Device Circuit Zone 6 Enabled Bypassed 7 Initiating Device Circuit Zone 7 Enabled Bypassed 8 Initiating Device Circuit Zone 8 Enabled Bypassed
2 1 Optional LWZE-4A/LWZE-8A/LWZR-8 Output 1 Enabled Bypassed
2 Optional LWZE-4A/LWZE-8A/LWZR-8 Output 2 Enabled Bypassed 3 Optional LWZE-4A/LWZE-8A/LWZR-8 Output 3 Enabled Bypassed 4 Optional LWZE-4A/LWZE-8A/LWZR-8 Output 4 Enabled Bypassed 5 Optional LWZE-4A/LWZE-8A/LWZR-8 Output 5 Enabled Bypassed 6 Optional LWZE-4A/LWZE-8A/LWZR-8 Output 6 Enabled Bypassed 7 Optional LWZE-4A/LWZE-8A/LWZR-8 Output 7 Enabled Bypassed 8 Optional LWZE-4A/LWZE-8A/LWZR-8 Output 8 Enabled Bypassed
3 1 Zone 1 Initiating Verified Supervisory Generic
2 Zone 2 Initiating Verified Supervisory Generic 3 Zone 3 Initiating Verified Supervisory Generic 4 Zone 4 Initiating Verified Supervisory Generic 5 Zone 5 Initiating Verified Supervisory Generic 6 Zone 6 Initiating Verified Supervisory Generic 7 Zone 7 Initiating Verified Supervisory Generic 8 Zone 8 Initiating Verified Supervisory Generic
4 1 NAC 1 Steady Temporal March SZC Non-Silenceable
2 NAC 2 Steady Temporal March SZC Non-Silenceable
5 1 IDC 1 Output 1 2 3 4 5 6 7 8
2 IDC 2 Output 1 2 3 4 5 6 7 8 3 IDC 3 Output 1 2 3 4 5 6 7 8 4 IDC 4 Output 1 2 3 4 5 6 7 8 5 IDC 5 Output 1 2 3 4 5 6 7 8 6 IDC 6 Output 1 2 3 4 5 6 7 8 7 IDC 7 Output 1 2 3 4 5 6 7 8 8 IDC 8 Output 1 2 3 4 5 6 7 8
6 1 Retard Reset Timer 15 20 25 30 40 50 50 50 seconds
2 Inhibit Timer 0 6 30 60 90 120 180 300 seconds 3 Cutoff Timer 0 1 2 5 10 15 20 25 minutes 4 Zone Code Round Count (3 to 8)=
7 1 Password Digit 1 =
2 Password Digit 2 = 3 Password Digit 3 = 4 Password Digit 4 =
8 1 AC Fail Signal Delay 0 Hours 6 Hours 9 1 LWZR-8 Enabled #1 LWRA-8B/W Enabled #2 LWRA-8B/W Enabled
LWCT-1 Enabled LWZE-4A/LWZE-8A Enabled
29
Page 33
LW-401
Operation, Installation, and Maintenance Manual
30
Page 34
WARNING: This equipment generates, uses, and can radiate radio
frequency energy and if not installed and used in accordance with the instructions manual, may cause interference to radio communi­cations. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference.
Page 35
P/N 315-095997FA-2
(446106)ww
Loading...