Ex-Or SceneSelect II SMD810 Instruction Manual

Warning ............................................................. 2
Features ............................................................ 2
Important Safeguards ........................................ 2
Internal View ................................................... ...3
Mounting ............................................................ 4
Supply & Load Cable Connections .................... 5
Connecting Serial Control Cables...................... 6
Hardware Controls ............................................ 7
Dimmable Lamps Chart .................................... 7
Changing Scenes Using The Program Key ........8
Troubleshooting................................................. 9
Specification ..................................................... 9
Contents
Ex-Or
Haydock Lane, Haydock, Merseyside WA11 9UJ
www.ex-or.com
W4386A
SMD810
Instruction Manual
MIXED DIMMER
SceneSelect II
Scene-setting and Dimming System
ISOLATE FROM MAINS SUPPLY BEFORE REMOVING THIS COVER
NO USER SERVICEABLE PARTS INSIDE
SERVICE BY QUALIFIED PERSONNEL ONLY
WARNING
Warning
TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS DEVICE TO RAIN OR MOISTURE. DO NOT ENERGISE UNLESS THE FRONT COVER IS IN PLACE. THIS DEVICE MUST BE EARTHED. INSTALLATION, PROGRAMMING AND MAINTENANCE MUST BE CARRIED OUT BY QUALIFIED PERSONNEL.
Simple Supply Requirement
230V 50Hz single phase at 40A.
4 Dimmed Outputs
Each dimmed 10A output is independently regulated, protecting loads from voltage surges and spikes. These outputs are overload protected by individual 10A circuit breakers.
4 Switched Outputs
Each switched output is rated at 10A. These outputs are overload protected by individual 10A circuit breakers.
4 Control Outputs
Each of the 4 optically isolated outputs can be configured to be either 1-10V, DSI Serial control or DALI broadcast, covering the latest types of HF Fluorescent Ballasts. Also compatible with 1-10V, DSI and DALI dimmable electronic transformers. These outputs can operate in tandem or independently of the switched outputs.
Convection Cooled
This device is convection cooled, requiring no forced cooling system when installed in accordance with these instructions.
Many Control Options
Control of this device can be from any of the SceneSelect control panels and ancillary products.
Simple Installation
Wall mount enclosure with mounting lugs facilitates installation. A cable gland plate is provided at the top of the enclosure for supply and load cables and a knockout for the low voltage (LV) control at the bottom.
Note: Channel 1 (leading edge phase control) & Channel 5 (switched output): Combined rating = 10A Channel 2 & Channel 6: Combined rating = 10A Channel 3 & Channel 7: Combined rating = 10A Channel 4 & Channel 8: Combined rating = 10A
Features
SMD810 Instruction Manual - W4386A
2
Important Safeguards
Read Instructions We recommend that you read this Instruction Manual prior to commencement of installation. Retain these instructions and give the end user the 'Changing Scenes Using the Program Key' guide on page 8, if applicable. Troubleshooting - If problems are encountered, please check the troubleshooting section on page 9 before calling Ex-Or technical support. Special Programming This device will only operate in ‘basic’ mode unless programmed via a computer. Should programming be required, contact Ex-Or for details. Once the data cable is connected to the device(s), the factory default settings will allow any control panel to control all channels in all dimmers. Power Sources This device should only be operated from the type of supply specified on the front panel. This device must be earthed. Output Circuits The load on a single circuit should not exceed 10A for a dimmed channel and 10A for a switched channel. Loads should be calculated to ensure that the total device load of 40A (10A per pair of channels: 1 & 5, 2 & 6, 3 & 7, 4 & 8) is not exceeded. Load Control Circuits If this device is being
used to control 1-10V, DSI or DALI broadcast HF Fluorescent Ballasts, a 2 core LV control cable is required to be run to the loads, in addition to the mains feed.
Load Type Default settings are for load control outputs to be 1-10V. Check to see what type of HF Fluorescent Ballasts are in the luminaires. Do not terminate the control lines to any DSI or DALI loads until the relevant channel has been programmed as DSI or DALI. When connecting 1-10V load control lines, pay attention that the correct polarity is maintained. Megger Testing Do not megger test any circuitry connected to the dimming system, as damage to the electronics may result. Mounting Location This device must be mounted the right way up, on a vertical surface (refer to page 4 for mounting instructions). The specified minimum clearance of 200mm for all sides must be adhered to. Install in a dry, well-ventilated location. This device may emit some mechanical noise. Take this into account when deciding the mounting location.
Data Cable The recommended minimum grade of cable for connections to the programming socket is Category 5 FTP (screened). This cable should be segregated from mains cables by a minimum distance of 300mm. If expected cable runs are over 600 metres for bus cables or 12 metres for analogue cables, consult Ex-Or for advice. Do not cut or terminate live data cables.
3
Internal View
SMD810 Instruction Manual - W4386A
Entry Gland Plate for Load Cables
Circuit Breakers and
Emergency Lighting Line Outputs
Dimmed or
Switched 230V Outputs
40A Single Phase
Supply Connections
4 x Side Entry
Gland Knockouts
DALI Broadcast,
1-10V or DSI
Control Ouputs
Earth Link
Accessory Port
SceneSelect
Bus Terminations
Low Voltage
Cable Gland
Network
Socket
Service LED
Service Switch
Loading...
+ 7 hidden pages