SPE Expert 2K-FA Quick-Start Guide
18
Protecting the SPE 2K-FA (Alarms)
o The 2K-FA protection system monitors and controls the amplifier’s most important parameters, such as
temperature of the heatsinks; maximum/minimum voltage on the PA; maximum PA current; SWR;/reflected
power; and very important, the input power to prevent and warn of “over-driving.”
o The protection system is carried out in two different ways:
- Through hardware circuits to ensure a minimum intervention time.
- Through software, with a combined action of the two CPU’s, to ensure the maximum protection, warnings
and alarms.
o The two results get constantly compared; every difference produces a protection trip and a consequent alarm.
There are three types of protections/alarms:
o SIMPLE - This is the most common case. An acoustic warning beep sounds, but no operator intervention is
required, as the control system automatically restores the correct operating conditions.
o SERIOUS - When automatic system recovery is not possible (e.g., the temperature climbs over the limits due to
obstruction of the fans,; SWR is too high; etc.). In this case the amplifier switches back to standby state and the
alarm message gets stored. Normally transmission can continue with the exciter only. Operator needs to locate
and remove the problem for the amplifier to amplify.
o FATAL - If the amplifier is in the b) state, but one CPU has a fault or it can’t continue operating or some fault
appears in the power-supply module, then the amplifier gets turned OFF with no further warning. To restart the
amplifier, the main switch in the rear panel has to be switched to [O] (OFF) for about 3 minutes, and then to the
[I] position (ON).
It is possible to read the alarm history in the standby mode by pressing the [SET] and then [ALARMS LOG] keys. To empty
the alarm stack, press the [TUNE] and [OPERATE] keys at the same time.
o If the acoustic alarm is very frequent during transmission, the possible causes should be investigated.