Ex-Or MLS2021DF, MLS2021DALIF, MLS2021DSM, MLS2021DALISM Installation Instructions

MLS2021DF & MLS2021DSM for DSI ballasts
Digital Gold PIR Detector with regulating photocell
MLS2021DF
MLS2021DALIF
MLS2021DSM
MLS2021DALISM
Installation and Commissioning
Instructions
Note: QuickSet Pro required for commissioning
1
Digital Gold PIR Detector with Regulating Photocell
Please note that UltraLite versions of these detectors (suffix CWL7) do not offer MLS functionality and cannot be connected using MLS cable.
Only suitably qualified personnel should install this equipment.
This is a high-performance, communicating presence detector which can be used as part of a full Ex-Or MLS Digital Managed Lighting System or as a stand-alone unit. It is equipped with a regulating photocell to control digital DSI or DALI ballasts (when using the detector’s Digital Output) and a volt-free output for control of non-dimmable lighting loads. The product incorporates Ex-Or’s OneSwitch Dimming, local manual operation of any controlled lighting load.
Fixing
MLS2021DSM/DALISM - The housing may be secured to a hard surface or to a BESA
box. The unit fits into the housing with a simple bayonet action.
MLS2021DF/DALIF - Supplied with a sinking (dry-lining) box for flush fitting. The sinking box fits into an 89mm diameter hole in a ceiling tile or plasterboard ceiling. To avoid damage to ceiling tile do not overtighten. Depth required behind ceiling 62mm from front flange plus an allowance for the minimum bend radius of the cable. No access above the ceiling is necessary.
Electrical Connections
This detector should be connected in accordance with the diagrams overleaf. Both the Digital Output and MLS connections are polarity-free however other MLS products require that polarity be maintained. The MLS cable should be mains-rated, unscreened, twisted pair of at least 1.5mm CSA. For further information please refer to Wiring Application Guide AN4001. Please note that UltraLite versions of these detectors
(suffix CWL7) do not offer MLS functionality and cannot be connected using MLS cable.
The detector is designed to control up to 25 DSI or DALI luminaires, a switched load of up to 6 Amps or a combination of the two. When controlling DSI or DALI ballasts the ballast type must not be mixed. The DSI or DALI input terminals on the ballasts should be connected in parallel with each other and to the Polarity-Free Digital Output terminals on the rear of the detector. Each DSI or DALI luminaire is controlled completely by its digital input and therefore would normally have a permanent power supply. Turning the power off to some lights within a control circuit will not affect the operation of those lights that remain powered up and under the control of the detector.
When switching via the volt-free output, multiple MLS2021D detectors may be connected in parallel provided the controlled load does not exceed 6 Amps.
Note: The digital dimming signals of two detectors should NEVER be connected
together. Their only connections should be to the digital inputs of high frequency ballasts of the correct type.
2
Using OneSwitch, MLS*, Switched and
VOLT­FREE OUTPU T
LIVE
NEUTR AL
EARTH
ONESW ITCH DIMMI NG
MLS2021D
Digital Outputs
(MAX 6 AMP S)
LOAD
Momentary push-to-make switch
These Connections are
Polarity-Free
Digital
MLS
Output
BUS
1 2 1 2
L
Permanent or switched
N
supply
E
Please note that the Earth terminal has no internal connection and is used for termination only.
* UltraLite-version detectors (suffix CWL7) do not offer MLS functionality and cannot be connected using MLS cable.
MLS Bus Connection (Some MLS devices require that polarity be maintained)
Digital output
Using Switched Output and MLS*
VOLT­FREE OUTPU T
LIVE
NEUTR AL
EARTH
ONESW ITCH DIMMI NG
In Parallel, using Switched Output only
MLS2021D
(MAX 6 AMP S)
NC
2 x MLS2021D
LOAD
These Connections are
Polarity-Free
Digital
MLS
Output
BUS
1 2 1 2
* UltraLite-version detectors (suffix CWL7) do not offer MLS functionality and cannot be connected using MLS cable.
NC
Optional MLS Bus Connection (Some MLS devices require
L
Permanent or switched
N
supply
E
Please note that the Earth terminal has no internal connection and is used for termination only.
that polarity be maintained)
Any connection not shown is NO C ONNE CTI ON
LOAD
(Max 6 Amps)
VOLT­FREE OUTPUT
LIVE IN LIVE IN
NEUTRA L NEUTRA L
EARTH EART H
ONE
SWITCH
Relay outputs may be connected together in parallel to cover larger areas, however the total load on all combined relay outputs must not exceed 6 Amps.
VOLT­FREE OUTPUT
NC NC
ONE
SWITCH
L
N E
Permanent or switched supply
3