1.4 GAS SUPPLY
The incoming service must be of sufficient size to supply
full rate without excessive pressure drop.
A meter is connected to the service pipe by gas supplier.
Any existing meter should be checked by supplier to
ensure it is of adequate capacity to pass the required rate
of gas for the unit, in addition to any other gas equipment
installed.
Installation pipe work should be fitted in accordance with
IGE/UP/2. The pipe work should be of adequate size but
not be smaller than the unit gas inlet connection,
ie. Rp½ (½” BSP).
If flexible tube is used, the gas supply tubing or hose shall
comply with national requirements in force. These will be
periodically examined and replaced as necessary.
An isolating cock must be located close to appliance to
allow shut-down during an emergency or servicing.
The installation must be tested for gas tightness.
Details of this procedure can be found in IGE/UP/1.
1.5 ELECTRICAL SUPPLY
Not applicable to these appliances.
1.6 WATER SUPPLY (IRN R001)
Warning - The unit shall not be used empty.
The appliance is intended for connection to a main water
supply only, connection is 15mm compression fitting.
Backflow prevention is by means of double check valve,
fitted at inlet. Supply pressure must be within range of
0.5 to 5 bar. A stop cock must be fitted in an easily
accessible position on the supply to enable shut off for
cleaning and maintenance.
Front trough drain should be situated over a floor grating
where possible.
1.7 HEAT INPUTS
1.8 INJECTOR SIZES
1.1 MODEL NUMBERS, NETT WEIGHTS
and DIMENSIONS
1.2 SITING
The unit must be installed upon a firm, level floor in a well
lit position. It requires to be secured to this surface.
The oven can be positioned to within 150mm of a
combustible wall.
Important
If the appliance is to be installed in suite formation with
other matching appliances of the DOMINATORPLUS
Series, the instructions for all units must be consulted to
determine the necessary clearance to any combustible
rear wall or overlying surface. Some appliances require
greater clearance than others and the largest figure
quoted in the individual instructions will therefore
determine the clearance for the complete suite of
adjoining appliances.
1.3 VENTILATION
The appliance flue discharges vertically at the rear.
There must be no direct connection of the flue to any
mechanical extraction system or the outside air. Siting
the appliance under a ventilated canopy is the ideal
arrangement.
Adequate ventilation, whether natural or mechanical,
must be provided to supply sufficient fresh air for
combustion and allow easy removal of combustion
products that may be harmful to health.
Recommendations of ventilation for Catering Appliances
are given in BS 5440:2.
For multiple installations, the requirements for individual
appliances should be added together. Installation should
be made in accordance with local and/or national
regulations applying at the time. A competent installer
must be employed.
Model
Width
(mm)
Depth
(mm)
Height
(mm)
Weight
(kg)
G3478
Steaming Oven
600 840 1625 96
SECTION 1 - INSTALLATION
UNLESS OTHERWISE STATED, PARTS WHICH HAVE BEEN PROTECTED BY THE MANUFACTURER
ARE NOT TO BE ADJUSTED BY THE INSTALLER.
Gas type kW (nett) Btu/hr (gross)
Natural gas 12.1 45,400
Propane gas 12.7 47,700
Gas type Main burner Pilot burner
Natural gas Ø3.2mm SIT No. 36
Propane gas Ø1.9mm SIT No. 19