INSTALLATION MANUAL
Set-up Drawing
Installation Precautions
Components
EcoPower®Flush Valve
For the best results, be sure to read the following installation instructions and use the product only as described in this manual.
c
Variation & Specification
Toilet Flush Valve
Figure
TET1LN32#CP
TET1GN32#CP
TEW1GN32#CP
1-1/2"
NPSM
4-3/4" 1/2"
(120 13mm)
11-1/2"
(292mm)
Min.2-1/4"
(57mm)
1"NPT
inlet supply
1. Prior to Installation
Prior to Installing your TOTO®`s EcoPower®Flush Valve, install the items
listed bellow:
· Closet fixture/Urinal fixture
· Drain line
· Water supply line
The supply piping to these devices shall be securely anchored to the
building structure to prevent the installed device from having unnecessary
movement when operated by the user. Care shall be exercised when
installing the device to prevent marring the exposed surface.
2. Important
All plumbing is to be installed in accordance with applicable codes
and regulations. Water supply lines must be sized to provide an
adequate volume of water for each fixture.
Flush all waterlines prior to operation.
The minimum pressure required to the valve is determined by the type
of fixture selected. Consult fixture manufacturer for pressure requirement.
Do not use toothed tools to install or service the valve.
Note
Be sure to install TOTO®`s EcoPower®Flush Valve so that the control stop
is situated no more than 11-1/2"(292mm) above the top of the bowl or
the urinal. Refer to local codes for special requirements.Except for
TET6GN#CP,
stop is installed 27" adove the
TEW6GN#CP and TET6LN#CP
top of the bowl for proper valve function.
3. Use care not to damage the surface of the infrared sensor.
, make sure that the control
1. Required tools
Adjustable wrench, Phillips and slotted screwdrivers.
2. Inspection
Unpack the flush valve and carefully make sure the cover, main unit and
all other parts are included and intact before starting installation of the
product.
Item Figure Description Q’ty
A
B
T
O
T
O
Valve Body
assembly
Top cover
assembly
1
1
Model number
Dimension of Cover
Detection time
Ambient temperature
Connection of the
water supply pipe
Minimum
Supply water
pressure
(Flowing)
Maximum
Shutoff pressure
Discharge quantity
per flush at 28 PSI
(196kPa)
(Factory set)
Urinal Flush Valve
TET1LN(32)#CP
TET6LN(32)#CP
7-3/4" (H) 4-1/2"(W) 3-1/8"(D)
(198mm(H) 115mm(W) 80mm(D))
Water temperature 34-104˚F (1-40˚C)
35 PSI (241kPa)
Approx. 1.28
gallon (4.8L)
TET1GN(32)#CP
TET6GN(32)#CP
6 seconds or more
32-104˚F (0-40˚C)
1"NPT
15 PSI (103kPa)
125 PSI (862kPa)
7 PSI (48kPa)
Approx. 1.6
gallon (6L)
TEW1GN(32)#CP
TEW6GN(32)#CP
Approx. 3.5
gallon (13L)
TET6LN32#CP
TET6GN32#CP
TEW6GN32#CP
1-1/2"
NPSM
TEU1LN(12,22)#CP
TEU1GN(12,22)#CP
4-3/4" 1/2"
(120 13mm)
27"
(686mm)
Check local codes
Min.2-1/4"
(57mm)
Check local codes
1"NPT
inlet supply
4. For Toilet Flush Valve
The toilet sensor valve may not function if toilet seat and/or lid cover are
left upright as it may block the sensor.
5. For Urinal Flush Valve
The Urinal Flush Valve is designed to be used with a washout urinal
for optimum performance. However, a siphon jet urinal may also be
substituted. Blowout urinals are not recommended.
6. The detection range of the infrared sensor is shown in the figure above.
Do not install a handrail or any other object within the detection zone
of the sensor, as any object blocking the sensor may cause the valve to
malfunction. Additionally, to avoid the possibility of valve malfunction, do not
install the flush valve in a location where the sensor faces a mirror,
stainless steel wall, other highly reflective surface or another infrared sensor.
Detection zone
The detection zone is self-adjusting and is equipped with a
3-second flush delay. (No flush delay for Urinal flush valve)
The detection zone may differ according to the color of the
user’s clothes.
When a user wears black clothes, the detection zone may
become smaller and the valve may not flush.
C
D
E
Toilet Flush Valve
F
Screw 2
Back-up
battery Pack
Tool
(Allen wrench)
Notice Label
1
1
1
Figure
Model number
Dimension of Cover
Detection time
Ambient temperature
Connection of the
water supply pipe
Supply water
pressure
Shutoff pressure
Discharge quantity
per flush at 28 PSI
(196kPa)
(Factory set)
TEU1LN(12,22)#CP
TEU1GN(12,22)#CP
7-3/4" (H) 4-1/2"(W) 3-1/8"(D)
(198mm(H) 115mm(W) 80mm(D))
6 seconds or more
32-104˚F (0-40˚C)
Water temperature 34-104˚F (1-40˚C)
3/4"NPT
Minimum required water pressure: 15 PSI (103kPa)
(flowing)
Maximum water pressure: 125 PSI (862kPa)
7 PSI (48kPa)
Approx. 0.5 gallon
(1.9L)
Approx. 1.0 gallon
(3.8L)
1-1/2"
NPSM
4-3/4" 1/2"
(120 13mm)
11-1/2"
(292mm)
Min.2-1/4"(57mm)
3/4"NPT
inlet supply
Check local codes
Max19-11/16"
(Max 500 mm)
L
Max31-1/2"
(Max 800 mm)
TET1GN(32)#CP
TEU1GN(12,22)#CP
TEW1GN(32)#CP
TET1LN(32)#CP
TEU1LN(12,22)#CP
TEW1LN(32)#CP
“AVOID”
DO NOT place the Infrared
15
Max21-1/4"
(Max 550 mm)
L
Max33-1/2"
(Max 850 mm)
TET6GN(32)#CP
TEW6GN(32)#CP
“AVOID”
DO NOT place the Infrared
20
sensor of one urinal so that sensor in front of a mirror,
it is in line with the sensor
of another automatic flush
stainless steel wall, or other
highly reflective surface.
valve sensor.
Infrared sensor of the
automatic flush valve.
Infrared sensor of the
another automatic
Mirror, Stainless steel wall or
other highly reflective surface.
Infrared sensor of the
automatic flush valve.
flush valve.
G
Owner's
Manual
Installation
H
Manual
(this manual)
For TET1GN32#CP, TEW1GN32#CP, TET6GN32#CP,
TEW6GN32#CP, TEU1GN(12, 22)#CP, TET1LN32#CP,
TET6LN32#CP AND TEU1LN(12, 22) #CP
Vacuum
I
breaker tube
(with spud
joint)
J Control stop
Sweat
solder kit
K
(Escutcheon,
covering tube,
adapter)
1
1
1
1
1
03585T3R
To be continued on the back
Installation Procedure Test Run
Note to the installer
7
6
Adjustment
Step 1 (For New Installation)
Escutcheon
White
White(Toilet type)
Yellow(Urinal type)
Yellow
Battery
Covering tube
Control Stop
Adapter
Min.4-1/4"(107mm)
Max.5-1/4"(133mm)
Install the control stop using a proper size escutcheon and
1. For left water supply, attach the sensor top cover in the
opposite direction so that the sensor will be at the front.
2. For retrofit installation, remove the old flush valve after
shutting off the control stop.
sweat solder adapter kit if applicable. Thread sealing
compounds should be used on male NPT threads only. The
distance from center of the control stop to center of the flush
valve should fall within 4-1/4" to 5-1/4"(107mm to 133mm).
Step 2
Determine the length of vacuum breaker tube to join the
flush valve and fixture spud. Cut the vacuum breaker tube,
if required, to the proper length. Assemble the spud nut
assembly to the fixture spud. Hand tighten spud nut to
fixture.
For sweat solder
Right Water Supply Left Water Supply
Step 5
Connect the connectors of solenoid valve
and generator with those of controller.
Step 3
Prior to inserting the flush valve tailpiece into the control stop,
be certain that the O-ring is in the groove at the end of the
tailpiece, the locking nut and the snap ring are located as
shown. Connect the flush valve with the control stop and the
vacuum breaker tube. Care should be taken not to damage the
O-ring when inserting the tailpiece into the control stop.
If lubrication is needed, wetting the O-ring with water will be
sufficient. Align the flush valve and securely tighten fixture spud
nut, vacuum breaker tube nut and locking nut with a wrench.
Step 4
Connect the connector of the battery with that of the controller
and set it at the proper position as shown below.
Step 6
Fasten the sensor top cover on body cover with the
supplied screws (use supplied allen wrench).
Step 7
Before the supply water is turned on, be sure all water
leaks are eliminated by tightening all the pipe connections.
If for any reason it becomes necessary to remove the
control stop , be certain the water is shut off at the main
supply valve.
Pipe connection
Pipe connection
Pipe connection
Escutcheon
Joint tube
Cap
Step 8
The flush valves are preset for fixture volume as marked
on the valve carton. The valve does not require adjustment
for variation in water pressure within its operating range.
To set the flush valve for proper operation, open the
control stop completely by using the adjusting screw and
flush the flush valve several times. Gradually adjust the
control stop closed, using the adjusting screw, so that the
rate of water flow into the fixture is not excessive, yet is
sufficient to adequately evacuate the waste. The cap for
the control stop should be placed after final adjustments
have been made.
Tighten the cap firmly with a wrench.
1. Make sure the control stop is open.
2. Sit on the toilet seat. (for Toilet flush valve)
Stand within two feet from the front of the flush valve.
(for Urinal flush valve)
3. Stay there for 6 seconds or more and then leave the
toilet seat or the urinal. The valve will automatically flush.
4. Press the manual flushing button and make sure the
valve flushes properly and the sensor red light is on for
2 seconds.
5. Recheck all the pipe connections for water leaks. If the
flush valve is not operating properly following the test
run consult the Troubleshooting section of the Owner's
Manual.
After the flush valve unit has been installed correctly,
please explain to your customer how to use it and tell them
to observe the following instructions.
1. Do not put any object in front of the sensor window
whic h cou ld o b st r uc t the s e ns o r, cau s in g it to
malfunction.
2. For troubleshooting, consult the Owner's Manual.
If you lack the necessary skills required or have
difficulty following the directions for installation,
main ten anc e, repa irs , troub les hoo tin g or
adjustments, of the product, do not proceed without
help from a qualif i ed pers o n to as sis t you in
performing any of these functions.
1. Adjustment of the discharge quantity
(1) Remove the sensor top cover.
(2) Adjust the discharge quantity by rotating the screw
on the piston valve.
2. Adjustment of the flow rate
Adjust the flow rate by turning the screw of the control
stop.
Turn the screw to the right to decrease the flow rate and
turn it to the left to increase.
3. Adjustment of the detection range
The detection range of the infrared sensor does not
need to be adjusted because it has been factory-preset.
Printed in September, 2007
8
Friction Washer
Vacuum Breaker
Tube Nut
Spud Nut
Slip Gasket
Rubber Gasket
Escutcheon
To increase To decrease
Control stop
Note
Control stop
Snap ring
O-ring
Supplied
Allen wrench