Ex-Or MLS2421DF, MLS2421DALIF, MLS2421DSM, MLS2421DALISM Ex-Or MLS2421DALIF Presence Detector Installation Instructions

MLS2421DSM
MLS2421DALISM
Installation and Commissioning
Instructions
Note: HP2000 required for commissioning
MLS2421DF & MLS2421DSM for DSI ballasts
MLS2421DALIF & MLS2421DALISM for DALI ballasts
with regulating photocell
MLS2421DF
MLS2421DALIF
2
Digital Gold Series Detector with Regulating Photocell
Please note that UltraLite versions of these detectors (suffix CWL7) do not offer MLS functionality and cannot be connected using MLS cable.
Only suitably qualified personnel should install this equipment.
The Digital Gold is a high-performance, communicating presence detector which can be used as part of a full Ex-Or MLS Digital Managed Lighting System or as a stand-alone unit. The MLS2421D detector is equipped with a regulating photocell to control digital DSI or DALI ballasts (when using the detector’s Digital Output) and a volt-free output for control of non-dimmable lighting loads. Digital Gold incorporates Ex-Or’s OneSwitch Dimming, local manual operation of any controlled lighting load.
Location
This is an extremely sensitive movement detector; it is essential therefore that it be installed on a rigid surface that will not itself be subject to movement or vibration.
Please note that this detector is not recommended for applications where there are large surface areas of metal, e.g. metal ceiling or floor tiles, as unpredictable sensitivity may result.
The units are graded according to four variations in operating frequency. Each type can be identified by different colour-coding on the detector label and carton. For reliable operation it is essential that units of the same colour code do not occupy adjacent positions in open-plan areas or in adjoining rooms (see below).
Yellow
Blue
Red
Green
Red
Green
Yellow
YellowBlue
Red
Green
YellowBlue
Yellow
Green
Green
Yellow
Green
Yellow
YellowBlue
Red
Green
Red
Green
YellowBlue
Red
Green
YellowBlue
Blue
Red
Red
Blue
Red
Blue
Yellow
Blue
Red
Green
Red
Green
Yellow
YellowBlue
Red
Green
YellowBlue
Yellow
Green
Green
Yellow
Green
Yellow
YellowBlue
Red
Green
Red
Green
YellowBlue
Red
Green
YellowBlue
Blue
Red
Red
Blue
Red
Blue
Note: Should you need to order additional detectors for an existing installation and need specific colour-coded detectors, please add the following suffixes to the part number: Y = Yellow, B= Blue, G= Green, R = Red. (There is normally no need to specify the colour codes as orders are dispatched with a suitable colour-code mix.)
Fixing
MLS2421DSM/DALISM - The housing may be secured to a hard surface or a BESA box. The unit fits into the housing with a simple bayonet action.
MLS2421DF/DALIF - Depth required behind ceiling: 62mm from front flange plus an allowance for the minimum bend radius of the cable. Sinking box fits into a 89mm diameter hole in ceiling tile or plasterboard ceiling. To avoid damage to ceiling tile, do not overtighten. No access above the ceiling is necessary.
Please note:Do not position this product on a pitch narrower than 5m.
Do not mount within 0.25m of a luminaire.
3
Electrical Connections
These Digital Gold detectors should be connected in accordance with the diagrams below. Both the Digital Output and MLS connections are polarity-free however other MLS products require that polarity be maintained. The MLS cable should be mains-rated, unscreened, twisted pair of at least 1.5mm CSA. For further information please refer to Wiring Application Guide AN4001. Please note that UltraLite versions of these detectors (suffix CWL7) do
not offer MLS functionality and cannot be connected using MLS cable.
These detectors are designed to control up to 25 DSI or DALI luminaires, a switched load of up to 6 Amps or a combination of the two. When controlling DSI or DALI ballasts the ballast type must not be mixed. The DSI or DALI input terminals on the ballasts should be connected in parallel with each other and to the Polarity-Free Digital Output terminals on the rear of the detector. Each DSI or DALI luminaire is controlled completely by its digital input and therefore would normally have a permanent power supply. Turning the power off to some lights within a control circuit will not have affect the operation of those lights that remain powered up and under the control of the detector.
When switching via the volt-free output multiple detectors may be connected in parallel provided the controlled load does not exceed 6 Amps. If digital ballasts are also being controlled the digital outputs from each detector must not be mixed even if they are of the same type.
W4178M
Wiring Examples
Digital Output
MLS BUS
These Connections are Polarity-Free
1 2 1 2
Using OneSwitch, MLS*, Switched and Digital Outputs
N
E
L
Permanent or switched supply
VOLT­FREE OUTPUT
LIVE
NEUTRAL
EARTH
LOAD
(MAX 6 AMPS)
ONESWITCH DIMMING
Digital output
MLS Bus Connection (Some MLS devices require that polarity be maintained)
Momentary push-to-make switch
Please note that the Earth terminal has no internal connection and is used for termination only.
Digital Output
MLS BUS
These Connections are Polarity-Free
1 2 1 2
Using Switched Output and MLS*
N
E
L
Permanent or switched supply
VOLT­FREE OUTPUT
LIVE
NEUTRAL
EARTH
LOAD
(MAX 6 AMPS)
ONESWITCH DIMMING
MLS Bus Connection (Some MLS devices require that polarity be maintained)
NC
NC
Please note that the Earth terminal has no internal connection and is used for termination only.
VOLT­FREE OUTPUT
NEUTRAL
LIVE IN
EARTH
ONE
SWITCH
NC
VOLT­FREE OUTPUT
NEUTRAL
LIVE IN
EARTH
ONE
SWITCH
NC
LOAD
(Max 6 Amps)
E
L
N
Permanent or switched supply
2 x MLS2421D In Parallel, using Switched Output only
Any connection not shown is NO CONNECTION
Relay outputs may be connected together in parallel to cover larger areas, however the total load on all combined relay outputs must not exceed 6 Amps.
* UltraLite-version detectors (suffix CWL7) do not offer MLS functionality and cannot be connected using MLS cable.
* UltraLite-version detectors (suffix CWL7) do not offer MLS functionality and cannot be connected using MLS cable.
4
Commissioning
The units are supplied with the factory default settings shown below which render commissioning unnecessary in many applications. To make use of the programmable settings, an infrared commissioning tool is required (HP2000). A ten-second time delay is selectable to aid commissioning.
Sensitivity to Movement
While the factory settings will be correct for many applications, the sensitivity can be adjusted if required. ON Sensitivity: This sets the detector’s range when the lights are ON. Choose setting from 1-100 where 1 is
lowest and 100 is maximum. (Note: Choose the lowest level possible to give adequate detection.) OFF Sensitivity: This sets the detector’s range when the lights are OFF. Choose % setting from 10% to
100% where 10% = 10% of ON Sensitivity and 100% = same as ON Sensitivity. This is an approximation and should be tested on site during commissioning.
Like all programmable parameters, the sensitivity settings will be retained in the event of a power failure and can be re-programmed any number of times.
Factory Default Settings
These are the settings to which the units have been programmed before they leave the factory.
Parameter
Power up Response Off Delay On Sensitivity Off Sensitivity Bus Connect 1st Zone 2nd Zone 3rd Zone 4th Zone Corridor 1 Begin/End Corridor 2 Begin/End Global 1 Rx Global 2 Rx Manual I/P Start Lamps Entry Scene Lamp Max Dimming Fade to Off When Vacant Bright-Out Pcell Rly Set-Point Low Set-Point High
Default Setting
ON AUTO 20 min 19 100% YES
--
--
--
--
--
-­NO NO LOCAL MAX 01 100% Reg 100% NO OFF NO Disabled 766 1022
Options
On/Off Auto, Manual/Bus, Manual only 1min-96hrs, 10 secs (walk test), Disabled 0-100 100%-10% in 10% increments Yes/No Address 1-100, -- (no zone), Comn 1-3 Address 1-100, -- (no zone), Comn 1-3 Address 1-100, -- (no zone), Comn 1-3 Address 1-100, -- (no zone), Comn 1-3 0-100, --, Building 0-100, --, Building Yes/No Yes/No Local/Share Max/Min Scenes 1-6 100%-10% Reg 100%-50% Yes/No Off, 9 Exit Scenes (3 options x 3 durations) Yes/No Disabled/Passive/Active 0-1023 0-1023
Options
Each of these settings can be re-programmed, if desired, by use of the infrared programming tool HP2000.
Photocell Control
i) Regulating Photocell
Regulating photocell control tries to maintain a constant level of total illumination in the space controlled by dimming and brightening the controlled luminaires to compensate for changes in illumination from other sources.
With the photocell configured as DISABLED the Regulating Control module is influenced only by the BRIGHT­OUT setting. BRIGHT-OUT = YES allows it to hold-off the lights at the start of occupancy if natural light already exceeds SET-POINT LOW and to extinguish the lights during occupancy if total light, after the controlled luminaires have been dimmed to minimum, exceeds SET-POINT HIGH continuously for a period equal to the OFF DELAY . The lighting is restored immediately if the illumination level subsequently drops below SET­POINT LOW.
If the photocell is configured for ACTIVE or PASSIVE control of the relay switched load then the Regulating Control module adopts the decision made by the Switching Control module in the case of turn-on inhibit on entry, but still obeys the BRIGHT-OUT YES/NO setting with regard to turn-off during occupancy.
ii) Switching Photocell (PHOTOCELL: ACTIVE or PASSIVE)
Both ACTIVE or PASSIVE modes hold off the controlled lighting on entry when natural light is sufficient, i.e. SET-POINT LOW is exceeded, but only ACTIVE mode will extinguish the lighting if natural light increases sufficiently during occupancy, i.e. SET-POINT HIGH is exceeded continuously for a period equal to OFF DELAY. The lighting is restored immediately if the illumination level subsequently drops below SET-POINT LOW.
iii) Photocell DISABLED
If the photocell is configured as DISABLED for relay Switching Control it will have no effect on the control of that load, which will be ON continuously during periods of occupancy unless commanded OFF via manual switch or infrared control. The photocell readings are still available for use by the Regulating Control module while in this mode.
Programming the Photocell Set-points
The parameters SET-POINT LOW and SET-POINT HIGH programme the detector’s photocell response The SET-POINTS can be manually programmed as numbers between 1 (darkest) and 1023 (brightest). This number is not scaled to correlate with ‘lux’ measurements made using a light meter, but nevertheless is a true representation of the light level perceived by the detector. To assist with finding the appropriate SET-POINT settings, the light level currently perceived by the photocell can be viewed on the HP2000 screen briefly, following a download operation. The number represents the light level read immediately before the download took place.
Tip: Turn the lights off (HP2000 UTILITIES/USER-REMOTE) to measure the perceived light level with no contribution from the controlled lighting.
Alternatively the SET-POINTs can be configured semi-automatically;
i) The Primary Interest is the Regulating Control Output.
With the photocell configured as DISABLED:-
Using HP2000 (UTILITIES / SET LIGHT LEVEL) or HC5 (+,- Scene 1) set the required light output from the controlled luminaires and then press and hold OK (HP2000) or Scene 1 (HC5) until the controlled lights "blink" to indicate that a new SET-POINT LOW has been stored and a calculated SET-POINT HIGH has also been inserted. Using the HP2000 the photocell can now be re-configured as ACTIVE or PASSIVE if required.
5
W4178M
ii) The Primary Interest is the Switching Control Output
With the photocell configured as ACTIVE or PASSIVE:-
1) If the lights are not already on, switch them on manually by pressing ‘UTILITIES/USER­REMOTE/Luminaire+/OK’ (HP2000) or "+" (HC5). Fluorescent lights do not reach full output until up to 15 minutes after being switched on, so ensure that the lights are fully warmed up before continuing.
2) Wait until the time of day when the natural light level is at the point below which you would want the lights to be on, and above which you would not want the lights to be on.
3) Start the internal self-programming mechanism by pressing ‘UTILITIES/SET LIGHT LEVEL/OK’ (HP2000) or Scene 1 (HC5). The detector takes a photocell reading, adds a small amount and stores the value in SET-POINT HIGH. Then it turns the lights off, makes another measurement and stores the value in SET-POINT LOW. The lights now switch on again to acknowledge a successful programming operation.
The two switching thresholds have now been set, and the difference between them is equal to slightly more than the contribution made by the electric lighting. This is the perfect amount of hysteresis to ensure that the lights will not oscillate.
OneSwitch
OneSwitch Dimming affords local control to the end-user whereby a simple, momentary, push-to-make wall switch can be used to raise or lower the lighting level or toggle the output of the unit ON or OFF. A short press (less than 1 second) toggles all outputs from both OFF to both ON or from either ON to both OFF. A long press will ramp the digital output either up or down with no effect on the volt-free output. If the output prior to pressing the switch is above 90% the output will ramp down; if below 90% it will ramp up. If the latest press and the current press are within 5 seconds of each other it will ramp in the opposite direction.
6
User Overrides
The end-user can configure a number of lighting scenes that can be recalled using a hand-held override. With an HC5 hand-held controller lighting can be overridden OFF or ON, or a set level can be chosen, affecting either the controlled group or, with an MLS system, the whole zone. Regulating and switched loads can be
adjusted independently through a combination of OneSwitch Dimming and the HC5.
7
Important Additional Notes
1. All terminals on this product are provided for final connections. It is not intended that the product be used as a junction box for looping cables.
2. A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.
3. Although nominally 12V, the dimming output is not SELV and therefore should be treated with the same respect as mains with regard to wiring practice. The 0V line of the dimming output is almost at Neutral potential.
4. The dimming control output should be connected only to the control input of the ballasts - never to other detectors.
5. Due to the fact that the photocell is on the ceiling looking down, it is not possible for measurements made with a lux meter on the working plane to remain constant when daylight illuminates the ceiling and the working plane to a differing extent. Therefore, products of this type should be regarded as capable of maintaining an APPROXIMATE light level only.
6. This equipment switches lights no more frequently than would a responsible human occupant. However, manufacturers of some lighting types (e.g. ‘2D’ luminaires) may specify a maximum number of switching cycles in order to achieve a predicted lamp life. Please check with the manufacturer of the luminaires to ensure that they are compatible with automatic controls in this respect.
7. The detectors are extremely sensitive to movement; they must be mounted on a solid surface which has no movement whatsoever.
W4178M
Ex-Or
Novar ED&S Limited Haydock Lane, Haydock, Merseyside WA11 9UJ
Tel: +44 (0)1942 719229 Fax: +44 (0)1942 508753 Email: technicalsales.ex-or@honeywell.com www.ex-or.com
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.
Dimensions
MLS2421DF/DALIF MLS2421DSM/DALISM
100mm
Flange:
15mm deep
100mm
62mm deep
behind ceiling
62mm
deep
Technical Data
2
MLS CABLE : 1.5mm unscreened twisted-pair (applicable when detector is used as part of a
full MLS Digital Managed Lighting System): see Application Note AN4001 OPERATING VOLTAGE: 230V 50Hz (UK & Europe) PRODUCT RATING AND RECOMMENDED CIRCUIT PROTECTION: 10 Amps MAXIMUM RECOMMENDED LOAD (VOLT-FREE): 6 Amps MAXIMUM RECOMMENDED LOAD (DSI/DALI): 25 Ballasts MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3.0m RANGE: Approx 7m dia at 2.4m ceiling height OFF DELAY: 1 min - 96 hours plus 10-second walk-test mode PHOTOCELL: Passive/Active/Regulating adjustable 50-5000 lux MATERIAL: Flame retardant PC/ABS COLOUR: White WEIGHT: 300g IP RATING: 2X
W4178M
Loading...