Faber Presence Installation Manual And User's Manual

Presence
Installation Guide
and
GB
IE
GB
IE
40011221-1138
1 < < < <
UK IRL
Installation
Guide
2 < < < <
UK IRL
1.1 1.2
1.3
1.4 1.5 1.6
3 < < < <
UK IRL
1.7 1.8
2.1
2.2
2.3 2.4 2.5
4 < < < <
UK IRL
2.6
3.1 3.2 3.3
4.1
4.2
A B
5 < < < <
UK IRL
1 Introduction
The fire can only be installed by a competent person in accordance with the Gas Safety Installation and Use regulations. We urgently advise you to read this installation manual properly. This appliance complies with the guidelines for European gas appliances (Gas Appliances Directive) and bears the CE mark.
2 Safety instructions.
The appliance should be placed, connected and annually checked in accordance with these installation instructions and valid national and local Gas Safety (Installation and Use) Regulations .
Check whether the data on the registration plate are in agreement with the local type of domestic gas and pressure.
It is not permitted to change the adjustments or the construction of the appliance!
Do not place any additional imitation logs or glowing coals on the burner or in the combustion chamber.
The appliance has been designed for ambience and heating purposes. This means that all surfaces of the appliance , including the glass, can become very hot (hotter than 100 °C). An exception to this are the bottom of the appliance and the controls.
Do not place any combustible materials within 0.5 m. of the radiation of the appliance and ventilation grills.
Due to natural air circulation of the appliance, moisture and volatile components from paint, building materials, floor coverings etc. that haven’t yet set, can be drawn through the convection system and can be deposited on cold surfaces as soot. That is why you should not use the appliance shortly after a renovation.
The first time the appliance is switched on, Let the fire run on maximum setting for several hours so that the lacquer coating will have an opportunity to set and possible vapours released can be safely removed by ventilation. We advise
you to be outside the room as much as possible during this process!
Please note that:
1. all transport packaging should be removed.
2. children or pets should not be present in the room.
No extra ventilation is required, due to the fact that the input of the appliance is not exceeding 7,0 kW.
3 Installation requirements
3.1 The fire
The fire is tested for installation without a hearth. Make 2 non combustible supports on the left and the right side of the burner unit. (see fig.
1.1)
3.2 Chimney breast
The appliance must be built into a non combustible existing or a new to be constructed false chimney breast. For the dimensions of the builders opening see fig.1.7.
framed frameless
A = 670mm 670mm B = Min. 100mm Min. 100mm C = 337mm 337mm+wall thickness D = max. 60mm wall thickness E = 460mm 430mm
Combustible shelf F = min. 350mm G = max.150mm
If the shelf depth is greater than 150mm, add 50 mm to shelf clearance height for every 25 mm increase in shelf depth
For the dimensions of the fire see chapter 11 till 14.
The false chimney breast must be ventilated on top and bottom with a minimum opening of 200cm2. The false chimney breast and its construction may not rest on the appliance. Therefore always use a lintel for a brick build chimney. For the minimum dimensions see fig 1.8.
For the finish, use special stucco (min. 100°C resistant) or glass fibre wallpaper to prevent discoloration or cracks etc. Recommended drying time: for plaster is a minimum of 24 hours per mm of coat applied.
6 < < < <
UK IRL
3.3 Requirements flue system and outlets Top outlet
The flue connector collar is for connection to a 125 mm (5 inch) internal diameter pipe or liner according BS EN 1856. The minimum effective height of the flue system must be 3 meter.
Rear outlet
In case of an installation in a masonry chimney convert the outlet to the rear outlet. Therefore unscrew the top outlet and fit the rear outlet on the fire. Take care to fill up all the holes with the screws.(see fig.1.3)
To collect the debris, there must be a minimum gap of 23 mm behind the appliance Use the supplied glass fibred-seal to seal the fire box to the builders opening.(see fig.1.2)
Chimney
The top of the chimney must always be higher then the top of the roof.
4 Preparation and Installation
instructions
4.1 Gas connection
The gas connection must comply with locally valid standards. We advise Pipe work from the meter to the appliance must be of adequate size. An isolator is factory fitted, no further isolation device is required. Place the gas connection in such a way that it is accessible for service and the burner unit can be disconnected at all times.
4.2 Preparation of the appliance
Remove the packaging of the appliance.
Clear a safe space to store the glass.
Remove the glass (see chapter 5) and
take the separately wrapped parts out of the appliance.
Prepare the gas connection.
Prepare the flue connection.
If necessary convert to rear outlet
(see chapter 3.3).
If necessary convert to framed version. Therefore: A. Remove the build in frame (see
fig.3.1)
B. Fit the frame support. (see
fig.3.2)
C. The frame now can be hung on
the support. (see fig.3.3)
4.3 Batteries.
The battery pack is fixed on a chain inside the burner unit on the right side. (see fig.2.2) Pull the chain to remove it.
To avoid overheating take care that the battery pack always is positioned correctly in the burner unit.
4.4 Placing the appliance
Take the installation requirements into account (see chapter 3).
Masonry chimney
Cut out the opening so that the appliance can be fitted easily.
prepare the 2 non combustible supports on the left and the right side in the builders opening (see fig. 1.1)
For a Top outlet connection
Pull a 5 inch liner into the chimney. Fit the fire in the builders opening and connect the liner on the top outlet.
For a Rear outlet installation
Fit the fire in the builders opening, use the supplied glass fibred-seal to seal the fire box to the builders opening.(see fig.1.3)
Do a gas leakage test on all joints and check burner and inlet pressure. See chapter 7 before closing the chimney
Reconstruct the wall of the chimney.
5 Removing the glass
Place the suction discs onto the glass
Remove the cover strips on the left
and right side by pushing the top (see fig.1.4)
Remove the cover strips on the left and right hand side (see fig.1.5)
Remove the sealing cord from the groove (see fig.1.6)
Lift the glass up and move slowly forward, now you can take the glass out.
To replace the glass repeat the process in reverse order. Remove all Fingerprints from the glass, these will be burned into it once the hearth is used.
7 < < < <
UK IRL
6 Placing the log set, decoration
material
It is not allowed to add different or more materials to the combustion chamber. Always keep the pilot burner free from decorative material! Do not toss all the decorative material onto the burner all at once, as the very fine dust may block the holes in the burner.
6.1 Imitation logs
Spread the vermiculate preferably by hand over the tube burner in the burner-slot. The surface of the vermiculate may be very slightly elevated from the burner plate but it should be levelled throughout the entire length.
Place the imitation logs according to instructions. (see fig.4.1) or the instruction card)
Start the pilot and main burner, according to the instructions in the user’s manual. Assess whether the flame distribution is correct.
Place the glass and check the flame picture into the appliance
6.2 Pebbles
Place the pebbles over the burner in the burner holder. Do not cover the grid in the front. Spread the pebbles evenly to a double layer. The surface of the pebbles may be very slightly higher then the burner tube (see fig.4.2)
Place the glass and check the flame picture.
7 Checking the installation
7.1 Checking the ignition of the pilot burner, main burner.
Start the pilot and main burner following the instructions in the user’s manual.
Check whether the pilot light is properly positioned above the main burner and is not covered by vermiculite and imitation log or pebbles.
Check the ignition of the main burner at full mark or low mark. (the ignition should take place quickly and easily).
7.2 Checking for gas leakage.
Check all connections and joints for possible gas leaks by means of a gas leak detector or spray
7.3 Checking the burner pressure and the inlet pressure
Check whether the burner pressure and the inlet pressure measured agree with the data indicated on the registration plate
7.4 Measuring the inlet pressure:
Turn off the gas control.
Get access to the burner unit by
removing the glass, log set and bottom plates as described in chapter
8.4.
Open the pressure gauge nipple B (see fig.2.6) a few turns and connect a pressure gauge hose to the gas control valve.
Fit the burner plate with burner (see fig. 2.4).
Carry out the measurement when the appliance is on at full gas mark and when it is on the pilot light.
If the inlet pressure is too high you are not permitted to connect the appliance.
7.5 Measuring the burner pressure:
Only perform this measurement if the inlet pressure is correct.
Follow the steps as described in chapter 7.4 to get access to the burner unit.
Open the pressure gauge nipple A (see fig.2.6) a few turns and connect a pressure gauge hose to the gas control valve.
The pressure must agree with the value indicated in the technical data in chapter 10. In case of deviations, get in touch with the manufacturer.
*Close the pressure gauge nipples and check these for gas leaks.
7.6 Spillage test
Carry out the lighting procedure and turn the fire to high.
Allow to warm up for 15 minutes and then using a smoke match with holder set 100% inside the middle part on top of the appliance (see fig.2.1) between the trim and the glass frame. The installation is satisfactory if most of the smoke is drawn into the tube.
Repeat the test with doors and windows to the premises open and closed, and with any extractor fans in
Loading...
+ 16 hidden pages