Ex-Or MLS2500D, MLS2500DF, MLS2500DWL, MLS2500DWLF, MLS2500DALI Installation Instructions

...
MLS2500D / MLS2500DF
MLS2500DWL* / MLS2500DWLF*
MLS2500DALI / ML2500DALIF
MLS2500DALIWL* /
MLS2500DALIWLF*
MLS2500D(WL) MLS2500DALI(WL)
MLS2500D(WL)F MLS2500DALI(WL)F
Installation and Commissioning
Instructions
Note: QuickSet Pro required for commissioning
Digital Mid Range Series Detector
Fixing
Only suitably qualified personnel should install this equipment.
1. This is an extremely sensitive movement detector; it is essential therefore that it be installed on a rigid surface that will not itself be subject to any movement or vibration.
2. Before isolating the circuits to be switched, check that all lighting is fully operational and that there is no moving equipment or machinery within the monitored area which may cause nuisance switching.
3. Position the detector where it has a good forward “view” of the area to be controlled. Ideal mounting location is normally in a corner by the entrance or at one end of a corridor at a height of 2.5 to 4m. Do not mount within 25cm of a fluorescent fitting.
Please note that this product uses microwave technology to detect occupancy and is not recommended
for applications where there are large areas of metal, e.g. metal ceiling or panelling, as unpredictable sensitivity may result.
Also, microwave presence detection is not completely attenuated by materials such as plasterboard,
wood and glass, so the possibility of unwanted presence detection through office partitions should be considered when determining detector positioning and sensitivity settings within the intended application.
4a. MLS2500D - Surface version Separate the detector from its back-box by loosening the locking screw so that approximately 3mm of
thread is visible and then twisting the detector off the back-box. Note the arrow symbol moulded into the bottom of the back-box. The fixing holes allow for mounting on a BESA box or direct to a rigid surface. Secure the back-box firmly to a rigid surface so that the arrow points into the controlled area.
4b. MLS2500DF- Semi-flush version Use a hole saw to drill a 76mm hole into the ceiling tile. The flush ring is designed to clamp the tile between
its two halves. Loosen the locking screw so that approximately 3mm of thread is visible and remove the bottom half of the flush ring. With the detector in the ceiling, pointing towards the area to be controlled, fit the bottom half of the flush ring to the assembly. Depending on the thickness of the ceiling tile, screws longer than those supplied may be required to hold the two halves of the flush ring together.
It is recommended that Mid Range detectors be ceiling mounted. Where this is not possible, the wall-mounting kit (WMK - see below) must be used.
Exploded view of detector for fixing into ceiling tiles.
WMK Wall-mounting Kit
(Supplied assembled)
Vertical installation
Use this method of mounting for racking aisle applications and where adjustment in the vertical plane will give improved control over the precise point of entry detection.
2
Horizontal installation
For general applications where ceiling mounting is not convenient and wide angle coverage in the horizontal plane is desirable. The WMK can be screwed to a hard surface or the lid of a conduit stop-end box.
Electrical Connections
Detectors should be connected in accordance with the diagram below.
Digital Mid Range Detectors are designed to control up to 25 DSI or DALI ballasts, a switched load of up to
10 Amps or a combination of the two. When controlling DSI or DALI ballasts the ballast types must not be mixed. The DSI or DALI input terminals on the ballasts should be connected in parallel with each other and to the Polarity-Free Digital Output terminals of the detector. Each DSI or DALI luminaire is controlled completely by its digital input and therefore would normally have a permanent power supply. Turning the power off to some lights within a control circuit will not affect the operation of those lights that remain powered and under the control of the detector.
When switching via the relay output, multiple MLS2500Ds' relay outputs may be connected in parallel provided the controlled load does not exceed 10 Amps. If digital ballasts are also being controlled, the digital outputs from different detectors must never be connected one to another, even if they are of the same type.
Live Out
Live In
Neutral
Earth
D1
D2
MLS 1
MLS 2
8
SW
L
7
L
6
N
5
4
D
3
D
(Digital Out)
M
MLS 2-core Bus Cable Do NOT connect to Mains
1 2
M
(MLS Bus)
SWITCHED LOAD
10 Amps Maximum
Live
Neutral
Mains Supply
Earth
Digital Dimming Signal Pair to Ballasts
Note: A means of disconnection must be incorporated into the fixed wiring in accordance with the current wiring regulations.
Always check product label before wiring
3
Commissioning
The units are supplied with the factory default settings, shown below, which render commissioning, apart from zoning, unnecessary in many applications. To allocate to zone(s), effected via the MLS Bus signals, and make use of the programmable settings, an infrared commissioning tool (QuickSet Pro) is required. A ten-second time delay is selectable to aid commissioning.
Sensitivity to Movement
While the factory settings will be correct for many applications, the sensitivity can be adjusted if required. ON Sensitivity: This sets the detector’s range when the lights are ON. Choose setting from 1-100 where 1 is
lowest and 100 is maximum. (Note: Choose the lowest level possible to give adequate detection.) OFF Sensitivity: This sets the detector’s range when the lights are OFF. Choose % setting from 10% to
100% where 10% = 10% of ON Sensitivity and 100% = same as ON Sensitivity. This is an approximation and should be tested on site during commissioning.
Like all programmable parameters, the sensitivity settings will be retained in the event of a power failure and can be re-programmed any number of times.
Factory Default Settings
These are the settings to which the units have been programmed before they leave the factory.
Parameter
Power Up Response Off Delay On Sensitivity Off Sensitivity Bus Connect 1st Zone 2nd Zone 3rd Zone 4th Zone Corridor 1 Begin/End Corridor 2 Begin/End Global 1 Rx Global 2 Rx Manual I/P Start Lamps Entry Scene Lamp Max Dimming Fade to Off When Vacant Bright-Out Pcell Rly Set-Point Low Set-Point High
Options
On/Off Auto, Manual/Bus, Manual only 1min-96hrs, 10 secs (walk test), Disabled 0-100 100-10% in 10% increments Yes/No Address 1-100, -- (no zone), Comn 1-3 Address 1-100, --, Comn 1-3 Address 1-100, --, Comn 1-3 Address 1-100, --, Comn 1-3 00-100, --, Building 00-100, --, Building Yes/No Yes/No Local/Share Max/Min Scenes 1-6 100-10% Regulate 100-50% No/Yes Off, 9 Exit Scenes (3 options x 3 durations) No/Yes Disabled/Passive/Active 0-1023 0-1023
Default Setting
ON AUTO 20 min 19 100% Yes
--
--
--
--
--
-­NO NO LOCA L MAX 01 100% 100% NO OFF NO Disabled 766 1022
Options
Each of these settings can be re-programmed, if desired, by use of the infrared programming tool QuickSet Pro.
- Manual Input is only available via the Wireless OneSwitch facility of the MLS2500DWL(F) and MLS2500DALIWL(F). See Application Note AN4021 for further information
4
Photocell Control
i) Regulating Photocell
Regulating photocell control tries to maintain a constant level of total illumination in the space controlled by dimming and brightening the controlled luminaires to compensate for changes in illumination from other sources.
With the photocell configured as DISABLED the Regulating Control module is influenced only by the BRIGHT-OUT setting. BRIGHT-OUT = YES allows it to hold-off the lights at the start of occupancy if natural light already exceeds SET-POINT LOW and to extinguish the lights during occupancy if total light, after the controlled luminaires have been dimmed to minimum, exceeds SET-POINT HIGH continuously for a period equal to the OFF DELAY . The lighting is restored immediately if the illumination level subsequently drops below SET-POINT LOW.
If the photocell is configured for ACTIVE or PASSIVE control of the relay switched load, then the Regulating Control module adopts the decision made by the Switching Control module in the case of turn-on inhibit on entry, but still obeys the BRIGHT-OUT YES/NO setting with regard to turn-off during occupancy.
ii) Switching Photocell (PHOTOCELL: ACTIVE or PASSIVE)
Both ACTIVE or PASSIVE modes hold off the controlled lighting on entry when natural light is sufficient, i.e. SET-POINT LOW is exceeded, but only ACTIVE mode will extinguish the lighting if natural light increases sufficiently during occupancy, i.e. SET-POINT HIGH is exceeded continuously for a period equal to OFF DELAY. The lighting is restored immediately if the illumination level subsequently drops below SET-POINT LOW.
iii) Photocell DISABLED
If the photocell is configured as DISABLED for relay Switching Control it will have no effect on the control of that load, which will be ON continuously during periods of occupancy unless commanded OFF via manual switch or infrared control. The photocell readings are still available for use by the Regulating Control module while in this mode.
Programming the Photocell Set-points
The parameters SET-POINT LOW and SET-POINT HIGH programme the detector’s photocell response. The SET-POINTS can be manually programmed as numbers between 1 (darkest) and 1023 (brightest). This number is not scaled to correlate with ‘lux’ measurements made using a light meter, but nevertheless is a true representation of the light level perceived by the detector. To assist with finding the appropriate SET-POINT settings, the light level currently perceived by the photocell can be viewed on the QuickSet Pro screen briefly, following a download operation. The number represents the light level read immediately before the download took place.
Tip: Turn the lights off with the QuickSet Pro (UTILITIES / LIGHTSPOT/MLS/LCM / IR REMOTE / HC5) to measure the perceived light level with no contribution from the controlled lighting.
Alternatively the SET-POINTS can be configured semi-automatically;
i) The Primary Interest is the Regulating Control Output.
With the photocell configured as DISABLED:-
Using QuickSet Pro (UTILITIES / LIGHTSPOT/MLS/LCM / SET LIGHT LEVEL) or HC5A (+,- Scene 1) set the required light output from the controlled luminaires and then press and hold OK (QuickSet Pro) or Scene 1 (HC5A) until the controlled lights "blink" to indicate that a new SET-POINT LOW has been stored and a calculated SET-POINT HIGH has also been inserted. Using the QuickSet Pro the photocell can now be re-configured as ACTIVE or PASSIVE if required.
5
ii) The Primary Interest is the Switching Control Output
With the photocell configured as ACTIVE or PASSIVE:-
1) If the lights are not already on, switch them on manually by pressing ‘UTILITIES / LIGHTSPOT/MLS/LCM / IR-REMOTE / HC5 / Luminaire+ / OK’ (QuickSet Pro) or "+" (HC5A). Fluorescent lights do not reach full output until up to 15 minutes after being switched on, so ensure that the lights are fully warmed up before continuing.
2) Wait until the time of day when the natural light level is at the point below which you would want the lights to be on, and above which you would not want the lights to be on.
3) Start the internal self-programming mechanism by pressing ‘UTILITIES / LIGHTSPOT/MLS/LCM / SET LIGHT LEVEL / OK’ (QuickSet Pro) or Scene 1 (HC5A). The detector takes a photocell reading, adds a small amount and stores the value in SET-POINT HIGH. Then it turns the lights off, makes another measurement and stores the value in SET-POINT LOW. The lights now switch on again to acknowledge a successful programming operation.
The two switching thresholds have now been set, and the difference between them is equal to slightly more than the contribution made by the electric lighting. This is the perfect amount of hysteresis to ensure that the lights will not oscillate.
6
Important Additional Notes
1. All terminals on this product are provided for final connections. It is not intended that the product be used as a junction box for looping cables.
2. Although nominally 12V, the dimming output is not SELV and therefore should be treated with the same respect as mains with regard to wiring practice.
3. Take care when choosing a location for this equipment since this type of device is capable of detecting large moving metal objects well beyond the normal range at which it is sensitive to human targets.
4. Please note that, although configurable as a regulating photocell, [closed-loop dimming according to daylight], due to the probable corner-of-room location where there will be excessive influence by daylight reflected from the walls, this product is not intended to achieve precise light level regulation measured on the working plane.
5. This equipment switches lights no more frequently than would a responsible human occupant. However, manufacturers of some lighting types (e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles in order to achieve a predicted lamp life. Please check with the manufacturer of the luminaires to ensure that they are compatible with automatic controls in this respect.
7
Technical Data
MLS CABLE: 1.5mm unscreened twisted-pair (applicable when detector used as part of a full MLS Digital
2
Managed Lighting System): see Application Note AN4001 OPERATING VOLTAGE: 230V ~ 50Hz (UK & Europe) SWITCH CAPACITY: 10 Amps max any lighting load except incandescent lamps: 1500W max (at 230V~) MAXIMUM RECOMMENDED LOAD (DSI/DALI): 25 Ballasts MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3.5m RANGE: Adjustable up to 20m OFF DELAY: 1 min - 96 hours plus 10-second walk-test mode PHOTOCELL: Passive/Active/Regulating adjustable 50-5000 lux MATERIAL: Flame retardant PC/ABS COLOUR: White RAL9010 WEIGHT: 180g (flush version), 160g (surface version) IP RATING: 4X OPERATING TEMPERATURE: 0 C to 40 C
o o
Contact Ex-Or Technical Helpline on 01942 719229 for guidance on installation and commissioning.
Honeywell Ex-Or
St. Marks Court, North Street,
Horsham, West Sussex RH12 1BW, UK Tel: + 44 (0)1942 719229 Fax: +44 (0)1942 272767 Email: technicalsales.ex-or@honeywell.com www.ex-or.com
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.
W4364E
Loading...