TABLE OF CONTENTS
SG UPSFeatures.......1
SG Series Online UPS Block Diagram......1
Important Safety Instructions(READ FIRST)....2
Chapter 1.
SG Series UPS Overview ......3
True Regenerative On-line Design .....3
Input Power Factor Correction.....3
Microprocessor Control......3
SNMP/HTTP Remote Management .....3
Extended Battery Bank Option.....3
Frequency Converter Option.....3
Chapter 2.
Installation Instructions (Common for all models)....4
Output Voltage & Green Mode Switch Settings Diagrams ..5
Floor Load Carrying Requirements......6
Lowering The Leveling Feet.....6
Installation Instructions for Hardwire Models...7
Extended Battery Bank Installation, Hardwire Models ...10
Installation Instructions for All Models (Except Hardwire)..13
Extended Battery Bank Installation, All Models (Except Hardwire).16
Chapter 3.
Operation.......17
Front Panel Indicators & Function Key Diagram...17
Models available with either 120V or 208-240Vac Input
True Double Conversion On-Line Design
Input Power Factor Correction
Dual Output Models Available with 120 & 208-240Vac
Wide Input Voltage Window
Pure Sinewave Output
Precision Output Voltage Regulation
Superior Brownout, Surge and Transient Protection
Internal System Bypass
Eliminates Generator Frequency & Voltage Drift
Microprocessor Control & RS-232 Communications
UPSILON®Monitoring & Shutdown Software
Optional Frequency Conversion
Optional Extended Battery Packs & Chargers
Optional External Maintenance Bypass Switch
Optional Internal SNMP/HTTP Interface Card
Two-Year Warranty
SG SERIES ON-LINE UPS SYSTEM BLOCK DIAGRAM
NOTE: All SG UPSs are constructed using metric screws, nuts and hardware.
1
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions which must be followed during the installation,
operation and maintenance of this UPS and its batteries. Please read all instructions before
operating this equipment and save this manual for future reference.
CAUTION
All of the models presented herein are designed for installation and use in a
temperature controlled environment, free of contamination.
CAUTION
This UPS utilizes voltage that may be hazardous. Do not attempt to disassemble.
This unit contains no user replaceable parts. Refer all servicing to Falcon
Electric, Inc.
THIS UPS IS NOT INTENDED TO BE USED IN CONJUNCTION WITH LIFE
SUPPORT OR OPERATING ROOM EQUIPMENT.
Always turn off the input and battery circuit beakers prior to cleaning and never
apply liquid or spray detergent on the UPS.
CAUTION
CAUTION
CAUTION
Never attempt to service batteries. High voltage exists within the unit, which
could cause electrical shock. Servicing of batteries should be performed or
supervised by personnel knowledgeable of batteries and the required precautions.
Keep unauthorized personnel away from batteries. When replacing the UPS
batteries, use the same number and type of batteries.
IMPORTANT
Allow at least 24 hours, after the UPS is first installed and turned on, to fully charge
the internal battery and assure the maximum backup time is available.
DO NOT
DO NOT connect the input of this UPS to its own output, as this may damage the
UPS.
DO NOT remove or unplug the UPS input when it is turned on. This removes the
safety ground from the UPS and the equipment connected to the UPS.
This UPS contains its own energy source (batteries). The output receptacles
may carry live voltage even when the UPS is not connected to an AC source.
CAUTION
CAUTION
IMPORTANT
Should the SG Series UPS unit be stored for more than two weeks, it is
mandatory that the battery circuit breaker be turned off prior to storage or
battery damage will result.
2
CHAPTER 1
CHAPTER 1
SG Series UPS - Overview
True Regenerative On-Line Design
As new and innovative technologies have become the backbone of today's businesses, maximum system availability is critical and downtime is more expensive than ever. Increasingly, businesses need a UPS that not only protects against blackouts, but also virtually eliminates more
frequent and subtle power disturbances. Surges, sags, line noise and brownouts can disrupt
proper operation of sensitive equipment. These disturbances may also create unnecessary production, service, and data recovery costs.
A True Regenerative On-Line UPS provides the highest level of protection against the widest
spectrum of power problems. The incoming AC utility source is converted to a regulated DC
voltage. From this DC voltage, a new AC voltage is regenerated, providing continuous, clean,
tightly regulated power to your equipment. Line-interactive and Off-line designs leave your equipment connected directly to dirty utility power. They only provide minimal transient, voltage and
backup protection. If your equipment operation is "Mission Critical", a true double conversion
On-Line UPS, such as Falcon®Electric's SG SeriesTMUPS Plus®, is the only clear choice.
Input Power Factor Correction
All SG Series UPS Plus models include state-of-the-art Input Power Factor Correction. This
greatly reduces the amount of current demanded from your building wiring system, yielding a
highly efficient, "building friendly" UPS.
Microprocessor Control
Falcon Electric's SG Series UPS incorporates advanced microprocessor technology. This technology makes possible a high level of internal UPS control and management. With the supplied
UPSILON®software, all SG Series UPS models support unattended shutdown, management,
data logging, and self-diagnostics. The software supports MS Windows®95, 98, NT, 2000, 2000
Server, ME, XP, Novell Netware®5 & 6, LINUX and FreeBSD. UPSILON for UNIX may be
purchased seperately and supports most popular UNIX platforms and OS versions.
SNMP/HTTP Remote Management Support
Our SNMP/HTTP Agent board provides remote management and monitoring over any Ethernet
LAN, WAN or the Internet utilizing a 10BaseT-type connection. The optional SNMP/HTTP agent
installs via an option slot located behind a cover plate on the back panel of every SG Series
model.
Extended Battery Bank Option
All SG Series models have a continuous duty inverter and support the addition of optional external battery/charger packs. Whether your application requires a few additional minutes or hours,
the SG Series will be ready. Falcon also offers optional battery charger upgrades for faster
recharging. Please specify your extended battery and charger requirements at the time of your
initial order.
Frequency Converter Option
With a factory modification at the time of order, any SG Series model can be configured for use
as an international frequency converter. This makes the SG Series UPS Plus an ideal choice for
worldwide power applications. Without this modification, all SG series models will detect the
incoming utility line frequency and automatically set its output frequency to match.
3
CHAPTER 2
CHAPTER 2
INSTALLATION INSTRUCTIONS
General - Common for all models
1.Verify the following is included in the UPS shipping carton:
(1) UPS, (1) Software Diskette(s) & Manual, (1) Owners Manual & (1) UPS/Computer
Cable.
2.Verify the UPS unit is configured for the proper input/output voltage and frequency. This
information is stated on the nameplate label located on the rear or the side panel of the
unit. If any special input plug and output receptacle configurations were specified at the
time of order, verify for proper configuration.
3.Set the output voltage and green mode switches located on the UPS rear panel for the
nominal UPS output voltage desired. See the switch setting tables located on page 5.
In most cases the nominal UPS output voltage should be set to match the incoming utility
voltage. This will assure a close matching voltage in the event the UPS is placed on
bypass. NOTE: Disregard the "ON" marking on the side of the actual dip switch
housing; use the tables in this manual or the silkscreen on the UPS rear panel only.
Dip switch 3 "enables" or "disables” the "Green Mode" function. The UPS is shipped
from the factory with the switch set in the "disabled" position (up). If SW3 is switched
down or to the "enabled" position, the Green Mode function is activated. When the
load connected to the output of the UPS drops to under 10% of the full rated UPS output
for 30 seconds, the UPS is automatically placed into bypass and the inverter is turned off.
NO BATTERY BACKUP IS PROVIDED AFTER THE GREEN MODE HAS ACTIVATED.
Dip switch settings must be made while the UPS is turned off. Any changes made while
the UPS is turned on will not take effect until the UPS is turn off and back on again since
the switch settings are read by the microprocessor only during initial UPS power up.
4.To prevent accelerated battery discharge during shipment, this UPS was shipped with the
battery circuit breaker turned off. TURN THE BATTERY DISCONNECT CIRCUIT
BREAKER ON PRIOR TO TURNING ON THE UPS INPUT CIRCUIT BREAKER.
CAUTION
NEVER TURN THE BATTERY CIRCUIT BREAKER OFF WHILE THE UPS AC CIRCUIT
BREAKER IS TURNED ON AND OPERATING FROM THE UTILITY VOLTAGE, OR UPS
DAMAGE MAY RESULT. UPS MUST BE COMPLETELY SHUT DOWN PRIOR TO
DISABLING THE INTERNAL BATTERY SUPPLY.
CAUTION
In the event this UPS is to be turned off or stored for more than two weeks, the battery
circuit breaker must be turned to the off position to prevent battery discharge. If placed in
long-term storage, every four months the UPS must be plugged in and turned on for 24
hours to allow the batteries to recharge and prevent battery damage. Failure to follow
these procedures will invalidate your warranty.
4
DIP
SWITCHES
SELECTION
ON = 1
OFF = 0
VIEW OF OUTPUT VOLTAGE & GREEN MODE SELECT SWITCHES
(LOCATED ON THE UPS REAR PANEL)
Disregard
“ON” Designation
TABLE
SWITCH SETTINGS FOR ALL MODELS
SW2 SW1 OUTPUT VOLTAGE 1
(All models)
OUTPUT VOLTAGE 2
(-TX & -TXC models only)
Down Down 208 Vac115 Vac
Down Up 220 Vac (default)120 Vac
Up Down 230 Vac125 Vac
Up Up 240 Vac130 Vac
GREEN MODE SWITCH SETTINGS FOR ALL MODELS
SW3 FUNCTION
Down GREEN MODE ON
Up GREEN MODE OFF
5
6.Select a suitable location for the UPS.
VERIFY THE FLOOR OR SURFACE SUPPORTING THE UPS WILL SUPPORT THE
WEIGHT OF THE UPS AND ANY OPTIONAL EXTENDED BATTERY BANKS.
7.If extended battery banks are to be connected to the UPS, please refer to page 7 for
hardwire models and page 16 for all other models.
8.If unattended computer shutdown and monitoring are desired, connect the green
UPS/Computer cable to the DB-9 connector located on the UPS rear panel. Then
install the shutdown and monitoring software provided with the UPS. For your
reference, UNIX shutdown and monitoring software is available from Falcon Electric
at an additional cost.
9.Verify the location selected has adequate ventilation to allow for the proper cooling of
the UPS.
DO NOT BLOCK UPS FANS OR AIR VENTS. THE UPS MUST NOT BE
INSTALLED IN AN ENCLOSED AREA.
10.For further installation instructions covering hardwire models SG5K-1TX, SG5K-2T,
SG6K-1TX, SG6K-2T and SG6K-2TX, please refer to page 7.
11.Lower the leveling feet.
a. Verify the flooring at the UPS or battery bank installation location is rated for
the weight of the equipment.
b. Roll the UPS or extended battery bank to the final installation location.
c. Locate the position of the (4) levelling feet underneath the UPS near its four
corners. (see picture below).
d. Using your fingers and a 12mm open end wrench, screw the levelling feet in
a clockwise direction, lowering the feet until all four feet are securely
against the floor.
12.For further installation details covering the following models having a line cord and
PDU, please refer to page 13. Models SG5K-1TXC, SG5K-2TC, SG5K-2TXC,
SG6K-2TC and SG6K-2TXC.
Leveling Feet Adjustment
6
Installation Instructions For Hardwire Models (see model numbers referenced below)
1.0UPS Input & Output Requirements.
IMPORTANT
Note: All SG Series hardwire UPS models must be installed by a licensed
electrician, in accordance with the National Electrical Code (NEC) ANSI/NFPA70
and all local regulations. It is further required that the input of SG Series hardwire
UPS be wired to a building service panel incorporating a dedicated “branch
rated” circuit breaker of the proper rating.