Important Safety Requirements & Instructions .............................................................................................................................. 1
Responsibilities of Installers and Technicians ................................................................................................................................. 2
Important Safety Requirements by UL Standards ......................................................................................................................... 3
Classes of Vehicular Gate Operators................................................................................................................................................... 4
General Specifications ............................................................................................................................................................................. 5
Hookup Electrical Power - Gate Travel Adjustment...................................................................................................................... 7
Standard Installation for Gates from 8’ to 14’ in Length ............................................................................................................. 7
Standard Installation for Gates from 14’ to 18’ in Length ........................................................................................................... 8
Space Required for Standard Gate in the Open Position ............................................................................................................ 8
Compact Installation and Minimum Space Required .................................................................................................................. 9
Exploded View Parts Diagram ............................................................................................................................................................18
Bill of Materials ...................................................................................................................................................................................19-20
Important Information for The Homeowner ................................................................................................................................. 23
Do not install this gate operator if you do not have experience or appropriate
WARNING
training with gate operators.
IMPORTANT SAFETY REQUIREMENTS & INSTRUCTIONS
WARNING To reduce the risk of injury or death:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. Never let children operate or play with gate
controls. Keep the remote control away from
children.
3. Always keep people and objects away from the
gate. NO ONE SHOULD CROSS THE PATH OF THE
MOVING GATE.
4. Test the Vehicular Gate Operator monthly.
The gate MUST reverse on contact with a rigid
object or stop when an object activates the
non-contact sensors. After adjusting the limit of
travel, retest the Vehicular Gate Operator. Failure
to adjust and retest the Vehicular Gate Operator
properly can increase the risk of injury or death.
5. Use the Emergency Release only when power
switch or circuit breaker has been turned off. Using the Emergency Release during a power failure can be a hazard if power is abruptly restored.
6. KEEP GATES PROPERLY MAINTAINED. Read the
Owner’s Manual. Have a qualified service person
make repairs to gate hardware.
7. The entrance is for vehicles only. Pedestrians
must use separate entrance.
8. SAVE THESE INSTRUCTIONS.
www.ramsetinc.com
1
RAMSET
RESPONSIBILITIES OF INSTALLERS AND TECHNICIANS
INSTALLATION
• READ AND UNDERSTAND THE INSTRUCTION MANUAL BEFORE ATTEMPTING
ANY INSTALLATION.
• DO NOT EXCEED THE EQUIPMENT SPECIFICATIONS.
RAM 300
• INSURE A SAFE AND PROPER INSTALLATION.
• INSTALL THIS EQUIPMENT IN ACCORDANCE WITH THE UL 325 SPECIFICATIONS.
• MAKE SURE TO ELIMINATE ANY PINCH POINTS EXISTING ON THE INSTALLATION.
ie. ROLLERS, ARMS…etc.
SAFETY DEVICES
• REMOVE OR PROTECT ALL PINCH POINTS FROM THE GATE OPERATOR’S ARMS.
• MAKE SURE EVERY INSTALLATION HAS A MINIMUM OF ONE SAFETY DEVICE
SUCH AS A PHOTOELECTRIC EYE OR LOOP DETECTOR.
• CHECK THE E.R.D. SENSITIVITY.
• MAKE SURE THAT ALL AREAS AROUND THE GATE ARE SAFE AND SECURE.
SUCH AS THE FRONT, REAR, AND TRAVEL AREA.
COMMUNICATE WITH THE ENDUSER
• INSTRUCT THE END USER ON HOW TO SAFELY OPERATE ALL FUNCTIONS
OF THE OPERATOR.
• INSTRUCT THE ENDUSER ON HOW TO SAFELY USE THE EMERGENCY
RELEASE.
• CLEARLY LABEL AND IDENTIFY THE CIRCUIT BREAKER FOR THE OPERATOR.
• SHOW THE ENDUSER THE LOCATION OF THE CIRCUIT BREAKER FOR THE
OPERATOR.
• THOROUGHLY EXPLAIN ANY AND ALL WARRANTIES ASSOCIATED WITH THE
OPERATOR AND INSTALLATION.
• KEEP A COPY OF EACH MANUAL HANDY FOR FUTURE REFERENCES.
• PROVIDE THE ENDUSER WITH THE “HOME OWNERS MANUAL PACKET”
INCLUDED WITH EVERY OPERATOR.
2
www.ramsetinc.com
IMPORTANT SAFETY REQUIREMENTS BY UL STANDARDS
RAMSET
Prior to installation, the following must be
observed: (per UL 325.56.8.4).
a) Install the gate operator only when:
1. The operator is appropriate for the construction of the
gate and the usage Class of the gate,
2. All openings of a horizontal slide gate are guarded or
screened from the bottom of the gate to a minimum
of 4 feet (1.22 m) above the ground to prevent a 2 1/4
inch (57.2 mm) diameter sphere from passing through
the openings anywhere in the gate, and in that portion
of the adjacent fence that the gate covers in the open
position.
3. All exposed pinch points are eliminated or guarded,
and
4. Guarding is supplied for exposed rollers.
b) The operator is intended for installation only on gates
used for vehicles. Pedestrians must be supplied with a separate access opening. The pedestrian access opening shall be
designed to promote pedestrian usage. Locate the gate such
that persons will not come in contact with the vehicular gate
during the entire path of travel of the vehicular gate.
c) The gate must be installed in a location so that enough
clearance is supplied between the gate and adjacent structures when opening and closing to reduce the risk of entrapment. Swinging gates shall not open into public access areas.
g) The stop and/or reset button must be located in the lineof-sight of the gate. Activation of the reset control shall not
cause the operator to start.
h) A minimum of two (2) WARNING SIGNS shall be installed,
one on each side of the gate where easily visible.
i) For gate operators utilizing a non-contact sensor in accordance with UL 31.1.1:
1. See instructions on the placement of non-contact sensors for each Type of application.
2. Care shall be exercised to reduce the risk of nuisance
tripping, such as when a vehicle, trips the sensor while
the gate is still moving, and
3. One or more non-contact sensors shall be located where
the risk of entrapment or obstruction exists, such as the
perimeter reachable by a moving gate or barrier.
j) For a gate operator utilizing a contact sensor in accordance with 31.1.1:
1. One or more contact sensors shall be located where
the risk of entrapment or obstruction exists, such as at
the leading edge, trailing edge, and postmounted both
inside and outside of a vehicular horizontal slide gate.
2. One or more contact sensors shall be located at the
bottom edge of a vehicular vertical lift gate.
RAM 300
d) The gate must be properly installed and work freely in
both directions prior to the installation of the gate operator.
Do not over-tighten the operator clutch or pressure relief
valve to compensate for a damaged gate.
e) For gate operators utilizing Type D protection:
1. The gate operator controls must be placed so that
the user has full view of the gate area when the gate
is moving.
2. The placard as required by 58.1.6 shall be placed
adjacent to the controls,
3. An automatic closing device (such as a timer, loop
sensor, or similar device) shall not be employed, and
4. No other activation device shall be connected.
f) Controls intended for user activation must be located at
least six feet (6’) away from any moving part of the gate
and where the user is prevented from reaching over, under,
around or through the gate to operate the controls. Outdoor
or easily accessible controls shall have a security feature to
prevent unauthorized use.
3. One or more contact sensors shall be located at the
pinch point of a vehicular vertical pivot gate.
4. A hardwired contact sensor shall be located and its
wiring arranged so that the communication between
the sensor and the gate operator is not subjected to
mechanical damage.
5. A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate operator for entrapment protection functions shall be located where
the transmission of the signals are not obstructed or
impeded by building structures, natural landscaping or similar obstruction. A wireless contact sensor
shall function under the intended end-use conditions.
6. One or more contact sensors shall be located on the
inside and outside leading edge of a swing gate. Additionally, if the bottom edge of a swing gate is
greater than 6 inches (152 mm) above the ground
at any point in its arc of travel, one or more contact sensors shall be located on the bottom edge.
7. One or more contact sensors shall be located at the
bottom edge of a vertical barrier (arm).
www.ramsetinc.com
3
RAMSET
RAM 300
CLASSES OF VEHICULAR GATE OPERATORS
Vehicular horizontal slide-gate operator (or system) - A vehicular gate operator (or system) that controls
a gate which slides in a horizontal direction that is intended for use for vehicular entrance or exit to a drive,
parking lot, or the like.
Vehicular swing-gate operator (or system) - A vehicular gate operator (or system) that controls a gate
which swings in an arc in a horizontal plane that is intended for use for vehicular entrance or exit to a
drive, parking lot or the like.
Residential vehicular gate operator-Class I - A vehicular gate operator (or system) intended for use at a
home of one-to four single family dwellings, or a garage or parking area associated there with.
Commercial/general access vehicular gate operator-Class II - A vehicular gate operator (or system)
intended for use in a commercial location or building such as a multi-family housing unit (five or more
single family units), hotels, garages, retail stores, or other buildings serving the general public.
Industrial/limited access vehicular gate operator-Class III - A vehicular gate operator (or system) intended for use in an industrial location or building such as a factory or loading dock area or other locations not
intended to service the general public.
Restricted access vehicular gate operator-Class IV - A vehicular gate operator (or system) intended for
use in a guarded industrial location or building such as an airport security area or other restricted access
locations not servicing the general public, in which unauthorized access is prevented via supervision by
security personnel.
RECOMMENDED ELECTRICAL CONNECTION
A 3 wire, 120 VAC electrical circuit with a 15 amps independent circuit breaker for single operator and a 20
amps for Master/Slave. Ideally, the electrical conduits should exit the concrete under the operator. Low
voltage control wires must be run in a separate conduit to the operator.
NOTE:Always consult and follow all local building and electrical codes prior to installation.
RECOMMENDED WIRE GAUGE
MAXIMIM CONDUIT DISTANCE IN FEET
USING COPPER WIRE BY WIRE SIZE
14ga.
12ga.
10ga.8ga.
INPUT POWER
MOTOR HP
AMPERES
RUNSTART
120V Single Phase1/24.75.0
4
Up to 100’100-350’350-650’800’
www.ramsetinc.com
GENERAL SPECIFICATIONS
Maximum Gate Length22 feet
Maximum Gate Weight800 lbs
CyclesContinuous
CapacitorsAerovox 65µƒ, 240 V, 50/60 HZ, protected S 1000AFC
ApplicationCommercial
RAMSET
Finish & ConstructionGold/Zinc plated 3/16” H.R. Metal
Continuous Duty Motor1/2 Hp 120 Volts. AC 4.5 amp. 1625 rpm.
Power Failure ReleaseExclusive Foot Pedal Release
Overall DimensionsH 22” - L 14½” - W 15”
Gate Travel SpeedApprox. 1’ per sec
Shipping Weight110 lbs
*Exclusive foot pedal release disengages gate from motor so it can be opened manually.
Do not exceed the specifications. The warranty on your unit will be void if
the installation exceeds the recommended specifications.
WARNING
RAM 300
www.ramsetinc.com
5
RAMSET
INSTALLATION SPECIFICATIONS
CONCRETE PAD CONSTRUCTION
Dimensions given for the pad are based
on soil bearing shear of 2000 P.S.F. These
figures may have to be adjusted
depending on local soil conditions.
1. Construct form for mounting pad
RAM 300
2. Locate mounting pad according to
3. Level top edge of form.
4. Set reinforcing bars and wire mesh.
5. Allow pad to cure for 48 hours,
6. Note: conduits 6” above concrete pad.
according to dimensions shown
in Figure 1 and 2.
dimensions given in illustration.
and remove forms.
Steel Square Tubing
CONDUIT FOR ELECTRIC POWER
CONDUIT FOR COMMUNICATION
CONDUIT FOR MASTER/SLAVE
26”
Property
13”
6 3/4”
Inside
2 1/2”
14”
20”
4x4
Outside
Property
STANDARD
INSTALLATIONS
Gates From: 8’-16’ (18”)
Gates From 16’-22’ (24”)
Gate Opened
Figure 1
Figure 2
Ground Level
DEDICATED CONDUIT
WITH 15 amp BREAKER
Allow 2” above
ground level
minimum for
leveling.
18”
1/2” REDHEAD
ANCHOR BOLTS 4X
Ground Level
18”
INDEPENDENT CONDUIT
FOR LOW VOLTAGE
WIRES
25”
24”
ELECTRICAL
CONDUIT FOR
MASTER/SLAVE
6
www.ramsetinc.com
HOOK UP ELECTRICAL POWERGATE TRAVEL ADJUSTMENT
CAUTION
Clutch tension bolts
need to be tightened to
a minimum of 40 lbs.
above weight of gate in
order to avoid slipping.
OUTLET LEADS
RAMSET
RAM 300
Note: Eliminate outlet leads. Hookup your
electrical 15 amp wires direct to outlet.
STANDARD INSTALLATION FOR GATES FROM 8’ TO 14’ IN LENGTH
Do not exceed the specifications. The warranty on your unit will be void if the
WARNING
Outside
Property
installation exceeds the recommended specifications.
Steel Square Tubing
4x4
28”
36”
Gate Rotation
Center
(Hinge)
Gate travel is adjusted by loosening the limit
cams and positioning them until proper gate
travel has been achieved.
8’ to 14’ Maximum Gate Length
44”
Gate Closed
Supplied Bracket
39”
Inside
Property
OPERATOR
PIVOT SHAFT CENTER
28 1/2
www.ramsetinc.com
67 1/2”
SHORT ARM DIM.LONG ARM DIM.
Figure 5
28”38”
7
RAMSET
STANDARD INSTALLATION FOR GATES FROM 14’ TO 18’ IN LENGTH
RAM 300
Outside
Property
Steel Square Tubing
34”
42”
Inside
Property
OPERATOR
PIVOT SHAFT CENTER
4x4
Gate Rotation
Center
(Hinge)
32 3/4”
14’ to 18’ Maximum Gate Length
50”
Gate Closed
Supplied Bracket
43 1/4”
Figure 6
76”
32”42”
SHORT ARM DIM.LONG ARM DIM.
SPACE REQUIRED FOR A STANDARD GATE IN THE OPEN POSITION
Outside
Property
Inside
Property
4’
14 7/8”
Gate Opened
4 ft. Length is the minimum
space required between
the open gate to the wall
for this standard installation
8
www.ramsetinc.com
Figure 7
COMPACT INSTALLATION FOR GATES UP TO 14’ IN LENGTH
RAMSET
Steel Square Tubing
Outside
Property
19 1/2”
27”
4x4
Gate Rotation
Center
OPERATOR
PIVOT SHAFT CENTER
Inside
Property
(Hinge)
20”
27”
Maximum Gate Length 14’
Gate Closed
Supplied Bracket
RAM 300
24 1/4”
44 1/4”
32”42”
SHORT ARM DIM.LONG ARM DIM.
Figure 8
20” minimum space
required between, open
gate and wall for this
compact installation.
MINIMUM SPACE REQUIRED FOR COMPACT INSTALLATION
Outside
Property
10”
20’
Gate Opened
Inside
Property
Figure 9
www.ramsetinc.com
9
RAMSET
SENSOR INSTALLATION
A non-contact sensor (photoelectric sensor or equivalent) and a contact
sensor (edge device or equivalent) is required on each individual installation
WARNING
Ramset Gate Operators should not be installed without non-contact sensing devices such as Loop Detectors,
photo electric sensors or the equivalent.
to comply with UL325.
RAM 300
Reversing Loops
on the ground floor,
prevents gate from
closing when vehicle is
in loop area.
Exit Loops
on the ground floor,
opens gate when
vehicle crosses
loop area.
Photoelectric Safety
Sensor (Photo Eye)
prevents the gate
from closing when
any object interrupts
the beam.
Figure 10
10
www.ramsetinc.com
RAMSET
Use 3-stranded, shielded wires
(not supplied) from Master to Slave.
Use jumper
JP7 to JP7
Route low-voltage wires for Master/Slave
in a conduit separate from power.
Conduit
for power
Set Dip Switch (C8) “Slave Mode” to ON for
slave operation.
(RH) Right Hand operation requires Dip Switch
(C7) “Left/Right” to be ON.
Dip Switch “C”
A B COMA B COM
SELECT
ON
OFF
L.E.D.’s light up when Opening,
Closing or Stopped
“Intelligate” Control Board
PUSHBUTTON CONTROLS
Three pushbuttons are located under the dip switches for operation of the gate (see Figure 11). The opening,
stop and closing buttons can be utilized to set limit switches and verify proper system operation when installing or servicing an operator.
Opening
Pressing this button will cause
Figure 11
the gate to open.
Stop
Pressing this button will cause
the gate to stop moving.
Closing
Pressing this button will cause
the gate to close.
Reset E.R.D. Board
Push all three pushbuttons for
approximately 5 seconds. All
three L.E.D.’s should blink.
MASTER/SLAVE INSTALLATION
RAM 300
Figure 12
www.ramsetinc.com
11
RAMSET
“Intelligate” Control Board
RAM 300
DIP SWITCH CONFIGURATION
Figure 13
Dip Switch “A”
Dip Switch “A” 1, 2 & 3;
AUTOMATIC TIMER TO CLOSE GATE
‘0’ is “OFF”‘1’ is “ON”
Switch 1 2 3Gate Open Duration:
1 1 160 seconds
1 1 045 seconds
1 0 130 seconds
1 0 015 seconds
0 1 110 seconds
0 1 005 seconds
0 0 100 seconds
0 0 0Disabled - command required to close
Dip Switch “A” 4 - 1/2 HP ERD
Dip switch A4 works with Dip switch B8
DIP A4B8 Sensitivity
OFFOFFMost Sensitive
ONOFF1/2 Hp — Medium Sensitivity
OFFON3/4 Hp — Medium Sensitivity
ONONLeast Sensitive
Dip Switch “B”
Dip Switch “B” 2; “PRE WARN”
Used with JP2 “Relay Connections”: pins 7 & 8.
Triggers a relay, for an alarm or light (not included),
for 3 seconds before the gate will move in any direction.
Sw.Function:
ONTriggers the relay on JP2 pins 7 & 8 for 3 seconds.
OFFRegular working conditions
Dip Switch “B” 3; “CONSTANT WARN”
Used with JP2 “Relay Connections”: pins 7 & 8.
Triggers a relay, for an alarm or light (not included), to be active anytime the gate is in motion.
Sw.Function:
Triggers the relay on JP2 pins 7 & 8 while the gate
ON
is moving
OFFRegular working conditions
Dip Switch “B” 4,5,6 & 7; Not in use at this time.
Leave in the ‘O’ position.
Dip Switch “B” 8 - 3/4 HP ERD
Dip switch B8 works with Dip switch A4
DIP A4B8 Sensitivity
OFFOFFMost Sensitive
ONOFF1/2 Hp — Medium Sensitivity
Dip Switch “B” 1; Not in use at this time.
Leave in the ‘Off’ position.
12
OFFON3/4 Hp — Medium Sensitivity
ONONLeast Sensitive
www.ramsetinc.com
Dip Switch “C”
RAMSET
DIP SWITCH CONFIGURATION
Dip Switch “C” 1; “SECURE CLOSE”
Sw.Function:
OFFNormal Operation
When power is lost, then regained, control board
ON
checks status of the gate. If open and safety devices are cleared, gate will close
automatically.
WARNING
When installing or servicing an operator, make sure switch
“C” 1 is ‘O’. If switch “C” 1 is ‘On’, the gate will move when
power is applied and severe injury may occur.
Dip Switch “C” 2; “FULL REV ERD”
Changes how long a gate will reverse when an obstruction is
met when closing.
Sw.Function:
ONReverses until the open limit is reached
OFF Reverses for 2 seconds and stops again.
Dip Switch “C” 5; “CLOSE DELAY”
One second delay on the closing of the gate.
Dip Switch “C” 6; “OPEN DELAY”
One second delay on the opening of the gate.
RAM 300
Dip Switch “C” 7; “LEFT / RIGHT”
Sw.Function:
OFF Left hand installations - All operators come factory
ON Right hand installations - Reverses motor & limit
switches without moving any wires.
Dip Switch “B” 8; Not in use at this time.
Leave in the ‘O’ position.
Dip Switch “C” 3; “RADIO CYCLE”
Sw.Function:
OFF
Normal Operation - gate only opens and closes
on the limit switches. If the gate is
in travel then it will always open.
Cycle mode - gate opens and closes on
ON
the limit switches, but if in travel, then it
will stop with a rst command and reverse with
a second command.
Dip Switch “C” 4; “ONE PASS”
Sw.Function:
OFFNormal Operation - fully opens and closes
One pass mode - The gate will open until “the re-
ON
versing loop” is initially activated and then cleared,
the gate will then close. If the “reversing loop”
is then activated again, before the gate is fully
closed, the gate will stop until the “reversing loop”
is cleared, then continue to close.
www.ramsetinc.com
13
RAMSET
SAFETY
RAM 300
TERMINAL STRIP CONNECTION
Figure 14
14
www.ramsetinc.com
TERMINAL STRIP CONNECTIONS
RAMSET
Terminal # 1 - COMMON
Low voltage common.
Terminal # 2 - REV LOOP:
Stops the gate from closing. If the gate is open, it
holds the gate open. If the gate is closing, it stops
and reopens the gate. If the gate is closed, the gate
will remain closed. The function can be altered with
Dip Switch “C” 4 (see “Dip Switch Configuration”).
Used with loop detectors, photo eyes, safety
edges…etc. Becomes active with a closed contact
to common.
Terminal # 3 - CLOSE
Closes the gate. Used with three button stations or
pushbuttons. Becomes active with a closed contact
to common.
Terminal # 4 - FIREBOX
Opens the gate. Used with fire department key
switches & controls. Opens with closed contact to
common. Closes immediately when closed
contact on common is removed.
reaching a limit switch, the alarm will sound for
6 minutes and the control board will not accept
any commands. After the 6 minutes the 24 VDC is
removed from the alarm connection and the board
resets to normal operation.
Terminal # 9 and 10 - LIMIT 1 & LIMIT 2
Direction depends on Dip Switch “C” 7 (See “Dip
Switch Configuration”). Stops the motor from
moving in one direction. These wires are preset in
factory and should not be moved. Becomes active
with a closed contact to common.
Terminal # 11 and 12 COMMON
Low voltage common.
Terminal # 13 - +24 VAC
Provides 24 VAC for peripheral accessories.
Terminal # 14 and 15 - MAG & MAG +
Supplies 24 VDC to a Magnetic Lock when the gate
is closing or closed. If gate is opening or opened,
then no power is supplied. Leave open if not used.
RAM 300
Terminal # 5 - EXIT
Opens the gate. Used with loop detectors, photo
eyes, keypads, phone entry systems, three-button
stations…etc. Becomes active with a closed contact
to common.
Terminal # 6 - PHANTOM
Keeps the gate open when the open limit switch
is activated. Used with loop detectors. Becomes
active with a closed contact to common.
Terminal # 7 - RADIO
Operation depends on dip switch “C” 3 (See “Dip
Switch Configuration”). Used with an RF receiver or
pushbutton. Becomes active with a closed
contact to common.
Terminal # 8 - EDGE
When triggered the gate will stop. The gate will
remain stopped until the detector is cleared.
Once the detector is cleared, the operator will
resume normal operation. If triggered twice before
Terminal # 16 - M BRAKE
Used ONLY on the Ram 50 Operator. If while the
gate is closed someone or something tries to
manually open the gate without a proper signal
(keypad, exit loop, radio signal…), the motor will
lock up for 6 minutes. After the 6 minutes, the
operator will then secure close the gate.
Terminal # 17 and 18 - MOTOR 1 & MOTOR 2
Supplies power to the motor. Direction depends on
Dip Switch “C” 7 (see “Dip Switch Configura-tion”).
These wires are preset and connected in the factory
and should not be moved.
Terminal # 19 and 20 - AC HOT & NEUTRAL
110 VAC or 220 VAC to power the operator. Voltage
is predetermined at factory and cannot be changed
by the installer or technician.
www.ramsetinc.com
15
RAMSET
RAMSET “INTELLIGATE” CONTROL BOARD
INTRODUCTION
Ramset’s “Intelligate” Control Board works with Sliding, Swinging and Overhead vehicular gate operators. It is controlled by a programmable microprocessor that reads and precisely executes all functions of
the Control Board. The Control Board is powered by
a separate mounted 24 VAC transformer. This allows
RAM 300
no necessary board modifications between 110 VAC
Power Transformer
3 Button Station
40VA.
JP9
plug-in
plug-in
JP10
and 220 VAC single-phase applications. Some of the
functions of the Control Board are: 0 - 60 seconds
automatic close timer, self adjusting E.R.D. with low
and high setting, constant warning, prewarning, secure close, one pass, open & close delay, left/right
hand operation, plug-in loop detectors and RS485
three wire master/slave connection.
Reverse Loop
Exit Loop
plug-in
JP2
Indicator lights, alarms and sirens
Phantom Loop
Figure 15
Relay Connections
Microprocessor
Reprogrammable,
controls all functions
of the operator.
Dipswitches
Automatic Timer, Prewarn,
Constant Warning, Secure Close,
Full Reverse ERD, Radio Cycle, One
Pass, Low / High ERD,
Adjustment, Close Delay,
Open Delay and Left / Right.
Foot Pedal Plug
Stops the motor from
running while the foot
pedal is engaged.
Master / Slave Plug
Synchronizes movement
between two gates. 3 wires
(A-, B- and Common).
JP3
JP11
JP7
Self adjusting, with low
ERD
and high adjustments.
3 Button Station
Open - Stop - Close
Standard Connections
Reverse Loop, Fire Box, Exit Loop,
Phantom Loop, Radio, Edge Sensor,
24 VAC and Magnetic Lock.
16
www.ramsetinc.com
WIRE BOARD CONNECTIONS
JP9 - Input Power:
1,2) 24 VAC power.
Connection from external transformer
to power Control Board.
JP3 - 3 Button:
1) Open 2) Stop 3) Close 4) Common
Used with a 3-button station to
open, stop, and close the gate. The
open and close are normally open connections
and the stop is a normally closed connection,
remove jumper wire when connecting 3 button
station. Common and stop are also used with a
photo eye used to protect the backplane of the
operators.
JP11 - Foot Pedal Plug:
Stops the motor from running while
the foot pedal is engaged.
RAMSET
JP2 - Relay Connections:
1) 24 VDC. 5) Relay Common
2) 24 VAC 6) Fully Closed-N.C.
3) 5 VDC 7-8) Constant/Prewarn
4) Fully Open-N.O. 9-10) E.R.D. Alarm.
If E.R.D. is triggered twice before reaching a
limit, 24 VDC is supplied to sound an alarm
(included with operator).
Fully Open N.O. (works with relay common)
Relay rated at 125 VAC, 2 amps. Normally open
connection. Open contact occurs until the
open limit is triggered. When the open limit is
triggered, a closed contact occurs.
Relay Common
Relay rated at 125 VAC, 2 amps. The common of
the Fully Closed N.C. relay and the Fully Open
N.O. relay.
RAM 300
JP7 - Master/Slave plug:
1) A 2) B 3) Common
Used to synchronize the operation
between two gates. A three-wire, Shielded
cable is needed to run from the A, B, &
Common (JP7) of the master P.C.B. to the A, B,
& Common (JP7) of the slave P.C.B.
JP10 - Loop Inputs:
1-2) Reverse 3-4) Exit
5-6) Phantom
Use with ILD-24s, Loop wires should be
connected to this plug.
JP4, JP5 & JP8 - Reverse,
Exit & Phantom Sensor:
Used with the Ramset ILD-24 plug-in loop
detector. The Loop wires should be connected
into the “LOOP INPUTS” plug.
Fully Closed N.C. (works with relay common)
Relay rated at 125 VAC, 2 amps. Normally closed
connection. Closed contact occurs until the
closed limit is triggered. When the closed limit
is triggered, an open contact occurs.
www.ramsetinc.com
17
RAMSET
PARTS DIAGRAM
RAM 300
Figure 16
53
41
6
71
74
72
70
75
54
23
42
52
13
81
83
79
84
78
82
4
77
78
84
40
14
85
63
37
8
36
57
55
26
11
12
10
31
73
28
69
25
76
2
27
35
33
32
3
1
15
9
7
16
15
34
5
24
29
30
39
18
www.ramsetinc.com
BILL OF MATERIALS
ITEMPART #PART DESCRIPTIONRAM 300
1800-00-04Chassis1
2800-02-04Gear Reducer - Size 50, Ratio 80:1 1
3800-04-10Motor, Standard - 120VAC 1/2 HP1
4800-08-00Pulley, Cast Iron - 5/8" x 10" (MA100) 1
5800-08-45Pulley, Cast Iron - 5/8" x 2" - AK201
6800-10-06Belt - 4L-3801
7800-12-00Shaft - 1" x 13" 1
8800-14-15Cover, Polyethylene Cap Arm1
9800-20-05Limit Switch2
10800-20-21Switch, Foot Pedal1
11800-22-03Spring - 1/4" x 1" 1
12800-24-10Foot Pedal Release 1
13800-28-20Square Pivot, 1 1/2" - 1" 1
14800-28-40Pivot Arm Release 1
15800-44-01Bearing, Flange - F2052
16800-48-05Cam, Limit Switch - 1" 2
17800-50-11Wire Harness - Motor1
18800-50-41Wire Harness - Outlet1
19800-50-90Wire Harness - Foot Pedal1
20800-51-03Wire Harness - Limit Switches1
21800-51-22Wire Harness - Radio terminal1
22800-51-23Wire Harness - XFMR to PCB1
23800-52-11Chain, Drive - #40 - 28 1/2" 1
24800-54-50Bracket, Limit Switch 1
25800-55-05Bracket, Foot Pedal Guide 1
26800-55-10Bracket, Foot Pedal Switch/Lockdown 1
27800-60-00Transformer, 120/240V to 18VAC - 40VA UL1
28800-60-10Switch, Rocker1
29800-62-00Control Board - Intelligate1
30800-64-00Edge Connector - 20 Pin1
31800-64-50Radio Receiver Terminal1
32800-66-02Lexan Control Board Cover 1
33800-66-50Lexan Limit Assembly Cover 1
34800-68-04Instruction Manual 1
35800-70-20Horn Alarm Buzzer1
36800-70-35Knob - 5/16" - 18 x 1 1/2"1
37800-70-36Knob - 5/16" - 18 x 1/2"1
38800-70-87Snap Ring - 1" 1
39800-70-98Warning Sign For Gates - Slide/Swing2
RAMSET
RAM 300
www.ramsetinc.com
19
RAMSET
ITEMPART #PART DESCRIPTIONQTY
RAM 300
BILL OF MATERIALS
40800-75-00ARM ASSEMBLY1
41800-28-00Arm, Metal Tubing - 1" x 2" x 32" - 12 awg1
42800-28-01Arm, Metal Tubing - 1" x 2" x 42" - 12 awg1
1. A) for 1/2 hp motors: turn dip
switch “A” 4 ‘On’.
B) for 3/4 hp motors: turn dip
switch “B” 8 ‘On’.
1. Disconnect all accessories, including
plug-ins, using the “Exit” input. If
problem persist, contact Ramset.
1. Disconnect all accessories, including
plug-ins, using the “Rev Loop” input.
If problem persist, contact Ramset.
1. Check all transmitters.
2. Remove receiver. If problem
persist, contact Ramset.
GATE DOESN’T OPEN.
GATE DOESN’T CLOSE.
GATE DOESN’T CLOSE
AUTOMATICALLY.
GATE AUTOMATICALLY
OPENS, BUT DOESN’T
AUTOMATICALLY CLOSE.
RADIO/RECEIVER HAS NO
RANGE.
1. Radio L.E.D. ‘On’.
2. 10 amp. fuse blown.
3. Opening accessory not
functioning.
1. No lights are ‘On’.
2. Exit, Rev Loop, Radio L.E.D.‘On’.
3. 10 amp. fuse blown.
4. Thermal/overload button
popped on motor.
1. Dip switches “A” 1-3 are all ‘Off’.
2. Dip switch not on all the way.
1. Motor direction wrong.1. Turn on dip switch “C” 7 (left/right).
1. Signal blocked.
2. Area not suitable for type of
Receiver.
1. See above symptoms/solutions.
2. Check/replace 10 amp. fuse.
3. Check/replace opening accessory.
1. See above symptoms/solutions.
2. See above symptoms/solutions.
3. Check/replace 10 amp. fuse.
4. Reset thermal/overload button on
the back of the motor.
1. Set dip switches “A” 1-3 for auto close.
2. Turn off dip switches “A” 1-3, then
turn the appropriate switches back
‘On’.
1. Make sure antenna is in proper
position & not shorted to chassis.
2. May need to change to long range
receiver.
22
www.ramsetinc.com
GATE ENTRANCE SAFETY PRECAUTIONS
Not following these instructions
may cause severe injury or death
to persons
1.
Never let children operate or play with
gate controls. Keep the controls away from
children.
2. The entrance is for vehicles only.
Pedestrians should use a separate entrance.
3. Always keep people, children and objects
away from the gate while the gate is in
operation. No one should cross the area of a
moving gate.
4. All opening devices, (such as a keypad,
cardreader…), should not be installed close
to the gate, where the gate could possibly
cause injury.
RAMSET
RAM 300
5. Use warning signs attached on both sides of
the gate.
www.ramsetinc.com
23
RAMSET
RAM 300
IMPORTANT INFORMATION FOR THE HOMEOWNER
Ask your technician about all the features of our
new Ramset operator.
Safety devices, such as reversing loops,
phantom loops, photo eyes, or miller edges
must be installed on your gate before the
operator may be used. Ask your technician
which safety devices best suit your safety needs.
Read your warranty certificate and fill out your
warranty extension card. Return the warranty
card, via certified mail, to Ramset within 90 days
of purchase:
Ramset Automatic Gate Services, Inc.
9116 De Garmo Ave.
Sun Valley, CA. 91352
Never let children operate or play with gate
controls. Keep the controls away from children.
The entrance is for vehicles only. Pedestrians
should use a separate entrance.
Use the emergency release only when the gate
is not moving & power is turned off to the unit.
Have the technician give you a demonstration of
how to use the emergency release.
Keep gates properly maintained. Have a
qualified gate technician service the gate
operator and gate hardware every six months to
a year. This includes checking of safety devices,
E.R.D. and battery back up systems.
Warning signs must be placed on every gate in a
highly visible area.
To reset the audible alarm on the gate operator
you must turn the power of the unit off for
approximately 10 seconds, then back on.
Always keep a good relationship with your
technician and keep his or her number handy
for future maintenance or emergencies.
24
Always keep people, children and objects away
from the gate while the gate is in operation. No
one should cross the area of a moving gate.
www.ramsetinc.com
Ramset wishes to thank you for trusting
us to meet your gate operator needs
www.ramsetinc.com
9116 De Garmo Ave.
Sun Valley, CA 91352
Tel: (818) 504-2533 • Fax: (818) 504-1141
www.ramsetinc.com