locking plug
Holes in Ceiling / Wall
Bracket
Terminals
AC Quick Connector
Mounting Plugs
Screws
WHERE NOT TO INSTALL SMOKE ALARMS
1. In areas near appliances or where normal
combustion regularly occurs (near furnaces, hot
water heaters).
2. In areas with high humidity like bathrooms,
near dishwashers or washing machines. Install at
least 3 metres away from these areas.
3. Air returns or heating and cooling supply vents.
Install at least 900mm away from these areas.
The air could blow smoke away from the
detector, interrupting its alarm.
4. In rooms where temperatures may fall below
5ºC or rise above 45ºC or in rooms where the
humidity rises above 85%.
5. In extremely dusty, dirty, or insect-infested
areas where loose particles interfere with smoke
alarm operation.
6. Near fluorescent lights. Electronic ‘noise’ may
cause nuisance alarms.
7. Smoke alarms are not to be used with detector
guards. Unless the combination (alarm and guard)
has been evaluated and found suitable for that
purpose.
WARNING: Incorrect orientation will result in a
decrease in operational effectiveness.
INSTALLATION INSTRUCTIONS
IMPORTANT: This smoke alarm must be
installed by a licenced electrician. Turn off AC
power during installation. Before installing this
smoke alarm ensure that there is no electrical
cabling or plumbing piping that will interfere with
the installation process. Use an appropriate
fastening system to secure the mounting
bracket to the substrate.
WARNING: To prevent injury this unit must be
securely attached to the wall or celling in
accordance to the installation instructions.
WIRING
• The smoke alarm will function either stand
alone or interconnected.
• All interconnected smoke alarms must be
supplied from a single power circuit.
• This smoke alarm can be connected to a circuit
protected by a Residual Current Device.
• Connect and power the smoke alarm with
220 ~240VAC single phase.
• Solid wires with 1mm2 (or larger) cross
sectional area are recommended for power
supply and inter-connection. Strip the live, neutral
and interconnection wires back to the length of
10mm. Connect the AC quick connector to the
fixed wiring in accordance with the requirements
of AS/NZS 3000. The colours of the wires are:
live = brown, neutral = blue and inter-connect =
white.
• The smoke alarm device shall be provided with
an all-pole mains switch from a circuit within the
household consumer unit. The all-pole mains
switch shall have a contact separation of at least
3 mm in each pole.
• All interconnected smoke alarms must be
supplied from a single circuit. It is recommended
that a maximum of 12 smoke alarms may be
interconnected in a multiple station arrangement.
Interconnecting more than 12 smoke alarms may
result in a power overload.
DO NOT CONNECT TO OTHER MODEL
SMOKE ALARMS.
• The diagram below illustrates interconnection
wiring, an incorrect connection may result in
damage to the alarm, failure to operate, or a shock
hazard. Connection to a fixed wiring in
accordance with AS/NZS 3000 wiring rules (find
out max distance between first and last
interconnected smoke alarm.
• The wire on the alarm harness is connected to:
Brown wire – Live wire of AC line
Blue wire – Neutral wire of AC line
White wire – I/O signal as interconnect line of
other units in the multiple station set up.
DO NOT connect White inter-connection wire to
live or neutral.
Mounting Instructions:
1. After selecting the proper location for your
smoke alarm, wire the AC quick connector
harness as described in the wiring instructions.
2. Turn the alarm body counter-clockwise and
take off the bracket.
3. If desired to lock the alarm in place, remove the
locking plug from the bracket with a screwdriver,
and keep aside for step 10.
4. Place the mounting bracket on the ceiling
surface or wall and use a pencil to mark the
position of the mounting holes and the hole
through which to bring the electical wiring to the
smoke alarm.
5. Move the mounting bracket and drill the two
small holes and the larger one. Use an
appropriate fastening system to secure the
mounting bracket to the substrate
6. Insert the battery into the battery box. Connect
the AC quick connector to the alarm body.
7. Fit the alarm to the bracket and turn the alarm
clockwise until it is firmly in place.
8. If desired, insert the locking plug saved from
earlier into the square gap on the side of the alarm
to lock it into place.
9. Turn on the AC power. The green LED indicator
should light up showing that the alarm is
connected to AC mains power.
10. Test the smoke alarm by pressing and holding
the Test button. See ‘Testing the Smoke Alarm’
below.
11. To prevent injury, ensure the smoke alarm unit
is securely attached to the ceiling in accordance
with the installation instructions.
OPERATION, TESTING AND MAINTENANCE
LED Indicators
GREEN: The green LED indicator shows that the
smoke alarm is connected to AC power.
RED – NORMAL: The red LED indicator flashes
once every 32 seconds when there is no smoke
present indicating the alarm is working properly.
RED – ALARM: The red LED indicator flashes
once per second when the Test button is pressed
or the smoke alarm is activated.
RED – HUSH: The red LED indicator flashes
once every 8 seconds whilst the smoke alarm is
in Hush mode.
LOW BATTERY INDICATOR: Occurs when the
smoke alarm sounds a chirp and flashes the
RED LED Indicator once every 32 seconds for a
minimum of 7 days. This indicates the battery is
low refer to Battery Replacement. Ensure the
battery is replaced as soon as possible.
FAULT: Occurs when the unit generates a ‘chirp’
once every 32 seconds. This indicates that the
smoke alarm has a fault (refer to Troubleshooting
section).
Testing the Smoke Alarm
Test the smoke alarm weekly and when replacing
the 9V backup battery. Testing the smoke alarm
will ensure that the circuitry, horn and battery are
operating correctly.To test the smoke alarm, press
and hold the Test button for at least 10 seconds.
The alarm will activate with a flashing RED LED
indicator and sound three short beeps then a short
pause. This continues until the Test button is
released. If no alarm sounds, refer to the
troubleshooting section to seek further assistance.
Alarm HUSH mode
The Hush function is designed to silence false
alarms. During a false alarm, press the Test
button for at least 5 seconds and the alarm will
silence for approximately 8 minutes. After this
period, the smoke alarm will return to normal
operation. Should more particles of combustion
continue to be detected, the alarm will activate
again. If particles of combustion are still present
after the Hush period, the alarm will sound again
until the area clears. If there are frequent false
alarms, it may be necessary to relocate the device
away from the cause. If the alarm continues
sounding false alarms without smoke, heat or
steam present, it may require maintenance or
cleaning. Refer to the troubleshooting section for
further assistance.
WARNING: If the smoke alarm sounds and it is
not being tested, the smoke alarm is quite likely
sensing smoke. This should not be ignored and
the alarm requires your immediate attention and
action.
First Alarm
White
Blue
Brown
Additional
Alarm
Additional
Alarm
Live Wire
Neutral Wire
Signal Wire