Fairchild TT7800, TA7800, TD7800, T7800 Series Installation, Operation And Maintenance Instructions

Page 1
FAIRCHILD T7800 EXTENDED RANGE
MINIATURE ELECTRO-PNEUMATIC TRANSDUCER
Installation, Operation and Maintenance Instructions
Figure 1. Model T7800 Extended Range Transducer Identification Number System.
GENERAL INFORMATION
The Model T7800 Series of Electro-Pneumatic Trans­ducer converts a DC input signal to a linearly proportional pneumatic output pressure.
1
Page 2
Specifications (continued)
HAZARDOUS AREA CLASSIFICATION
FM Approval (continued):
Non-Incendive: (4-20 mA and voltage input units) (TDFI7800, TAFI7800, TDFN7800, TAFN7800)
Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups F, and G; Class III, Division 2; NEMA 4X Enclosure; Te mperature Code T4.
(TTFI7800, TRFI7800, TTFN7800, TRFN7800)
Class I, Division 2, Groups A, B, C and D; Te mperature Code T4.
CSA (Canadian Standards Association) Approvals:
Intrinsically Safe: (4-20 mA only) (TDCI7800, TACI7800)
Class I, Division 1, Groups C and D; Class II, Division 1, Groups E, F, and G; Type 4 Enclosure; Rated 4-20 mA, 30 VDC Maximum; Te mperature Code T6.
(TTCI7800, TRCI7800)
Class I, Division 1, Groups C and D; Te mperature Code T6.
Approvals are valid when connected through a Shunt Zener Diode Safety Barrier meeting the following para­metric requirements:
System Type 1:
System Type 2:
System Type 3:
Single Channel Polarized Rated: 28.5V Max. 300 Ohm Min.
Dual Channel Polarized Rated: 28.5V Max. 300 Ohm Min. and 10V Max. 50 Ohm Min.
Dual Channel Polarized Rated: 28.5V Max. 300 Ohm Min. and 28V Diode return per channel.
Division 2 Approvals: (4-20 mA only) (TDCI7800, TTCI7800, TRCI7800)
Class I, Division 2, Groups A, B, C and D; Rated 4-20 mA, 30 VDC Maximum; Te mperature Code T6.
(TACI7800)
Class I, Division2, Groups A, B, C and D; Class II, Division 2, Groups E, F, and G; Type 4 Enclosure; Rated 4-20 mA, 30 VDC Maximum; Te mperature Code T6.
FM (Factory Mutual) Approvals:
Intrinsically Safe: (4-20 mA only) (TDFI7800, TAFI7800)
Class I, Division 1, Groups C and D; Class II, Division 1, Groups E, F, and G; Class III, Division 1,Fibers; NEMA 4X Enclosure; Te mperature Code T4.
(TTFI7800, TRFI7800)
Class I, Division 1, Groups C and D; Te mperature Code T4.
Entity Parameters
1
Vmax Imax
1
Vmax = Maximum Voltage
2
Imax = Maximum Current
= =
30 VDC 200 mA
2
Ci Li
3
4
3
=
4
0 F
=
0 mH
Ci = Capacitance
Li = Inductance
ATEX Approvals: Intrinsically Safe: (4-20 mA only) (TAEI7800, TDEI7800, TTEI7800, TREI7800)
II 1G (T4) EEx ia IIB, T4 (-200 C to +720 C Ambient).
(TAEI7800, TDEI7800)
IP65 Enclosure.
Transducer Parameters
1
Umax
2
Imax
1
Umax = Maximum Voltage
2
Imax = Maximum Current
(Ui)
(Ii)
=
28 V
=
100 mA
3
Wmax
4
(Ci)
Ceq
5
Leq
(Li)
3
Wmax = Maximum Power
4
Ceq = Capacitance
5
Leq = Inductance
2
(Wi)
= = =
0.7 W 0 0
Page 3
INSTALLATION
The Model T7800 can be mounted directly onto a flat surface using two 10-32 Screws. For more information, see Figure 2. “TA7800 Outline Dimensions”.
The Model T7800 is supplied with a Mounting Kit EA­16799-1 for Panel or Wall Mounting and a Mounting Bracket Kit EA-16893-1 for Din Rail Mounting. For more informa­tion, see Figure 3. on page 3 and Figure 7. on page 5.
An Optional Mounting Kit EA-19254-1 is available when installing the unit on a 2" pipe. For more information, see Figure 8. on page 5.
NOTE:
The TR7800 Transducer is designed for use with the TR Rack Kit. Physically, it is the same as the TT7800 (Terminal Block) Unit except that the terminal block has been rotated to the rear. For more information, see Figure 6. “TR7800 Outline Dimensions” on page 4.
Figure 2. TA7800 Outline Dimensions.
Figure 3. Mounting Kit EA-16799-1. (Included with Unit)
ATEX Directive - Special Conditions for Safe Use:
The enclosure is manufactured from aluminum alloy. In rare cases, ignition sources due to impact and friction sparks could occur.
This shall be considered when the equipment is installed in locations that specifically require Group II, category 1G equipment
3
.
Page 4
Installation (continued)
5 15/64
133.0
1/4 NPT
Outlet
Port (2)
(typical)
1 33/64
38.7
++
V
Z
OUT
OUT
Z
_
V
S
S
IN
1/4 NPT Inlet Port (2) (typical)
IN
Figure 4. TT7800 Outline Dimensions.
90 Alternating Positions
S
21/4
57.1
27/32
21.5
4 57/64
124.3
15/16
33.3
127/64
36.2
4 21/32
118.1
5 15/64
133.0
1/4 NPT
Outlet
Port (2)
(typical)
1/4 NPT
Outlet
Port (2)
(typical)
OUT
OUT
1 33/64
38.7
_
++
V
VS
OUT
OUT
IN
1/4 NPT Inlet Port (2) (typical)
IN
Figure 5. TD7800 Outline Dimensions.
21/4
57.1
Vent
IN
1/4 NPT Inlet Port (2) (typical)
IN
111/16
42.9
27/32
21.5
457/64
124.3
Figure 6. TR7800 Outline Dimensions.
4
Page 5
Installation (continued)
Figure 7. Din Rail Mounting Kit EA-16893. (Included with Unit)
Figure 8. Optional Mounting Kit EA-19254-1. (Sold Separately)
5
Page 6
Pneumatic Connections
Electric Connections
Clean all pipelines to remove dirt and scale before instal­lation.
Apply a minimum amount of pipe compound to the male threads of the fitting only. Do Not use teflon tape as a sealant. Start with the third thread back and work away from the end of the fitting to avoid the possibility of contaminating the transducer. Install the transducer in the air line.
The inlet and outlet ports, in the lower valve body, are labeled on the ends of the transducer. Tighten connec­tions securely. Avoid undersized fittings that will limit the flow through the transducer and cause a pressure drop downstream. For more information, see Figure 2. “Outline Drawing” on page 3.
NOTE:
Instrument quality air, per ISA Standards S7.3­1981, is required. Use a filter to remove dirt and liquid in the air line ahead of the trans­ducer for correct performance. If an air line lubricator is used, it MUST be located down­stream, beyond the transducer.
The user is responsible for insuring that the environment in which the unit will be in­stalled, and the operating gas, are compatible with the materials in the transducer.
Make connections to the Terminal Block, Conduit Connec­tor or the DIN Connector as shown below in Figure 9. “Electrical Connections”.
Wiring in Hazardous Areas
Wiring in hazardous areas should be performed in accor­dance with the table 1. and any local codes that apply.
Table 1. Hazardous Location Wiring Practices.
Country
U.S.
Agency
FM
Code
ANSI/ISA RP 12.6
ANSI/NFPA 70 Canada Europe
CSA ATEX
CED Part 1
EN 50 039
Intrinsically Safe Connections
Refer to the latest revision of the indicated drawing.
Table 2. Intrinsically Safe Connections.
Underwriting Group Drawing Number
FM (Factory Mutual) CSA (Canadian Standards) ATEX
EC-18970 EC-18971 EC-18972
Figure 9. Electrical Connections.
6
Page 7
CALIBRATIONS / ADJUSTMENTS
SPLIT RANGE OPERATION
Equipment Required for Calibration:
Pneumatic Supply capable of delivering up to 150 psig.
Current Supply capable of delivering up to 60 mA.
Pressure Gage capable of a digital readout up to 150
psig with an accuracy of .1%.
Digital Volt Meter capable of a readout up to 60 mA with an accuracy of .02%.
The following adjustments are provided:
Full Range Operation Lo/Hi Span Forward/Reverse Mode Calibration - Zero and Span Split Range Operation Damping Adjustments
FULL RANGE OPERATION
Lo/Hi Span Adjustment
1.
Set the Lo/Hi Span Jumper to the Hi position for 0-30 psig, 0-60 or 0-120 psig output range. For more information, see Table 3. “Full Range Operation” on page 8.
Lo/Hi Span Adjustment
1.
Set the Lo/Hi Span switch to the Lo position for 0-15 psig, 15-30 psig, 0-30 psig, 30-60 psig, 0-60 psig, or 60-120 psig, output range. For more information, see Table 4. “Split Range Operation” on page 8.
Forward Acting Mode Adjustment
2.
Set Fwd/Rev Mode Jumper to the Forward position.
• Forward Acting Calibration - Zero
3.
Apply the minimum input signal and adjust the Zero screw for minimum output pressure.
• Forward Acting Calibration - Span
4.
Apply the maximum input signal and adjust the Span screw for maximum output pressure.
5.
Repeat steps 3-4 until the desired output range is obtained.
Reverse Acting Mode Adjustment
NOTE:
6.
DO NOT reverse the input leads.
Set Fwd/Rev Mode Jumper to the Reverse position.
Forward Acting Mode Adjustment
2.
Set Fwd/Rev Mode Jumper to Forward position.
• Forward Acting Calibration - Zero
3.
Apply the minimum input signal and adjust the Zero screw for minimum output pressure.
• Forward Acting Calibration - Span
4.
Apply the maximum input signal and adjust the Span screw for maximum output pressure.
5.
Repeat steps 3-4 until the desired output range is obtained.
Reverse Acting Mode Adjustment
NOTE:
6.
DO NOT reverse the input leads.
Set Fwd/Rev Mode Jumper to the Reverse position
• Reverse Acting Calibration - Zero
7.
Apply the maximum input signal and adjust the Zero screw for minimum output pressure.
• Reverse Acting Calibration - Span
8.
Apply the minimum input signal and adjust the Span screw for maximum output pressure.
• Reverse Acting Calibration - Zero
7.
Apply the maximum input signal and adjust the Zero screw for minimum output pressure.
• Reverse Acting Calibration - Span
8.
Apply the minimum input signal and adjust the Span screw for maximum output pressure.
9.
Repeat steps 7-8 until the desired output range is obtained.
Additional Adjustments
• Damping Adjustment
The Damping Adjustment is used so that the transducer can be tuned for optimum response and stability in a particular application.
For best performance start Damping Adjustment at maximum adjustment (fully clockwise). Gradually turn counterclockwise until slight oscillation occurs and then turn back clockwise until oscillation is minimized. For more information, see Figure 10. “T7800 Calibration Configuration”
Turn Damping Adjustment clockwise to increase
1.
damping function.
9.
Repeat steps 7-8 until the desired output range is obtained.
Turn Damping Adjustment counterclockwise to
2.
decrease damping function.
7
Page 8
Calibrations / Adjustments (continued)
Table 3. Full Range Operation.
Input
4-20 mA, 0-5, 1-5, 0-10 & 1-9 VDC
HI SPAN SETTING (Current & Voltage)
J7 Jumper
Adjustment
Output
psig BAR (kPa)
0-30 0-2 0-200 HI 0-60 0-4 0-400 HI 0-120 0-8 0-800 HI
Zero
J7
Span
Position
Jumper
H
Table 4. Split Range Operation.
Input
4-20 mA, 0-5, 1-5, 0-10 & 1-9 VDC
1
Split Range Output.
J7
Jumper
Output
psig
0-15 0-1 0-100 LO
15-30 1-2 100-200 LO
0-30 0-2 0-200 LO
30-60 2-4 200-400 LO
0-60 0-4 0-400 LO
60-120 4-8 400-800 LO
BAR
1
1
1
1
1
1
1
1
1
LO SPAN SETTING
(Current & Voltage)
1
1
1
L
J1 Jumper
FORWARD ACTING
OPERATION
(Current Unit)
Span
Position
(kPa)
1 1 1
1
1
1
DAMPING ADJUSTMENT
Decrease
Damping
Function
Span
Adjustment
Increase Damping Function
J1
REVERSE ACTING
OPERATION
(Current Unit)
C
B
A
D
J1
J1
B
A
J1
FORWARD ACTING OPERATION (Voltage Unit)
C
B
A
REVERSE ACTING OPERATION (Voltage Unit)
D
C
A
B
D
C
D
Figure 10. T7800 Calibration Configuration.
8
Page 9
Table 5. T7800 Transducer Components.
Item
Qty.
Description
1 2 3 4 5 6 6 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 22 23 24 25 26 27 28 29 30 31
Cover, Machining
1
Screw
2
Screw
2
1
2
3
4
1
1
1
1
1
1
2
5
1
1
Gasket
1
Nozzle Body Assembly
1
Orifice Assembly
1
Orifice Assembly
1
Orifice Assembly
1
Spring
1
Disk
1
Diaphragm
1
Spacer Ring
1
Diaphragm Assembly
1
Foam Block
1
Valve Body Assembly
1
Screw
3
Pintle
1
Spring, PIntle
1
O-Ring
1
Plug
1
Screw
2
Diaphragm
1
Spacer Ring
1
Diaphragm Assembly
1
Diaphragm Assembly
1
Spring
1
Foam Block
1
Valve Body Assembly
1
Screw
3
Pintle
1
Spring, Pintle
1
O-Ring
1
Plug
1
Screw
2
1
For All Service Kits.
2
EA-19267-4 Service Kit Components Only.
0-30 psig, [0-2.0 BAR], (0-200 kPa)
3
EA-19267-5 Service Kit Components Only.
0-60 psig, [0-4.0 BAR], (0-400 kPa)
4
EA-19267-6 Service Kit Components Only.
0-120 psig, [0-8.0 BAR], (0-800 kPa)
5
EA-19267-5 & EA-19267-6 Service Kit
Figure 11. Exploded Drawing.
9
Page 10
MAINTENANCE
TROUBLE-SHOOTING
To clean the Orifice, use the following procedure:
Shut off the valve that is supplying air to transducer.
1. It is not necessary to remove the Transducer from the air line.
Remove the Orifice Assembly (6) from the unit. For
2.
more detailed information see Figure 11. “Exploded Drawing” on page 9.
Clean with alcohol and dry with compressed air.
3.
NOTES:
Parts must be completely dry before reassem­bling.
If the standard maintenance procedure does not correct the trouble, install Service Kit.
Table 6. Trouble-Shooting.
Problem
No Output
Solution (check)
Supply Pressure Clogged Orifice
Leakage
Low or Improper Span Adjust
Connections
Zero and Span Adjust Supply Pressure Low Output Leakage
Erratic Operation
DC Signal Loose Wires or Connections Liquid in Air Supply
WARNING:
Failure of Transducer could result in out­put pressure increasing to supply pres­sure possibly causing personal injury or damage to equipment.
LEGAL NOTICE:
The information set forth in the foregoing Installation, Operation and Maintenance Instructions shall not be modified or amended in any respect without prior written consent of Fairchild Industrial Products Company. In addition, the information set forth herein shall be furnished with each product sold incorporating Fairchild's unit as a component thereof.
IS-50T7800E Litho in USA Rev. H 04/05
Loading...