Explorer FX15 Technical Bulletin

Page 1
Technical Bulletin FX15 Controller Issue Date November 14, 2005
FX15 Controller
Introduction to FX15...............................................................................3
Key Concepts....................................................................................................... 4
FX15 ...................................................................................................................................4
Installation...............................................................................................5
North American Emissions Compliance..............................................................................6
Detailed Procedures ...........................................................................................7
Mounting Instructions........................................................................................................ 7
Assembling the Integrated MUI......................................................................................... 8
Connection Details.......................................................................................................... 10
Connection Details for I/O Expansion (XT-XP Modules) on Local Extension Bus..........13
Connection Details for the N2 Open Card ...................................................................... 14
Connection Details for the LON Card ............................................................................. 17
Connection Details for the Remote User Interface ......................................................... 19
Connection Details for the Programming Key................................................................. 22
Inputs and Outputs...............................................................................26
Inputs and Outputs...............................................................................26
Introduction.......................................................................................................26
Key Concepts....................................................................................................27
Detailed Procedures .........................................................................................28
Isolation Diagram............................................................................................................ 28
FX15 I/Os Powered at 24 VAC.........................................................................................29
Analog Inputs..................................................................................................................30
Digital Inputs................................................................................................................... 36
Analog Outputs............................................................................................................... 37
Digital Outputs ................................................................................................................ 39
Extension Modules ......................................................................................................... 42
Troubleshooting................................................................................................44
Reading 9999 or Invalid from the Analog Inputs............................................................. 44
© 2005 Johnson Controls, Inc. 1 Code Number LIT-12011107
www.johnsoncontrols.com
Page 2
FX15 Controller Technical Bulletin
2
Can Not Properly Read Current Sensors........................................................................ 44
Operation...............................................................................................45
Introduction.......................................................................................................45
Key Concepts....................................................................................................46
Software Programming and Application Configuration................................................... 46
Alarm and Event Management ....................................................................................... 46
Time Scheduling............................................................................................................. 46
User Interfaces ............................................................................................................... 46
Security...........................................................................................................................47
Supervisory Option ......................................................................................................... 47
Application Upload/Download......................................................................................... 47
User Interface ................................................................................................................. 48
Security...........................................................................................................................50
Specifications and Technical Data ...................................................... 51
Ordering Codes.................................................................................................51
Technical Specifications..................................................................................54
I/O Technical Details....................................................................................................... 54
N2 Open Card................................................................................................................. 56
LON Connection ............................................................................................................. 56
Programming Key........................................................................................................... 57
FX15 ............................................................................................................................... 57
FX15 Extended Range ................................................................................................... 58
Page 3
FX15 Controller Technical Bulletin
Introduction to FX15
3
Figure 1: FX15 Classic
The FX15 is a high performance field controller of the Facility Explorer system, specifically designed for commercial Heating, Ventilating, Air Conditioning, and Refrigeration (HVACR) applications such as chillers and rooftops, indoor packaged air conditioning units, air handling units, and close control units.
The controller has 27 physical inputs and outputs and supports a wide range of temperature sensors and actuating devices. Additional physical inputs and outputs may be achieved by adding the XT/XP expansion modules on the local Extension bus.
The FX15 controller is fully programmable or configurable, using the FX Tools Pro software package, for a wide range of commercial environmental control applications.
The FX15 controller is also available with a serial communication card for integration into a Building Automation System with a LONWORKS® or N2 Open bus network.
For stand-alone applications an on-board, real-time clock circuit is also included to support the start-stop scheduling of equipment and real-time based control sequences.
The FX15 can be integrated, as a slave device, in a distributed control application managed by a master controller (FX16 Master Controller or Master Display).
Optional accessories make the FX15 controller the state of the art solution for the HVACR market:
• N2 Open, plug-in communication card
• LON, plug-in communication card
• user interface: Medium User Interface (MUI) and Large User
Interface (LUI)
Page 4
FX15 Controller Technical Bulletin
4
Key Concepts
FX15
Features
• fully programmable using FX Tools package
• interchangeable RS-485 - N2 Open or LON FTT10 communication
cards for supervisory system
• DIN rail mounting
• female connector option: screw or spring clamp connectors
• Input/Output (I/O) expansion modules
• optional user interfaces: integrated, local, or remote
• events displayed on user interface (up to 12 events)
• easy commissioning via proprietary commissioning tool
• Programming Key for easy application uploading and downloading
Page 5
FX15 Controller Technical Bulletin
Installation
This chapter takes you through the process of installing an FX15.
5
75 (2.95)
179 (7.05 )
44 (1.73)
215 (8.46)
122 (4.8)
142 (5.59)
BB
Figure 2: Mounting Dimensions for FX15 (Shown with Integral User
Interface and Screw Connectors)
180.5 (7.11)
66 (2.6)
49 (1.93)
35 (1.38)
46.5 (1.83)
Panel cut-out
Figure 3: Panel Cut-Out Dimensions for User Interfaces
Two different types of terminal connectors are available: spring clamp or screw connectors. The screw connectors are included, while the spring clamp connectors must be ordered separately. For details, see Ordering Codes.
IMPORTANT: For installation with Clas s 2 inputs and outputs only, no special mounting precautions are generally necessary. For use with one or more line voltage outputs (above 30 V), installation as part of a UL 508A industrial control panel may be required by the local building or electrical authority. These controllers are presently UL Recognized as Temperature Indicating and Regulating Equipment in accordance with UL 873. UL Listing as Open Energy Management Equipment per UL 916 is pending.
Page 6
FX15 Controller Technical Bulletin
6
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy, and if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Page 7
FX15 Controller Technical Bulletin
Detailed Procedures
Follow these instructions to properly install and connect the FX15.
!
WARNING: Risk of Electric Shock. Disconnect power supply before making electrical connections. Contact with components carrying hazardous voltage can cause electric shock and may result in injury or death.
Mounting Instructions
To mount an FX15:
1. Snap the controller onto the 35 mm (1.38 in.) rail for DIN rail
mounting. To release the controller, insert a screwdriver in Slots B and lift the retaining clip. Since the retaining clip is spring-loaded, you can also remove the controller without a screwdriver by carefully pushing the controller up against the clip and then tilting the top forward to release the top lug from the DIN rail.
2. Make wiring terminations with detachable connectors, which accept
1 x 1.5 mm2 (0.002 in.2)/14 AWG cable. There are two types available: screw and cage clamp connectors. For details, see Ordering Codes.
7
Terminations of the Supervisor Link, Expansion Bus, and Remote Display are made via the connectors provided with the controller.
3. Verify that the wiring has been correctly installed and that voltage
levels are appropriate for the various input signals according to the application.
4. Set the jumpers and address switches of the controller as required.
For more information, see Jumper Details.
Page 8
FX15 Controller Technical Bulletin
8
Assembling the Integrated MUI
To assemble the integrated MUI:
1. Remove the controller front cover.
2. Hook the display to the top FX15 cover.
Figure 4: Open the Controller
Figure 5: Display Installation
3. Push down until it locks.
PUSH
Figure 6: Display Locking
Page 9
FX15 Controller Technical Bulletin
4. Open the controller.
Figure 7: Open the Controller
5. Insert the flat in the specific holes.
!
9
NO
Figure 8 : Flat Cable Inserting
6. Close the controller and secure it with the two screws.
Page 10
FX15 Controller Technical Bulletin
10
Connection Details
LP-FX15D2x and LP-FX15D7x Wiring Diagram
Figure 9: Connection Details for the FX15 (9 Relays)
Page 11
FX15 Controller Technical Bulletin
LP-FX15D1x and LP-FX15D6x Wiring Diagram
11
Figure 10: Connection Details for the FX15 (5 Triacs+4 Relays)
Consider the following information when you work with the connections details for the FX15:
• All commons are electrically dependent.
• Analog outputs are opto-isolated and are externally powered at 24
VAC. In order to maintain the opto-isolation, a separate power supply (3 VA) must be used only for the analog outputs.
• Digital inputs are opto-isolated and are externally powered at 24
VAC. In order to maintain the opto-isolation, a separate power supply (3 VA) must be used only for the digital inputs.
Page 12
FX15 Controller Technical Bulletin
a
b
d
e
12
Jumper Details
b
a
AI1 AI2
AI3
AI4 AI5
AI6
1 2 3
e
Figure 11: Jumper Connections
Table 1: Jumper Connections
c
Analog Input (AI) 0-20/4-20 mA Resistive, 0-10 V or Ratiometric
AI1-AI6 Jumpers Closed Jumpers Open
Sensors Power Supply AVPS +5 V EXT VDC+16 V
Terminal Number 13 Pins closed between 1
Battery Type CR2032, average life time: 3 years, dispose OFF
Pin strip closed: battery backup enabled Pin strip open: battery excluded (to preserve charge)
Jumper be kept in storage without power for an extended period of time. The jumper must be set to ON before the controllers is installed and powered up; otherwise back-up RAM and RTC will
not be enabled. Plug-in connector for optional cards insertion
is set to ON at the factory and should only be set to OFF if the controllers are to
d
d
and 2
c
Battery
(Default configuration)
Pins closed between 2 and 3 (Default configuration)
Page 13
FX15 Controller Technical Bulletin
Connection Details for I/O Expansion (XT-XP Modules) on Local Extension Bus
13
Figure 12: Connection Details for the XT/XP Modules
Consider the following information when you work with the connections details for the XT/XP Modules:
• maximum XT modules: 4 XT91D00s
• maximum bus length: 1.2 m (4.0 ft)
• Install a repeater (for example, RP-9100-810x) to regenerate the
RS-485 signal in case more than 31 N2 devices have to be connected on the same N2 bus trunk and/or the N2 bus trunk length is more than 1,200 m (4,000 ft).
• Install 220 ohm end-of-line resistors at each end of the XT-Bus line
when the bus length is greater than 100 m (330 ft). When the bus length is less than 100 m (330 ft), insert only one 220 ohm resistor at the FX15 end only.
Page 14
FX15 Controller Technical Bulletin
Selectio
14
Connection Details for the N2 Open Card
The FX15 comes either with the N2 Open Card preassembled or the card can be assembled at a later time in the field. For details, see Ordering Codes.
The N2 Open plug-in serial card allows the FX15 to be connected to an N2 Open serial network through the RS-485 standard.
LED
Address
n
Figure 13: N2 Open Plug-in Communication Card
Figure 14: N2 Open Card Connection
Assembling the N2 Communication Card
To assemble the N2 communication card:
1. Power off the controller (hot plug-in not allowed).
2. Open the controller. See Figure 15.
Page 15
FX15 Controller Technical Bulletin
Figure 15: Open the Controller
3. Insert the card. See Figure 16.
15
Align the pins as shown in figure.
Figure 16: Insertion of the N2 Open Card
4. Set the address dip-switches.
5. Replace the lid and close it.
IMPORTANT: The Complementary Metal Oxide Semiconductor (CMOS) integrated circuit in the controller and on the communication card are sensitive to static current discharges. Take suitable precautions.
Page 16
FX15 Controller Technical Bulletin
16
Address Selection
Through the dip-switches (see Figure 13), select the serial address of the controller in the N2 Open network. The address selection is done in binary mode.
Example.:• 1st ON, all others open address = 20 + 01 + … = 1
• 1st ON, 4th ON, all others open address = 20 + 01 + 02 + 23 = 9
The address zero is not allowed. The factory default address configuration is 1.
IMPORTANT: Cycle the controller power in order for new serial address to become active.
Network Layout
Refer to the N2 Communication Bus Technical Bulletin (LIT-636018).
Page 17
FX15 Controller Technical Bulletin
Connection Details for the LON Card
The FX15 comes either with the LON card preassembled or communication-less and the card can be optionally assembled later in the field. For details, see Ordering Codes.
The LON plug-in serial card allows the FX15 to be connected to a
ONWORKS network.
L
Service PIN Reachable from the controller top lid
17
Figure 17: LON Plug-in Communication Card
Figure 18: LON Card Connection
Assembling the LON Communication Card
To assemble the LON communications card:
1. Power off the controller (hot plug-in not allowed).
2. Open the controller. See
Figure 19.
Page 18
FX15 Controller Technical Bulletin
18
3. Insert the card. See Figure 20.
Figure 19: Open the Controller
Align the pins as shown in figure.
Figure 20: Insertion of the LON Card
4. Replace the lid and close it.
IMPORTANT: The CMOS integrated circuit in the controller and on the communication card are sensitive to static current discharges. Take suitable precautions.
Refer to the LONWORKS FTT-10A Free Topology User’s Guide (078-0156-01F) for technical guidelines associated with free topology restrictions. Refer to the Junction Box and Wiring Guidelines for Twisted Pair LONWORKS Networks (005-0023-01) for more detailed information on wiring specification. These documents are available on the Echelon® Web site (www.echelon.com).
Page 19
FX15 Controller Technical Bulletin
Connection Details for the Remote User Interface
The FX15 can support up to two Medium User Interfaces (MUIs) at the same time.
The MUI is available in 2 models: panel mount (up to 3 m [9.8 ft]) and wall mount (up to 1 km [0.6 mi]). The FX15 can support 1 panel mount MUI plus 1 wall mount MUI or 2 wall mount MUIs (see Figure 22).
For the panel mount connection use the pre-cabled connection kit (LP-KIT007-000C), 3 m (9.8 ft) long, with a phone jack on the MUI side and a preassembled screw connector on the FX15 side.
19
Figure 21 and
Figure 21: Installation for One Local and One Remote MUI
Page 20
FX15 Controller Technical Bulletin
20
MUI-008_10 2002
FX15
Max 1 Km, total length
MUI 2MUI 1
1
1
5
2
6
3
7
4
8
5
2
6
3
7
4
8
FX15 "Universal"
LL+ LL- +9V Com
FX15 "Classic"
Com +16V LL- LL+
To Power Supply 9 ÷ 48 VDC 12 ÷ 24 VAC
(not used)
To FX15
To MUI 2
V Com (-)
V /~
RT Com RT-
(not used)
RT+
Figure 22: Installation for Two Wall Mount MUIs
To Power Supply 9 ÷ 48 VDC 12 ÷ 24 VAC
To MUI 1
(+)
Page 21
FX15 Controller Technical Bulletin
Assigning the Medium User Interface’s N2 Address in Case of Multiple Connections
At power up, the MUI automatically has a default N2 address equal to 1.
If you connect multiple MUIs, the second MUI N2 Address must be changed to avoid communication conflicts.
When the second MUI displays Device Offline, as shown in Figure 23, press the
and
keys simultaneously to switch the N2 Address
to 2. See Figure 24.
Figure 23: MUI N2 Address Selection
21
Figure 24: MUI N2 Address Changed
Page 22
FX15 Controller Technical Bulletin
2
22
Connection Details for the Programming Key
The Programming Key is used to upload an application from a personal computer or from a preprogrammed FX15. The application is then downloaded to other FX15 controllers.
Upload Download
Download / Upload
LED
LEDs
Download / Upload failed
<1 sec
to select
>3 sec
to confirm
>15 sec
for MEMORY ERASE
Figure 25: Programming Key
LP-KIT100-001_09 200
Page 23
FX15 Controller Technical Bulletin
Connecting the Programming Key to an FX15
To connect the Programming Key to an FX15:
1. Power off the controller.
2. Detached any connect user interfaces from the Remote Display Port
JP2.
3. Plug the Programming Key into the Display Port (see Figure 26).
24 VAC230 VAC
Remote Display Port
(JP2)
FX16-018_09 2003
Figure 26: Programming Key Connection to FX15
23
E
d
S
e
l
A
i
R
a
f
d a o
l
n w o D
d a o
l p U
E
d
d
Y
a
a
o
R
o
l
l
p
O
p
m
t
r
U
M
i
U
c
f
/
/
E
e
n
l
d
d
M
o
e
a
c
a
s
r
o
l
o
o
o
l
o
f
n
t
t
n
w
c
w
o
e
o
c
c
s
D
e
e
D
s
s
5 1
3
1
>
>
<
D E L
s D E L
4. Power the controller and download/upload the application.
Connecting the Programming Key to a Personal Commuter
Figure 27: Programming Key Connection to PC
Page 24
FX15 Controller Technical Bulletin
24
To connect the Programming Key to a personal computer:
1. Connect the terminal adapter (included in the programming key kit)
to the RS-232/485 converter connected to the personal computer.
Table 2: Terminal Adapters
Adapter RS-232/485 Converter
1 2 3 4
Com Not used RT­RT+
2. Power the key via AC/DC adapter.
3. Launch FX Loader.
4. Upload the application.
Performing a Programming Key Memory Erase
If the key is already loaded with an application and there is the necessity to substitute it with a different application, the user has to do a memory erase.
The memory erase is automatically performed by FX Loader. However, in the case where the application is loaded from a personal computer or where the application has to be loaded from another FX15, the user has to manually perform the memory erase.
To perform a Programming Key memory erase:
1. Power up the key, either by hot-plugging it to an FX15 (already on)
or with an AC/DC adapter.
2. Initiate the memory erase by pressing the Programming Key button
for 15 seconds. During the erase, the green Light-Emitting Diode (LED) slowly
blinks. Then the green and the yellow LED blinks, 2 times alternatively, and finally the green LED remains steady on. The flash erases.
If the two LEDs blink simultaneously, it means that the erase process has failed. Retry. When the memory is completely erased, the LEDs stop blinking. The key is now ready for a new upload. The memory erase is also necessary if the previous upload from the FX15 goes wrong (communication has been interrupted).
Page 25
FX15 Controller Technical Bulletin
Error Codes
The error codes can only be seen if the FX15 has been mounted with an integrated MUI display (LP-DIS60U10-C).
Table 3: Error Codes
Error Code
51
52
52
Meaning Possible Cause Action
Private ID mismatch
Memory full Attempt to upload an
Memory empty Attempt to download an
Controller and application in the key have different protection IDs
application to a key already loaded
application from an empty key
Save the application with the proper ID (if available) and retry the download.
Proceed with the memory erase and retry uploading.
Upload the key with the target application.
25
Page 26
FX15 Controller Technical Bulletin
26
Inputs and Outputs
Introduction
The FX15 features the following I/O Channels:
• six high resolution Analog Inputs (13 bit, A/D Converter)
• eight opto-isolated Digital Inputs from potential free contacts, each
with transition counter
• nine Digital Outputs (4 Relays and 5 optionally Relays or triacs)
• four opto-isolated Analog Outputs
Figure 28: FX15 I/Os
Page 27
FX15 Controller Technical Bulletin
Key Concepts
Analog Inputs
The FX15 accepts six high resolution, universal analog inputs; each of them can be configured as active or passive by application software and jumper configurations.
Digital Inputs
The FX15 accepts eight opt-isolated digital inputs from voltage free contacts.
Analog Outputs
The FX15 provides up to four 0-10 VDC opto-isolated analog outputs.
Digital Outputs
The FX15 provides nine digital outputs, available in two hardware configurations with 9 Relays or 4 Relays and 5 triacs.
27
Page 28
FX15 Controller Technical Bulletin
28
Detailed Procedures
Isolation Diagram
Figure 29: Insulation Diagram
(*) Opto-isolated (maximum 500 V) if an additional separated power supply is used
(**) Not isolated (***) DC/DC converted with dielectric strength up to 1000 V
Page 29
FX15 Controller Technical Bulletin
A
FX15 I/Os powered at 24 VAC
29
15 V
Figure 30: Powering FX15 I/Os
In order to maintain the insulation between the FX15 power supply and the I/Os, run the power supply cable respecting the polarity as shown in Figure 30, adding an External Protection fuse (2 A) to avoid mis-wiring.
IMPORTANT: Not respecting the power supply polarity will result in a short circuit causing the blowing of the external fuse.
Page 30
FX15 Controller Technical Bulletin
AI4AI5A
30
Analog Inputs
The six high-resolution analog inputs can be configured to accept a wide range of voltage, current and resistive input signals.
See I/O Technical Details for the complete FX15 I/O table. A dedicated jumper is placed on board for each analog input. This
jumper should be installed in its closed position if the connected sensor provides a current signal (0-20/4-20 mA). This jumper should be installed in its open position if the connected sensor provides a resistive, ratiometric, or voltage (0-2/0-10 V) input signal.
AGND
AI1 AI2
a
FX16-025_1 0 2003
AI1
Figure 31: Analog Input Jumpers
AI2
AGND
EXT V
AI3
AGND
AI3
AI4
AGND
EXT V
AI5
AGND
AI6
AGND
I6
The active sensor (voltage or current) inputs are ranged using programmable range parameters within the application software. These parameters, HighRange and LowRange, define the equivalent values for reading at High (10 V, 20 mA) and Low (0 V, 4 mA, 0 mA) signal input. Voltage and current inputs from differential pressure transducers can be linearized by a square root function (SQRT), which operates over the complete range of the input.
The passive sensors (resistance) have a preprogrammed linearization curves within the application software. For these sensors, the measurement range is fixed. The user can set the reliability range via software.
The read signal is converted by the FX15 according to the related Analog Input object setup, available setup are:
• Linear 0-10 V
• SQRT 0-10 V
• Linear 0-10 V, 20% suppression (2-10 V)
• Linear 0-2 V
• SQRT 0-2 V
• Linear 0-2 V, 20% suppression (0.4-2 V)
• Linear 0-20 mA
• SQRT 0-20 mA
• Linear 0-20 mA, 20% suppression (0.4-2 mA)
• Resistance 2k ohm
Page 31
FX15 Controller Technical Bulletin
• A99
• NTC 2k2 ohm
• Ni1000 JC
• Ni1000 JC Extended
• Ni1000 Landis and Gyr
• Ni1000 DIN
• Pt1000
• Ratiometric
The measurement unit is also configurable to enable the controller to propagate via network the measured value according to the appropriate scale unit. Available configurable units are:
• Temperature
• Percentage
• Air Pressure
• Liquid Pressure
31
• Flow
• Concentration
• Ampere
• Voltage
A configurable filter constant in seconds is performed by the FX15 on its Analog Inputs for the reduction of signal instability. An additional Anti-Spike filter can be configured to limit the rate of change of the input values to the value indicated by this attribute.
The FX15 provides a jumper configurable (Terminal 13) +5V AVPS (Analog Voltage Power Supply) or a +16V External VDC, supply for active analog input sensors (See
Jumper Details at page 12)
The EXT VDC can supply up to 80 mA for a maximum of four 0/4-20 mA active sensors. The AVPS can supply up to 10 mA for ratiometric sensors.
Connecting Active 0-10 V Sensors
The FX15 can accept all the active temperature, pressure, flow and humidity sensors providing 0-10 VDC signals.
Figure 32 shows the connection between an FX15 and an HT-9001 probe.
Page 32
FX15 Controller Technical Bulletin
32
Active Humidity and Temperature Sensor
HT-9001-UDx
CAB -Bt
1 2 3
AI1
AGND
4 5
AGND
EXT V
FX15
FX16
-
AI2
6 7
AGND
8
AI3
EXT V
Figure 32: Active 0-10 V Probe, Connection Diagram
The inputs must be pre-configured in order to accept 0-10 V signals by the application software resident in the FX15. The AI Jumpers must be opened (factory default setting) in order to accept voltage inputs.
Table 4: Active 0-10 V Sensors
FX15 Terminals HT-9001 Terminals Description
AGND (1) EXT V (3) AI1 (2) AI2 (5)
A Common Reference C Sensor Power Supply 16 V, 80mA B Humidity Output 0-10 V Bt Temperature Output 0-10 V
Note: The numbers between the brackets are the FX15 terminal numbers.
Page 33
FX15 Controller Technical Bulletin
Connecting Passive Resistive Sensors
The FX15 analog inputs accept linear resistive signals as the Resistive 2kΩ. The Analog Input software can also linearize signals provided by
the most common sensors as Ni1000, A99, Pt1000, and NTC 2k2. The inputs must be preconfigured in order to accept A99 resistive
signals by the application software resident in the FX15. The AI Jumpers must be opened in order to accept resistance input (Factory default setting). Figure 33 shows an A99 wiring diagram. The resistive sensors have to be connected in the same way.
A99BB
Resistive Temperature Sensor
33
1 2 3
AGND
Figure 33: A99 Resistive Sensor Connection Diagram
IMPORTANT: The two resistive probe leads are the same, in that they have
no polarity; therefore, it is not necessary to respect any specific order when connecting to the terminal block.
AI1
4 5
AGND
EXT V
FX16
FX15
AI2
6 7
AGND
8
AI3
EXT V
Page 34
FX15 Controller Technical Bulletin
34
Connecting Active Current Sensors
The FX15 analog inputs can accept a maximum of four active current sensors, powered by the FX15 itself, in the range 0-20 mA or 4-20 mA. The AI has to be configured via software (and hardware jumpers) in order to accept current signals. If a 4-20 mA sensor has to be connected, the specific hardware jumpers has to be closed (see Figure 31) and the application can be configured through the FX Builder, setting 0-20 mA, 20% suppression.
The FX15 can be connected to P299xAx series of Johnson Controls® pressure sensors which generate a 4-20 mA signal.
P299xAx
Active Pressure Sensor
1 2 3
AGND
AI1
4 5
AGND
EXT V
AI2
6 7
AGND
8
AI3
EXT V
FX16
Figure 34: Pressure Sensor Connection Diagram
Table 5: Active Current Sensors
FX15 Terminals P299xAx Cable Description
AGND (1) EXT V (3) AI1 (2)
Green Common Reference Brown Sensor Power Supply 16 V, 80 mA White Pressure Output 4-20 mA
Note: The numbers between the brackets are the FX15 terminal numbers.
Page 35
FX15 Controller Technical Bulletin
A
Connecting Active Sensors Powered by 24 VAC
The FX15 can accept active temperature, pressure, flow, and humidity sensors providing 0-10 V or current signals powered by 24 VAC.
A second transformer (24 VAC/24 VAC, 3 VA maximum) powering only the Analog Input is required in order to maintain the insulation from the microprocessor.
35
Active Sensor
123
AGND
AI1
EXT V
45
AGND
67
AI2
8
AI3
AGND
FX16
FX15
powered at 24 V
32 33 34 35
EXT V
Earth
3 VA max
24 Vac
V ~ Com
V ~ Hot 24V
24V
939291
24 Vac
220Vac24 Vac
15 V
Figure 35: Active Sensor powered at 24 VAC Connection Diagram
Table 6: Active Sensors Powered by 24 VAC
FX15 Terminals Sensor Cable Description
AGND (1) AI1 (2)
Green Common Reference White Signal Output
Note: The numbers between the brackets are the FX15 terminal numbers.
IMPORTANT: Not powering the Analog Input with a second transformer or powering the AI with the power supply on another FX controller, will result in a short circuit causing the failure of the FX15.
Page 36
FX15 Controller Technical Bulletin
A
36
Digital Inputs
The FX15 features eight opto-isolated digital inputs from potential free contacts. A digital input is active depending on its polarity setting. The default setting is Direct, which means that it is active (true) when closed.
I/O Technical Details for the complete FX15 I/O table.
See
Digital Inputs Powered by 24 VAC
The eight FX15 Digital Inputs must be 24V powered, through terminals 34 and 35, both AC or DC voltage can be used, if DC is used then the power supply of the DIs will have to be necessarily independent from the controller power supply, being the FX15 compatible with VAC power only. The digital inputs can use the same FX15 voltage supply or they can be separately powered, in order to maintain the microprocessor opto-isolation from the controller voltage supply.
220Vac24 Vac
3 VA max
3221
DICom
DI8
DI V ~ Com
DI V ~ Hot
24V
V ~ Hot
V ~ Com
Earth
939291
15 V
220Vac24 Vac
DI1
242322 33 34 35
DI2
DICom
DICom
FX16
FX15
Figure 36: Powering Digital Inputs Maintaining Opto-Isolation Table 7: Digital Inputs Powered by 24 VAC
FX15 Terminals Description
DI V ~ Hot (35) DI V ~ Com (34) DI8 (33) DICom (32)
24 VAC, Digital Inputs Power Supply Digital Inputs Power Supply Common Digital Input 8, Voltage-Free contact Common Reference, Voltage-Free contact
Note: The numbers between the brackets are the FX15 terminal numbers.
Page 37
FX15 Controller Technical Bulletin
Using Analog Inputs as Digital Inputs
In case the user needs more than the 8 digital inputs available, the FX15 allows you to use an analog input as digital input.
37
Analog Outputs
FX15
Figure 37: Digital Input Connection Diagram
The Analog Input needs to be properly configured in FX Tools to read the digital input.
The FX15 provides up to four, 0-10 VDC, 2A maximum, opto-isolated analog outputs. The Analog Output objects provide the interface between the four hardware Analog Output channels and the control application. See I/O Technical Details at page 54 for the complete FX15 I/O table.
The analog outputs can be configured for direct or reverse acting in the application software.
The output signal can be limited by high limit (MaxOutput) and low limit (MinOutput) values.
Powering and Connecting the Analog Outputs
The analog outputs can be separately powered, through Terminals 79 and 80, in order to ensure microprocessor isolation from the controller power supply (see Figure 39).
The FX15 analog outputs are commonly used to drive proportional devices and can be connected to all the Johnson Controls Proportional Valve Actuators.
The following figure represents the connection diagram.
Page 38
FX15 Controller Technical Bulletin
38
AO Com
AO1
AO Com
FX16
AO2
24V
AO Com
AO3
AO Com
AO4
AO V ~ Com
AO V ~ Hot
Earth
V ~ Com
V ~ Hot
71
75
747372
787776
8079
91
9392
15 VA
220Vac24 Vac
Figure 38: Connecting the Analog Output without Opto-isol ation
IMPORTANT: Make sure to respect connection polarities.
FX15 Terminals Description
AO Com (77) AO4 (78) AO V~ Com (79) AO V~ Hot (80)
Common Reference Analog Output 0-10 V Common Reference Power Supply 24 VAC
Note: The numbers between the brackets are the FX15 terminal numbers.
The insulation from the microprocessor is achieved if a different 24 VAC power supply from the one used to power the controller is used to power the analog outputs (through Terminals 79 and 80).
Page 39
FX15 Controller Technical Bulletin
A
FX16
24V
AO Com
AO Com
AO1
AO2
AO Com
AO3
AO Com
AO4
AO V ~ Com
AO V ~ Hot
V ~ Com
Earth
V ~ Hot
39
71
75
747372
787776
8079
91
9392
3 V
220Vac24 Vac
220Vac24 Vac
15 VA
Figure 39: Separately Powering Analog Outputs
FX15 Terminals Description
AO Com (77) AO4 (78) AO V~ Com (79) AO V~ Hot (80) V~ Hot (93) V~ Com (92)
Common Reference Analog Output 0-10 V AO Common Reference AO Power Supply 24 VAC FX15 Power Supply 24 V FX15 Common Reference
Note: The numbers between the brackets are the FX15 terminal numbers.
Digital Outputs
The FX15 features 9 digital outputs, available in two hardware configurations: all 9 Relays or 4 Relays and 5 triacs.
The Digital Outputs can be configured for direct acting or reverse acting in the application software.
!
WARNING: Risk of Electric Shock and Property Damage.
Disconnect each of multiple power supplies before making electrical connections. More than one disconnect may be required to completely de-energize equipment. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
Connecting the Relays
The FX15 features up to nine Digital Outputs with electromechanical relays. To simplify assembly, the common terminals of some relays have been grouped together. The relays are divided into six groups, according to the distance of insulation.
Page 40
FX15 Controller Technical Bulletin
40
41 51 55 6242 52 56 6343 53 5754 6144 45 46 47 48
Group #6Group #5Group #4Group #3Group #2Group #1
Max
8(3)250V~
TB6
FAI L no
FAIL nc
DO1 no
DO1 Com
FX16-026_11 2003
TB3
DO2 Com
DO2 no
TB5TB4
DO4 no
DO3 no
DO3 Com
DO5 no
DO4/5 Com
DO7 no
DO8 no
DO6 no
DO6/7/8 Com
Figure 40: Relay Groups
Inside each group, the relays have just single isolation and thus must be connected to the same voltage supply. Between the groups, there is a double isolation and thus the groups can be connected to different voltage supplies.
Figure 41 displays a typical application of the relay outputs as connection example.
DO6 no
54
DO7 no
DO 6/7/8 Com
DO8 no
575655
FAIL Com
Note: Relays DO6-DO8 are not hardware interlocked and incidental energization of more than one relay at the same time might lead to fan motor damaging.
N
Speed2
Speed1
Fan
Speed3
~ 230Vac
L
Figure 41: Connecting a Three-Speed Fan Motor
Page 41
FX15 Controller Technical Bulletin
Connecting the Triacs
The FX15 triac (0.5 A, 24 VAC) digital outputs are commonly used to operate in PAT and DAT modes.
54 575655535251
41
DO3 no
DO4 no
DO6 no
DO 4/5 Com
DO7 no
DO8 no
DO 6/7/8 Com
Figure 42: Triac Groups
In particular the Digital Outputs PAT mode can be used through the triac outputs to drive Incremental Valve Actuators.
Figure 43 displays an example of a triac connection.
FX15 Terminals Description
DO4 (51) DO5 (52) V ~ Hot (93) DO 4/5 Com (53)
Note: Between round brackets are reported the FX15 terminal numbers.
Figure 43: Connecting an Incremental Actuator
24V ~ Down command 24V ~ Up command 24V ~ Hot Reference 24V ~ Common Reference
Page 42
FX15 Controller Technical Bulletin
42
Extension Modules
The input/output capacity of the FX15 may be extended by connecting up to four extension modules via the Extension Bus (XT-Bus, terminal J1).
An extension module if formed by an XT91D00 processor/communications module and one or more XP expansion modules. The expansion modules provide input/output capability for the extension modules. The following are available for the XT91D00 extension module:
• XP91D02: six analog inputs and two analog outputs
• XP91D03: eight digital outputs (triac)
• XP91D04: four digital inputs and four digital outputs (triac)
• XP91D05: eight digital inputs
• XP91D06: four digital outputs 230 VAC (relay) (EU only)
• XP91D07: four digital outputs 24 VAC (relay) (NA only)
Analog inputs to extension modules may be 0-10 V, 0-20 mA or passive RTD-Ni1000 (Johnson Controls characteristic only), Pt1000 or A99 sensors.
Analog inputs to the XPA-421-5 module only may additionally be RTD-Ni1000 (LandG and DIN), Pt100 and NI100 sensors or a 5 K ohm potentiometer.
Voltage and current inputs from differential pressure transducers can be linearized by a square root function.
Digital inputs to extension modules are potential-free contacts. The input is active (true) when the contact is closed.
Digital counters are available in extension modules, which do not have analog inputs or outputs. Digital counters are associated with digital inputs. The number of positive transitions of the physical digital input required to increment the counter can be programmed in the extension module.
Note: Counter values are saved in EEPROM by XT/XP only at the power down, in the particular situation of an application downloading to the FX15 the increments occurred from the last XT/XP power-up and the download are lost. The problem can be overcome if a power down of the XT/XP module of interest is executed right before proceeding with the program download.
Analog outputs in extension modules can be configured to provide 0-10 V, 0-20 mA or 4-20 mA signals. The output is ranged by low range and high range variables to provide a 0-100% signal to the extension module.
Page 43
FX15 Controller Technical Bulletin
X
X
X
X
X
Digital outputs in extension modules can only be configured as on/off or pulse type, and the physical output may be a triac or a relay contact. Pulse type outputs switch on for a configurable period (1 to 1275 ms) for each transition of the connected variable.
An XT91D00 can be combined with its expansion modules to provide the following configurations:
• 8 analog inputs/outputs
• 8 digital inputs/outputs, with digital counters associated with the
digital inputs
• 8 analog inputs/outputs and eight digital inputs/outputs
• 16 digital inputs/outputs, with digital counters associated with the
digital inputs within the first eight input/output points
Extension Bus (J1)
43
FX15 "Classic"
FX15-C-007_ 10 2002
XT
XT
XP-9103XP-9104
XT
T
P-9102
P-9103
P-9103
P-9107
Figure 44: Example of Maximum Configuration
XP-9103
XP-9103
XP-9107
Page 44
FX15 Controller Technical Bulletin
44
Troubleshooting
Reading 9999 or Invalid from the Analog Inputs
• Error/Condition: The Analog Input object retrieves an Invalid
value through network variables or the User Interface Unit shows 9999 or Invalid customized tag;
• Problem: Happens in the case the signal applied to the Analog
Input channel does not match with the one configured via software on the Analog Input Object. The read signal is outside the configured reliability range. The problem can be due to the Jumper configuration of the Analog Input channel which can not be set according to the signal provided by the sensor;
• Solution: In case the signal does not match with the configured,
change the Analog Input Object configuration via FX Builder. If the software is properly configured but the problem still happens, check the analog inputs jumpers are properly set in order to accept the sensor signal and verify the probe functioning and wirings.
Can Not Properly Read Current Sensors
• Error/Condition: Connecting an active, current sensor to an
Analog Input channel, the AI Object retrieves an Invalid value;
• Problem: In the case the AI Object is properly configured and the
probe is correctly wired and functioning, the problems may be due to a wrong AI Jumper configuration;
• Solution: A dedicated Jumper is placed on board for each Analog
Input Channel. This Jumper is used in its close configuration in the case the connected sensor provides a Current signal (0-20/4-20 mA). Its open configuration has t o b e used for R e s i stiv e , R a tio- M e t r ic or Volt a g e ( 0 - 2 / 0 - 1 0 V ) input signals.
Page 45
FX15 Controller Technical Bulletin
Operation
Introduction
The FX15 is a high performance field controller and it has been designed to respond to a wide range of applications including dual compressor chillers and rooftops, close control units, packaged air handling units, unit vents, and water source heat pumps.
The FX15 has 27 physical input/output points on board and can be further expanded by connecting the XT91D00/XP91Dxx Series expansion modules.
Parameters in the control application can be displayed and modified from the optional user interface.
45
Page 46
FX15 Controller Technical Bulletin
46
Key Concepts
Software Programming and Application Configuration
The FX15 provides configurable control algorithm, memory and connectivity services, real-time functions, and I/O expansion through its customizable, objects and services oriented, architecture. The device configurations can be created and downloaded into the target controllers via the FX Tools Pro software package.
The tools available in the package are:
• FX Builder: The programming and configuration of the Facility
Explorer controllers is done using the menus, navigation trees, and graphic screens of the FX Builder tool. The configuration includes the definition of the controllers to be connected, the physical inputs and outputs and data points to be monitored and the format of the display screen of the controller.
• FX Builder Express: A simplified version of the FX Builder, called
FX Builder Express, is also available to configure a library of standard applications specifically designed for Facility Explorer controllers. The configuration is done using the specific graphic user interfaces of the FX Builder Express.
• FX CommPro N2/LON: Parameter configuration, machine tuning,
default parameters saving for successive configurations are all things possible with the FX CommPro tool with 2 protocols supported: N2 Open, LONWORKS.
Alarm and Event Management
The FX15 manages and records events or alarms that are associated with data points or variables in the control application.
The table of active events and the event history log may be viewed on the user interfaces.
Time Scheduling
This feature allows introducing functions based on a weekly time schedule. The clock is battery backed up with an average duration time of 2 years.
User Interfaces
The FX15 can have different user interface options (integrated, local, or remote) proving the possibility to display and edit all the data point and information of the running a pplicatio n. The u ser interfac e is fully configurable at design time.
Page 47
FX15 Controller Technical Bulletin
Security
The FX Tools and the FX controllers come with an embedded security features based on the use of two IDs: the Family ID and the Customer ID. This security feature prevents tampering with the applications and provides source code protection.
Supervisory Option
The FX15 can be integrated into a supervisory building automation system for continuous monitoring of the control system. The FX15 supports two methods of integration:
• N2 Open Integration
• LONWORKS Integration
Application Upload/Download
The FX15 is a fully programmable controller and the application can be downloaded to the controller with the FX Tools or uploaded/downloaded via Programming Key.
47
Page 48
FX15 Controller Technical Bulletin
48
User Interface
The FX15 can be connected to up to 2 remote user interfaces with the possibility to display/edit all the data point and information of the running application. The user interface application is fully configurable at design time. The user interface must be of the same type. The user interfaces are optional, which means that the controller can work also without any display plugged-in.
The configuration is integrated, local, for example: panel mount (up to 3 m [9.8 ft]) or remote, for example: wall mount (up to 1km [0.6 mi]):
• integrated: directly plugged on top of the controller
• local: up to 3 m (9.8 ft) from the controller, power supply and data
communication via the flat telephone cable included in the LP-KIT007-000C
• remote: up to 300 m (984 ft) from the controller.
The display must be independently powered; the data communication is done via a 3 pole shielded cable (not provided) connected to the Remote Display Connection of the FX15.
The FX15 can support 1 integrated user interface or 1 panel mount or wall mount user interface or 1 panel mount display + 1 wall mount user in or 2 wall mount ones. For the panel mount connection use the pre-cabled connection kit (LP-KIT007-000C), 3 m (9.8 ft) long, with a phone jack on the MUI side and a preassembled screw connector on the FX15 side.
The user interface models connectable to the FX15 are:
• LP-DIS65P10-0C: Large User Interface (LUI), panel, flush mount
or hand held, 4x20 backlit LCD, IP54, extended temperature range:
-20 to +50°C (68 to 122°F), standard JCI front-plate. The front-plate is fully customizable upon minimum order.
Figure 45 : Large User Interface (LUI)
Page 49
FX15 Controller Technical Bulletin
• LP-DIS60U10-C: Integrated Medium User Interface, Integrated,
4x20 backlit Lighting Control Data (LCD), IP54, extended temperature range: -20°C (68°F) to +50°C (122°F)
Figure 46 : Integrated Medium User Interface (MUI)
• LP-DIS60P10-0C/LP-DIS60P11-0C: Medium User Interface, 4x20
backlit LCD, IP54, extended temperature range: -20°C (68°F) to +50°C (122°F). Panel mount, non-isolated version, and wall mount isolated version
49
Figure 47 : Medium User Interface (MUI)
For more details about the connection possibilities, refer to the specific user interface technical bulletin.
Page 50
FX15 Controller Technical Bulletin
50
Security
The FX Tools Pro and the Facility Explorer controllers come with an embedded security feature based on the use of two IDs: the Family ID and the Customer ID.
Family ID
Family ID differentiates different hardware types and prevents the downloading of the wrong application to the wrong controller.
Table 8: Family ID
Facility Explorer Controller
FX05 Advanced
FX10 Standard FX10 Advanced FX15 FX15 Universal
FX Builder Code Family IDs
FX05P11-02 0218 FX05P11-12 0210 FX05P11-22 0211 FX05P12-02 0212 FX05P12-12 0214 FX05P12-22 0215 FX05P13-02 0213 FX05P13-12 0216 FX05P13-22 FX10B1x FX10B3x FX15D1x FX15D0x
0217 0301 0311 0402 0401
Customer ID
Customer ID protects a controller downloaded with a custom developed application and protects the application source code from editing by unauthorized users. Three Customer ID types are used:
• Public ID: applications that are saved with Public ID can be
downloaded and commissioned by any user with the Public ID enabled in FX Tools.
• Demo ID: applications that are saved with the Demo ID can only be
downloaded to demo controllers.
• Customer/Private Specific ID: Applications that are saved with a
specific customer/private ID will make those applications source files readable only by users who have the same ID enabled in FX Tools. Once a controller has been downloaded with a specific Customer ID, the controller will become customer specific and only allow downloading of application with the same customer specific ID.
Page 51
FX15 Controller Technical Bulletin
51
Specifications and Technical Data
Ordering Codes
Table 9: FX15 Controller Ordering Codes Description
LP-FX15D10-000C LP-FX15D11-000C
LP-FX15D12-000C
LP-FX15D60-000C
LP-FX15D61-000C
LP-FX15D62-000C
LP-FX15D20-000C LP-FX15D21-000C
LP-FX15D22-000C
LP-FX15D70-000C
LP-FX15D71-000C
LP-FX15D72-000C
FX15, 4 Relays + 5 triacs, without the application FX15, 4 Relays + 5 triacs, N2 Open card preassembled,
without the application FX15, 4 Relays + 5 triacs, L
without the application FX15, 4 Relays + 5 triacs, integrated MUI display, without the
application FX15, 4 Relays + 5 triacs, N2 Open card preassembled,
integrated MUI, without the application FX15, 4 Relays + 5 triacs, L
integrated MUI, without the application FX15, 9 Relays, without the application FX15, 9 Relays, N2 Open card preassembled, without the
application FX15, 9 Relays, L
application FX15, 9 Relays, integrated MUI display, without the
application FX15, 9 Relays, N2 Open card preassembled, integrated MUI,
without the application FX15, 9 Relays, L
MUI, without the application
ONWORKS card preassembled, without the
ONWORKS card preassembled, integrated
Table 10: FX15 Extended Range Controller Ordering Codes Description
LP-FX15X10-000C LP-FX15X11-000C
LP-FX15X12-000C LP-FX15X20-000C LP-FX15X21-000C
LP-FX15X22-000C
FX15, 4 Relays + 5 triacs, without the application FX15, 4 Relays + 5 triacs, N2 Open card preassembled,
without the application FX15, 4 Relays + 5 triacs, L
without the application FX15, 9 Relays, without the application FX15, 9 Relays, N2 Open card preassembled, without the
application FX15, 9 Relays, L
the application
ONWORKS card preassembled, without
ONWORKS card preassembled,
ONWORKS card preassembled,
ONWORKS card preassembled,
Table 11: Communication Card Ordering Codes Description
LP-NET151-010C LP-NET152-010C
N2 Open communication card
ONWORKS communication card. On-field commissioning
L
Page 52
FX15 Controller Technical Bulletin
52
Table 12: User Interface Displays Ordering Codes Description
LP-DIS65P10-0C
LP-DIS60P10-0C
LP-DIS60P11-0C LP-DIS60U10-C
Table 13: Accessories Ordering Codes Description
LP-KIT007-000C
LP-KIT015-000C LP-KIT015-001C LP-KIT100-000C DT-9100-8901
LP-KIT100-001C
Large User Interface V.2, (4x20 character) LCD backlit display (LUI with std JCI front plate)
Medium User Interface V.2, (4 x20 character) LCD backlit display, panel mount version
Medium User Interface V.2, (4 x20 character) LCD backlit display, wall mount isolated version
Integrated MUI, (4 x 20) LCD backlit display for FX15
Link cable for the connection of the FX15 to the MUI/LUI display -3m (19 ft)
Kit of female screw connectors Kit of female cage clamp connectors FX Programming Key Power Supply for Programming Key and LUI: 230 VAC/12
VDC Power Supply for Programming Key and LUI: 230 VAC/12
VDC
Table 14: Room Command Modules Available Only in Europe Ordering Codes Description
LP-TR23024-10VA LP-KIT006-000C LP-KIT006-001C LP-KIT006-002C
LP-KIT006-003C
Transformer for FX05, 10 VA Room Sensor module for FX05 +/- dial, occupancy button,
fan speed, service port Room Sensor module for FX05 12-28°C dial Room Sensor module for FX05 12-28°C dial, occupancy
button, service port Room Sensor module for FX05 +/- dial, occupancy button,
service port
Table 15: Room Command Modules Available Only in North America Ordering Codes Description
LP-KIT006-004C
LP-KIT006-005C
LP-KIT006-006C
LP-KIT006-007C
Room Sensor module for FX05, warm/cool adjustment dial, occupancy button, fan speed selector switch, service port, US mounting kit
Room Sensor module for FX05 warm/cool adjustment dial, occupancy button, US mounting kit
Room Sensor module for FX05 setpoint (54-82°F) adjustment dial, occupancy button, fan speed selector switch, service port, US mounting kit
Room Sensor module for FX05 setpoint (54-82°F) adjustment dial, occupancy button, service port, US mounting kit
Page 53
FX15 Controller Technical Bulletin
Table 16: Expansion Modules Ordering Codes Description
LP-XT91D00-000C LP-XP91D02-000C LP-XP91D03-000C LP-XP91D04-000C LP-XP91D05-000C LP-XP91D06-000C
LP-XP91D07-000C
Extension module Expansion board: 6 AI, 2 AO Expansion board: 8 DO (triacs) Expansion board: 4 DI, 4 DO (triacs) Expansion board: 8 DI Expansion board: 4 DO (relays) 230 VAC (Europe
only) Expansion board: 4 DO (relays) 24 VAC (North
America only)
Table 17: Demo Cases and Controllers Ordering Codes Description
DEMO-FX15-071 DEMO-FX15-072 DEMO-FX15-081 DEMO-FX15-082 LP-FX15DEM-010C
LP-FX15DEM-011C
Demo case FX15 + N2 Open communication, 230 V Demo case FX15 + LON communication, 230 V Demo case FX15 + N2 Open communication, 120 V Demo case FX15 + LON communication, 120 V FX15 controller + Integrated display + N2 Open
comm. Card with DEMO ID FX15 controller + Integrated display + LON comm Card with DEMO ID
53
Table 18: Software Ordering Codes Description
LP-FXTPRO-0
LP-FXTEXP-0
FX Tools Pro CD-Rom (FX Builder, FX Builder Express, FX CommPro N2, FX CommPro LON)
FX Tools Express CD-Rom (FX Builder Express, FX CommPro N2)
Page 54
FX15 Controller Technical Bulletin
54
Technical Specifications
I/O Technical Details
IMPORTANT: For installation with Class 2 inputs and outputs only, no
special mounting precautions are generally necessary. For use with one or more line voltage outputs (above 30 V), installation as part of a UL 508A industrial control panel may be required by the local building or electrical authority. These controllers are presently UL Recognized as Temperature Indicating and Regulating Equipment in accordance with UL 873. UL Listing as Open Energy Management Equipment per UL 916 is pending.
Table 19: Analog Input (AI) Terminals Channel Type Remark/Application
TB1 (1-15)
TB1 (3, 8)
TB1 (13)
List of Available Sensor Input Sensor Type Linearization Range Accuracy
Ni1000 JCI Ni1000 JCI Extended Ni1000 Siemens™ Ni1000 DIN Pt1000 A99 NTC 2.2K 0 to 5 VDC ratiometric 0 to 10 VDC 0 to 20 mA
AI1, AI2, AI3, AI4, AI5, AI6
EXT-VDC +16 V, 80 mA Directly power from the
AVPS/EXT­VDC
Figure 30. Software configurable.
See
Application: temperature, humidity, pressure
controller. Maximum four
0-20/4-20 mA sensors AVPS = +5 V, 20 mA EXT-VDC = +16 V, 80
mA
To directly power
ratiometric sensors,
with AVPS or
0-10 V, 0/4 - 20 mA
Sensors with EXT-VDC.
The selection between
AVPS and EXT-VDC is
done through jumpers.
@ 20°C (68°F) ambient
-45 to 120 °C (-49 to 248°F) +/- 0.5° C (0.9°F) 20 to 287°C (68° to 548.6°F) +/- 0.5° C (0.9°F)
-50 to 160°C (-58 to 320°F) +/- 0.5° C (0.9°F)
-60 to 180°C (-76 to 356°F) +/- 0.5° C (0.9°F)
-50 to 605°C (-58°F to 1121°F) +/- 0.6° C (1.08°F)
-50 to 110°C (-58 to 230°F) +/- 0.5° C (0.9°F)
-40 to 150°C (-40 to 302°F) +/- 0.5° C (0.9°F) 10 to 90% of supply voltage 0.3% 0 to 10 Volts 0.3% 0 to 20 mA 0.3%
Page 55
FX15 Controller Technical Bulletin
Table 20: Digital Input (DI) Terminals Channel Type Remark/Application
TB2 (21-33)
TB2 (34, 35)
DI1, DI2, DI3, DI4, DI5, DI6, DI7, DI8
DI V~ Hot DI V~ Com
Potential free contacts
24 VAC/DC Power supply for the
Digital Inputs. Must be used in order to maintain the opto-isolation a separate power supply from the one used for the controller.
Table 21: Digital Output (DO)
55
Terminal
TB3
TB4
TB5
TB6
Channel Type Remark/Application
DO1, DO2, DO3 SPST 8(3)A
power relays
DO4, DO5 SPST 5(3)A
power relays
or
0.5A/24 VAC triacs
DO6, DO7, DO8 SPST 5(3)A
power relays
or
0.5A/24 VAC triacs
DO9 SPDT NC
8(3)A 250V relay
Maximum switching power: 2000VA, 240W, 0.5HP, 250 VAC
UL/CUR rating: 8A 250 VAC 8A 30 VDC VDE rating: 8A 250 VAC Expected electrical life min.
operations: 1 x 105 operations (360 ops x hour)
Dielectric strength: coil-contacts 4000 Vrms
Maximum switching power:
1.250 VA, 150 W Rating (resistive): 10 A
125 VAC, 5A 250 VAC, 5 A 30 VDC
Expected electrical life (min operations): 10A 125 VAC 5x104 5A 250 VAC 5x104 5A 30 VDC 105
Dielectric strength: coil-contacts 4000 Vrms for 1 min
Same as TB3 relays Fail relay for enhanced
security. The relay will return to its NC position not only at power fail but also in case the microprocessor should fail: watch-dog, brown-out, etc.
Page 56
FX15 Controller Technical Bulletin
56
Table 22: Analog Output (AO) Terminals Channel Type Remark/Application
TB7
TB8
TB8 (79, 80)
AO1, AO2 0-10 VDC (maximum
AO3, AO4 0-10 VDC (maximum
AO V~ Hot AO V~
Com
N2 Open Card
Table 23: N2 Open Card
RS-485 line
Devices RS-485/232 Converter
Electrical Isolation
Used to drive motor
1.5 mA)
1.5 mA)
24 VAC Power supply for the Analog
Maximum length without repeater: 1200 m (4000 ft), AWG26 twisted pair with shield.
Maximum of 32 per 1200 m (4000 ft) bus segment. IU-9100 if third party converter is used then make
sure it supports automatic DSC (Data Send Control) 1500 V
actuators, power triacs, frequency drives. 16-bit resolution.
Used to drive motor actuators, power triacs, frequency drives. 16-bit resolution.
Outputs. In order to maintain the opto-isolation a separate power supply from the one used for the controller, must be used.
LON Connection
Table 24: LON Connection
LON network and Line Terminators
Nodes
Cable type:
Belden® 85102 Belden 8471 Level IV 22 AWG
Daisy chained Bus Topology: two terminators of 100 ohm required, one at each end of the bus. Free (start) topology: single terminator of 50 ohm required.
64 (if repeaters are not used), FTT-10 nodes only.
Length with FTT-10 devices Bus Topology Free Topology
2700 m (1.7 mi) 500 m (0.3 mi) 2700 m (1.7 mi) 500 m (0.3 mi) 1400 m (0.9 mi) 400 m (0.3 mi)
Page 57
FX15 Controller Technical Bulletin
Programming Key
Table 25: Programming Key
Power Supply
Memory type and size Connection to controller
Enclosure IP class Ambient Limits
Agency Listing
Directly powered from the Display Bus port of the FX15 or from an AC/DC adapter 230V to 12 VAC ÷ 15 VDC min 2 VA
Flash memory 1 Mbytes Via RS-485, not isolated, 10 cm cable provided
with the key IP40 Operating: 0°C (32°F) – 40°C (104°F), 10-95% rH
(noncondensing) Storage: -20°C (-4°F) – 70°C (158°F), 10-95% rH
(noncondensing) 73/23 EEC directive: EN 60730
FX15
Table 26: FX15
Product Power Supply
Requirements Power Consumption Protection Class
Isolation Ambient Operating
Conditions Ambient Storage
Conditions Dimensions (H x W x D)
Weight (with package) I/O ratings Connection terminals for
signals and power supply
LON/N2 Open bus connection terminals
Connection terminals for extension bus and remote display
Continued on next page…
FX15 24 VAC ±15%, 50/60 Hz - Class 2 Power
Supply 15 VA at maximum load IP20 controller IP40 integrated MUI See Isolation Diagram.
-20 to +50°C (-4 to 122°F), 10 to 95% rH (noncondensing)
-20 to +70°C (-4° to 158°F), 10 to 95% rH (noncondensing)
142 mm (5.6 in.) x 215mm (8.5 in.) x 49 mm (1.9 in.)
0.74 Kg (1.6 lb) I/O Technical Details.
See Screw terminals for maximum 1 x 1.5 mm2
(0.002 in. or Cage clamp connectors 1 x 1.5 mm wires
To be ordered separately
Screw terminals, cable size 0.05 to 1.5 mm (0.002 in.2), AWG30 to AWG14 Belden cable, 2-core twisted pair with shield
Screw terminals, cable size 0.05 to 1.5 mm (0.002 in.2), AWG30 to AWG14
2
) wires
2
(0.002 in.2)
2
2
57
Page 58
FX15 Controller Technical Bulletin
58
Single cable lengths
Digital Inputs DI1 - DI8 Analog Inputs AI1 - AI6 Triac outputs (when present) Analog Outputs AO1 - AO4 Remote Display
Extension Modules
Display and Extensions cable type
Compliance
United States: FCC Compliant to CFR 47, Part
UL compliance
FX15 Extended Range
Table 27: FX15 Extended Range
Product Power Supply Requirements
Power Consumption Protection Class
Isolation Ambient Operating
Conditions Ambient Storage Conditions
Dimensions (H x W x D)
Weight (with package) I/O ratings Connection terminals for
signals and power supply LON/N2 Open bus connection
terminals
Connection terminals for extension bus and remote display
Continued on next page…
Maximum 100 m (328.1 ft) with diameters ≥ 0.6 mm (0.02 in.)
Maximum 100 m (328.1 ft) with diameters ≥ 0.6 mm (0.02 in.)
Maximum 100 m (328.1 ft) where A ≥ 1.5 mm (0.002 in.2)
Maximum 100 m (328.1 ft) where A ≥ 1.5 mm (0.002 in.2)
Maximum 3 m (9.8 ft) if display is powered by controller. Maximum 1km (1.9 mi) if display independently powered
Maximum 1km (0.6 mi) Belden 4-core, twisted pair, shielded 89/336 EEC directive: EN 50081-1
(EN 61000-6-3), EN 50082-1 (EN 61000-6-1) 73/23 EEC directive: EN 60730
15, Subpart B, Class A Canada: Industry Canada, ICES-003 UL873 Recognized (XAPX2, XAPX8)
FX15 extended range 24 VAC ±15%, 50/60 Hz - Class 2 Power
Supply 15 VA at maximum load IP20 controller IP40 integrated MUI See Isolation Diagram.
-40 to +60°C (-40 to 140°F), 10 to 95% rH (noncondensing)
-20 to +70°C (-4 to 158°F), 10 to 95% rH (noncondensing)
142 mm (5.6 in.) x 215 mm (8.5 in.) x 49 mm (1.9 in.)
0.74 Kg (1.6 lb) See Screw terminals for a maximum 1 x 1.5 mm2
(0.002 in Screw terminals, cable size 0.05 to 1.5 mm
(0.002 in.2), AWG30 to AWG14, included in the package. Belden cable, 2-core twisted pair with shield
Screw terminals, cable size 0.05 to 1.5 mm (0.002 in.2), AWG30 to AWG14, included in the package.
I/O Technical Details.
2
) wires, included in the package.
2
2
2
2
Page 59
FX15 Controller Technical Bulletin
59
Single cable lengths
Digital Inputs DI1 - DI8 Analog Inputs AI1 - AI6 Triac outputs (when present) Analog Outputs AO1 - AO4 Remote Display
Extension Modules
Display and Extensions cable type
Maximum 100 m (328.1 ft) with diameters ≥
0.6 mm (0.02 in.) Maximum 100 m (328.1 ft) with diameters ≥
0.6 mm (0.02 in.) Maximum 100 m (328.1 ft) where A ≥ 1.5 mm
(0.002 in.2) Maximum 100 m (328.1 ft) where A ≥ 1.5 mm
(0.002 in.2) Maximum 3 m (9.8 ft) if display is powered by
controller. Maximum 1 km (1.9 mi) if display
2
2
independently powered Maximum 1km (0.6 mi) Belden 4-core, twisted pair, shielded
Compliance
89/336 EEC directive: EN 50081-1 (EN 61000-6-3), EN 50082-1 (EN 61000-6-1) 73/23 EEC directive: EN 60730
United States: FCC Compliant to CFR 47,
Part 15, Subpart B, Class A
Canada: Industry Canada, ICES-003
UL compliance
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
UL873 Recognized (XAPX2, XAPX8)
Controls Group Global Headquarters
507 E. Michigan Street P.O. Box 423 Published in U.S.A. and Europe Milwaukee, WI 53201
Loading...