Ex-Or UC1201PF, UC1221PSM, SV2, UC1221PF, UC1201PSM Installation Instructions

UC1201PF / UC1201PSM UC1221PF / UC1221PSM
LightSpot Washroom Series
UC1201PF UC1221PF
UC1201PSM
SV2
UC1221PSM
(included)
Installation and Commissioning
Instructions
Note: HP10 or HP2000 required for commissioning
Novar ED&S Limited Haydock Lane, Haydock, Merseyside WA11 9UJ
Tel: + 44 (0)1942 719229 Fax: +44 (0)1942 508753 Email: technicalsales.ex-or@honeywell.com www.ex-or.com
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.
W4250E
LightSpot presence-detecting washroom controls
Only suitably qualified personnel should install this equipment.
LightSpot washroom controls are high performance presence detectors with photocell. The photocell can operate in three modes: Passive, Active or Disabled. Further information can be found overleaf.
Fixing
UC1201PSM / UC1221PSM - The housing may be secured to a hard surface or a BESA box. The unit fits into the housing with a simple bayonet action.
UC1201PF / UC1221PF - Depth required behind ceiling: 62mm from front flange plus an allowance for the minimum bend radius of the cable. Sinking box fits into an 89mm diameter hole in ceiling tile or plasterboard ceiling. To avoid damage to ceiling tile, do not overtighten. No access above the ceiling is necessary.
Note: Do not mount within 25cm of a luminaire.
Solenoid Valve
The solenoid valve must be plumbed into the water feed to the urinal header tank and connected to the LooSpot detector using 230V cable.
The required direction of water flow is shown on the valve. Avoid contamination by swarf, flux etc.
Connection Examples
Single UC1201PF or UC1201PSM
Controlling water
LightSpot
VOLT­FREE OUTPUT
* *
NEUTRAL
LIVE IN
LIVE IN
EARTH
External
Link
* The Live terminals are internally linked
SOLENOID VALVE
L
N
E
Permanent or switched supply
Single UC1221PF or UC1221PSM
The UC1221 has two outputs, one influenced by the photocell (R1), the other not (R2). This is useful in applications where a fan or water is being controlled in addition to any lighting.
VOLT­FREE OUTPUT
LIVE OUT
LIVE IN
NEUTRAL
EARTH
LightSpot
(Max 6 Amps) INFLUENCED
BY PHOTOCELL
LIGHTING
SOLENOID VALVE
OR
FAN
L
N
E
Permanent or switched supply
Multiple UC1201PF or UC1201PSM
Larger areas can be covered by connecting extra units in parallel. The total load current must not exceed 6 Amps in case only one unit is activated.
LIGHTING,
LightSpot LightSpot
VOLT­FREE OUTPUT
LIVE IN
*
LIVE IN LIVE IN
*
NEUTRAL NEUTRAL
EARTH EARTH
VOLT­FREE OUTPUT
External Link External Link
* *
LIVE IN
FAN OR VALVE
* The Live terminals are internally linked
L
Permanent or switched
N
supply
E
W4250E
HP10 Parameter Options for UC12xxP
PHOTOCELL
ENABLED
MOVEMENT DETECTOR AUTOMATIC OPERATION
NOT
USED
POWER UP
ON
PHOTOCELL
24 Hr Cycle*
10
5
min
20
min
min
5
10
min
min
MODE
= ACTIVE
20
min
Pleas e note t hat add itional parameters are available via the HP2000 Programmer.
ON
21 3 4 5 6 7 8 9 10 11 12
POWERUP
OFF
OFF
* Operates on R2 if Twin-Output Unit, R1 on Single-Output Unit. If controlling water with Single­Out put Uni t the p hotocel l cannot be used.
OFF DELAY
Add together to give required time.
All OFF = 10 secs
(Volt-free R2)
No 24 Hr Cycle
OFF DELAY
Add together to give required time.
All OFF = 10 secs (Switched-live R1)
PHOTOCELL
MODE
= PASSIVE
PHOTOCELL
DISABLED
SEMI-AUTOMATIC
MOVEMENT DETECTOR
OPERATION
NOT
USED
Off Delay
Independent Off Delays may be set for each output between 5 and 35 minutes. A 10-second Off Delay is available for walk-testing the product. In a typical office environment a 20-minute Off Delay is usually satisfactory
Movement Detector Operation (Automatic / Semi-Automatic)
Where absence detection is required (ie the user manually turns lights ON if required but lights still turn off automatically once an area is vacated), semi-automatic operation can be set via the programmer. It should be noted that this mode of operation affects only the switched-live output. Where semi-automatic operation is required on both outputs, please contact Ex-Or for assistance.
Power Up Setting (On/Off)
Set to ON the detector will automatically switch its outputs on when Mains is applied. If set to OFF, the detector will power up without turning its outputs on, wait for 15 seconds and THEN look for movement. Only if the area is occupied will the outputs switch on at this time. The detector must be set to Power Up ON when used in conjunction with semi-automatic operation.
Photocell Operation (Passive/Active/Disabled)
Both the single-output detector and the dual-output detector have an in-built photocell. On the dual-output detector the photocell does not affect the volt-free output - ie the volt-free output will turn ON regardless of natural light levels when occupancy is detected. The photocell has three modes of operation - Passive, Active and Disabled. Its operational behaviour is governed by the setting chosen and by the values stored in the Upper and Lower thresholds (see diagram overleaf).
Passive - The photocell will inhibit turn-on of the controlled load if sufficient natural light is available. It will not turn the load off whilst an area is occupied
Active - The photocell will turn the controlled load on and off as required whilst natural light levels fluctuate during a period of occupancy. This mode of operation operates in conjunction with a passing cloud timer (PCT). The PCT is asymmetrical in operation - the load will be switched on immediately should natural light levels fall beneath the lower threshold, however, the load will not turn OFF should natural light levels increase beyond the upper threshold level unless that increase is constantly above the threshold for the duration of the Off Delay.
Disabled - The photocell has no effect regardless of natural light levels.
24hr Cycle (Yes/No)
If the detector has seen no movement for 24 hours, the output (selectable on dual-output version, default = volt-free) will be switched ON for the duration of the time delay, if 24hr Cycle is set to ON. Used in conjunction with a suitable valve the need for separate urinal flush control is removed.
Commissioning
The units are supplied with factory default settings (power-up on, fully automatic operation, a 20 minute off delay, no 24hr cycle, photocell disabled). Programme using the MLS Digital Programmer with LCD display (HP2000), or the LightSpot Programmer (HP10) incorporating 12 dil switches.
Walk-test Mode
Walk-test mode is used to check that the detector is operating as required. The short off-delay enables the installer to check that lights are switching on when movements are made at the edge of the detection zone. It is easier to carry out a walk-test when the photocell is not holding the lights off. cont.
1. Change the programmed Off Delay to 10 seconds using either an HP10 or HP2000.
2. Move around the area that is being controlled, stopping for 10 seconds to allow the lights to switch off, before moving and triggering the lights back on. Re-programme the desired Off Delay once testing is complete.
Setting the Photocell (Photocell only affects the ‘Live Out’ output)
1. Wait until the time of day when the ambient light level is equal to the level at which you want the photocell to
become active.
2. Using the HP2000, select ‘Set Light Level’ from the Utilities menu and press OK while pointing at the
detector to store the current light level - the lights must be on prior to starting this process. The detector stores two values in Lower Threshold and Upper Threshold (see diagram). This procedure can also be accomplished by using the HP10 Basic Programmer’s ‘Store’ button, however editing of stored threshold values is not possible with the HP10.
3. If required, these values can be manually edited via the HP2000. Please note, these are not Lux levels but a
representation of the light levels perceived by the detector at the time of the store command.
Note: If the photocell is set to Passive, only the value in the Lower Threshold is relevant.
If the photocell is set to Active, once the ambient light level drops below the Lower Threshold value, the
lights will turn ON. If the ambient level exceeds the value of the Upper Threshold for the duration of the off­delay (Passing Cloud Timer) then the lights will turn ON. If the photocell is set to ‘Disabled’ when a Set Light Level operation is made, it will revert to operating in Passive mode.
Washroom Mode
Both the single-output and dual-output version of this product allow the control of water for washroom management applications (urinals). In order to maintain good standards of hygiene the products feature a washroom mode (24hr Cycle) that, if enabled, ensures that when urinals have not been used for 24 hours (i.e. the controlled area has been unoccupied), a hygiene flush occurs. Please note that when used on the single-output unit (controlling lighting and urinals), it is not possible to have the photocell influence the output status as this could prevent flushing of the urinals. On the dual-output unit the ‘flush’ will occur on the volt-free output although this can be changed via the HP2000 Programmer.
Important Additional Notes
1. All terminals on this product are provided for final connections. It is not intended that the product be used as a junction box
for looping cables.
2. A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.
3. This equipment switches lights no more frequently than would a responsible human occupant. However, manufacturers of
some lighting types (e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles in order to achieve a predicted lamp life. Please check with the manufacturer of the luminaires to ensure that they are compatible with automatic controls in this respect.
Technical Data
OPERATING VOLTAGE: 230V 50Hz (UK & Europe) RECOMMENDED CIRCUIT PROTECTION: 10 Amps TERMINAL CAPACITY: 2 x 2.5mm MAXIMUM LOAD: 6 Amps per output (not exceeding 10A in total on UC1221P) MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3 metres RANGE: Cone-shaped detection pattern, diameter (at floor level) = 2.4 x mounting height
OFF DELAY 1 & 2: 1 minute - 96 hours adjustable (5-35 mins via HP10) and 10-second Walk Test Mode. ( Each output independently adjustable.) PHOTOCELL: Adjustable 50-5000 lux via HP10 / HP2000 COLOUR: White MATERIAL: Flame retardant PC/ABS WEIGHT: 200g approx IP RATING: 3X
2
2.5m
6.0m
Dimensions
62mm
deep
(behind ceiling)
100mm
10mm
deep
(Flange)