6. Commissioning
Checklist
Check the installation using the checklist below. If in
doubt, refer to the manual “Energy-efficient detection
technology”, order no. 35100.
Always consider the following questions for each
installation:
1. Is the correct detector being used?
2. Is it placed in the correct corner?
3. Is it at the correct height?
4. Is the correct lens fitted?
5. Is the correct logic unit being used?
6. Is the power supply correctly rated for the
detectors, relays and logic?
7. Do you have the necessary skills and tools to
carry out final adjustment of the installation?
You should also answer the following questions about
the light sources:
1. Is the correct type of light source being used?
2. Is the correct control method being used for the
light source?
3. Is the correct type of ballast being used?
If you can answer yes to all the questions in the
checklist then you can continue with commissioning.
•
Check the voltage and polarity, and connect the
power supply.
•
Set the “Photocell” to “Off”. If the photocell is not to
be used it should always be turned off. See the
“Photocell” section if the photocell is to be used.
•
Turn down the delay time to “Min” using the “Time”
potentiometer.
•
Move the jumper to the “Activity High” position.
•
Carry out a run test in the entire area covered by
presence detection.
Note! The lens must be fitted and the cover must be
in place. Adjust vertically and horizontally as
required.
•
After completing the run test and adjustment, set the
time to the lowest possible. In the case of dynamic
lighting control in a stairwell or corridors, for
example, this should be 1–2 minutes. In other
applications, such as a classroom or garage, the
time should be set to 6–8 minutes or according to
the light source manufacturer’s recommendations.
•
Set the jumper according to the level of activity in the
premises.
•
Disconnect the LED when adjustment is complete
(see “Jumpers”), to reduce the risk of tampering.
7. Technical specification.
Adjustment
Vertical: +10º to –20º calibrated scale
Horizontal: Up to 30º
Electrical
Voltage: 10-16 VDC
Current: 25 mA at 13,8 VDC
Start-up time: < 2 minutes
Relay output: Changeover contacts
2 A / 30 VDC,
0,5 A // 60 VDC (resistive)
LED Walking test (switchable)
Test point: For background interference.
Detector: Dual-elements, low-noise,
pyroelectric detector
Environment
Ambient temp.: 0º to + 50ºC
Storage temp.: - 20º to + 60º
Dimensions: 102 x 70 x 50 mm
Weight: 100 g
Colour: White
8. Accessories
Field indication diode BL-1
Used for adjusting detection area. Art. No. 13035.
For further information see handbook “Presence
Detection”
Protective Grille
For mounting in exposed premises as for indoor sports.
There is also one model that can be used for mounting
a detector in 45º with angel plate to a wall.
For further information see handbook “Presence
Detection”
Universal bracket
BR1, BR2, BR3 can be used when the detector cannot
be mounted directly in the corner. With the bracket the
detector can be moved out a short distance and still
give maximum coverage. Use with precaution.
Contact Extronic for further advice and information
when a bracket is used.
Lens-library
See lens-library in handbook for a great number of
changeable lenses.
Handbook
Handbook “Presence Detection”.
Extronic AB • 10 06 01 Tel: 08-771 26 00