Manual instructions
Installation and Operation
Manual de instrucciones
Uso y mantenimiento
ES
EN
DOCUMENT CODE: 602305M0063
Page 2
2
fagorindustrial.com
INDEX
ENGLISH
SPECIFICATION CHART ...........................................................................................................................4
MACHINE INTRODUCTION ..........................................................................................................................5
1.1 Introduction to machine & models .......................................................................................5
1.2 Important safety information ..................................................................................................5
INSTALLATION .................................................................................................................................................6
2.1 General information .....................................................................................................................6
2.2 Transport, handling, unpacking, location ......................................................................6
2.3 Intended use and restrictions ...............................................................................................7
2.4 Manufacturer’s identification label description .........................................................7
2.5 Installation and assembly ........................................................................................................8
2.6 Connections (electrical) ............................................................................................................8
OPERATION........................................................................................................................................................8
3.1 General information .....................................................................................................................8
3.2 Control panel description .......................................................................................................8
3.2.1 Electronic Control...............................................................................................................8
3.3 Machine settings and programs ............................................................................................9
MAINTENANCE .............................................................................................................................................. 10
4.1 General safety rules................................................................................................................ 10
4.2 Machine cleaning and maintenance routine ................................................................. 10
4.2.1 Cleaning the Condenser Coil ....................................................................................... 10
4.2.2 Cleaning the Gasket .......................................................................................................... 11
4.2.3 Draining the Unit ................................................................................................................ 11
4.3 Machine disposal ........................................................................................................................ 11
TROUBLESHOOTING CHART .................................................................................................................. 12
5.1 Troubleshooting chart ............................................................................................................ 12
Page 3
3
fagorindustrial.com
ESPAÑOL
INTRODUCCION ............................................................................................................................................ 13
1.1 Introducción a los equipos y modelos ........................................................................... 13
1.2 Información de seguridad ...................................................................................................... 13
INSTALACION ................................................................................................................................................ 14
2.1 Información General ................................................................................................................. 14
2.2 Transporte, manejo, desempaque y localización ...................................................... 14
2.3 Uso y restricciones ................................................................................................................... 15
2.4 Placa de identificación del Fabricante .......................................................................... 15
.......................................................................................................................................................................... 15
2.5 Instalación y Ensamble ........................................................................................................... 16
2.6 Conexiones ...................................................................................................................................... 16
OPERACION .................................................................................................................................................... 16
3.1 Información General ................................................................................................................. 16
3.2 Descripción del panel de control ..................................................................................... 16
3.2.1 Control electronico ......................................................................................................... 16
3.3 Configuraciones del Equipo ................................................................................................. 17
4.1 Reglas de seguridad general .............................................................................................. 18
4.2 Rutina de limpieza y mantenimiento del equipo ........................................................... 18
4.2.1 Limpiando el condensador ............................................................................................. 18
4.2.2 Limpieza del empaque plástico ..................................................................................... 19
4.2.3 Drenado ................................................................................................................................... 19
4.3 Disposición del equipo ............................................................................................................. 19
SOLUCIONANDO PROBLEMAS ............................................................................................................. 20
5.1 Solucionando problemas........................................................................................................ 20
ELECTRIC DIAGRAM / DIAGRAMA ELECTRICO .............................................................................. 21
ANEXOS ............................................................................................................................................................ 24
Page 4
4
fagorindustrial.com
SPECIFICATION CHART
PREMIUM LINE “N”
NOTES:
__________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ _______________________________________________________________________________________
MODEL
HP
DIMENSIONS
(in) mm
VOLTAGE
(V)
AMP.
(A)
REFRIGERANT
CHARGE
TIPO
REFRIG.
BTUS/
HR
WEIGHT
(LB)
QVR-1 N
1/4
(17 x 31 x 80)
685 x 675 x 1825
115 220
5.0
3.1
11.3 Oz.
R-134a
1660
264 lb
QVR-1G N
1/3
(37 x 27 x 84)
1105 x 812 x 1981
115 220
6.6
3.5
11.3 Oz.
R-134a
2104
440 lb
QVR-2 N
1/3
(55 ¼ x 27 ¾ x 84 ½)
1371 x 812 x 1981
115 220
6.9
3.5
13.4 Oz.
R-134a
2104
476 lb
QVR-2G N
1/3
(17 x 31 x 80)
685 x 675 x 1825
115 220
5.2
3.9
13.4 Oz.
R-134a
1660
264 lb
QVR-3 N
1/2
(27 x 31 x 80)
685 x 812 x 1981
115 220
5.8
3.9
22.2 Oz
R-134a
1666
280lb
QVR-3G N
1/2
(37 x 27 x 84)
1105 x 812 x 1981
115 220
7.2
3.9
22.2 Oz
R-134a
2104
440 lb
QVF-1 N
3/4
(55 ¼ x 27 ¾ x 84 ½)
1371 x 812 x 1981
115 220
9.8
4.5
16.6 Oz.
R-134a
2104
476 lb
QVF-1G N
3/4
(17 x 31 x 80)
685 x 675 x 1825
115 220
9.8
4.5
16.6 Oz.
R-404A
2493
280 lb
QVF-2 N
3/4
(27 x 31 x 80)
685 x 812 x 1981
115 220
11.5
6.5
21.5 Oz.
R-404A
2493
280 lb
QVF-2G N
3/4
(55 ¼ x 27 ¾ x 84 ½)
1371 x 812 x 1981
115 220
11.5
6.5
21.5 Oz.
R-404A
3644
456 lb
QVF-3 N
1
(72 x 27 ¾ x84 ½ ) 2060 x 812 x 1981
115 220
16.0
9.5
33.2 Oz.
R-404A
*
*
Page 5
5
fagorindustrial.com
MACHINE INTRODUCTION
1.1 Introduction to machine & models
FAGOR Reach Ins feature dual and triple paneL glass door, contributing to energy efficiency and savings. Standard digital control displays precise temperature for customer convenience while LED lights showcase the best out of your products.
Details make this line unique .
New enhanced digital controller and display. Digital controller refrigerators to keep food quality for longer period of
time.
Door alarm and user friendly controls to adapt to different enviroments. Factory balanced refrigeration system, environmentally friendly R-134a /
R-404A.
Stainless steel coved corner floor to meet NSF requirements.
4” castors and door locks standard.
Recessed door handles.
1.2 Important safety information
DANGER: Power must be turned off and disconnected from the power source whenever performing maintenance, repair or cleaning the condensing unit.
If machine still running when power is off, disconnect power at the circuit breaker before unplugging the machine. WARNING: Machine and compressor warranties are void if failure is due to improper electrical installation. Do not introduce hot foods, chemical or corrosive products, drugs, or open beverage bottles.
Notes
____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________
Page 6
6
fagorindustrial.com
INSTALLATION
2.1 General information
2.2 Transport, handling, unpacking, location.
2.3 Intended use and restrictions.
2.4 Manufacturer’s identification label description.
2.5 Installation and assembly.
2.6 Connections (electric, gas, water)
2.1 General information
You can find in you equipment the following symbols, or stickers to identify some type of warnings or useful information about your equipment.
2.2 Transport, handling, unpacking, location
Upon receiving your new FAGOR REACH IN, check the package and the machine for any damages that may have occurred during transportation. Visually inspect the exterior of the package, if damaged, open and inspect the contents with the
carrier. Any damage should be noted and reported on the delivering carrier’s
receipt.
In the event that the exterior is not damaged, yet upon opening, there is concealed damage to the equipment notify the carrier immediately. Notification should be made verbally as well as in written form. Request an inspection by the shipping company of the damaged equipment. Retain all crating material until inspection has been made. Contact the dealer through which you purchased the unit.
Check the compressor compartment housing and visually inspect the refrigeration package. Be sure lines are secure and base is still intact.
Page 7
7
fagorindustrial.com
2.3 Intended use and restrictions
FAGOR equipment is not designed for personal, family, or household purposes, and its sale for such purposes is not intended. In the event the equipment is so used, this warranty shall be null and void, and the equipment is so used, this warranty shall be null and void, and the equipment shall be deemed to have been sold “as is-where is” without any warranty of any kind, including without limitation any warranty of title, non-infringement, merchant-ability or fitness for a particular purpose.
The equipments are conforms to UL and NSF- 7 standards.
If you want know more about other restrictions about your equipment see the warranty that is located in the final part of your manual.
2.4 Manufacturer’s identification label description
The data plate is located inside the cabinet, near the top front, left corner. Under no circumstances should the data plate be removed from the unit. The data plate is essential to identify the particular features of your machine and it is of great benefit to installers, operators, and maintenance personnel. It is recommended that, in the event the data plate is removed, you copy down the essential information in this manual for reference before installation. Removal of data plate will void the warranty.
Model
Refrigerant
Type
Electricals
Serial Number
(8 digits and ends in “M”)
Code
Serial Number
Page 8
8
fagorindustrial.com
2.5 Installation and assembly
Units represented in this manual are intended for indoor use only. Be sure the location chosen has a floor strong enough to support the total weight of the unit and contents. For the most efficient operation, be sure to provide good air circulation inside and outside of the unit.
INSIDE CABINET The first cleaning must be made when you unpack the unit and before switching it on. Clean it with water and a mild detergent. When it is clean and dry, insert the accessories in the appropriate places, for the best use of the user.
OUTSIDE CABINET Be sure the unit has good air circulation around it. Avoid hot corners and locations near stoves and ovens. It is recommended the unit be installed no
closer than 2” from any wall. The place where the refrigerator is placed must be
open and clean, avoiding that de fan of the condensing unit absorbs materials which are deposited then into the condenser blades and coil, which can produce failures.
The unit should not be installed under ambient temperatures higher than 100 °F.
If the relative humidity is higher than 60 %, the door frames may sweat water. This is not a malfunctioning of the unit.
2.6 Connections (electrical)
Refer to the amperage data in this manual or on data plate and your local code or the National Electrical Code to be sure unit is connected to the proper power source. Verify correct incoming voltage according to the Data Plate information. The data plate in located inside the unit, near the top front left corner. Under any circumstances should the data plate be removed from the unit. The data plate is essential to identify the particular features of your unit and is of great benefit to installers, operators and maintenance personnel. It is recommended that, in the event the data plate is removed, you copy down the essential information in this manual for reference before installation. A protected circuit of the correct voltage and amperage must be run for connection of the supply cord. Unit must be grounded and connected in accordance with NEC Article 422 Appliances.
OPERATION
3.1 General information.
3.2 Control panel description.
3.3 Machine settings and programs.
3.1 General information
Good air flow inside the cabinet is critical. Do not block air flow to the fans. Allow three inches of space along the front, back, and sides.
3.2 Control panel description
3.2.1 Electronic Control
After connecting your unit, turn ON rocker switch located next to the controller. The display will light up showing the temperature inside the unit. Also, the compressor and fan icons will flash for a period of three minutes. After this delay the unit will start cooling. Verify you don't have any alarms on the temperature controller. If after you turn ON the equipment the controller shows the alarm icon or an error code, call for technical service. They will help you fix the problem.
Page 9
9
fagorindustrial.com
3.3 Machine settings and programs
Changing the Set Point of the temperature on the controller
The unit comes with a factory default set point ( 32°F Refrigerators). These set values will make the unit perform at its maximum capacity. Therefore, it is not recommended to change the set point. If set point needs to be changed, follow the next steps.
1. Push the SET button for one second. You should see a flashing number.
Release the button.
2. Press the up and down arrows to increase or decrease the set
temperature. Then press the set button to save the new set point.
Note:
The maximum value you can set in the controller is: For refrigerators: 5°C (40°F)
3. If you wish decrease the value of the set point for a new temperature,
press the button DOWN arrow (see the picture below). Press this button to reach the desired value. Release the button and then press the SET button to keep, and save, the new value.
Note:
The minimum value you can set in the controller is: For refrigerators: -1°C (30°F)
Manual Defrost
To select manual defrost, hold the button DOWN arrow for 5 seconds. The snow flake icon will appear on the display. When this icon is solid it indicates that the equipment is in Defrost mode.
To exit manual defrost, hold the DOWN button arrow for 5 seconds. The snow flake icon will turn off. Wait 2 minutes for the compressor to start
FIGURE 1
ALARM MENU
ON/OFF
ENERGETIC SAFETY MODE
To increase Set Point of Temperature /Continues cycle
To Change the set point To access programming mode
To decrease Set Point of Temperature To set a manual defrost
Page 10
10
fagorindustrial.com
MAINTENANCE
4.1 General safety rules.
4.2 Machine cleaning and maintenance routine.
4.3 Machine disposal.
4.1 General safety rules
Neglecting the condenser coil cleaning procedures WILL VOID YOUR WARRANTY associated with the compressor or cost to replace the compressor!
Proper cleaning of stainless steel requires soft cloths or plastic souring pads. Never use steel pads, wire brushes or scrapers!
4.2 Machine cleaning and maintenance routine
Cleaning solutions need to be alkaline or non-chloride cleaners. Any cleaner containing chlorides will damage the protective film of the stainless steel. Chlorides are also commonly found in hard water, salts, and household and industrial cleaners. If cleaner containing chlorides are used be sure to rinse repeatedly and dry thoroughly upon completion.
Routine cleaning of stainless steel can be done with soap and water. Extreme stains or grease should be cleaned with a non-abrasive cleaner and plastic scrub pad. There are also stainless steel cleaners available which can restore and preserve the finish of the steels protective layer.
Never use and acid based cleaning solution! Many food products have an acidic content which can deteriorate the finish. Be sure to clean the ALL food products from any stainless steel surface. Common items include peppers, tomatoes and other vegetables.
4.2.1 Cleaning the Condenser Coil
Disconnect machine. Remove front bottom panel and carefully slide out the condensing unit. The condenser coil requires regular cleaning; recommended every 30-60
days, depending of the accumulation of dust and grease. If the buildup on the coil consists of only light dust and debris the condenser coil can be cleaned with a simple brush. Heavier dust build up may require a vacuum or even compressed air to blow though the condenser coil. If heavy grease is present there are de-greasing agents available for refrigeration use and specifically for the condenser coils. The condenser coil may require a spray with the de-greasing agent and then blown through with compressed air.
Be sure all electrical and mechanical parts are dry before turning on the power. Never use a high pressure water wash for this cleaning procedure as water can damage the electrical components located near or at the condenser coil. Do not place filter material in front of condenser coil. This material blocks air-flow to the coil similar to having a dirty coil!
If you keep the Condenser clean you will minimize your service expense and lower your electrical costs. Failure to maintain a clean condenser coil can initially cause high temperatures and excessive run times. Continuous operation with dirty or clogged condenser coils can result in compressor failures.
To put back the condensing unit in its place, slide in the unit carefully. BE SURE DRAIN PIPE IS LOCATED OVER THE PAN. Replace front bottom panel
Page 11
11
fagorindustrial.com
4.2.2 Cleaning the Gasket
Gaskets require regular cleaning to prevent mold and mildew build up and also to keep the elasticity of the gasket. Gasket cleaning can be done with the use of warm soapy water. Avoid full strength cleaning products on gaskets as this can cause them to become brittle and prevent proper seals. Also, never use sharp tools or knives to scrape or clean the gasket which could possibly tear the gasket and rip the bellows.
Gaskets can easily be replaced and do not require the use of tools or authorized service persons.
The gaskets can be pulled out of the grove in the door and new gaskets can be “pressed” back into place.
4.2.3 Draining the Unit
Each unit has a drain located inside the unit which removes the condensation from the evaporator coil and evaporates it at an external condensate evaporator pan. Each drain can become loose or disconnected from moving or bumping the drain.
IF YOU NOTICE EXCESSIVE WATER ACCUMULATION ON THE INSIDE OF THE UNIT be sure the drain tube is connected from the evaporator housing to the condensate evaporator drain pan.
IF WATER IS COLLECTED UNDERNEATH THE UNIT you may want to check the condensate evaporator drain tube to be sure it is still located inside the drain pan. The leveling of the unit is important as the units are designed to drain properly when on a level surface, if your floor is not level this can also cause drain problems. Be sure all drain lines are free of obstructions; typically food product is found blocking drain lines causing water to back up and overflow the drain pans.
4.3 Machine disposal
The product’s life-cycle is around 7 to 10 year from the First use an instalation date.
FAGOR equipment is manufactured without dangerous or toxic materials. Some parts of the equipments are biodegradable.
The disposing after the product’s life-cycle shall be determined according to the rules and laws established in the city or State of residence.
REMEMBER TO TAKE CARE OF THE ENVIRONMENT.
Page 12
12
fagorindustrial.com
TROUBLESHOOTING CHART
5.1 Troubleshooting guide chart
5.1 Troubleshooting chart
Follow the next steps before requesting warranty service. Failure to do so, may result in service charges for you and may void your warranty:
1)
Refrigerator doesn’t work:
a. Check that the machine is still connected. b. Check that the ON/OFF button is in the ON position.
2)
Refrigerator doesn’t reach temperature :
a. Verify unit is not on saving mode b. Check that the thermostat or controller is not in OFF position. c. Check that the machine is not in the defrost cycle. d. Ensure Equipment is in a ventilated place and removed
minimum of 2 inches from any other appliance and away from any heat source.
e. The environment maximum temperature must be 38 °C/ 100°F. f. To insure proper air flow, product must not be placed
higher than the maximum level mark located on the internal wall of the unit.
g. If FREEZER, check that the temperature is not Celsius. h. Check that the gasket is in good condition and door is sealed. i. Check that the fan is moving. Open the door and press and
hold doors witch for verification.
j. Dont put any food inside until the unit has reached the proper
temperature.
k. If FREEZER, food must be previously frozen before being placed
inside the cabinet.
l. Be sure castors or legs were installed.
3)
There is water inside the refrigerator:
a. Check that the drain pan inside the cabinet is in position. b. Check that there is not food clogging the drain line.
4)
There is water under the refrigerator:
a. Check that the drain pipe is over the pan.
b. Check that the cabinet is level.
Warning: To i n s u r e proper operation of equipment, it is recommended that the unit is on for 24 hours prior to the introduction of perishables.
Page 13
13
fagorindustrial.com
INTRODUCCION
1.1 Introducción a los equipos y modelos
Los armarios FAGOR cuentan con puerta de vidrio de panel doble y triple, contribuyendo al ahorro y eficiencia energética.
Estándar de control digital muestra la temperatura precisa para comodidad del cliente mientras
Luces LED exhibir lo mejor de sus productos...
Los detalles hacen que esta línea única.
• Nuevo mejorada pantalla y controlador digital.
• Refrigeradores controlador digital para mantener la calidad de
los alimentos durante largo periodo de tiempo.
• Puerta alarma y usuario amigables controles para adaptarse a diversos ambientes.
• Fábrica había equilibrado sistema de refrigeración ecológico R­134A.
Acero inoxidable coved piso esquina para cumplir los
requerimientos de NSF.
• 4 "ruedas y cerraduras de puerta estándar.
Manijas de puerta empotrado.
1.2 Información de seguridad
El equipo debe ser apagado y desconectado de la fuente de alimentación cuando realizar el mantenimiento, reparación o limpieza de la unidad condensadora. Si la máquina sigue funcionando cuando está apagado, desconecte la alimentación principal antes de desenchufar la máquina.
La garantía de la maquina y el compresor se anulan debido a la instalación eléctrica inadecuada. No introdusca alimentos calientes, productos quimios o corrosivos, drogas o botellas destapadas
Notes
____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________ ____________________________________________________________________________________________
ESPAÑOL
Page 14
14
fagorindustrial.com
INSTALACION
2.1 Información General
2.2 Transporte, manejo, desempaque y localización
2.3 Uso y restricciones
2.4 Placa de identificación del Fabricante
2.5 Instalación y ensamble
2.6 Conexiones (eléctricas, agua, gas)
2.1 Información General
En el equipo usted ecnontrara los siguientes simbolos y/o pegatinas que le ayudaran a identificar peligros y/o informacion util relacionada con su equipo.
2.2 Transporte, manejo, desempaque y localización
Al momento de recibir su equipo FAGOR, verifique el empaque en búsqueda de daños que pudieran haber ocurrido durante el transporte del mismo. Inspeccione de manera visual el exterior del empaque, si el mismo se encuentra dañado, abra e inspeccione, delante de la empresa transportadora, todo el equipo. Cualquier daño debe ser anotado y reportado en el recibo de entrega de la empresa transportadora.
IMPORTANTE: Una vez que se haya retirado todo el material del empaque, revise por la parte posterior del equipo el compartimiento del compresor. Inspeccione visualmente el sistema de refrigeración y asegúrese que las tuberías no estén dobladas y que no presenten alguna fisura, asegúrese que la base esté intacta.
Si al momento de abrir el empaque existe un daño oculto en el equipo, notifíquelo de inmediato a la empresa transportadora mediante un llamado telefónico así como también de manera escrita. Solicite una inspección por parte de la compañía transportadora si el equipo está dañado. Conserve todo el material de embalaje hasta que se haya realizado la inspección, contacte al proveedor con el que adquirió su equipo FAGOR.
Page 15
15
fagorindustrial.com
2.3 Uso y restricciones
EL equipo FAGOR no está diseñado para fines personales, familiares o del hogar, y su venta para esos fines no está prevista. En el caso de que el equipo se utiliza con tal fin, esta garantía será nula de pleno derecho, y el equipo se considerará que se han vendido "como es, donde es" sin garantía de ningún tipo, incluyendo, sin limitación, cualquier garantía de título, no infracción, los comerciantes la capacidad o aptitud para un propósito en particular.
Los equipos cumplen con los estándares de las normas UL y NSF-7
Si usted quiere saber más acerca de otras restricciones relacionadas con el equipo ver la garantía que se encuentra localizada al final del manual.
2.4 Placa de identificación del Fabricante
La placa de datos se encuentra dentro del gabinete, cerca de la parte superior delantera, a la izquierda. Bajo ninguna circunstancia debe quitar la placa de datos de la unidad. La placa de datos es esencial para identificar las características particulares de su máquina y es de gran beneficio para los instaladores, operadores y personal de mantenimiento. Se recomienda que, en caso de que se retira la placa de datos, copie la información esencial en este manual para referencia antes de la instalación.
Remoción de la placa de datos anulará la garantía.
Modelo
Tipo
Refrigerante
Especificaciones
eléctricas
Numero de Serie
(8 dígitos con terminación
en “M”)
Código
Numero de Serie
Page 16
16
fagorindustrial.com
2.5 Instalación y Ensamble
Las unidades presentadas en este manual están diseñadas para uso interior solamente. Asegúrese de que la ubicación elegida tiene un piso lo suficientemente fuerte para soportar el peso total de la unidad y contenidos. Para la operación más eficiente, asegúrese de proveer buena circulación de aire dentro y fuera de la unidad.
DENTRO DEL GABINETE La primera limpieza debe hacerse cuando Desempaque el aparato y antes de encenderlo. Limpie con agua y un detergente suave. Cuando esté limpio y seco, inserte los accesorios en los lugares apropiados, para el mejor aprovechamiento del usuario.
FUERA DEL GABINETE Asegúrese que la unidad tenga buena circulación de aire alrededor de él. Evite rincones calientes y lugares cerca de estufas y hornos. Se recomienda instalar la unidad a no menos de 2 " de cualquier pared. El lugar donde se coloca el refrigerador debe estar ventilado y limpio, evitando que el ventilador de la unidad condensadora absorba materiales que luego se depositan en las láminas del condensador y bobina, que puede producir fallas.
La unidad no debe ser instalada bajo temperaturas ambientales superiores a 100 ° F.Si la humedad relativa es superior al 60%, los marcos de las puertas pueden sudar agua. Esto no es un mal funcionamiento de la unidad.
2.6 Conexiones
Tome en cuenta los datos sobre el amperaje y voltaje que aparecen en la placa matricula del equipo. Es indispensable que la instalación eléctrica del usuario cumpla con los requerimientos y normatividades eléctricas nacionales y locales correspondientes al lugar donde se instalara el aparato.
El equipo debe ser instalado en un circuito protegido por sobrecargas y/o cortos circuitos así como por variaciones de voltaje.
IMPORTANTE: El contacto o enchufe debe tener conductor de tierra física obligatoriamente.
OPERACION
3.1 Información General
3.2 Descripción del panel de control.
3.3 Configuraciones del Equipo.
3.1 Información General
La buena circulación de aire dentro del gabinete es crítico. No obstruya el flujo de aire de los ventiladores. Coloque el equipo a no menos de 3 pulgadas de espacio a lo largo del frente, parte posterior y los lados como separacion para una ventilacion adecuada.
3.2 Descripción del panel de control
3.2.1 Control electronico
Después de conectar su unidad, active el interruptor situado en el controlador. La pantalla se encenderá mostrando la temperatura dentro de la unidad. Además, los iconos del compresor y del ventilador destellarán durante un período de tres minutos. Después de este retraso, la unidad comenzará de enfriamiento. Verificar que no tienes ninguna alarma en el regulador de temperatura. Si después de encienda el equipo el controlador muestra el icono de alarma o un código de error, solicite servicio técnico. Te ayudarán a solucionar el problema.
Page 17
17
fagorindustrial.com
3.3 Configuraciones del Equipo
Cambiando el Set Point (ajuste de temperatura)
El controlador tiene un SET POINT de temperatura programado de fábrica para garantizar el correcto funcionamiento del equipo. Si usted lo desea, puede cambiar el SET POINT de temperatura. Para ello, siga los pasos:
1. Pulse el botón de SET durante 2 segundos. Usted verá un número
parpadeando, suelte el botón, el número parpadeando es el valor del SET POINT de temperatura.
2. Si deseas aumentar el valor del SET POINT para una nueva temperatura,
presione el botón de flecha hacia arriba. Pulse este botón para alcanzar el valor deseado, suelte el botón y luego presione el botón de SET para guardar el nuevo valor.
Nota:
El valor maximo que el control puede mostrar es en refrigeradores: 5°C (40°F)
3. Si desea disminuir el valor del SET POINT para una nueva temperatura,
presione el botón de flecha hacia abajo. Pulse este botón para alcanzar el valor deseado, suelte el botón y luego presione el botón de SET para guardar el nuevo valor.
Nota: El valor minimo que el control puede mostrar es en refrigeradores: ­1°C (30°F)
Deshielo Manual
Para selecionar el deshielo manual, mantener precionado el boton de flecha hacia abajo abajo por 5 segundos. El icono del deshielo parpadeara y se mostrara en la pantalla. Cuando el icono deje de parpadear el equipo estara en modo de deshielo.
FIGURA 1
Menú alarmas
Encendido/Apagado
Modo Ahorro energía
Incrementa el Set Point de la Temperatura Ciclo Continuo
Cambiar el set point Acceder al modo de configuración
Decrementar el Set Point de la Temperatura
Page 18
18
fagorindustrial.com
Para salir del modo deshielo mantener presionado por 5 segundos el boton de la flecha hacia abajo.el icono de dehsielo se apagara. Esperar 2 minutos para que el compresor comience a funcionar.
MANTENIMIENTO
4.1 Reglas de seguridad general.
4.2 Rutina de limpieza y mantenimiento del equipo
4.3 Disposición del equipo
4.1 Reglas de seguridad general
Cualquier negligencia con los procedimientos de limpieza del compresor puede anular la garantía y generar un costo del remplazo del compresor.
Para la limpieza del acero inoxidable use paños suaves o esponjas. Nunca usar esponjas metalicas, cepillos de alambre o algun tipo de lija.
4.2 Rutina de limpieza y mantenimiento del equipo
La limpieza debe ser a base de limpiadores alcalinos o libres de cloro. Cualquier limpiador que contiene cloruros dañará la película protectora del acero inoxidable. Cloruros son también comúnmente encontrados en agua dura, sales y productos de limpieza domésticos e industriales. Si se utilizan limpiador que contienen cloruros asegúrese de enjuagar varias veces la superficie y seque bien al finalizar. La limpieza de rutina del acero inoxidable puede hacerse con agua y jabón. Las manchas de extremo o grasa deben limpiarse con un paño no abrasivo exfoliante limpiador. También hay limpiadores de acero inoxidable disponibles que se pueden restaurar y conservar el acabado de la capa protectora de los aceros. Nunca use una solución de limpieza a base de ácido. Muchos productos alimenticios tienen un contenido ácido que puede deteriorar el acabado. Asegúrese de limpiar los todos los productos alimenticios de cualquier superficie de acero inoxidable.
4.2.1 Limpiando el condensador
Desconecte la máquina. Quite el panel delantero inferior y cuidadosamente Deslice hacia afuera la unidad condensadora. La bobina del condensador requiere una limpieza regular; recomendado cada 30 a 60 días, dependiendo de la acumulación de polvo y grasa. Si la acumulación en la bobina consta de sólo luz el polvo y suciedad del serpentín del condensador puede limpiarse con un cepillo simple. Mayor acumulación de polvo puede requerir un vacío o incluso aire comprimido para soplar aunque el serpentín del condensador. Si hay grasa pesada hay agentes desengrasante disponible para el uso de refrigeración y específicamente para los serpentines del condensador. La bobina del condensador puede requerir un spray con el agente desengrasante y luego soplado a través con aire comprimido.
Asegúrese de que todas las partes mecánicas y eléctricas estén secas antes de conectar la alimentación. Nunca usar agua de alta presión para este procedimiento de limpieza, puede dañar los componentes eléctricos se encuentran cerca o en el serpentín del condensador. No coloque el material del filtro delante de la bobina del condensador. Este material bloquea el flujo de aire a la bobina similar a tener una bobina sucia!
Si mantienes el condensador limpio va a reducir al mínimo sus gastos de servicio y reducir sus costos de electricidad. No mantener un serpentín del condensador limpio inicialmente puede causar altas temperaturas y excesivos ciclos de operación. Operación continua con serpentines del condensador sucio u obstruido puede ocasionar fallas del compresor.
Para devolver la unidad condensadora en su lugar, deslice la unidad con cuidado. ASEGÚRESE DE QUE EL TUBO DE DESAGÜE ESTÁ SITUADO SOBRE LA BANDEJA.
Page 19
19
fagorindustrial.com
4.2.2 Limpieza del empaque plástico
El empaque requiere una limpieza regular para evitar la acumulación de moho arriba y también para mantener la elasticidad del mismo. La limpieza puede realizarse con el uso de agua caliente y jabón. Evitar productos de limpieza ya que esto puede causar que se tornen quebradizos y evitar el sellado adecuado. Además, nunca utilice herramientas o cuchillos para raspar o limpiar el empaque, posiblemente podrían romper el empaque y rasgar el fuelle.
Los empaques pueden ser reemplazados fácilmente y no requieren el uso de herramientas o personas autorizadas de servicio.
4.2.3 Drenado
Cada unidad tiene un drenado ubicado dentro de la unidad que elimina la condensación de la bobina del evaporador y lo evapora en un exterior condensado del evaporador. Cada drenaje puede ser removido o desconectado.
Si percibe excesiva acumulación de agua en el interior de la unidad asegúrese de que está conectado el tubo de desagüe del evaporador a la bandeja de drenaje de condensado del evaporador.
La nivelación de la unidad es importante, ya que las unidades están diseñadas para drenar adecuadamente cuando sobre una superficie nivelada, si el piso no está nivelado esto también puede causar problemas de drenaje. Asegúrese de que todas las líneas de desagüe estén libres de obstrucciones.
4.3 Disposición del equipo
El ciclo de vida promedio de los productos FAGOR es de 7 a 10 años apartir de la fecha de uso e intalacion primera.
Los equipos FAGOR son fabricados sin materiales toxicos o peligorosos. Algunas partes son biodegradables.
La disposicion final del equipo despues del termino del ciclo de vida sera definido por el cliente de acuedo a las reglas, y leyes establecidas en la ciudad y/o estado de residencia.
RECUERDE CUIDAR EL MEDIO AMBIENTE.
Page 20
20
fagorindustrial.com
SOLUCIONANDO PROBLEMAS
5.1 SOLUCIONANDO PROBLEMAS
5.1 Solucionando problemas
Algunas veces, las fallas son debido a causas simples que pueden ser solucionadas por el usuario. Antes de pedir ayuda a un técnico calificado, debe hacer algunas verificaciones. Estas fallas no están cubiertas por la garantía:
1) El refrigerador no funciona: a. Verifique que la maquina este conectada de forma correcta y que
exista el voltaje correcto para el equipo.
b. Verifique que el “Botón Encendido/Apagado” este en la posición de
“Encendido”.
2) El refrigerador no da la temperatura adecuada: a. Verifique que el equipo no está en el ciclo de deshielo.
b. Verifique que la temperatura no esté en °F. c. Verifique que el control no marque alguna alarma. d. Verifique que el SET POIT de temperatura es el correcto. e. Verifique que no existe obstrucción al flujo del aire en el interior
del equipo.
f. Verifique que el ventilador ó los ventiladores funcionan
correctamente. Abra la puerta y presione el interruptor (micro­switch) de la puerta para verificarlo.
g. Verifique que no haya hielo en el evaporador. h. Asegúrese que el condensador este limpio y que no haya objetos
que obstruyan el paso de aire por las tuberías del condensador.
i. Verifique que el ventilador del condensador funciona.
3) Hay agua dentro del equipo: a. Asegúrese que el panel de drenaje que se encuentra en el interior
del gabinete esté en su posición correcta.
b. Verifique que no haya alimento obstruyendo la línea del drenaje.
4) Hay agua debajo del equipo: a. Verifique que el tubo de drenaje esté dentro de la bandeja de
evaporación.
b. Verifique que el gabinete este nivelado.
Page 21
21
fagorindustrial.com
ELECTRIC DIAGRAM / DIAGRAMA ELECTRICO
QVR-1_N
QVR-2_N
Page 22
22
fagorindustrial.com
QVR-3_N
QVF-1_N
Page 23
23
fagorindustrial.com
QVF-2_N
QVF-3_N
Page 24
24
fagorindustrial.com
ANEXOS
Page 25
25
fagorindustrial.com
Page 26
Circuito Exportación N° 201
Parque Industrial Tres Naciones
San Luís Potosí, S.L.P. México
Teléfono Planta S.L.P.: + 52 (444) 137 0500 Ext.538
Sin costo: 01 800 00 FAGOR
MULTI-SOLUTION MANUFACTURER OF FOODSERVICE EQUIPMENT
13105 NW 47th Ave
Miami, Fl. 33054
Phone: (866) 463-2467
Loading...