Faber Duet M Smart, Duet L Smart Installation Manual

Installation manual
Duet M Smart
Duet L Smart
ENG
Installation manual Duet M,L Smart
1 < < < <
Installation manual Duet M,L Smart
2 < < < <
Installation manual Duet M,L Smart
1.0
1.1
1.2
1.3a
1.3b
3 < < < <
Installation manual Duet M,L Smart
1.4
1.5
1.6
1.7
1.8
Y
X
4 < < < <
Installation manual Duet M,L Smart
2.0a
2.0b
2.0c
2.1
3.0
3.1
3.2
4.0
B
A
Q
R
S
T E
B
5 < < < <
Installation manual Duet M,L Smart
4.1
4.2
4.3
4.4
6 < < < <
Installation manual Duet M,L Smart
7 < < < <
Installation manual Duet M,L Smart
1 Dear user
Congratulations on your purchase of a Faber fire! A quality product from which you will experience warmth and atmosphere for many years. We recommend that you read this manual carefully before using the fireplace. If any problem arises despite our strict quality control, you can always contact your dealer or Glen Dimplex Benelux B.V.
For any warranty claims, it is essential you first register your fireplace. During this registration, you’ll find all information regarding our warranty.
Please note!
The details of your fireplace can be found in the user manual.
You can register your fire at: www.faberfires.com
Glen Dimplex Benelux B.V. Address: Saturnus 8 NL-8448 CC
Heerenveen Tel: +31 (0)513 656 500 Email: contact@faberfires.com Info: www.faberfires.com
1.1 Introduction
Installation and maintenance of the appliance must be carried out by a professional with proven knowledge and competence. A professional takes into account all technical aspects such as heat radiation and gas connection as well as flue gas exhaust requirements.
Where the installation instructions are not clear, national/local regulations must be followed.
1.2 Check
Check the fireplace for transport damage and immediately report any damage to your supplier.
1.3 CE Declaration
We hereby declare that Glen Dimplex Benelux B.V. released Faber gas-atmosphere heating appliance by its design and construction method complies with the Regulation (EU): 2016/426 and (EU) 2015/1188.
Product: gas room heater Model: Duet M Smart Duet L Smart
This declaration will become null and void as soon as the unit is in any way modified without written authorization of Glen Dimplex Benelux B.V.
2 Safety instructions
Please note!
It is advisable to always install a screen for the fireplace if children, elderly or disabled people are present in the same room as the fireplace. If
regularly vulnerable persons can be present in the room without supervision, sufficient protection must always be placed around the fireplace.
This appliance must be installed according
with the rules in force and used only in a sufficiently space.
The appliance must be checked annually
in accordance with this installation manual and the applicable national and local regulations.
Ensure that the data on the type label
matches the local gas type and pressure.
The appliance is designed for atmosphere
and heating purposes. This means that all visible surfaces, including the glass, can become hotter than 100°C. An exception by free standing models is the underside of the fireplace and the control buttons.
Do not use the remote control and / or
app outside the room where the fire is located. So that you are always aware of the situation around the fireplace when it is being operated.
The settings and the construction of the
fireplace must not be changed!
Do not place extra imitation wood or
other material on the burner or in the combustion chamber.
Do not place any combustible materials
within 0,5m of the radiation area of the fire.
Through the natural air circulation of the
fireplace moisture and uncured volatile components from paint, building materials and carpeted floors, etc. are attracted. These parts can settle as soot on cold surfaces. Therefore do not light the fireplace shortly after installation.
2.1 Using the fire for the first time
Provide extra ventilation and open all the windows of the room during the initial start-up of the fire. Let the fire burn at the highest setting for a few hours so that the paint gets the chance to harden and any released vapours are safely removed. Keep vulnerable people and pets out of this room during this process.
8 < < < <
Installation manual Duet M,L Smart
3 Installation requirements
3.1 Appliance
This appliance may not be installed in a
chlorine-containing environment. (Pools
etc.).
This appliance must be built into an
existing or new false chimney.
For appliances with flexible gas pipes, the
control unit (fig. 1.0) is placed on the right
side of the crate for transport reasons.
Detach and mount it together with the
remote access door in as low as possible
position in the false chimney.
(To prevent damage to cables and pipes
during transport, they are bound together
by tie wraps. Remove these to ensure
proper operation of the appliance.)
If desired, a 2 meter pipe set is available
(article number 20900715).
3.2 False chimney
The false chimney should be of non-
combustible material.
The space above the fire should always be
ventilated using grids with minimal free
passage of 200cm² per grid.
The false chimney construction should not
rest on the build-in frame of the fireplace.
3.3 Discharge and outlet requirements
First, carry out a flue calculation (see chapter 11) and place the right flue restrictor before installing the outlet! (Generally a 30mm flue restrictor is installed).
For supply and discharge always use the
prescribed and to be supplied Faber flue
materials. Please contact Glen Dimplex
Benelux B.V.. Only with use of these
materials Faber can guarantee proper
performance.
The distance to combustible materials
must be min. 50mm, calculated from
outside of the flue material (EN 1856-1
T600 N1 D VM – L20040 O(50)).
Outlets (fig. 1.2)
The balanced flue pipe for combined air supply and discharge can use a wall terminal or a roof terminal. Verify that the desired outlet meets the local regulations regarding pollution and ventilation openings.
Please note!
For proper functioning, the outlet must at least be 0,5m away from:
Corners of the building;
Roof overhangs and balconies; Roof edges (with the exception of the
ridge edge, see chapter 15).
C11, outlet via facade
Through a wall or façade, use a Faber wall outlet. Depending on the flue calculation this can be 100/150mm or 130/200mm.
C31, outlet via roof
For a (flat) roof, use a Faber roof outlet with a diameter of 100/150mm.
C91, existing chimney
For an existing chimney, use a Faber chimney outlet with a diameter of 100/150mm. In this case the existing chimney acts as air inlet an inserted flexible stainless steel pipe discharges the flue gas. The top (Faber chimney cover plate) and the bottom (Faber chimney connection set) should be airtight.
Depending on the calculated flue diameter, you must use a flexible stainless steel pipe of Ø100mm (article number AJ005503) or Ø130mm (article number AJ005603) as specified by Faber. For this, contact Glen Dimplex Benelux B.V.
Please note!
The minimum chimney diameter for a
130mm flexible stainless steel pipe must be 200x200mm and for a 100mm flexible stainless steel pipe and 150x150mm.
Don’t connect more than one fire at the
existing chimney.
The chimney must be in good condition:
o No leakage; o Well cleaned.
For more information about the connections to existing chimney ducts, please request the installation instructions “Chimney Connection Set”.
4 Preparation and installation
instructions
4.1 Gas connection
The gas connection must comply with the applicable local standards.
Please note!
Provide a flexible gas connection with at
least 0,5m extra length, so that the control unit can be removed for installation and service!
Calculate the gas pipe so that no
pressure drop occurs.
9 < < < <
Installation manual Duet M,L Smart
We advise using a gas connection directly from the gas meter to the appliance, with a shut-off valve in the proximity of the appliance, which must always be freely accessible. Position the gas connection so that it is easily accessible for service and the burner unit can be disassembled at any time.
4.2 Electrical connection
Install a 230VAC/50Hz wall socket near the fireplace for connecting the control unit.
See fig. 1.3a for the wiring diagram:
A = Adapter (6V) B = Gas valve C = Receiver D = Ignition pin
See fig. 1.3b for the wiring diagram with I.T.C (optional):
A = Adapter (6V) B = Gas valve C = Receiver D = Ignition pin E = I.T.C. (Intelligent Technical Controller)
4.3 Smart Home installation
Please note!
This is only possible if the fire is equipped with I.T.C!
The controller can be connected to an external source, such as a Domotica system, by using a Faber Interface Unit (article number A9323000).
4.4 Preparing the fireplace
Remove the fireplace from its packaging.
Ensure that the gas supply pipes under
the appliance are not damaged.
Remove the glass and any mouldings,
store them at a safe place and remove the
packaged parts from the fireplace.
Prepare the gas connection on the gas
valve.
4.5 Positioning the fireplace
Take into account the installation requirements (see chapter 3). Place the fireplace at the right place and level it (see fig. 1.5-C of 1.6-C).
Rough height adjustment:
With the adjustable (optional) legs.
Accurate height adjustment:
With the adjustable feet.
Hanging on the wall
The fireplace can also be mounted on the wall by using the optional wall bracket (see fig. 1.4 and attachment 17.9 and 17.10).
4.6 Installing the flue pipes
Install the flue pipes according to the installation manual supplied with the appliance (40011968)!
The distance to combustible materials
must be min. 50mm, calculated from the outside of the flue pipe.
Never start immediately with length-
adjustable concentric flue pipe on the appliance.
Horizontal sections should be installed to
allow a slope towards the appliance (3 degrees).
Built the system from the appliance. If this
is not possible you can make use of an extendable adapter section.
For fitting of the flue system, the 0,5m
length-adjustable pipe must be used. Make sure that the inner pipe is always 15mm longer than the outer pipe. Wall­and roof terminal can also be cut. These components must be secured with a self­tapping screw.
4.7 Constructing the false chimney
Before positioning the false chimney, we advise to perform a functional test with the fireplace as defined in chapter 7 “Checking the installation”.
False chimney
Construct the false chimney of non-
combustible material in combination with metal profiles or of masonry/concrete blocks.
Always use a lintel or reinforcing bars
while bricking the false chimney. They should not be placed directly on the fireplace.
Make sure that the fireplace never
functions as a load-bearing construction, because of the expansion of the fireplace through warmth.
Ventilation
Correct ventilation prevents damaging overheating of the gas control block and its electronics and also limits the temperature of the convection air. Use the (optional) supplied Faber ventilation grids (article number A9296400) or a similar alternative with a minimum free passage of 200cm² per grid, in the space above the fire, when building the false chimney. Within the false chimney, an horizontal screen plate, made of non-combustible material,
10 < < < <
Installation manual Duet M,L Smart
must be installed just above the ventilation openings. (see fig. 1.5-A and 1.6-A).
Installation and finishing
Please note!
Take into account a minimum distance of
2mm due to expansion of the fireplace.
Take into account the thickness of any
finishing layer!
Check during installation whether the
glass can still be installed.
Method I – cover strip (fig. 2.0a)
See fig. 2.1, build the false chimney
against:
o Distance profiles A; o Build-in frame D; o Build-in supports C.
The top of distance profiles A must have
the same height as point E.
Before placing the cover strips, remove
the build-in supports C.
Method II – plateau + cover strip (fig. 2.0b)
Please note
After installation, the top of the plateau must have the same height as point E, see fig. 2.1.
See fig. 2.1, remove the distance profiles
A. To ensure the air tightness of the
appliance, replace the screws!
Build the false chimney against:
o Build-in frame D; o Build-in supports C.
Build the plateau against distance holders
B;
Before placing the cover strips, remove
the build-in supports C.
Method III – plateau + insert strip (fig. 2.0c)
Please note
After installation, the top of the plateau should be 4mm higher as point E, see fig. 2.1.
Perform the steps of Method II.
Placing the cover strips / insert strip
Place the horizontal cover strip Q (fig. 3.0)
or the horizontal insert strip R (fig. 3.1).
Place the vertical cover strips S (fig. 3.2).
these are held in place by adjustable
magnets.
The insert strip R can be removed by the supplied magnet T (see fig. 3.1).
5 Removing glass
5.1 Front glass
Remove the horizontal cover strip (fig.
3.0) Q or the horizontal insert strip R (fig.
3.1). The insert strip R can be removed by the supplied magnet T (see fig. 3.1).
Place the suction cups on the glass (fig.
4.0).
Remove the glass sealing cord (fig. 4.1). Carefully lift the glass and pull the
underside towards you (fig. 4.2).
For replacing the glass repeat the steps in reverse order.
Please note!
Avoid fingerprints on the glass, these are no longer removable once the fire is used.
5.2 Side glass
For cleaning only it’s not necessary to remove the
side glass.
First remove the front glass. (see chapter
5.1).
Remove the log set, bottom plate and
burner (fig. 4.3).
Place the suction cups on the glass (fig
4.0).
Remove the glass sealing cord. In this position, slide the glass forward.
Lift the glass slightly and push the bottom into the appliance (fig. 4.4).
For replacing the glass repeat the steps in reverse order.
Please note!
Avoid fingerprints on the glass, these are no longer removable once the fire is used.
11 < < < <
Installation manual Duet M,L Smart
6 Placing decoration material
Please note!
It is not permitted to use other or to add
more material in the combustion
chamber.
Do not throw the decoration material on
the burner at once. It is possible that the
burner gets clogged.
See the supplied decoration instruction card or chapter 18.1 or 18.2:
Place part of the ash material at the
burner and the cover plate.
Place the log set. Divide the rest of the ash material at the
burner and the cover plate.
Please note!
Keep the pilot flame free from ash material.
Start the fireplace as described in the user
manual.
Assess whether the flame distribution is
good. Move or remove any ash material
to create a nice glow bed.
Install the front glass and check the fire
image.
7 Checking the installation
Checking for gas leaks
Check with a gas leak finder all connections and pipes for gas leakage.
Check inlet- and burner pressure Check if the inlet pressure correspond to the data on the rating plate.
Measuring the inlet pressure:
Close the shutoff valve. Turn the
measuring nipple “A” (fig. 1.1) a few turns
to open and connect a measuring hose to
the gas valve.
Take this measurement when the
fireplace runs at high and low settings.
Do not connect the unit if the inlet
pressure deviates (+20% and -20%).
Measuring the burner pressure: Check the burner pressure only with proper inlet pressure.
Turn measuring nipple “B” (see fig. 1.1)
some turns open and connect a measuring
hose to the gas valve.
The pressure must correspond to the
value indicated in the technical specifications of this manual. In case of deviation contact the manufacturer.
Please note!
Close both pressure measuring nipples and check for gas leakage.
Check ignition and burner Ignite the fireplace by using the remote control as described in the user manual and test all burner possibilities.
7.1 Checking the flame image
Let the fireplace burn for at least 20 minutes at highest setting and check the flame for:
flame distribution; colour of the flames.
If one or both points are not acceptable then check:
The position of the logs and/or the
amount of ash material.
The pipe connections for leaks.
(in case of blue flames);
That the correct flue restrictor is fitted
(see fig. 1.8);
The outlet:
o Wall terminal has the correct
position and side up;
o Roof terminal has the correct
position.
If the maximum lengths of the flue gas
outlet is not exceeded.
If possible, carry out a flue gas analysis
(see section 7.2).
7.2 Flue gas analysis
It is possible to check the combustion gases and supply air with a CO/CO2 flue gas analyser. There are two measuring pipes between the build­in frame and the front glass (fig. 1.7).
X = measuring pipe air supply Y = measuring pipe flue gas
The ratio CO2 and CO must not be greater than 1:100.
Example: CO2 is 4% and CO is 400ppm, measured at the highest point. If the ratio is greater than 1:100 or flue gases are measured in the air supply, check the points in section 7.1.
12 < < < <
Installation manual Duet M,L Smart
8 Instructions for client
Recommend that the fire should be
checked annually by a qualified specialist
to ensure the safe use and to guarantee a
long service life.
Provide instructions on the operation of:
o the appliance; o the remote control; o if present, the App and its
settings.
Give advice and instructions on care and
cleaning of the glass:
Emphasize the danger of fingerprint burns
at the glass.
Handover to customer:
o installation manual; o user manual; o decoration instruction card; o suction cups; o sample Faber glass polish.
9 Annual maintenance
Check
Check and clean if necessary:
the combustion chamber; the burner the pilot flame; the wooden logs for breakage; the glass(es); the outlet.
Replace ash material if necessary.
Cleaning
Remove the front glass (see chapter 5). You can clean the glass with Faber glass polish. This is a specially formulated cleaning agent that can be ordered at authorized Faber dealers. Never use aggressive cleaning agents or abrasive products.
Please note!
Avoid fingerprints on the glass; these are no longer removable once the fire is used.
Now carry out check-up as described in chapter 7.
For an extensive maintenance instruction "maintenance protocol gas fires" see:
10 Conversion to other gas type
This can only be done by replacing the burner. To do so, please contact your dealer. Always provide the type and serial number of the appliance when ordering.
11 Flue calculation
A simple way to calculate whether the exhaust configuration is possible in combination with your fireplace, use the “Faber Flue App V2”:
This is available free of charge and can be downloaded via:
Internet:
Android and PC (Windows Store, (Windows 10)).
App Store:
iPhone, iPad and Mac.
Google Play:
Android smart phones and Android tablets.
Alternatively, you can use the calculation sheet (see chapter 13). The options for flue lengths and any flue restrictors are defined in a restrictor table, see 11.1 and 11.2. Start Length (STL), Total Vertical Height (TVH) and Total Horizontal Length (THL) are used in the table.
Start length (STL):
The first part that is placed on the fireplace and represents a certain value (fig. 12.1, 12.2 and 12.3 A, N and F). You can find this value in the upper row of the restrictor table.
Total Vertical Height (TVH):
TVH is the height difference measured from the top of the appliance to the outlet. This can be measured or determined in the building plan. For clarification, see also the TVH indication in the drawings (fig. 12.1, 12.2 and 12.3).
13 < < < <
Loading...
+ 30 hidden pages