Fantech SHR 8005R Installation Manual

Page 1
CC
C
U
S
R
Installation Manual
IMPORTANT - PLEASE READ AND SAVE THIS
MANUAL BEFORE INSTALLING UNIT
CAUTION - Before installation, careful consideration must be given to how
this system will operate if connected to any other piece of mechanical equip­ment, i.e. a forced air furnace or air handler, operating at a higher static. After installation, the compatibility of the two pieces of equipment must be con­firmed by measuring the airflow’s of the Heat Recovery Ventilators. It is always important to assess how the operation of any HRV may interact with vented combustion equipment (i.e. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.).
NEVER - install a ventilator in a situation where its normal operation, lack of
operation or partial failure may result in the backdrafting or improper func­tioning of vented combustion equipment!!!
Heat Recovery Ventilators
Your ventilation system should be installed in conformance with the appropriate provincial or state require­ments or in the absence of such requirements with local building codes.
Pool and Spa Ventilation Models
SHR 8005R • SHR 14105R
Page 2
Page 3
SHR 8005R
0
50 100 150 200 250 275 300 350 400 450 500 550 600 650 700 750 800 850 900 950
2007-10-01
Thermal Effectiveness
10%
30%
50%
70%
90%
0 400 800 1200
Airflow (cfm)
Effectiveness
0 189 378 566
Airflow (l/s)
0
50 100 150 200 250 275 300 350 400 450 500 550 600 650 700 750 800 850 900 950
2007-10-01
Airflow Performance
0.0
0.4
0.8
1.2
1.6
0 400 800 1200
Airflow (cfm)
External Static Pressure, (in wg)
0
99
199
298
0 189 378 566
Airflow (l/s)
External Static Pressure (Pa)
High Medium Low Recirculation
Light Commercial HRV
The Fantech SHR8005R is designed to provide an economi­cal solution for high humidity applications such as indoor swimming pools, spas and fit­ness facilities. The higher humid­ity generation rate in these appli­cations leads to annoying window
condensation, mold and struc­ture deterioration. It’s designed to reduce the occurrence of condensation in the indoor environment by first operating in recirculation mode, moving air around the structures, sweeping windows dry and eliminating troublesome cold spots, then switching to air exchange mode as needed. Air exchange mode simply exhausts humid air to the outside and replaces it with drier air from outside. The airstreams are separated by an energy efficient heat recovery core which uses the energy in the exhaust air to lower the load on the HVAC system. Automatic defrost and provisions for condensation are standard.
APPLICATIONS INCLUDE:
• Indoor Pools • Night Clubs
• Spa's • Locker Room
• Health Centers • High humidity Applications
POWER & WEIGHT
• Volts 120V
• Amperage 5.4 Amps Total
• Weight 80.3 Kg (177 Lbs)
• Shipping Weight 98 Kg (217 Lbs)
• Blowers (x2) 115V, 60 Hz, 2.7 Amps
• Phase Single
Airflow Performance
Airflow (l/s)
External Static Pressure, (in wg)
Airflow (cfm)
Thermal Effectiveness
Airflow (l/s)
External Static Pressure (Pa)
SPECIFICATIONS
CASE 20 gauge G90 galvanized steel coated with baked
powder paint, insulated with 25mm (1 inch) and 50mm (2 inch) on outdoor air side foil-faced high density polystyrene foam for condensation control.
BLOWERS Two (2) maintenance-free Ebm-Papst™ backward inclined motorized impellers with permanently lubricated sealed ball bearings and (TOP) thermal overload protected.
HEAT RECOVERY CORES The heat recovery cores are fixed plate cross-flow heat exchanger using 1100 alloy aluminum and capable of transferring sensible heat between air streams. The heat recovery cor inducing geometry in order to maximize heat transfer while allowing an effective evacuation of condensate. The plates are hemmed to avoid cross-contamination of airstreams.
FILTERS The exhaust and fresh air streams are protected by MERV1 washable filters constructed to meet UL Class2. Optional MERV6 filters are direct replacement to the MERV1. Use of MERV6 filters will add an additional system pressure of 72 Pa (0.29in.wg) at 378 l/s (800cfm).
MOUNTING Unit can be rod mounted or seated on a platform. Flanged connections are provided for suitable ductwork connections. Unit shall be adaptable for easy service of electrical components.
CONTROLS External three (3) position (Low/Standby/Medium) rocker switch that will offer continuous ventilation. Compatible with all Fantech HRV controls.
FROST CONTROL During the defrost sequence, a motorized damper temporarily blocks the incoming fresh air stream so that the warm air from the building can circulate thr HRV. The exhaust blower shuts down and the supply blower switches into high speed to maximize the effectiveness of the defrost strategy.
SERVICEABILITY Unit has hinged or screwed access panels on front and back. Cores, filters, motors and drain pan are serviceable from either sides of the unit. Fan assemblies are mounted on a removable sliding base. Heat recovery cor mounted in slide-out rails for ease of inspection, removal and cleaning. Accessibility to the electrical box is maintained for any unit installation.
es are engineered with a turbulence
ough the
es are
Effectiveness
Airflow (cfm)
3
Page 4
SHR 8005R Light Commercial HRV
9
24mm(36.4")
203mm(8")
576mm(22.7")
66mm(2.6")
818mm(32.2")
5
08mm(20")
653mm(25.7")
559mm(22")
9
14mm(36")
888mm(35")
855mm(33.7")
ELECTRIC BOX (can be relocated in the field to either the front or the back of the cabinet)
LOW VOLTAGE C
ONTROL PANEL
HIGH VOLTAGE ENTRY
63mm(2.5")
513mm(20.2")
Outdoor or Recirculated Air
Indoor Air
Standard Configuration as shipped from factory.
Outdoor or Recirculated Air
Indoor Air
Dimensions
PORT CONFIGURATION
The unit has access doors on the front and back. Also, the main control panel may be moved from front to back allowing for ducting layout.
Outdoor or
Recirculated
Airflow
Fresh Air
from Outside
Air
Indoor
Air
Factory Setting. Unit may be easily reversed in field.
Stale Air
from Inside
Indoor
Air
Recirculated Air from Building
Outdoor or
Recirculated
Air
Stale Air
4
to Outside
Fresh Air
to Inside
Recirculated Air to Inside
Page 5
SHR 14105R
0
50 100 150 200 250 275 300 350 400 450 500 550 600 650 700 750 800 850 900 950
1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550
0.0
0.4
0.8
1.2
1.6
0 600 1200 1800
0
99
199
298
398
0 283 566 849
Airflow Performance
0.0
0.5
1.0
1.5
2.0
0 600 1200 1800
Airflow (cfm)
External Static Pressure, (in wg)
0
125
251
376
0 283 566 849
Airflow (l/s)
External Static Pressure (Pa)
High Recirculation Medium Low
0
50 100 150 200 250 275 300 350 400 450 500 550 600 650 700 750 800 850 900 950
1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550
2007-10-01
200
1400
Termal Effectiveness
30%
50%
70%
90%
0 600 1200 1800
Airflow (cfm)
Effectiveness
0 283 566 849
Airflow (l/s)
Light Commercial HRV
The Fantech SHR14105R is designed to provide an economi­cal solution for high humidity applications such as indoor swimming pools, spas and fit­ness facilities. The higher humid­ity generation rate in these appli­cations leads to annoying window
condensation, mold and struc­ture deterioration. It’s designed to reduce the occurrence of condensation in the indoor environment by first operating in recirculation mode, moving air around the structures, sweeping windows dry and eliminating troublesome cold spots, then switching to air exchange mode as needed. Air exchange mode simply exhausts humid air to the outside and replaces it with drier air from outside. The airstreams are separated by an energy efficient heat recovery core which uses the energy in the exhaust air to lower the load on the HVAC system. Automatic defrost and provisions for condensation are standard.
APPLICATIONS INCLUDE:
• Indoor Pools • Night Clubs
• Spa's • Locker Room
• Health Centers • High humidity Applications
POWER & WEIGHT
• Volts 120V
• Amperage 10.6 Amps Total
• Weight 116 Kg (255 Lbs)
• Shipping Weight 134 Kg (295 Lbs)
• Blowers (x4) 115V, 60 Hz, 2.7 Amps
• Phase Single
Airflow Performance
Airflow (l/s)
External Static Pressure, (in wg)
Effectiveness
Airflow (cfm)
Thermal Effectiveness
Airflow (l/s)
SPECIFICATIONS
CASE 20 gauge G90 galvanized steel coated with baked
powder paint, insulated with 25mm (1 inch) and 50mm (2 inch) on outdoor air side foil-faced high density polystyrene foam for condensation control.
BLOWERS Four (4) maintenance-free Ebm-Papst™ backward inclined motorized impellers with permanently lubricated sealed ball bearings and (TOP) thermal overload protected.
HEAT RECOVERY CORE The Heat recovery Cores are fixed plate cross-flow heat exchanger using 1100 alloy aluminum and capable of transferring sensible heat between air streams. The heat recovery cor inducing geometry in order to maximize heat transfer while allowing an effective evacuation of condensate. The plates are hemmed to avoid cross-contamination of airstreams.
FILTERS The exhaust and fresh air streams are protected by MERV1 washable filters constructed to meet UL Class2. Optional MERV6 filters are direct replacement to the MERV1. Use of MERV6 filters will add an additional system pressure of 90 Pa (0.36in.wg) at 665 l/s (1410cfm).
MOUNTING Unit can be rod mounted or seated on a platform. Flanged connections are provided for suitable ductwork connections. Unit shall be adaptable for easy service of electrical components.
CONTROLS External three (3) position (Low/Standby/Medium) rocker switch that will offer continuous ventilation. Compatible with all Fantech HRV/ERV controls.
FROST CONTROL During the defrost sequence, a motorized damper temporarily blocks the incoming fresh air stream so that the warm air from the building can circulate thr HRV. The exhaust blower shuts down and the supply blower switches into high speed to maximize the effectiveness of the defrost strategy.
SERVICEABILITY Unit has hinged or screwed access panels on front and back. Cores, filters, motors and drain pan are serviceable from either sides of the unit. Fan assemblies are
External Static Pressure (Pa)
mounted on a removable sliding base. Heat recovery cor mounted in slide-out rails for ease of inspection, removal and cleaning. Accessibility to the electrical box is maintained for any unit installation.
es are engineered with a turbulence
ough the
es are
Airflow (cfm)
5
Page 6
SHR 14105R Light Commercial HRV
914mm(36")
559mm(22")
1199mm(47.2")
1305mm(51.4")
203mm(8")
66mm(2.6")
576mm(22.7")
610mm(24")
653mm(25.7")
855mm(33.7")
888mm(35")
513mm(20.2")
H
IGH VOLTAGE
ENTRY
LOW VOLTAGE
CONTROL PANEL
E
LECTRIC BOX (can be relocated in the field
to either the front or the back of the cabinet)
63mm(2.5")
Outdoor or Recirculated Air
Indoor Air
Standard Configuration as shipped from factory.
Outdoor or Recirculated Air
Indoor Air
Dimensions
PORT CONFIGURATION
The unit has access doors on the front and back. Also, the main control panel may be moved from front to back allowing for ducting layout.
Outdoor or
Recirculated
Airflow
Fresh Air
from Outside
Air
Indoor
Air
Factory Setting. Unit may be easily reversed in field
Stale Air
from Inside
Indoor
Air
Recirculated Air from Building
Outdoor or
Recirculated
Air
Stale Air
6
to Outside
Fresh Air
to Inside
Recirculated
Air to Inside
Page 7
MODES OF OPERATION
1. Continuous / Ventilation Mode
In this mode of operation, both fans are operating and exchanging air with the outside. The heat recovery ventilator (HRV) constantly exchanges the air at the rate you select, either at low or medium speed, and switches to high speed when activated by an optional remote control. Continuous mode is recommended, since pollutants are slowly but constantly being generated in a building.
2. Recirculation Mode
In recirculation mode, the supply motor continues to run and a damper moves to block off air entering from outside, drawing air instead from the conditioned space. The exhaust to outside motor is OFF when in recir
culation mode.
3. Intermittent / Standby Mode
The system is always on standby and operates at high speed when activated by an optional remote control (required): "Standby" should be selected if the user wishes to stop the unit from continuous exchange.
4. Defrost
A preset defrost sequence is activated at an outdoor air temperature of -5ºC (23ºF) and lower. During the defrost sequence, the motorized damper in the bypass module (BPM) temporarily blocks the incoming fresh air stream so
that the warm air from the room can circulate through the HRV. The exhaust blower shuts down and the supply blower switches into high speed to maximize the effectiveness of the defrost strategy. During this cycle, the unit will not create a negative pressure. Please note that these systems are configured to defrost with the BPM devices installed on the fresh air from outside port. Alternate config­uration are available by contacting our technical support department.
SETTING SPEED
Intermittent operation can be obtained by toggling the switch located on outside of cabinet. External low voltage contacts allow for high speed operation when an optional remote control is used.
Convenient Optional Low Voltage Wall Controls
Main Control
EDF1R
Triple Function Wall Control
The EDF1R is designed to pro­vide 3 modes of operation to the Heat/Energy Recovery Ventilator.
• Pressing the “Fan” button once initiates the unit to run at a continuous low speed of operation (green).
2-wire
Boost Switches
RTS 2
Pushbutton Timer
• 20-Minute Timer with LED
• Boosts system to high
• Up to five can be used
2-wire 3-wire
• Use in bathrooms,
• Pressing the button twice allows the HRV/ERV to run continuous cycle of 20 min­utes on and then standby for 40 minutes.
• Touch the button a third time and the system will run recir­culation at high speed (red).
The ventilation system will stay on the last function selected until it is manually changed.
Light
speed with the touch of a button
with one system
kitchens, laundry
RTS3
Pushbutton Timer
• 20-40-60 Min. Boost Timer
• Press button once to energize system to high speed for 20 minutes
• Press button twice unit unit will run for 40 minutes on high speed.
• Press button three times for 60 minutes of high speed
• Up to five can be used with one system
EDF5
Five-Function Wall Control
• Features: Digital Display, Maintenance Light, Power Button, Cycle Timer,
Longer Override Timer, Speed Control and Dehumidistat Control.
• Intermittent, Recirculation or
2-wire
Continuous Ventilation Modes
• Use in one central location
MDEH1
Dehumidistat
2-wire
• Rotary Dial Dehumidistat
• Just turn dial to set desired humidity level
• Multiple units can be used
• Install in bathrooms, kitchen, laundry
• Dehumidifies when air out­side is dryer than air inside
7
Page 8
INSTALLATION
A
B
F
E
D
C
G
LOCATION
The HRV must be located in a conditioned space where it will be possible to conveniently service the unit. Typically the HRV would be located in the mechanical room, above a drop ceiling or an area close to the outside wall where the weatherhoods will be mounted. Attic installations are not recommended due to extreme temperatures, and difficulty in performing, required service & maintenance. Care must be taken to locate the recirculation port in an area that will not cause any unwanted contaminant to be drawn into the liv­ing space during recirculation and defrost.
Connecting appliances to the HRV It is not recommended, including:
- clothes dryer
- kitchen exhaust hoods
- combustion venting
TIP: Flexible duct connectors should be installed between the HRV and the galva­nized ductwork.
- central vacuum system
These appliance may cause lint, dust or grease to collect in the HRV , damaging the unit.
NOTE: Connecting any of these type of appliances to the HRV will invalidate your warranty
Model A B C D E F G
SHR 8005R 23.8Kg (52.5lbs) 22.5Kg (49.6lbs) 390mm (15.4") 85Kg (187lbs) 20Kg (44lbs) 18.8Kg(41.3lbs) 448mm (17.6")
SHR 14105R 30.4Kg (67lbs) 27Kg (60lbs) 544mm (21.4") 109Kg (241lbs) 27.7Kg (61lbs) 24.3Kg (53.5lbs) 455mm (18")
Installing Drain Line
Through normal operation and including defrost mode, the HRV may produce some condensation. This water should flow into a nearby drain, or be taken away by a condensate pump. The HRV and all condensate lines must be installed in a space where the tempera­ture is maintained above freezing point. A “P” trap should be made in the drain line. This will prevent odors fr
om being drawn back
up into the unit.
Install the drain hose, making a “P” trap
Tee
Drain
Spout
Connector
Tape
or Tie Wrap
The water should be drained back into the pool and not wasted
8
Page 9
INSTALLING DUCTS GOING TO / FROM OUTSIDE
INSTALLING THE DUCTING TO THE WEATHERHOODS
OUTSIDE WEATHERHOODS –
prevent birds and rodents from entering into the ductwork. Do not use smaller mesh as it will be very susceptible to plugging up. The preferred location of the weatherhoods is:
• No less than 3 m (10 ft.) apart from each other.
• At least 457.2 mm (18 inches) snow line or ground level.
• Supply hood must be kept away from sources of contaminant, such as automobile exhaust fumes, gas meters, garbage cans, containers, cooling towers, tar roofs, etc.
• Avoid prevailing winds, whenever reasonably possible.
The outside perimeter of the weatherhood must be sealed to prevent leakage into the building.
The weatherhoods must have built-in "bird" screens with 6.35 mm (1/4 inch) minimum mesh to
DUCTING FROM THE WEATHERHOODS–TO AND FROM THE HRV – Galvanized sheet metal ducting with sufficient cross sec-
tion with an integral single piece of insulated wrap with vapor barrier should be used to connect the HRV to the weatherhoods. The R-value of the insulation should be adequate for condensation control. Insulated flex duct may be used in moderation, if sized and installed properly. (Consult local codes)
All ducts should be sealed using a good bead of high quality caulking (preferably acoustical sealant) and a high quality aluminum foil tape, or other approved duct sealant.
INSTALLING DUCTS TO / FROM INSIDE
To maximize airflow in the ductwork system, all ducts should be kept short and have as few bends or elbows as possible. Forty­five degree are preferred to 90˚ elbows. Use “Y” tees instead of 90˚ elbows whenever possible.
All duct joints must be fastened with screws or duct sealant and wrapped with a quality duct tape to prevent leakage. Aluminum foil duct tape is recommended.
SUPPLY AIR DUCTING
In buildings without a forced air HVAC systems, fresh air should be supplied to all habitable areas. It should be supplied from high wall or ceiling locations. The grilles that are to be used should be designed to properly and comfortably sweep cold surfaces.
Optional inline duct heaters may be used to add heat if required. Typically the reheat is best done using a coil off the same boiler that heats the pool water.
Direct Connection to Furnace/ Air handler return duct
• Should you wish to hard duct the supply air directly into the cold air return of the HVAC systems, remember to check the airflow bal­ance of the HRV with the HVAC systems fan both “on”and “off” to determine that it does not imbalance the HRV more than 10%. Make sure you respect the minimum distance from the supply air in of the HRV and the HVAC systems.
• It may be necessary to install a separate fresh air supply ductwork system if the heating is other than forced air.
When installing an HRV, the designer and installer should be aware of local codes that may require smoke detectors and/or firestats in the HVAC or HRV ductwork. Because an HRV is designed to bring fresh air into the building, structures may require supply voltage interrupt when smoke or flame sensors are triggered, or when a central fire alarm system is activated.
Exhaust Air ducting
The stale air exhaust system is used to draw air from the points in the building where the worst air quality problems occur. ( See installation examples in the manual.)
9
Page 10
Magnehelic
Magnehelic
Gauge
D
uct
Air
Flow
Pito t Tub e
AIR FLOW BALANCING
INTERIOR WALL
EXTERIOR WALL
EXTERIOR WALL
POOL HRV
MECHANICAL ROOM
E
XTERIOR WALL
RECIRCULATION
BACKDRAFT DAMPER
MDH1 Control
EDF1R Control
INTERIOR WALL
EXTERIOR WALL
EXTERIOR WALL
POOL HRV
EXTERIOR WALL
RECIRCULATION
BACKDRAFT DAMPER
RETURN GRILL
MDH1 Control
EDF1R Control
MECHANICAL ROOM
• The balancing procedure consists of measuring the exhaust air leaving the system and the supply air entering the system and ensuring that these two are equal. A deviation of 10% or less is acceptable.
A*
Pitot tube and gauge
A The duct’s airflow veloc-
ity is generally meas­ured with a magnehelic gauge and a pitot tube.
• To avoid airflow turbu­lence and incorrect readings, the airflow velocity should be meas­ured on steel ducting a minimum of 3 duct cross-section from the unit or elbow and before any transition.
Note: A professional air balancer should be contacted to commission the system properly. A skilled HVAC Tech may complete the balance of air providing they possess the proper equipment. Call Fantech Technical support for assistance.
INSTALLING BYPASS MODULE (BPM)
REFER TO BPM INSTALLATION, OPERATION AND MAINTENANCE DOCUMENT FOR INSTRUCTIONS
INSTALLATION EXAMPLES
Installation with Grille
10
Page 11
INSTALLATION EXAMPLES CON'T
INTERIOR WALL
E
XTERIOR WALL
EXTERIOR WALL
P
OOL HRV
EXTERIOR WALL
AIR HANDLER
RECIRCULATION
B
ACKDRAFT DAMPER
M
DH1 Control
E
DF1R Control
MECHANICAL ROOM
HVAC
MAINTENANCE
CAUTION MAKE SURE UNIT IS UNPLUGGED BEFORE ATTEMPTING ANY MAINTENANCE WORK
The following components should also be inspected regularly and well maintained.
The motor - The motors are factory balanced and lubri­cated for life. They require no maintenance.
The unit - The inside of the unit should be wiped clean as needed.
Condensation Pan - Units with drain hoses should have their line and connection checked regularly.
Outside hoods - The outside hoods need to be checked every season to make sure there are no leaves or insects blocking the airflow. Check regularly that there are no pol­lutants near the intake hood. Make sure they are clear of any snow accumulation during the winter months.
FILTERS
The filters need to be checked and cleaned once a month or when they appear dirty.
FIXED PLATE
Clean cores on a average every 3-6 months or as needed.
a) Open access door & remove filters. b)
c) Wash the cores in warm soapy water or light coil
d) Install clean cores making sure the matting sur-
e) Install the clean filters f) Replace access door
Note: Core installation label on the outer end of the core.
To install the clean Core and Filters.
a) First mount the bottom flange of the core guide into the
b
c) Mount the top flange of the core guide into the top
d) With all four corners in place and the core straight and
Carefully pull on handle of core and pull evenly outward.
Cores may be snug, but will slide out of the channel.
solution.
faces have one sealing edges between each cores to minimize leaks.
bottom channel approximately 6mm (1/4")
) Mount the left or right side flange of the core guide
approximately 6mm (1/4") followed by the other side
channel approximately 6mm (1/4")
even, push hard in the centre of the core until the core stops on the back of the cabinet.
11
Page 12
WIRING DIAGRAM SHR 8005R AND SHR 14105R
DASHED LINES INDICATED ADDITIONAL COMPONENTS FOUND IN MODEL TYPES FAH1200 & FAH1400
WHT/YELLOW
WHT/GREEN
YELLOW
WHT/BLUE
GREEN
BLUE
RED
BLUE
BLUE
BROWN
BLACK
BROWN
BLACK
EXH2
GREEN
EXH1
GREEN
CAP1BCAP1A
GREEN
BLACK
RED
STAND BY
T.P
SW1
LOW
MED
BLACK
BROWN
BLUE
BROWN
BLACK
BLUE
CAP2BCAP2A
SUP1
GREEN
SUP2
GREEN
D.M
Supply Voltage
8 AMPS, 250V, 3AB or
3AG FAST ACTING
12 AMPS, 250V, 3AB or
3AG FAST ACTING
GREEN
COM
CUR SW
IN
DEHUM
TIMER
+
+ -
-
N.C.
COM
N.O.
FURNACE
INTERLOCK
EDF
+ -
BLUE
BLACK
RED
GREEN
GREEN
YELLOW
MCI-7018/7030
YELLOW
GREEN
GREEN
BLACK
RED
BLACK
RED
BLUE
BLACK
RED
WHITE
BLACK
WHITE
UNI-CTRL
JUMPER SETTINGS
OFF
ON
ON
OFF
ON
OFF
ON
J4J6J5
J7
J1J2J3
(GROUND)
N (WHITE)
L (BLACK)
FUSE SPECIFICATION
FAH0800
HCE PCB REPLACEMENT
FAH0900
FAH1400
FAH1200
TYPE FUSE RATING
PROGRAMEXP
COM
N.O.
N.C.
AUX
J7
CUR SW DEHUM TIMER AQS WALL
PWR
N
.O.
C
OM
J6 J5
DEFROST
J4
J3 J2 J1
United States
1712 Northgate Blvd.,
Sarasota, FL. 34234
Phone: 800.747.1762; 941.309.6000
Fax: 800.487.9915; 941.309.6099
www.fantech.net; [email protected]