Ex-Or LR30SM, LR30B, LR30C1, LR15B, LR15F Installation Instructions

...
Ex-Or by Honeywell
St. Marks Court, North Street, Horsham, West Sussex, RH12 1BW, UK.
Tel: +44 (0)1942 719229 Fax: +44 (0)1942 508753 Email: technicalsales.ex-or@honeywell.com www.ex-or.com
LightSpot Long Range Series
Detectors: LR15, LR30
Installation & Commissioning Instructions
LW4008
CHOOSING A POSITION
Select a position on a rigid surface where the detector has a clear view of all the occupants who are expected within the monitored area.
Face the detector away from glass panels or thin partitions which have movements occuring behind them (e.g. trees etc).
The detectors are extremely sensitive to movement; they must be mounted on a solid surface which has no movement whatsoever.
Do not mount above 3.5m without seeking technical advice.
Often a corner position makes the best use of the detector’s wide detection pattern.
Take care to position the detector clear of unwanted movement such as fans and moving machinery.
For operation in racking aisles, see Application Note AN4010.
MOUNTING
Flush Mounted Unit
LR15F, LR30F
Mounts onto own back box
It is recommended that LR-type detectors be ceiling mounted but, if wall mounting is required, the wall-mounting kit (WMK) must be used.
Surface Mounted Unit
LR15SM, LR30SM
Wall-mounting kit (WMK) available
Surface Mounted Detector
with mounting box
LR15B, LR30B
WMK Wall-mounting kit
(Supplied assembled)
Examples of WMK application
Horizontal installation
For general applications where ceiling mounting is not convenient and wide angle coverage in the horizontal plane is desirable. The WMK can be screwed to a hard surface or the lid of a conduit stop-end box.
ELECTRICAL CONNECTIONS
Detectors are supplied with a choice of mountings:
- within the lid of the control unit housing
- in separate housings for remote mounting. A wall-mounting kit is available for the LR15SM and LR30SM.
If mounted in a separate housing, the detector and its control unit should be interconnected using a minimum 0.75mm mains rated
2
2-core screened cable. If required, ‘Pyro’ or ‘FP200’ can be used.
The d.c. voltage measured between terminals B + C at the detector should not be less than 10 volts.
Three detectors may be connected in parallel to the control unit terminals. See ‘Control Unit Installation & Commissioning Instructions’ for details.
1 2 3 4 5 6 7
CONTROL
UNIT
A B C
SCREENED
D
LEAD
E F G
A B C
LIGHTSPOT
DETECTOR
Please Note: Correct connections are essential for successful operation. Reversed connections may damage the equipment.
Vertical installation
Use this method of mounting for racking aisle applications and where adjustment in the vertical plane will give improved control over the precise point of entry detection.
During Commissioning
Where the detector is fitted into the lid of a control unit, the box lid may be temporarily held by two of its fixing screws as shown. This gives access to the controls during commissioning. The screws must be securely tightened to ensure adequate temporary support.
LRDKIT - Rugged Installation Option
For more demanding locations, the LRDKIT (available separately) provides a robust IP67 and IK08 rated housing for the LR30F. It allows the sensor to be mounted either horizontally or vertically, for ceiling or wall mounting, and to be rotated within different planes for optimal performance.
Horizontal orientation
Vertical orientation (for wall mounting)
Dimensions (mm): 180 (h) x 130 (w) x 150 (d)
Vertical orientation (for ceiling mounting)
Loading...