STOVE AND PELLET INSERTS USER MANUAL
2
3
ENGLISH ............................................................... 4
1. WARNINGS ..............................................................4
2. SAFETY .....................................................................4
3. SAFETY DEVICES ....................................................5
4. INSTALLATION ........................................................5
4.1. INSTALLATIONS ALLOWED ..........................................................6
4.2. INSTALLATIONS NOT ALLOWED ...............................................6
4.3. CONNECTION TO THE SMOKE EVACUATION SYSTEM .6
4.3.1. SMOKE CHANNEL OR FITTINGS ...............................6
4.3.2. CHIMNEY OR INDIVIDUAL FLUE ............................... 7
4.3.3. CHIMNEY CAP .....................................................................8
4.4. CONNECTION TO EXTERNAL AIR INLETS ............................8
4.5. INSULATION, FINISHINGS, COVERING AND SAFETY
RECOMMENDATIONS .................................................................................9
4.6. NATIONAL, REGIONAL, PROVINCIAL AND TOWN
COUNCIL REGULATIONS ...........................................................................9
5. INSERTS INSTALLATION .......................................9
5.1. INSERT COMPARTMENT MINIMUM MEASUREMENTS 9
5.2. AIR INLETS ...........................................................................................10
5.3. AIR CIRCULATION PIPES .............................................................10
5.4. STANDARD ASSEMBLY ................................................................11
5.5. FRAMES ASSEMBLY EXCLUDING MODEL P80 ............11
5.6. INSERT EXTRACTION ....................................................................12
6. HOT AIR DUCTING .............................................. 12
6.1. TOSCA PLUS  EMMA PLUS .......................................................12
6.2. ELISIR ......................................................................................................12
6.3. COMFORT PLUS ...............................................................................12
6.4. GRAZIOSA STEEL/LUX PLUS .....................................................13
7. PELLETS AND FEEDING ..................................... 13
8. PRODUCT FUNCTIONALITY ............................. 14
8.1. CONTROL BOARD...........................................................................14
8.2. DISPLAY ICONS KEY.......................................................................14
9. FUNCTIONING CYCLE ........................................ 15
9.1. BASIC INSTRUCTIONS .................................................................. 15
9.2. IGNITION ..............................................................................................15
9.3. WORK .....................................................................................................15
10. ADDITIONAL THERMOSTAT ............................. 16
10.1. STOVE FUNCTIONING WITH ADDITIONAL EXTERNAL
THERMOSTAT OPTIONAL ...................................................................16
10.2. INSTALLATION ................................................................................. 16
10.3. ADDITIONAL THERMOSTAT FUNCTIONING FOR
DUCTING MOTOR CONTROL ...............................................................16
11. THE REMOTE CONTROL ..................................... 16
11.1. REPLACING THE BATTERIES ...................................................... 16
12. SET TINGS MENU ................................................. 17
12.1. SET CLOCK ..........................................................................................17
12.2. CHRONO ..............................................................................................18
12.2.1. RECOMMENDATIONS ..................................................18
12.2.2. PROG R A MMING EXAMPLE ....................................... 18
12.2.3. CHRO N O MENU TABLE ..............................................19
12.3. LANGUAGE .........................................................................................20
12.4. USER ....................................................................................................... 20
12.4.1. DISPLAY ............................................................................... 20
12.4.2. PELLETS ............................................................................... 20
12.4.3. STAND  BY ......................................................................... 20
12.4.3.1. STAND  BY WITH DIGITAL
THERMOSTAT AS PER STANDARD ...............20
12.4.3.2. STBY WITH ADDITIONAL EXTERNAL
THERMOSTAT ..........................................................21
12.4.3.3. HOW TO ACTIVATE OR DEACTIVATE
STAND  BY ...............................................................21
12.4.4. KEYS LOCKED ................................................................... 21
12.4.5. V2  FAN ...............................................................................21
12.4.6. ENABLE V2 .........................................................................21
13. CLEANING THE UTILITY ..................................... 23
14. CLEANING OF THE “T” FITTING FOR ELISIR ...24
15. TECHNICIAN YEARLY CLEANING ..................... 25
16. DISPLAYS .............................................................. 26
17. ALARMS ................................................................ 27
18. WARRANTY CONDITIONS ................................ 28
WARNINGS
4
WARNINGS1.
Installation must be carried out by qualified staff and/or manufacturer technical assistance, who must provide the buyer with a declaration of conformity for the system and will assume full responsibility for final installation and as a consequence the correct functioning of the installed product. It is necessary to bear in mind all laws and national, regional, provincial and town council Standards present in the country the appliance has been installed. The manufacturer cannot be held responsible for the failure to comply with such precautions.
1. Electric connections: it is therefore recommended that after any
intervention on the product, that authorised sta pay particular attention to the electric connections, especially the stripped parts of the wires. These must not escape from the terminal board in any situation, thus preventing possible contact with the live parts of the wire.
2. Type of use: this stove must be destined for the use for which it has been expressly realised.
3. Liability of the manufacturer: The manufacturer is exempt from any liability, contractual and extracontractual, for injury/ damage caused to persons/animals and objects, due to installation, adjustment and maintenance errors and improper use.
4. Check integrity of the product: After the packaging has been removed, check the integrity and completeness of the contents. If this does not comply, contact the dealer where the appliance was purchased.
5. Electric connections: All electric components that make up the stove must be replaced with original spare parts exclusively by an authorised after-sales centre, thus guaranteeing correct functioning.
6. Maintenance:The stove must be serviced at least once a year, programming it in advance with qualified staff and/or the manufacturer's technical after-sales assistance. Nota bene: In case
of thermo product or boiler, the product or system venting is not covered by the warranty.
SAFETY2.
For safety reasons, remember that:
The stove must not be used by persons (including children) with reduced physical, sensorial and mental capacities or who are unskilled persons, unless they are supervised and trained regarding use of the appliance by a person responsible for their safety.
Children must be controlled to ensure that they do not play with the appliance.
Do not touch the stove when you are barefoot or when parts of the body are wet or humid.
The safety and adjustment devices must not be modi ed without the authorisation or indications of the manufacturer.
Do not pull, disconnect, twist electric cables leaving the stove, even if disconnected from the electric power supply mains.
It is advised to position the power supply cable in a way that it does not come into contact with hot parts of the appliance.
The power supply plug must be accessible after installation.
Do not close or reduce the dimensions of the airing vents in the place of installation. The airing vents are indispensable for correct combustion.
Do not leave the packaging elements within reach of children or unassisted disabled persons.
The hearth door must always be closed during normal functioning of the product.
When the appliance is functioning and hot to the touch, especially all external surfaces, attention must be paid
Check for the presence of any obstructions before switching the appliance on following a prolonged standstill period.
The stove has been designed to function in any climatic condition (also critical). In particularly adverse conditions (strong wind, freezing) safety systems may intervene that switch the stove o . If this occurs, contact the technical after-sales service and always disable the safety system.
If the  ue should catch  re, be equipped with suitable systems for su ocating the  ames or request help from the  re service.
This appliance must not be used to burn waste
Do not use any in ammable liquids for ignition
During the  lling phase do not allow the bag of pellets to come into contact with the product
The majolicas are top quality artisan products and as such can have micro-dots, crackles and chromatic imperfections. These features highlight their valuable nature. Due to their di erent dilation coe cient, enamel and majolica produce crackling, which demonstrate their e ective authenticity. To clean the majolicas, it is recommended to use a soft, dry cloth. If a detergent or liquid is used, the latter could penetrate inside the crackles, highlighting the same.
SAFETY DEVICES
5
ENGLISH
SAFETY DEVICES3.
SAFETY DEVICES
Key: * = present,
- = not present
STOVES
INSERTS
Circuit board: intervenes directly by sending the product into alarm conditions until complete cooling, in the case of: breakage of  ue gas motor, pellet feed motor breakage, black out (if more than 10 seconds), no ignition
**
Upper door micro switch (combustion chamber): if the combustion chamber is opened, the pellet feed motor functioning is blocked (*in some models)
*_
Insert blocking micro switch: if the end run micro switch warns that the insert is not blocked, electric energy does not pass to power it
-*
Flow sensor: in the case of inadequate depression, it takes the machine to alarm conditions
**
F2.5 A 250V fuse (stoves): protects the machine from violent current drops
**
85°C calibrated mechanical bulb with manual rearm: intervenes by blocking fuel feed whenever the pellet tank t° reaches the limit of 85°C. Rearm must be performed
by quali ed sta and/or the manufacturer's technical after-sales assistance.
**
Pellet feed-box temperature control probe: if the tank
should overheat, the machine modulates automatically in order to return to normal temperature values (* in some models)
**
Mechanical air pressure switch: blocks the pellets in the event of insu cient depression (in the models where envisioned)
**
INSTALLATION4.
The installation must be in compliance with:
UNI 10683 (2005) heat generators fed with wood and
other solid fuels: installation.
The chimneys must be in compliance with:
UNI 9731 (1990) chimneys: classi cation based on thermal
resistance.
EN 13384-1 (2006) Thermal and  uid dynamic calculation
methods.
UNI 7129 point 4.3.3 Fire Department dispositions, local rules
and prescriptions.
UNI 1443 (2005) chimneys: general requisites. UNI 1457 (2004) chimneys: clay/ceramic  ue liners.
GLOSSARY
CLOSED HEARTH APPLIANCE
Heat generator which opening is only allowed through the loading of the fuel during use.
BIOMASS
Biological material, excluding the material incorporated in geological formations and transformed into fossils.
BIOFUEL
Fuel produced directly or indirectly by biomass.
CHIMNEY
Vertical pipe with the aim of collecting and expelling the fuel products coming from only one appliance, at a convenient height from the ground.
SMOKE CHANNEL OR FITTING
Pipe or connecting element between heat generator appliance and chimney to evacuate fuel products.
INSULATION
Group of set-ups and materials used to prevent the transmission of heat through a wall that separates rooms with di erent temperatures.
CHIMNEY CAP
Device positioned at chimney peak to ease the dispersion of combustion products into the atmosphere.
CONDENSATE
Liquid products which form when the fuel gas temperature is lower or equal to the water dew point.
HEAT GENERATORS
Appliance which allows to produce thermal energy (heat) through the rapid transformation, through combustion, of the chemical energy of the same fuel.
GATE VALVE
Mechanism for modifying the combustion gas dynamic resistance.
COMBUSTION PRODUCT EVACUATION SYSTEMS
Flue gas exhaust system independent from the appliance constituted by a  tting or smoke channel, chimney or individual  ue and chimney cap.
FORCED DRAUGHT
Air circulation by means of the fan activated by electric motor.
NATURAL DRAUGHT
Draught which determines in a chimney/ ue due to e ect of the volume mass di erence existing between smoke (hot) and surrounding atmosphere air, without any mechanical intake aid installed inside it or at its peak.
RADIATION AREA
Area immediately near the hearth in which the heat caused by combustion is di used, where there must be no combustion materials .
REFLUX AREA
Area where leaking of the fuel products is veri ed, from the
INSTALLATION
6
appliance towards the installation room.
The installation must be preceded by checking the chimneys,  ues or unload terminals positioning regarding:
Installation prohibitions Legal distances Limitations disposed by local administrative regulations or
particular authority prescriptions.
Conventional limitations deriving from condominium
regulations, constraints or contracts.
INSTALLATIONS ALLOWED4.1.
Only appliances working in a sealed manner with respect to the room or which do not place the room in depression with respect to the external environment, can exist or be installed in the room where the heat generator will be installed. Appliances for cooking food and relative hoods without extractor are only allowed in kitchens.
INSTALLATIONS NOT ALLOWED4.2.
In the room where the heat generator will be installed the following must not pre-exist or be installed:
hoods with extractor
collective type ventilation pipes. Should these appliances be in adjacent rooms, communicating with the installation room, the simultaneous use of the heat generator is forbidden, where a risk exists of one of the two rooms being placed in depression respect to the other.
CONNECTION TO THE SMOKE 4.3.
EVACUATION SYSTEM
UNI 10683 (2005) Standard
SMOKE CHANNEL OR FITTINGS4.3.1.
To mount the smoke channels, non- ammable elements will have to be used, ideal for resisting combustion products and their eventual condensing. The use of  exible metal and asbestos cement pipes to connect the appliances to the  ue is forbidden, even for pre-existing smoke channels. There must be continuity between the smoke channel and the  ue so that the  ue does not lean on the generator. The smoke channels must not cross rooms where the installation of the combustion appliances is not allowed. The mounting of the smoke channels must be carried out in order to guarantee smoke seal for the appliance functioning conditions, limit the formation of condensate and avoid it being transported towards the appliance. The mounting of horizontal routes must be avoided. For appliances where ceiling or wall non coaxial discharges respect to the appliance smoke outlet have to be reached, the direction changes will have to realised using open elbows not higher than 45° (see  gures below). For the heat generator appliances equipped with electric fan for expelling fumes, the instructions below must be followed:
45°
<
 gure 1
Insulating product
45°
<
 gure 2
Flue
Inspection
The horizontal routes will have to have a minimum upward
slope of 3%
The length of the horizontal route must be minimal and,
however, not longer than 3 metres
The number of direction changes including the one for e ect of using the "T" element must not be more than 4 (if 4 bends are used, use double wall piping with an internal diameter of 120 mm).
In any case, the smoke channels must seal the fuel and condensing products and be insulated if they pass externally to the installation room. The use of counterslope elements is forbidden. The smoke channel must allow the recovery of soot or be brushable. The smoke channel must have constant section. Any section changes are only allowed at the  ue coupling. It is forbidden to have other air supply channels and pipes for plant engineering, especially if over-sized, transit inside the smoke channels. The mounting of manual draught adjustment devices on forced draught appliances is forbidden.
INSTALLATION
7
ENGLISH
CHIMNEY OR INDIVIDUAL FLUE4.3.2.
The chimney or individual  ue must respond to the following requisites:
seal the combustion products, be waterproof and adequately
insulated in line with the use conditions;
be realised with materials which resist the normal mechanical
stresses, heat, action of the fuel products and any condensing;
have mainly vertical progress with deviations from the axis
not higher than 45°;
be adequately distanced from fuel or  ammable materials
through air space or opportune insulation;
REFERENCES
In ammable
objects
Non-in ammable
objects
A 200 mm 100 mm
B 1500 mm 750 mm
C 200 mm 100 mm
have preferably circular internal section: the square or rectangular sections must have round corners with a radius not lower than 20 mm;
have constant internal section, free and independent;
have rectangular section with max. ratio between the sides of 1.5.
It is recommended that the smoke pipe be equipped with a collection chamber for solid materials and any condensing situated under the smoke channel inlet, so that it can be easily opened and inspected from airtight door.
A
S
 gure 3
S=  oor protection
Minimum 80 cm
2
B
C
A
 gure 4
< 3 m
3 - 5 %
 gure 5
Inspection
 gure 6
Chimney cap
Flue pipe
Inspection
INSTALLATION
8
 gure 7
External pipe that is isolated
inspection
< 3 m
45°
45°
 gure 8
inspection
Appliance connection to the  ue and fuel products evacuation. The  ue must receive the discharge from only one heat generator. The direct discharge towards closed spaces is forbidden, even with clear sky. The direct discharge of the fuel products must be at roof and the smoke pipe must have the features provided in the "Chimney or individual  ue" section.
CHIMNEY CAP4.3.3.
The chimney cap must comply with the following requisites:
have an internal section equivalent to that of the chimney;
have useful outlet section not lower than double the chimney internal section;
be built in order to avoid rain, snow, foreign bodies penetrating the chimney and so that, in the event of winds in any direction and inclination, the discharge of the fuel products is assured.
be positioned in a way to guarantee an adequate dispersion and dilution of the combustion products and, however, outside the re ux area in which the formation of counterpressures occurs. Such area has di erent dimensions and con guration depending on the covering inclination angle. It is therefore necessary to adopt the minimum heights indicated in the  gure
layouts below.
The chimney cap must not have mechanical intake means.
FLAT ROOF
50 cm
< 5 m
> 5 m
< 5 m
50 cm
 gure 9
SLOPING ROOF
H min
β
>A
<A
>50 cm
Z
Z=REFLUX AREA
 gure 10
CHIMNEY CAPS, DISTANCES AND POSITIONING
Roof
inclination
Distance between
the ridge and the
chimney
Minimum chimney height
(measured from outlet)
β A (m) H (m)
15°
< 1,85 0.50 m over the ridge > 1,85 1.00 m from roof
30°
< 1,50 0.50 m over the ridge > 1,50 1.30 m from roof
45°
< 1,30 0.50 m over the ridge > 1,30 2.00 m from roof
60°
< 1,20 0.50 m over the ridge > 1,20 2.60 m from roof
CONNECTION TO EXTERNAL AIR 4.4.
INLETS
The appliance must be able to use the necessary air to guarantee regular functioning through external air inlet. The air inlets must comply with the following requisites:
have a total free section of at least 80 cm.
must be protected by grates, metal net or suitable protections as long as they do not reduce the minimum section stated in the previous point and positioned in order to avoid them being obstructed.
If the combustion agent air is withdrawn directly from outside through a pipe, a downward bend must be mounted outside or a protection against the wind and no grates or similar must be positioned, (it is recommended that the air vent always communicates directly with the installation room even if the air is
INSERTS INSTALLATION
9
ENGLISH
withdrawn from outside through a pipe). The air  ow can also be obtained from an adjacent room, as long as the  ow takes place freely through permanent openings communicating with the outside. The adjacent room, with respect to the installation room, must not be put in depression with respect to the external environment by means of reverse draught caused by the presence of another used appliance or intake device in such room. The permanent openings in the adjacent room must comply with the above-described requisites. The adjacent room cannot be set up as garage, storage for combustion material or activity with danger of  re.
INSULATION, FINISHINGS, 4.5. COVERING AND SAFETY RECOMMENDATIONS
The coverings, independently from the materials from which they are made, must constitute a self-supporting construction with respect to the heating block and not be in contact with it. The cross members and  nishings in wood or combustion materials must be positioned outside the hearth radiation area or adequately insulated. If coverings in combustion material or sensitive to heat exist in the space above the generator, an insulating and non combustible protection diaphragm must be inserted. Elements in combustible or in ammable material like wooden furniture, curtains, etc., directly exposed to the hearth radiation, must be positioned at a safe distance. The appliance installation must guarantee easy access for cleaning the appliance itself, discharge gas pipe and  ue.
NATIONAL, REGIONAL, 4.6. PROVINCIAL AND TOWN COUNCIL REGULATIONS
It is necessary to bear in mind all laws and national, regional, provincial and town council Standards present in the country the appliance has been installed.
INSERTS INSTALLATION5.
The model is supplied with a sliding base in iron, which allows it to be installed in a pre-existing chimney, allowing it to be extracted, with the machine o , easily both for feeding pellets into the tank and for any maintenance or end of season cleaning. If there is no pre-existing  ue, one can be built using the insert­holder pedestal (optional kit); in fact, the latter  xes the insert to the  oor. Image key: primary air (A), combustion gas discharge (B), frame (C), sliding base (D), ducting (F)
C
A
B
D
Comfort Maxi
 gure 11
A
B
D
C
F
Comfort Plus
 gure 12
A
B
D
C
Comfort Mini/Mini Chrystal/P80
 gure 13
INSERT COMPARTMENT MINIMUM 5.1.
MEASUREMENTS
For correct functioning of the insert, during construction of the  ue the measurements between the insert and internal walls of the  ue must be respected. From the clearance measurements of the stove given in the technical features, it is necessary to consider at least 50 mm of air in the upper part and on the 2 sides. The  ue outlet pipe must always
maintain a minimum distance of 50 mm from in ammable parts.
COMFORT/P80
50mm
50 mm
50 mm
 gure 14
INSTALLATION
10
COMFORT MAXI
85 mm 85 mm
60 mm
50 mm 50 mm
 gure 15
COMFORT PLUS /MINI/CRYSTAL
35 mm
35 mm
60 mm
 gure 16
AIR INLETS5.2.
Regarding the air intake box, it is possible to apply the intake pipe above the base or below depending on requirements.
These operations must be carried out by a quali ed technician and/or the manufacturer's technical after-sales assistance.
COMFORT MAXI - MINI
 gure 17
 gure 18
COMFORT PLUS
 gure 19
 gure 20
AIR CIRCULATION PIPES5.3.
It is necessary to create air recirculation inside the structure that covers the insert for correct functioning. This prevents the appliance from over-heating. To guarantee this, just realise one or more openings in the lower part and in the upper part of the covering. The following measurements must be respected:
Lower part (cold air inlet) total minimum surface
including openings of 600 cm.
The openings in the lower part must be realised below the rest bottom.
Upper part (hot air outlet)  total minimum surface