Falcon 8230, 8240 Installation Instructions Manual

Page 1
*640072*
Electro-Mechanical
640072
Models 8230 & 8240
Swing Operator
Installation Instructions
Table of Contents
General ...........................................................................................................................................................................................................1
Replacement Parts & System Components ...................................................................................................................................................1
1 Pre-Installation Site & Product Check..........................................................................................................................................................2
2 Operator Installation ....................................................................................................................................................................................3
3 Wiring...........................................................................................................................................................................................................5
5 Operational Check .......................................................................................................................................................................................7
6 Operator Adjustment .................................................................................................................................................................................... 8
7 Release For Service ..................................................................................................................................................................................10
8 Falcon Software .........................................................................................................................................................................................10
General
The Falcon Operator is a low energy automatic electromechanical swinging door operator for use on hinged, center pivoted and offset pivoted doors. When activated, the Falcon drives the door to full open position, then electrical power is turned off and the door is closed by spring force. The activating circuit opens the door from any position in the closing swing. During a power failure, the Falcon Operator acts as a manual door closer (Size 3). Door opening and closing cycles, including opening speed, back check speed, hold open time delay, closing speed, latch position, and backcheck position are adjustable.
WARNING
Always disconnect main power to the
operator prior to servicing or cleaning.
Part 26” Header
Control Box
Gear Box
Part Pull Standard Push Finish
Arm Assembly
8230-3462 8240-3462
8230-3454 8240-3462
8230-3077T 8240-3077 AL689
26” Pull System
(screw pack not shown)
CAUTION
This operator is for indoor use only.
Replacement Parts & System Components
26” Push System
(screw pack not shown)
CAUTION
Do not mount any accessories directly
to the operator.
Pull arm -3077T and track -3038 Arm & track assy -3077PLCM
Page 2
1 Pre-Installation Site & Product Check
1a Check that the product model is correct for the required application.
1b Check that all parts listed on the Bill of Material are in the shipping container.
1c Check the architectural drawings and nal approved shop drawings for the position of frame and structural openings.
1d Check header and frame dimensions and required clearances.
26”
1/8” max reveal
26”
1e Check door width:
26” minimum for 26” Push Operator 30” minimum for 26” Pull Operator
1f Check that door weight is 200 lbs. or less. For heavier door, consult factory.
1g Check that a 115 volt, single phase, 60 Hz, fused 15 amp, 3-wire power supply is available at the side jamb with
approximately 12” of wire available to connect to the Operator. UL approved exible conduit is recommended for the
115 volt power line. The 115 volt power supply must be a dedicated circuit from the main circuit breaker panel and must NOT be
connected into any building lighting system that operates orescent lights.
Page 3
2 Operator Installation
1/4”-20
Remove screw to remove control box from mounting bracket
26” Pull, 26” Push
2a Remove Control Box from Operator Mounting Bracket, then remove Motor/Gearbox from Bracket:
26” Pull, 26” Push
1/4”-20
Remove screw to remove control box from mounting bracket
2b Prepare Header/Frame and Door:
26” Pull System ................................. See Below
26” Push System .................................... Page 5
Drop Mount Application ........................... Page 5
2c Install Operator Mounting Bracket on Header/Frame. Do not install the center screws until you’ve attached the Motor
Gearbox assembly in step 2d.
2d Install Motor/Gearbox on Operator Mounting Bracket. If there is not a mounting surface for both screws on the
Gearbox, use the ¼”-20 nut removed in 2.1 to secure the gearbox. Then install the Control Box.
2e Proceed to Step 3: Wiring (page 6).
CAUTION
When mounting to an aluminum frame, the use of rivet
nuts is strongly recommended.
26” Pull System
Header/Frame and Door Preparation
Drill 1/2” hole in jamb
6
tube in this area for low voltage wire access
1-11/16”
Control
Box
6”1/5-518”/3-9
Gearbox
24”
Page 4
26” Push System
26” Push System
Header/Frame and Door Preparation
6”1/5-518”/3-9
Control
Box
Gearbox
6
1-3/16”
5/8”
Header/Frame and Door Preparation
6”1/5-518”/3-9
6
Control
Box
Gearbox
1-3/16”
5/8”
Drop Mount Application (26” Push System Only)
Header/Frame and Door Preparation
6”1/5-51
8”/3-9
4
Page 5
3 Wiring
Arm Locking
Screw
Fig. 2
CAUTION
Make sure all wires are properly dressed and secured to prevent interference
Route all wiring away from moving parts, sharp edges, and heat sources
Use copper conductors only
Do not modify the factory wiring or connect into existing electrical circuits or devices
3a Refer to the appropriate wiring diagram for the Control Box (page 12) or the diagram supplied for custom applications.
Connect the following cables:
• Ground Cable (Ground the Operator properly with the earth from main supply)
• Hall Effect Cable (Do not wrap the Hall Effect Cable around the Motor Power Cable)
• Motor Power Cable (Do not wrap the Motor Power Cable around the Hall Effect Cable)
• Control Box Power Cable
3b Connect activate and lock accessories, as needed.
Refer to the accessory instructions for any accessories used. Do not connect any remote activating device to the door unless it is located within line of sight of the door.
3c When wiring is complete, proceed to Step 4: Arm and Cover Installation (page 6).
4 Arm & Cover Installation
WARNING
Keep hands, clothing, wires, tools, etc., AWAY FROM
Operator Motor when the Operator Motor is turned on.
4a Make sure the Operator Power is connected.
4b Install a jumper across the control box Main Act and Main Act Com.
4c The operator motor will activate and drive to the Full Open position, and remain there.
4d Push Arm Installation
1. Open the door to 90°, and attach the Main Arm to the operator spindle at 90° to the opening (+/- 10°) with the 8mm socket head
screw (see g. 1).
2. Remove the arm locking screw from the Rod & Shoe. Insert rod into forearm tube and reinstall the arm locking screw loosely. Attach
Rod & Shoe to door. With the door open to 90°, tighten the arm locking screw (see g. 2).
8mm Socket
Head Screw
Arm Locking
±10°
Screw
Fig. 1
Fig. 2
Page 6
4e Pull Arm Installation
Pull Arm
Fig. 4
Arm Adjustment
Screws
1. Slide the pull arm roller into the track, then insert a track end cap on each end of the track and install track to door.
2. Attach the Pull Arm to the track roller with the roller locking screw and to the operator spindle loosely with the 8mm socket head
screw. Open the door to 90°, and tighten the 8mm socket head screw (see g. 3).
3. Attach arm if required. Due to the mesh of the arm to operator spindle, the door may be open to slightly more or less than 90°. To
adjust arm, remove arm adjustment screws, push door open to 90° and reinstall arm screws (see g. 4).
Pull Arm
Arm Locking
Screw
8mm Socket
Head Screw
Arm Adjustment
Screws
Fig. 3
Fig. 4
4f Remove the jumper from the control box Main Act and Main Act Com. The door should close.
4g Connect actuator wiring as required (see page 12).
4h Test the operator. (See Chapter 5: Operational Check on page 8)
4i Adjust the operator as required. (See Step 6: Operator Adustment on page 9)
4j Install the cover assembly onto the operator.
4k Release the operator for service. (See Step 7: Release for Service on page 11)
Page 7
5 Operational Check
5a Activate the operator using the activation device. The operator will perform one sizing cycle.
Sizing Cycle: Occurs after power is turned on and a legitimate activation signal is received. During the sizing cycle, the door opens and closes one time.
5b If the door does NOT OPEN AT ALL during the sizing cycle:
• Check the door for binding.
• If an electromechanical lock is being used, check that the lock disengages before the operator opens the door.
• Check fuses, circuit breakers and connections.
• Adjust the operator and check the door operation (see Step 6: Operator Adjustment on page 9). Below are default settings:
Opening Speed 9:00 Back Check Speed 3:00 Hold Open Time Delay 10:00 Latch Position 12:00 Closing Speed 12:00 Back Check Position 4:00 (fully clockwise)
5c If the door does NOT OPEN FULLY during the sizing cycle:
• Check the door for binding.
• Increase the back check speed slightly and re-check the door operation. Repeat until door opens fully.
5d If the door OPENS TOO FAST during the sizing cycle, decrease the back check speed slightly and re-check the door
operation. Repeat until the door opens at desired speed.
5e After the sizing cycle is completed and the door(s) are closed, apply a maintained activatin signal. Check that the door
remains open while the signal is applied.
5f When the door is operating properly, continue with step 4k on page 7.
Page 8
6 Operator Adjustment
See table below and diagrams (page 10) for operator feature adjustment.
After adjusting, cycle the door several times to check for proper operation.
NOTE
Adjust Operator for the SLOWEST operation practical, in accordance with
the latest revisions of the Americans with Disabilities Act (ADA); ANSI/BHMA
A156.19 Standards for Power-Assisted and Low Energy Power-Operated Doors;
and local codes.
Opening Speed: 5 seconds or more Latch Location: 10 degrees or more
Closing Speed: 3 seconds or more Latch Speed: 1.5 seconds or more
Features Control Description Counter
Opening Speed Opening Speed Controls opening speed
of door
Back Check Speed Back Check Speed Controls the speed of the
door near the full open position to prevent door slamming
Hold Open Time Delay Hold Open Time Delay Controls the length of
time the door remains in the full open position: 1 sec to 30 sec
Back Check Position Back Check Position Door position where back
check speed engages
Latch Position Latch Position Door position at which
deceleration towards full closed begins in order to prevent door slamming
Closing Speed Closing Speed Controls closing speed
of door
Delayed Activation DLY ON: Delays opening
of door for strike applications (1 second delay)
Clockwise
Clockwise
Slower Faster
Slower Faster
Less Time Down to 1 sec More Time Up to 30 sec
Less Pressure Required More Pressure
Required
Less Latch More Latch
Slower Faster
Push and Go PNG ON: Pushing the
door open 5° causes operator to open door for remainder of open cycle
Page 9
Fuse
Main Power
Power
Motor
On
Delay
Open Speed
Back Check Speed
Back Check Pos
Close Speed
Latch Pos
Hold Open
Push
-n­Go
On
Fuse
12 VAC
O
Delay
Speed Open
Speed Check
Back
Pos Check Back
Speed Close
Pos Latch
Open Hold
Go
-n­Push
O
Page 10
7 Release For Service
7a Remove all tools, installation equipment and debris from the vicinity of the door.
7b MANDATORY: Install all Safety, Trafc Control and Instruction Labels onto the door, as required.
Failure to do this will leave the INSTALLER LIABLE for any accidents that occur.
7c Give verbal instruction on how to properly operate the door to the owner or person in charge.
7d Give verbal instruction to the owner or person in charge on periodic inspection of the door for the following:
• Occasional damage
• Developing problems
• Minor preventative maintenance
7e Provide the owner or person in charge with a contact name and phone number to call for future service and
maintenance.
IMPORTANT
Be sure to install all Safety, Trafc Control and Instruction
Labels onto the door, as required.
8 Falcon Software
8a Operation:
1. Sizing:
From start-up (sizing), the door will activate via:
Main Input (Main Act and Main Act Com).
The rst motion of the door will be towards the Door Open position. The speed during Sizing is automatic and cannot be set from a
potentiometer.
The door drives to full open and the system sets the open counter to full open.
The door closes at Closing Speed. The system sets the closed counter to Full Closed when the latch goes up at the Closed position.
The system calculates all other parameters required for normal operation based on the two values of Full Open and Full Closed.
Page 11
2. Standard Operation
Upon a legitimate activation signal, the door accelerates to opening speed while monitoring the current load on the drive output. If the
current exceeds the specied level, the door will stop and close.
The door travels at it’s set speed (based on the potentiometer setting) until it reaches the Back Check position, where it will decelerate to the Back Check Speed.
The door will stop at the Hold Open position and remain there until an activation or the Hold Open Timer is cleared.
The door then closes at its Closing Speed (based on the potentiometer setting) up to the latched position.
If the Closing Speed is decreased by driving the motor in the open direction (a xed setting), power is added to allow the spring to
continue closing the door to the Full Closed position.
8b Wiring
For clarity, not all
components are shown
on the control box PC board
J5, 2-position
Motor Power Cable J3, 4-position Hall Effect Cable
Control box
grounding stud
Multiple activation devices
should be connected in parallel
120VAC
Input
Plug cables into these receptacles
External
24 VDC
Power Supply
J8, 10-position Control Box Power Cable
J1, 6-position Main Power Cable
24VDC +
24VDC -
12VAC
12VAC
Activation Device
N/O Dry Contacts
Safety Sen
Safety GND
Main Act
Main Act Com
Black DC-
Electric Lock,
Electric Strike, etc.
Relay N/O
Relay Com
Relay N/C
Depending on Device
Connect Fail Safe to Relay N/C Fail Secure to Relay N/O
Connection to external devices must be made using CL2, CL2P, CL2R, or CL2X Class 2 wire or equivalent.
© Allegion 2018
Printed in U.S.A.
640072 Rev. 06/18-e
Page 12
Loading...