MLS Digital
MLS2000SSP MK2
Scene Switch Panel
Installation and Commissioning
Instructions
Note: QuickSet Pro required for commissioning

MLS Digital Scene Select Panel MLS2000SSP MK2
Only suitably qualified personnel should install this equipment
Dimensions
ON
1 2
3
82mm
86mm
5
OFF
4
6
144mm Module
146mm Fascia
The module's enclosure and its supporting frame are designed to attach to the front of any standard
Two-Gang Box, sinking, dry-lining or surface mounting, with a minimum depth of 30mm.
Connection
It is imperative that the MLS bus is wired with the correct type of cable. Normally it should be 1.5mm
unscreened twisted pair. Please read Application Note AN4001 for more details.
Two-core mains-rated cable is recommended for the dimming signal (see Note 3 below). The dimming
control output should be connected only to the control inputs of ballasts - never to a detector.
The supporting frame of the module must be earthed, via its earth terminal, to render the metal fascia safe.
TOP
MLS2000SSP Mk2
230V ~ 50Hz.
Power consumption <10W
o
ta 0.. 40 C
Please read instructions prior to installation.
Novar ED&S Ltd
Haydock Lane, Haydock
Merseyside. WA11 9UJ
Tel: 01942 719229
Fax: 01942 272767
L N
MAINS INPUTS
DIRECTION OF CABLE INSERTION
D1
DIGITAL
OUTPUT
POLARITY
FREE
D2
MLS BUS
POLARITY
FREE
MLS
MLS
VIEW ON REAR OF
MODULE ENCLOSURE
BOTTOM
2
WARNING
UNDER NO CIRCUMSTANCES SHOULD MAINS POWER (e.g. 200-250V ~) BE
APPLIED TO THE MLS BUS CONNECTIONS OR THE DIGITAL DIMMING OUTPUT
CONNECTIONS. THIS WILL CAUSE DAMAGE AND COULD BE HAZARDOUS.
Important Additional Notes
1. All terminals on this product are provided for final connection. It is not intended that the product be used
as a junction box for looping cables.
2. A means of disconnection must be incorporated in the fixed wiring in accordance with the current wiring
regulations.
3.The dimming signal, while nominally 12V, should not be treated as ELV as its 0V line (D1 above) is close to
Mains Neutral potential.