This Operating Instruction describes the main features of the Exor operator panels. The Manual refers to
the following models:
JSmart707 Field-ready HMI 7” color TFT, PCAP touchscreen, Ethernet port PoE
JSmart710 Field-ready HMI 10.1” color TFT, PCAP touchscreen, Ethernet port PoE
JSmart715 Field-ready HMI 15.6” color TFT, PCAP touchscreen, Ethernet port PoE
JSmart721 Field-ready HMI 21.5” color TFT, PCAP touchscreen, Ethernet port PoE
The manual contains safety standards that must be respected for the personal safety and to avoid damage.
Indications of attention are divided into three levels of severity:
DANGER: indicates a failure to observe safety rules and such failure may cause death or serious injuries.
DANGER
!
ATTENTION:indicates a failure to observe safety rules and that deciency may cause damage.
ATTENTION
!
CAUTION:indicates a failure to observe safety rules and that deciency may cause defects to the equipment
or inconsistencies.
JSmart700 products are ideal for eld installation in critical areas. High-resolution displays and multitouch
PCAP touchscreen with a robust glass front.
Power-over-Ethernet (PoE) for maximum simplicity of connection using standard shielded CAT 5 wiring. Full
IP protection with the use of dedicated connectors for the maximum flexibility of installation, from mounting
arm to a simple M22 hole. The product includes environment and motion sensors to make this device a true
IIoT edge device for Industry 4.0 applications.
The JSmart product family has been optimized for use as an embedded browser or as a JMobile HMI device.
• Open platform for Linux applications
• Performing HTML5-compatible browser with graphic accelerator
• JMobile runtime with OPC UA Server and Client
• Optional CODESYS V3 PLC for integrated HMI and control applications
3V 7mAh Vanadium-Lithium, rechargeable, not user-replacea
ble, model VL1220.
Flash 4GB (8GB for JSmart715 and JSmart721)
RAM 1GB (2GB for JSmart715 and JSmart721)
Hardware clock Clock/Calendar with back-up battery
Accuracy RTC (at 25°C) <100ppm
Environmental conditions
Operating temperature (surrounding -20 ÷ +55°C (vertical installation) EN 60068-2-14
air temperature)
Storage temperature -30 ÷ +80°C (JSmart707, 710) EN 60068-2-1
-20 ÷ +70°C (JSmart715, 721) EN 60068-2-2
EN 60068-2-14
Operating and storage humidity 5 ÷ 85 % RH not-condensing EN 60068-2-30
Vibrations 5 ÷ 9 Hz, 7 mm
9 ÷ 150 Hz, 1 g
Shock ± 50 g, 11 ms, 3 pulses per axis EN 60068-2-27
Protection class IP67 (requires appropriate connectoris EN 60529
and cables)
EN 60068-2-6
p-p
Electromagnetic Compatibility (EMC)
Radiated disturbance test Class A CISPR 22
CISPR 16-2-3
Electrostatic discharge immunity test 8 kV (air electrostatic discharge) EN 61000-4-2