Input Voltage Current Draw Max.
120VAC, 60Hz .02A
24VAC, 60Hz/24VDC .02A
12VDC .03A
28 30 32 34 36 38 40 42 44 46 48
2 26 28 30 32 34 36 38 40 42 44 46 4 26 28 30 32 34 36 38 40 42 44 46 6 26 28 30 32 34 36 38 40 42 44 46
8 25 11/16 27 11/16 29 3/4 31 3/4 33 3/4 35 13/16 37 13/16 39 13/16 41 13/16 43 13/16 45 7/8 10 25 1/4 27 1/4 29 5/16 31 3/8 33 7/16 35 1/2 37 1/2 39 1/2 41 9/16 43 5/8 45 5/8 12 24 9/16 26 11/16 28 3/4 30 7/8 33 35 37 39 1/8 41 3/16 43 1/4 45 1/4 14 23 11/16 26 28 30 1/4 32 3/8 34 7/16 36 1/2 38 5/8 40 11/16 42 3/4 44 13/16 16 22 11/16 25 27 1/4 29 7/16 31 9/16 33 3/4 35 7/8 38 40 42 3/16 44 5/16 18 21 3/8 23 13/16 26 1/8 28 7/16 30 11/16 32 7/8 35 37 1/4 39 3/8 41 1/2 43 5/8 20 19 13/16 22 3/8 24 7/8 27 1/4 29 5/8 31 7/8 34 1/8 36 3/8 38 9/16 40 3/4 43 22 20 11/16 23 3/8 25 7/8 28 3/8 30 3/4 33 35 3/8 37 5/8 39 7/8 42 24 24 1/4 26 7/8 29 3/8 31 13/16 34 1/4 36 1/2 38 13/16 41 26 27 13/16 30 3/8 32 7/8 35 5/16 37 11/16 40 28 31 3/8 33 7/8 36 3/8 38 3/4 30 29 5/8 32 5/16 34 7/8 37 3/8 32 33 1/4 35 13/16
A = Dimension of door jamb to wall (Inch)
Nearest Whole
Number
B = dimension of door width (Inch)
Magnetic Door Holder Placement Chart
7830
DOOR
DOOR JAMB
®
SURFACE ADAPTER
HOUSING
WALL LINE
SEM 7830
Sentronic Electro-Magnetic
®
Single Door Holder Surface Wall Mount
Step 1: Locate the Surface Mount Box
A. The magnet is shipped partially assembled for protection. Unscrew the cover from the magnet
bracket assembly. Unscrew the magnet bracket assembly from the surface mount box. Keep the screws for later reattachment.
B. See Fig. 1. Measure dimensions A and B. Find the intersection of those two dimensions in
Table 1. The intersection is dimension C, the centerline of the surface mount box location. ( 180° installations, take B dimension and subtract 5 5/8” to find the centerline of junction box. Note: Optional extensions maybe needed.)
C. If dimension A or B is not shown on the chart, extrapolate to find dimension C as follows.
If dimension A is 11” and dimension B is 36”, then:
dimension C = 33 7/16 - ((33 7/16 - 33)/2) = 33 7/32
If dimension A is 12” and dimension B is 35”, then:
dimension C = 33 - ((33 - 30 7/8)/2) = 31 15/16 If dimension A or B is beyond those listed in Table 1 or if they intersect in a blank area in Table 1, use optional extensions as needed to align contact plate and magnet.
D. See Fig. 2. The center of the surface mount box should be located about 5” from the top of the
door. Using the 10 x 1 ½” PHWS screws, attach the surface mount box vertically to the wall with the surface conduit knockout pointing in the desired direction. Anchors to be provided by others
to suit wall construction other than wood. The box must at least withstand a 50 pound pull. E. Install the ½” x 11/32” surface conduit as needed. F. Pull wire in accordance with applicable codes, standards, and authorities having jurisdiction.
Electrical specifications are shown below.
CAUTION
!
IMPROPER INSTALLATION MAY
PROPERTY DAMAGE. FOLLOW ALL
INSTRUCTIONS CAREFULLY. FOR
QUESTIONS, CALL LCN AT
800 - 526 - 2400
For
Table 1
2 ½”
64mm
2 13/16”
70mm
Fig. 2
WALL PORTION
4 5/8”
117mm
Surface Conduit Knock out
Fig. 3
Back view of magnet assembly
12/06 © 2006 SCHLAGE LOCK Company. All rights reserved D.P. # 29351
COM
24V
120V
12V
Earth Ground
Step 2: Install the Magnet
A. See Fig. 3. Connect the supply earth ground wire to the green wire on the magnet bracket assembly. Connect
the power supply common wire to the screw terminal marked COM. If the supply voltage is 24V, connect the power supply hot wire to the screw terminal marked 24V. If the supply voltage is 120V, connect the power supply hot wire to the screw terminal marked 120V. If the supply voltage is 12V, connect the power supply hot wire to the screw terminal marked 12V. Polarity is important on the 12V input. There are protective plastic tabs over the terminal screws. Break off the two tabs that protect COM and the desired voltage so that the screw heads are exposed.
B. See Fig. 2. With the magnet wired, position the magnet bracket assembly into the surface mount box and
attach it to the box using the (4) 10-24 shorter screws from step 1A. Tighten firmly. Attach the cover housing using the (2) 10-24 longer screws from step 1A.
Surface Mount Box
Magnet Bracket Assembly
Cover
Fig. 4
Locking Screw
Install Armature
For drill hole template, remove paper from the back to reveal sticky back of template.
Wood Screws
Thru bolts
Fig. 5
WOOD SCREW MOUNTING
FOR SOLID WOOD CORE DOORS
This view shows the contact plate locking screw accessible from the top. Rotate backup plate 180° for underside access.
Backup Plate
½”
13mm
Set Screw
Backup Plate
Armature
1 5/8”
41mm
Contact Plate locking screw
Contact
Plate
Fig. 6
THRU BOLT MOUNTING
RECOMMENDED FOR
HOLLOW METAL, HOLLOW CORE
OR COMPOSITE TYPE WOOD DOORS
Contact Plate locking screw
Door Plate
Door Plate
1 3/4”
44mm
Armature
1 5/8”
41mm
Contact
Plate
(2) #10 x 1 ½”
Armature
Pull Side
of Door
(2) 1/4-20 x 2”
Armature
Pull Side
of Door
Step 3: Install the Door Armature
A. See Fig. 4. Slightly loosen the contact plate locking screw using a 5/32 Allen wrench so the contact plate can rotate with some
resistance. Remove the protective paper from the drill template sticky-back label on the back of the door armature.
B. Place the armature against the floor magnet. This is best done with power applied to the magnet. If power is not available, hold
the armature in place by hand. The armature contact plate must fully cover the magnet. If the contact plate is not centered and flat on the magnet, reduced holding force will result.
C. With the armature against the magnet, open the door and press it against the armature and magnet. Pull the door away to transfer
the drill template to the door.
Template may need assistance with transferring to door, using a flat blade screwdriver on the
template tab that sticks out and push it onto the door while pulling the door away.
D. See Fig. 5 and 6. Determine if the armature will be mounted using the wood screw kit or the thru bolt kit. The thru bolt kit
is recommended for 1 hollow metal, hollow core, or composite-type wood doors. If using the wood screw kit, drill the center two holes on the template using a 1/8 bit by 1 deep. If using the thru bolt kit, drill the outer two holes on the template using a 5/16 bit all the way through the door. Remove the template after the holes are drilled.
¾”
¼”
E. Attach the armature to the door using the appropriate plate and screws. If using the wood screws and backup plate, tighten the
armature set screw against the backup plate as the last step using the 1/16 Allen wrench provided.