Fairchild T9000 Installation Instructions Manual

Page 1
FAIRCHILD T9000 DIGITAL
ELECTRONIC PRESSURE CONTROLLER
Installation Instructions
5.17
131.3
3.51
0.70
17.9
Pilot Filter
89.2
1.57
39.9
Exhaust Port 1/4" NPT 1/4" BSPT 1/4" BSPP
0.42
IN
10.7
2.17 55
OUT
3.00
76.2
1.93 49
1.13
28.6
1.50
38.1
Display
Remote Pressure Sensor
Adaptor
OUT
0.50
12.7 Hex
0.93
23.5
0.70
17.8
Inlet & Outlet Ports 1/4" NPT 1/4" BSPT 1/4" BSPP
3.30
83.8
1.43
36.2
0.20
ref BSPP Plug
1.80
45.7
5.1
Accessory Right Angle Connector
1/4-20 UNC-2B or M6X1 Mtng Holes
2 x
0.34
8.6
0.88
22.2
0.59 15
2.50
63.5
4.25 108
5.00 127
1.55
39.2
1.90
48.1 CLEAR
0.46
11.6
1.75
1.12
44.5
28.3
Figure 1.
T9000 Outline Dimensions shown with Mounting Kit 19634-3 or -4
INSTALLATION
The Model T9000 is supplied with a Mounting Kit 19634-3 (or 19634-4 for metric threads) for Panel or Wall Mounting. For more information, see Figure 1. above.
(Included with Unit)
LEGAL NOTICE: The information set forth in the foregoing Installation, Operation and Maintenance Instructions shall not be modified or amended in any respect without prior written consent of Fairchild Industrial Products Company. In addition, the information set forth herein shall be furnished with each product sold incorporat­ing Fairchild's unit as a component thereof.
1
Page 2
REMOTE PRESSURE SENSING
The T9000 series pressure controllers can sense pressure from a remote location in the process system by employing the remote pressure sensing port. Remote pressure sensing can be usefull for improving system response and eliminating the pressure drop associated with air flowing through the outlet tubing between the pressure controller and the process.
Remote pressure sensing is accomplished by removing the remote sensing port plug and inserting the 21665-* remote pressure sensing adaptor in the port. This special adaptor blocks the pressure sensing passage coming from the outlet chamber of the pressure controller and makes the on board feedback pressure sensor connection available at the adaptor.
CAUTION:
Because of propagation delays in long feedback lines, the there is a limit in the length of the feedback line that can be employed, otherwise the system pressure will oscillate. In general terms, the longer the feedback line, the larger the line must be to affect a stable system. Adjustment of the T9000's PID constants may also be required. Be sure there are no restrictions (kinks in the line or undersize fittings) in the feedback line. Some experimentation may be required to determine the line size for the length of run of the feedback line.
CAUTION:
To prevent damage to the Remote Pressure Sense Port Adaptor, support the Remote Pressure Sense Adapter with a wrench when installing the air line fitting. For more information,see Figure 3. below.
21665-* ADAPTOR
Figure 2.
TANK
FEEDBACK TUBE
OUTLET TUBE
Remote Pressure Sensing
* Remote Pressure Sense Port Adaptors
Part Number
21665-1N
21665-1U
Pipe Connection
1/8-27 NPTF
1/8-28 BSPT
2
Page 3
PNEUMATIC CONNECTIONS
Clean all pipelines to remove dirt and scale before installation.
Apply a minimum amount of pipe compound to the male threads of the air line only.
sealant.
Start with the third thread back and work away
Do Not use teflon tape as a
from the end of the pipeline to avoid the possibility of getting pipe compound into the air lines.
The inlet and outlet ports are labeled on the bottom of the Pressure Controller. Tighten connections securely. Avoid undersized fittings that will limit the flow through the transducer. For more information, see Figure 1. "T9000 Outline Dimensions" on page 1.
CAUTION:
Oil free air is required. Use a filter to remove dirt and liquid in the air line ahead of the pressure controller. If an air line lubricator is used, it MUST be located downstream to avoid interference with pressure controller performance.
Supply pressure must be no less than 5 psig, [0.35 BAR], (35 kPa), above maximum output.
Pressure Controller Electrical Connections
ELECTRIC CONNECTION
For the T9000 Pressure Controller, make connections as shown below in Figure 2. "Electrical Connections". For compatible cord sets and connections refer to Table 1. below.
For signal lines of six feet or less, 22 gage wire may be used. For longer signal lines, use 18 gage wire. Shielded cable must be used for the signal lines for noise immunity.
Table 1. T9000 Cables
Part number
032-IPI-018-2
032-IPI-019-2
(Sold Separately)
Description
Cable w/one straight connector (2 meter)
Cable w/one right angle connector (2 meter) shown
Model T9000 Series
Figure 2.
¹ Colors apply only to FIPC DeviceNet compatible cables.
PIN #
1
2
3
4
5
6
Wire Color
Brown
White
Blue
Black
Gray
Pink
Function
(+) 4-20mA or 0-10vdc FEEDBACK
(-) FEEDBACK RETURN
(+) 4-20mA or 0-10vdc CONTROL SIGNAL
(-) CONTROL SIGNAL RETURN
(-) SUPPLY RETURN
(+) 18-32VDC SUPPLY
6
1
KEY
2
5
4
3
Electrical Connections.
FAIRCHILD INDUSTRIAL PRODUCTS CO.
REGISTERED TO ISO 9001:2008
10002346 QM08
Fairchild Products Company 3920 West Point Blvd. • Winston-Salem, NC 27103 phone: (336) 659-3400 • fax: (336) 659-9323 sales@fairchildproducts.com • www.fairchildproducts.com
FAIRCHILD
precision pneumatic & motion control
®
II-500T9000 Litho in USA Rev _ 4/11
3