Ex-Or MLS2001DMBF, MLS2001DALIMBF, MLS2001DMBSM, MLS2001DALIMBSM Installation Instructions

MLS Digital Mid-Bay Detector
MLS2001DMBF & MLS2001DMBSM for DSI ballasts
MLS2001DALIMBF & MLS2001DALIMBSM for DALI ballasts
MLS2001DALIMBF
MLS2001DMBSM
MLS2001DALIMBSM
Installation and Commissioning
Instructions
Note: HP2000 required for commissioning
MLS Digital Mid-Bay Detector: MLS2001DMBF/SM for DSI & MLS2001DALIMBF/SM for DALI ballasts
Only suitably qualified personnel should install this equipment.
Fixing
Flush Version: Depth required behind ceiling: 62mm from front flange plus an allowance for the minimum bend radius of the cable. Sinking box fits into a 89mm diameter hole in ceiling tile or plasterboard ceiling. Note: If the sinking box is being fitted to a hard substrate such as metal, increase the hole size to 91mm. To avoid damage to ceiling tile, do not overtighten. No access above the ceiling is required.
Surface Version: The housing may be secured to a hard surface or a BESA box. The unit fits into the housing with a simple bayonet action.
For aisle or corridor applications, there is an optimum orientation for approach:
Centre of facet
Path of optimum
sensitivity
Align to arrow
5
1 °
for optimum sensitivity
Note: When operating in 'Regulating Photocell' mode, a closed feedback loop is formed by the luminaire, the reflective surface beneath, and the photocell. For this control loop to function correctly, the photocell must have a good view of the reflected light only from the luminaire(s) under its control – NOT from adjacent luminaires not under its control. This means that the higher the detectors are mounted, the further apart they must be in order to ensure that they see mostly 'their own light'. Therefore, it is recommended that detectors are mounted on a pitch not less than 50% of the mounting height when using the regulating photocell function.
Connection
Control of a group of luminaires is achieved via the detector’s two-wire digital control circuit. Each luminaire to be controlled must contain a digital regulating type ballast with the appropriate DSI or DALI input. Ballast types must not be mixed. Connect all ballasts in the control group (max 25) in parallel and also to the polarity-free digital output of the detector.
Each luminaire is controlled completely by its digital input and therefore would normally have a permanent power supply. If, however, it is desired to have manual wall switches, any or all of the fittings in a controlled group may also be controlled in the traditional way - by turning off the power. The control circuit will continue to operate properly even if some of the luminaires in the group have had mains power removed.
The MLS Bus must be connected to the MLS Bus Network. An MLS Bus Power Supply is required for each network of up to 200 MLS devices. Refer to the MLS Bus Power Supply Installation Instructions before commencing any bus wiring.
It is imperative that the MLS Bus is wired in the correct type of cable. Normally this will be 1.5mm² unscreened twisted pair. See Application Note AN4001 for details.
Do not connect mains to the MLS Bus wiring
‘OneSwitch’ Dimming
OneSwitch dimming affords local control to the end-user whereby a simple, momentary, push-to-make wallswitch can be used to raise or lower the lighting level or to toggle the output ON/OFF. A short press of the switch (less than 1 second) will toggle the output status while a longer press will raise or lower the output. Each time the switch is pressed, the direction of dimming reverses. If the switch has not been pressed for 5 seconds, the direction will be up (brighter) - unless the output is already above 90% in which case the direction is down. If the switch is held continuously, and the output reaches maximum, the light output will remain at this level until the switch is released - a latching switch may be connected in parallel allowing the occupancy detection to be overridden on (Note: If the initial direction was down, when the output reaches minimum it will ramp back up automatically).
Setting the Regulating Photocell
This product is intended for use with high frequency regulating ballasts with digital control inputs. An infrared programming tool, the HP2000, is required for programming the regulating light level set point.
Using the HP2000 Programmer, enter the Utilities menu and select ‘Set Light Level’. Use the ‘up’ and ‘down’ buttons to manually adjust the light output from the luminaire(s) and when at the required level press and hold ‘OK’ to store. The luminaire(s) will blink to acknowledge a successful store operation.
Commissioning
Parame ter Options Pre-Set Notes
Power Up On / Off On
Sets the lum inaire state at pow er up irres pective of occupancy. Use ful in redu cing s tart-up load followin g power cut. Power-u p off ­resp onds to occupancy after 30 seco nds .
Res pons e Auto, Manual/Bus , Manual only Auto If set to Au to, the presence detector s witches the lum inaire on and
off automatica lly. If set to Manual Only, it ca n only be turned on by usi ng OneSwi tch or the hand-he ld controller. If set to Ma nual/Bus , an MLS Bus turn-on com mand for a Zone to which the detector belon gs will als o bring the light on. In all m odes the "When Vacant" behaviour (be low) is initiated autom atically.
Off Delay 1 min - 96 hrs, 10-s ec (walk-test), Dis abled 2 0 mi ns
The time for whi ch the lum inai re will stay on followin g the las t detected m ovemen t. Also 10-s econd setting for walk-testin g.
On Sensi tivity 0 -100 100
Sens itivity to movemen t when area is occup ied. 100 = m ax
Bus Co nnect Yes / No Yes
Do/Do not Sign al/Rece ive on MLS Bus .
1st - 4th Zone Addre ss 1-100; -- (no zone); Com mo n 1-3 No Zone Individual Zone s in fluencin g and being influ enced by this de tector.
Corrido r 1 & 2 0-100; -- (no zone); Buildi ng No Zone
Zone range s in fluencin g and being influ enced by this detector.
Global 1 & 2 Rx Ye s / No No
Res pond to selective load she dding .
Manual Input Sha red / Local Local
Do/Do not s igna l OneSwitch com m ands acros s the MLS Bus.
Start Lamps Max / Min Max
Sets the level at which the lam ps s trike when turning on .
Entry Scene 1-6 Scene 1
Sets whi ch sce ne is recalle d when un occupi ed area is entered .
Bright Out Yes / No N o If set to yes, moveme nt fails to refres h the off delay if ambie nt light
level exceeds 12 5% of se t level and the lum inaire will s witch off when the off dela y has elapsed . NB: Dimm ing m us t be set to 100% .
Dim mi ng Reg 50%-R eg10 0% 100% Can be s et to op erate between 50% an d 100% ba llas t output from
max down to a bottom -end limi t when worki ng on pho tocell control .
Lam p Max 10%-10 0% 100%
Can be s et to li mi t the absol ute maximum output of the ballas t i n all operatin g mo des .
Fade to Off Yes / No No
When no pres ence is detected , and after the off delay period, the lam ps can fade out ins tead of s witching off (approx 80 second s to fade from 10 0% to 0%).
When Vacant Off / Min / Reg <25% / Scene 6 Off Options for a vacant area after it has tim ed out. Lum inai res can turn
off, remain at m inim um output, or regulate with a 25% outpu t limit, until the next period of occup ancy. If prog ram med to remai n at min im um, to regul ate belo w 25% or go to s cene 6, there are further program mable op tions to switch off after 3 times the Off Delay (XTN) or when no further movem ent has been detected anywhere in the build ing (BLD ).
Set-point Low 0-1023 1023 Aiming po int as ph otocell adjus ts ba llas t output.
Set-point Hig h 0-1023 1023 L evel above which ph otocell s witche s its output off (only if Bri ght
Out = Yes ).
100 Hou r Burn-In Burn-in 10 0 hrs / Cancel / Resu me 0 hr See Application Note: AN4028
Additional feature acc essible under Utilities on HP200 0:
The factory default settings shown in the table below will be appropriate for most applications. However, the installer does have the facility to re-programme all parameters using the HP2000 Programmer. These parameters may be re-programmed any number of times and all settings will be retained in the event of a power loss.
Lens Mask
A lens mask (MBPIRLM) is available to mask end-of-aisle movement from being detected.
Important Additional Notes
1. All terminals on this product are provided for final connections. It is not intended that the product be used as a junction box for looping cables.
2. A means for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations.
3. Although nominally 12V, the dimming output is not SELV and therefore should be treated with the same respect as mains with regard to wiring practice. The 0V line of the dimming output is almost at Neutral potential.
4. The dimming control output should be connected only to the control input of the ballasts - never to other detectors.
5. Due to the fact that the photocell is on the ceiling looking down, it is not possible for measurements made with a lux meter on the working plane to remain constant when daylight illuminates the ceiling and the working plane to a differing extent. Therefore, products of this type should be regarded as capable of maintaining an APPROXIMATE light level only.
Dimensions Electrical Connections
OneSwitch
62mm
deep
100mm
Flange: 10mm deep
BALLAST
CONTROL
L
N
MLS Bus
Connection
230V 50Hz Mains Supply
Polarity-free Digital Output to compatible luminaires
To further
MLS Devices
Technical Data
MLS CABLE: 1.5mm unscreened twisted-pair : see Application Note AN4001 MAXIMUM RECOMMENDED MOUNTING HEIGHT: 12.0m RANGE: 360 cone-shaped detection pattern, diameter (at floor level) (d) = 1.75 x mounting height (h)
2
o
h
d
MINIMUM MOUNTING PITCH (SPACING): 0.5 x mounting height (regulating mode only - see note under ‘Fixing’) OPERATING VOLTAGE: 230V 50Hz (UK & Europe) PRODUCT RATING & RECOMMENDED CIRCUIT PROTECTION: 10 Amps CAPACITY: 25 ballasts OUTPUT: 2-wire digital polarity free PHOTOCELL: Regulating OFF DELAY: Adjustable via Programmer - factory pre-set to 20 minutes DEPTH REQUIRED BEHIND CEILING (FLUSH VERSION): 62mm from front flange plus an allowance for the minimum bend radius of the cables. WEIGHT: 200g approx COLOUR: White MATERIAL: Flame retardant PC/ABS IP RATING: 4X OPERATING TEMPERATURE: 0 C to 40 C
o o
Ex-Or
Novar ED&S Limited Haydock Lane, Haydock, Merseyside WA11 9UJ
Tel: +44 (0)1942 719229 Fax: +44 (0)1942 508753 Email: technicalsales.ex-or@honeywell.com www.ex-or.com
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.