Technical Data
MLS CABLE: 1.5mm unscreened twisted-pair: see Application Note AN4001
OPERATING VOLTAGE: Powered from the MLS Bus (not SELV)
The chassis of this device must be Earthed.
AMBIENT TEMPERATURE RANGE: 0 - 50 C
DEPTH REQUIRED BEHIND WALL: 35mm
WEIGHT: 150g
DIMENSIONS: 86 x 86 x 30mm
Fascias must be ordered separately using the following part codes:
MSS182BSS - Brushed Stainless Steel
MSS182WHI - White
MSS182PBR - Polished Brass
MSS182POC - Polished Chrome
Please note:
Please note that the flat head countersunk screws supplied with the unit
must be used in order to ensure proper fit of the fascia plate. If the
application requires longer screws, M3.5 extension studs should be used
(MK Part No: MK 3710 is recommended).
Use only the dry-lining box supplied as other types may not fit.
Honeywell Ex-Or
Albery House, Springfield Road,
Horsham, West Sussex RH12 2PQ
Tel: + 44 (0)1942 719229
Fax: +44 (0)1942 272767
Email: technicalsales.ex-or@honeywell.com
www.ex-or.com
2
o
W4327E
MLS Digital Local Control Plate
MLSLCP4 MK2
for use with the MLS Digital range
Installation and Commissioning
Instructions
General Installation and Operation
The MLSLCP4 should be mounted on the supplied single-gang
sinking box supplied. When mounting ensure that the orientation
information on the plate is followed. Ensure that the mounting frame
and the metallic fascia plate are bonded to the building Earth grid via
the Earth terminal block provided on the mounting frame.
The MLSLCP4 Local Control Plate is designed to operate as part of an
MLS Digital installation. This device sends messages to other
equipment that is actually in control of the lights. It provides simple,
manual control over a group of light fittings programmed to the same
zone address, allowing the end-user to select one of three pre-set
scenes, to dim, brighten or switch off the lighting as required.
The MLSLCP4 also allows brightness control; this is initiated by a
long press on Button 2 (brighten) or Button 3 (dim). To facilitate
minor adjustments of the light level, the MLSLCP4 remains in
manual mode for a few seconds, allowing momentary presses of the
dimming buttons. The buttons revert to scene-selecting mode after
the short time out.
The MLSLCP4 will control the lights programmed to its zone only.
This is set via an 8-way dil switch on the reverse of the unit as in the
following diagram. Each switch has a value - 1, 2, 4, 8, 16, 32 and
64 (the switch designated ‘Mode’ should remain OFF). Using a
combination of these will allow any zone to be set from 1 - 100.
The MLSLCP4 connects directly to the MLS bus via the terminals
located on its reverse. 1.5mm mains-rated unscreened twisted-pair
2
must be used for this connection, however if just a short spur is
required to the plate then single cables may be used. Polarity must
be maintained throughout.
Commisioning
Adding together the value of
ONON
switches 1-7 that are set to
‘ON’ sets a Zone number for
the con tr ol p l a t e . T hi s
diagram shows values 2 and
16 set to ‘ON’ and therefore
denotes Zone 18.
1 2 3 4 5 61 2 3 4 5 6 7 8
8
2 41
16 32 64
Mode
NOTE: Switch 8 should be
left OFF.
Earth Terminal on
Mounting Frame
MLS - MLS +
MLS Connections
NOTE: The MLSLCP consumes two ‘nodes’ on the MLS Bus
(max 200 with RB2000 Bus Power Supply; max 100 with
RB2000LT Bus Power Supply ‘Lite’).