Ex-Or SceneSelect II Installation Instructions

Important Notes
Data Cable -
It should be segregated from mains cables by a minimum distance of 300mm, unless the FTP cable itself is mains-rated.
Recommended cable types include:
Belden 9503 RS Components 368-687
One pair is paralleled for GND, one pair paralleled for +12V, and one pair used for DATA+ and DATA -.
The screen of the data cable must be connected where there is a terminal provided.
Wall Boxes - To comply with local electrical standards, this product
may be required to be installed into a metal wallbox 45mm deep (not supplied).
Special Programming - This device will only operate in ‘basic’ mode unless programmed via a computer. Should programming be required, contact Ex-Or for details. Once the Bus cable is connected to the device(s), the factory default settings will allow any control panel to control all channels in all dimmers.
Programming Information - This manual is an installation guide only. For detailed programming information contact Ex-Or.
Use Category 5 FTP (screened) cable as a minimum.
Serial Cable Permanent Connections
D+
+12V
D
White for DATA-
Sample Colours
ORANGE/WHITE PAIR
BLUE/WHITE PAIR
GREEN/WHITE PAIR
SCREEN (Must be connected if there is a screen/shield terminal provided)
GND
SHIELD
Recommended Connection Method and Colour Coding
Green/White pair paralleled for GND Orange/White pair paralleled for +12V Blue/White pair Blue for DATA+
The colour coding scheme used is not critical, as long as the same scheme is used throughout the installation.
SceneSelect II
Scene-setting and Dimming System
Control Panels
1
2
3
OFF
Installation Guide
Ex-Or Limited
Haydock Lane, Haydock, Merseyside WA11 9UJ Telephone: 01942 719229 Fax: 01942 272767 Email: ex-or@ex-or.com
W4109D
Connecting Bus Cables
Connect the SceneSelect Bus cable to all devices in a “daisy chain”. Start at the first device, then loop into and then out of devices, with a single cable terminating at the last device.
There should not be any spurs or stubs (X, Y or T joins). The first and last device should terminate one cable, all other devices should terminate two cables. Devices may be wired in any order.
Physical constraints may dictate that Bus cable spurs are necessary. In these cases, SBE SceneSelect Bus Extenders should be used. Consult Ex-Or for details.
A SceneSelect Bus cable that is connected to an energised dimmer is live. Do not cut or terminate live data cables.
Connect Data Cable in a "Daisy Chain"
Manufactured by: Unit 6-119/133 McEVOY St. Alexandria NSW 2015 AUSTRALIA
SceneSelect II
INSTALLATION DETAILS
WARNING
MAINS SUPPLY BEFORE
REMOVING THIS COVER NO USER SERVICEABLE PARTS INSIDE SERVICE BY QUALIFIED PERSONNEL ONLY
ISOLATE FROM
1 cable
2 cables
2 cables
Manufactured by: Unit 6-119/133 McEVOY St. Alexandria NSW 2015 AUSTRALIA
SceneSelect II
INSTALLATION DETAILS
INPUT: 230 V 50-60Hz 10 A OUTPUT: 1 x 230V 10A MOUNT VERTICALLY AGAINST WALL ENSURE GOOD VENTILATION FOLLOW INSTALLATION INSTRUCTIONS
WARNING
MAINS SUPPLY BEFORE
REMOVING THIS COVER NO USER SERVICEABLE PARTS INSIDE SERVICE BY QUALIFIED PERSONNEL ONLY
ISOLATE FROM
2 cables
Specification
Supply:
9 - 16 Volts DC from SceneSelect bus network. Standard Series - 18mA nominal Classic Series - 16mA nominal
Compliance:
CE, C-Tick